Clarification. Summary of Changes. Summary of Changes. Alan Cavers Area Manager Fire & Security Systems Group

Similar documents
Canadian Fire Alarm Association (CFAA)

CERTIFICATION BULLETIN

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Building Name: Our Lady of Sorrows Date: July 10, 2013

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

CERTIFICATION BULLETIN

Louis-Philippe Gagnon Alarm System Auditor UNDERWRITTERS LABORATORIES OF CANADA May 13 th, 2015

Changes in NFPA

Fire Signal Receiving Centres vs. Proprietary Fire Signal Receiving Centres CAN/ULC-S561 ALAN CAVERS ULC

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

CAN/ULC-S561. To comply, or not to comply. actually it s not even a question! Underwriters Laboratories of Canada. By Alan Cavers & Brian McBain

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Fire Resistant Cables - Update Alan Cavers Engineering Manager Certificate Services Group

Fire Alarm System Fundamentals

BULLETIN BU/EL Revised August 11, 2015

2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

STANDARDS BULLETIN

Fire Alarm System Training

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

VERIFICATION OF FIRE ALARM SYSTEMS

Full Service Central Station Fire Alarm Listing Evaluation

FIRE & LIFE SAFTEY STANDARD

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

1 Exam Prep Fire Alarm Signaling Systems Tabs and Highlights

Recent Revisions and Proposed Key Changes to Fire Code

Bold items are particular to the City of Euless

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

NFPA 72 Code Changes vs 2013

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

Interfacing Fire Alarm, Sprinkler and Elevator Systems

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

FIRE SAFETY REQUIREMENTS FOR PRE RESIDENTIAL BUILDINGS OF THREE OR MORE STORIES (DOROTHY MAE ORDINANCE - NO. 158,963)

SECTION FIRE ALARM SