REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM

Similar documents
The Science Behind Water Mist Protection of Typical Building Hazards

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

Examination of Performance of Water Mist Fire Suppression Systems under Ventilation Conditions

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

An experimental study of the impact of tunnel suppression on tunnel ventilation

The Experimental Study and Simplified Model of. Water Mist Absorbing Heat Radiation

WATER MIST CONVENTION AND EXHIBITION

So, How do Fire Starts & Spreads? A question we need to understand and appreciate the dynamics of fire life cycle.

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

TECHNICAL NOTES. Literature Review on Hybrid Fire Suppression Systems. Peter Raia Michael J. Gollner University of Maryland

EXPERIMENTAL STUDIES ON THE EFFECT OF THE FIRE POSITION ON PLUME ENTRAINMENT IN A LARGE SPACE

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

Hot Issues in Fire Engineering 28 February 2012

Max Fire Box Users Guide

WAS STARTED BY CARLOS BAHAMONDES MASAFIERRO

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

An Overview of Extinguishing Systems for Computer Equipment

EXPERIMENTAL STUDY ON EXTINCTION OF A POOL FIRE WITH WATER MIST

Water Mist Fire Suppression

Analysis of Water Mist Suppression with Foam Additive in Wind Generator

Performance of an Improved Household Refrigerator/Freezer

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

SCALE MODEL STUDIES ON SMOKE MOVEMENT IN INCLINED TUNNEL WITH LONGITUDINAL VENTILATION AND SMOKE BARRIERS

Suppression of pool fire in a large enclosure with water mist

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

NECESSITY OF CARRYING OUT FULL-SCALE BURNING TESTS FOR POST-FLASHOVER RETAIL SHOP FIRES

Heat Release Rate of an Open Kitchen Fire of Small Residential Units in Tall Buildings

PRELIMINARY EXPERIMENTAL STUDY OF DOUBLE-SKINNED FAÇADE

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

EXPERIMENTAL CLEAN ETHANOL POOL FIRE SUPPRESSION BY USING WARM WATER MIST

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Research on Mobile Water Spray Device Reducing the Temperature of Metro Fire

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Shalaby Institute of Fire Protection Heyrothsberge, Germany.

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

2. Gas B. The column of hot gases, flames, and smoke rising above a fire; also called convection column, thermal updraft, or thermal column

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

K.F. Fong *, C.K. Lee, T.T. Chow

Department of MCE, Islamic University of Technology 2. Abstract

Modeling water-mist based suppression of 34 GJ car-deck fires using FDS

2012 International Symposium on Safety Science and Technology Investigation on compressed air foams fire-extinguishing model for oil pan fire

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING

FULL-SCALE BURNING TESTS FOR RETAIL SHOP FIRES: PRELIMINARY STUDIES

Sprinklers Modeling for Tunnel Road Fire Fighting

THE CONTROL METHOD OF THE INFLOW TURBU- LENCE INTERACTION NOISE FOR ROUTER COOLING FAN

CFD Simulation of the Water Mist Effect on Fire

Hot Air-Microwave Combined Drying Characteristics of Gypsum Board. Won-Pyo Chun, Sung-Il Kim, and Ki-Woo Lee 1

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

Jonathan Redding Area Sales Manager FOGTEC Fire Protection Cologne, Germany

ASSESSING FIRE SAFETY PROVISIONS FOR SATISFYING GREEN OR SUSTAINABLE BUILDING DESIGN CRITERIA: PRELIMINARY SUGGESTIONS

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

A study for a fire spread mechanism of residential buildings with numerical modeling

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS

Experimental Room Fire Studies with Perforated Suspended Ceiling

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Study on the Interaction of Water Mists with Fires in the Confined Space

Study on an environmental simulation system of low/high temperature. for great space

CFD Analysis of Fire Characteristics on Subway Junction Station

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

Thermal Performance Enhancement of Inclined Rib Roughness Solar Air Heater

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

COOLING SYSTEMS FOR CONTINOUS GALVANIZING LINE Miroslav Raudensky a, Milan Hnizdil a, Jaroslav Horsky a, FrédéricMarmonier b

ASSESSMENT OF TIMBER PARTITION MATERIALS WITH FIRE RETARDANTS WITH A ROOM CALORIMETER

Simulation of Full-scale Smoke Control in Atrium

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

I wish I could protect my business with the most suitable Water Mist solution to fit my needs.

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Computational Study of Effects of Drop Size Distribution in Fire Suppression Systems

Laboratory study on the cooling effect of flash water evaporative cooling technology for ventilation and air-conditioning of buildings

Sprinklers in Combustible Concealed Spaces

MIST FIRES AND EXPLOSIONS: FACT OR MYTH? Introduction

Recent Advances in Energy, Environment and Economic Development

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Development of Bionic Air Cooler Used in High Temperature Coal Mine

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

How design fires can be used in fire hazard analysis

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

Transcription:

, Volume 5, Number 4, p.170-175, 2003 REVIEW ON WATER MIST FIRE SUPPRESSION SYSTEM N. Zhu Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water mist fire suppression system (WMFSS) is one of the candidates in substituting the Halogen-based total flooding system. The system with strong spray momentum gives a satisfactory performance in extinguishing solid fires, liquid fires as well as kitchen fires under no ventilation. Nozzle with high discharge momentum and low operating pressure are the goal. Water mist discharged is assumed to evaporate completely when they meet the flame. In this way, a WMFSS can be used to extinguish electrical fires. However, it is observed that very fine water drops are very easily affected by indoor aerodynamics. The mist might not able to reach the flame if there is a strong upward air movement induced by the plume, and mechanical ventilation if there is any. Therefore, understanding this phenomenon is important for integrating the design of a WMFSS with the mechanical ventilation system. Measuring the extinguishing time could also indicate the effectiveness of the WMFSS under different conditions. This paper will review some characteristics of the WMFSS like nozzle design, extinguishing time and interaction with ventilation. Currently, to develop a practical design and testing guide for general application in premise is the most urgent need. Keywords: water mist, ventilation, extinguishing time, heat released rate, nozzle design 1. INTRODUCTION Water Mist Fire Suppression System (WMFSS) is an active fire extinguishing system. It is a candidate to substitute the banned Halogen-based total flooding system after 1987. Its first application appeared in 1940s. However, it did not become popular like sprinkler systems due to high techniques requirements, high investment and no general guide to follow. At that period, WMFSS was mostly used in marine applications to protect the machine and cruises lives. The systems attracted the attention from the industry after the whole world has started to care about global environment. The system is very clean and green. There is no ozone depletion effect and global warming effect as the system makes use of water as the extinguishing medium. The WMFSS utilizes phase cooling, oxygen displacement and radiation attenuation as the major tactics to extinguish a fire. The total heat extraction consisted of two parts as heat transferred and heat evaporated [1]. It is known that with enough discharging momentum, the heat transfer coefficient could be maximized mostly. When the water drops size reduced, the total surface area of water droplets increased. The time for water mist to absorb heat and evaporate to steam was then reduced. Therefore, the extinguishing ability could be increased and water damage was minimized. The oxygen displacement also plays a major role in extinguishing fire [2]. Under normal atmospheric pressure, the water drop expanded around 1900-fold when evaporation at high temperature. The rapid expansion of water vapor displaced the air around the flame. As the oxygen concentration level was reduced below the flammable limit, the starving effects slowed down the development of the flame and even reduced the flame height. The radiation attenuation can prevent the fire spreading to the un-ignited fuel which enlarged the pre-flashover time effectively. The radiation emitted from the burning fuel did harm to the people and protected objects inside the compartment. Radiation blockage by the water mist inside the compartment could protect human beings and equipment in addition to extinguish the fires. It was reported that when the water droplets were smaller than 50 µm, they could attenuate the radiant heat more effectively. It was hypothesized that the fine water drops absorb the radiant heat from the flame and re-radiate the lower temperature droplet or vapor. 2. DESIGN OF WATER MIST NOZZLE The system consists of pressure source, water source, pipe-net as well as the water mist nozzle. Every component in the system is important to ensure the stable extinguishing performance of the system. Among all, the nozzle seem to be the most critical part because a well designed and installed nozzle could ensure fine enough water drops and maintain the discharging distribution properly. Therefore, the design of the water should be studied clearly and carefully. There are three types of nozzles in the major streams of the market based on the water mist generation principles. They are impingement nozzle, pressure jet nozzle and twinfluid nozzle. In addition to these three, there are 170

also some innovations on generating fine or ultrafine water mist [3]. Impingement nozzle The impingement nozzle has some similarities to a conventional sprinkler nozzle on the appearance as well as the inner structure aspects. The impingement nozzle has a deflector in front of the small orifice. Sometimes, the diffusers are in ballshape, plat shape or other special spiral-shape. When the water is discharged from the water inlet, it strikes onto the diffuser and break-up into water mist. Most impingement type nozzles have screens to filtrate the water and prevent the small orifice from blocking by some substances in the water. The impingement nozzles are directly connected to a water source, in most cases the water pump and could be controlled either manually or automatically. Pressure jet nozzle The high water pressure only type nozzle has no diffuser or deflector. The generation principles of pressure jet nozzle are to make use of high pressure to push the water through the small orifice with high velocity. After leaving the orifices, the jet of water breaks up into fine water drops due to the complex physical change including fluid viscosity, jet diameter and the velocity of the jet. In order to create fine enough drops, the operation pressure needed is higher than that of impingement nozzle. The higher pressure offered, the finer the water drops will be. However, there is an upper limit for the pressure required. When the pressure reaches the upper limit, further increase will not lead to the increasing of the fine magnitude of water drops from the nozzle. Many companies provide removable nozzle cap for the easy clean and maintenance of the nozzle head. Twin fluid nozzles In addition to the single-phase flow type nozzle, twin fluid nozzle is also widely adopted in the industry. It makes use of compressed gas as the atomizing medium. The compressed gas shear the water into fine water drops in the mixing chamber and discharging from one or several orifices. The advantages of using the twin-fluid nozzles are that the system could use low pressure to generate fine enough water droplets. Therefore, the common types of pipes and valve could be used. However, the dual pipe-system increasing the initial input and the balance of air and water pressure also raises the complexity of the system design. Recently, Yang et al. [4] have developed a twinfluid nozzle by using the emulsible substance as the atomizing medium. The operating principles are that when the compressed air is passing though the air atomizing orifice, the velocity of the air is further increased to a higher level. Meanwhile, the under pressure water passes through the water atomizing orifice and raises the velocity also. When the high velocity water flow strikes and collides with several high velocity air flows from the orifices, the water begins to have emulsification phenomenon in the mixing chamber. It is known that after emulsification, the viscosity and surface tension of the water drops are decreased. The characteristics of emulsible water are very unsteady and easy to break up into smaller pieces when meeting the disturbance. The emulsible water inside the mixing chamber is still remaining very high pressure. When it is discharged from the discharging orifices, it could break up to the water mist with expected water droplet sizes. By flashing of superheated water There is a generation method which is not applied so widely, i.e. generating water mist by flashing of superheated water. The main principles of this method are to make use of the change of pressure and temperature. When the superheated water which is with 175 o C in an under-pressure container with 10 bar released to atmosphere, certain percentage of superheated water flashes into the vapor, and then condenses into fog form. By using this method, much finer water droplets could be produced than by any mechanical generation methods. The sudden energy release leads to the intense cooling of the spray. Therefore, after traveling for about 30 cm, the temperature of the water mist could reach not higher than 35 o C. This method is developed by Brown and York in 1962 [5]. Recently, Mawhinney has carried out some studies on this topic that led to a conclusion that ultra-fine water droplets may not be more effective than the normal water mist droplets in extinguishing the liquid pool fire [6]. 3. EXTINGUISHING PERFORMANCE REVIEW There are many factors to indicate the effectiveness of the WMFSS. For instance, change of HRR, change of room temperature, change of the gas concentration inside the compartment as well as the extinguishing time can reveal the extinguishing performance of the WMFSS to some extent. Integrated all these factors could show the true scenarios and system performance more concrete and accurate. However, only using one or some of the factors could simplify this engineering problem when comparing the different systems on the same basis. Picking extinguishing time as the indicator is 171

the consideration for easy comparison as well as better understanding for users. WMFSS could be applied differently like totalflooding system, local applied system or even portable extinguisher. For the total flooding application, many researches have been conducted. Series of experiment were carried out by Pepi to reveal the intermediate pressure WMFSS for extinguishing the flammable liquid fire [7]. It was found out that WMFSS spent around double time to extinguish the high pressure spray fire than that with low pressure. For Class A fires, the extinguishing time was exceeding 10 minutes in the experiments which is quite long and could be regarded as an unsatisfactory performance. For the local application, the Minimum Spray Heat Absorption Ratio (SHAR) is more important to be considered than that in total-flooding system [8]. Enough mass of water should be provided by the nozzle to reach the minimum heat extraction value. Through some case studies, it was also found that the extinguishing time could be very short which is in the order of seconds for a good nozzle location. However, if the burning objects have a longer preheat period, a much longer spraying time is required to prevent the re-ignition. For water mist portable extinguisher, it was found that the extinguishing time for the liquid fire like cooking oil and flammable liquid fire was very short within 5 s [9]. For the solid fire, no fire flareup was observed and the fire was quickly controlled. The extinguishing performance for the solid fire was highly dependent on that the water mist applied. In addition to the different applications, different fuel type, fire size and fire location, the extinguishing times are also affected greatly. For instance, according to Table 1, it is obviously to see that for different fuel type, the extinguishing time is different even for the same fire size [10]. When the fire size, i.e. the Heat Released Rate (HRR) increases, the extinguishing time reduces. It indicates that the WMFSS is more effective for extinguishing bigger size fires. Table 1: Comparison of extinguishing time for different flash-point liquid fires Types of fires HRR Extinguishing times Heptane spray fire 1.0 MW 1:34 Diesel spray fire 1.0 MW 3:13 Heptane spray fire 2.0 MW 0:20 Diesel spray fire 2.0 MW 0:38 Heptane spray fire 6.0 MW 0:26 Diesel spray fire 6.0 MW 0:50 4. INTERACTION WITH VENTILA- TION CONDITIONS As the water droplet is so fine that they are very easily affected by the aerodynamic circumstances inside the compartment, therefore how the mechanical ventilations affect the performance of the WMFSS should be studied in more detail. The ventilation conditions could affect the extinguishing time, gas concentration, the water discharge pattern as well as other performances of the WMFSS. In several design guides, like NFPA 750 and SFPE handbook, it generally assumed that all the MVAC system for thermal comfort should be shut down upon activation of the WMFSS [2,11]. If the MVAC system was still working or there was some natural ventilation existing, the performance of WMFSS might be affected. A study on the performance of WMFSS under ventilation conditions were carried out by Liu et al. [12]. Three ventilation circumstances including no ventilation, natural ventilation and forced ventilation were tested. From experiments, they showed that the ventilation would not have so big impact on the water mist discharged with strong spray momentum and vice versa. It is concluded that in order to achieve a better fire extinguishing performance, enough spray momentum should be offered. A series of experiments were conducted to investigate the performance of the low pressure WMFSS and it was concluded that it was most difficult to extinguish a low flash point liquid pool fire in a ventilation compartment. From Fig. 1 and Fig. 2, it was clear that no extinguishment happened when the door was open. At the position near the ceiling, the room temperature is 5 o C higher in the case of natural ventilation than that with no ventilation. The possible explanation was that the water mist drops might escape from the door way and the system lost some extinguishing capacities. In order to give a clearer picture on the ventilation effect for the WMFSS, some small-scale experiments were carried out in the fire chamber of Department of Building Services Engineering of The Hong Kong Polytechnic University. The results are shown in Fig. 3. It is shown that when the room was under forced ventilation conditions, the room temperature remained in high level as the fire was only controlled but not extinguished. In the natural ventilation case, the extinguishing time was a little longer than that with no ventilation. 172

Temperature (C) Discharge Ignition Extinguishment Elevations 2.90m 2.35m 1.80m 1.25m 0.70m 0.15m 38 o C Time (s) Fig. 1: Room temperature for pool fire with door closed Discharge Elevations Temperature (C) Ignition 2.90m 2.35m 1.80m 1.25m 0.70m 0.15m 43 o C Time (s) Fig. 2: Room temperature for pool fire with door open In addition to affecting the room temperature, it can be clearly seen from Table 2 that the extinguishing time increased when the WMFSS was operated under ventilation conditions. When the ventilation system in the compartment is operated, the main extinguishing mechanisms might be changed as the ventilation rate [13]. With limited ventilation and heat entrapment, the oxygen concentration in the compartment can be reduced rapidly. However, in the case of well-ventilated fire, the total discharged water should be enlarged dramatically even to 10 times. 173

180 150 Discharge No ventilation Natural ventilation Temperature (C) 120 90 60 30 Ignition 0 Fig. 3: Room temperature for pool fire with different ventilation conditions 0 40 80 120 160 200 Time (s) Fig. 3: Room temperature for pool fire with different ventilation conditions Table 2: Comparison of extinguishing time for different ventilation conditions Case Type of fire Fire size Ventilation conditions Extinguishing time Case 1 1 shielded round fire 500 kw No ventilation 1:55 1 shielded round fire 500 kw With ventilation 2:48 Case 2 1 shielded spray fire 520 kw No ventilation 1:53 1 shielded spray fire 520 kw With ventilation 3:47 5. CONCLUSION The WMFSS is a good alternative for the Halogen based total flooding system. It has no damage to the environment and also has a strong capability in extinguishing liquid fires under no ventilation conditions. The water mist nozzle is a key component for ensuring the system performance and therefore, WMFSS designers and researchers should pay attention to nozzle design. Although the WMFSS has many advantages, the case-dependent and varying performance of the WMFSS under ventilation conditions creates a significant problem in practical applications. Therefore, more studies both by experiments and by modeling should be conducted further. ACKNOWLEDGEMENT This project is funded by a PolyU research studentship. REFERENCES 1. M.M. Braidech, J.A.Neale, A.F. Matson and R.E. Dufour, The mechanisms of extinguishment of fire by finely divided water, Underwrites Laboratories Inc. for the National Board of Fire Underwriters, N.Y., pp. 73 (1955). 2. J.R. Mawhinney and R. Solomon, Water mist fire suppression systems, Fire Protection Handbook, National Fire Protection Association, Quincy, Mass, USA (1997). 3. Z.G. Liu and A.K. Kim, A review of water mist fire suppression systems - Fundamental studies, Journal of Fire Protection Engineering, Vol. 10, No. 3, pp. 32-50 (2000). 4. L.J. Yang, W. Wang, Z.B. Hu and Z.P. Zhang, Study of atomizing characteristics of two-phase flow emulsification water mist nozzles, Beijing Hong Kong Hang Tian Da Xue Xue Bao/Journal of Beijing University of Aeronautics and Astronautics, Vol. 28, No. 4, pp. 413-416 (2002). 5. R. Brown and J.L. York, Spray formed by flashing liquid jets, American Institute of Chemical Engineers Journal, Vol. 8, No. 21, pp. 149-153 (1962). 174

6. J. Keary and R. McGovern, Characterization of a heated water extinguishing system, Unpublished manuscript, Department of Experimental Physics, University College Galway, Galway, Ireland (1994). 7. J.S. Pepi and M. Arvidson, Machinery space fire test data on a diffuser-impingement water mist nozzle, Fire Suppression and Detection Research Application Symposium, Orlando, Florida (1997). 8. R. Wigus, Engineering relations for water mist fire suppression systems, Proceedings of Halon Options Technical Working Conference, Albuquerque, NM, pp. 397-409 (1995). 9. Z.G. Liu, A.K. Kim, D. Carpenter and P.L. Yen, Portable water mist fire extinguishers as an alternative for halon 1211, Proceedings of Halon Options Technical Working Conference, Albuquerque, NM, pp. 435-439 (2001). 10. J.S. Pepi, Performance evaluation of a low pressure water mist system in a marine machinery space with open doorway, Proceedings of Halon Options Technical Working Conference, Albuquerque, NM, p.424 (1995). 11. NFPA 750, Water mist fire suppression system, National Fire Protection Association, USA (2000). 12. Z.G. Liu, A.K. Kim and J.Z. Su, Examination of performance of water mist fire suppression systems under ventilation conditions, Fire Protection Engineering, Vol. 11, No. 1, pp. 164-193 (2001). 13. Z.G. Liu, A.K. Kim and J.Z. Su, Examination of the extinguishment performance of a water mist system using continuous and cycling discharge, Fire technology, Vol. 35, No. 4, pp. 336-361 (1999). 176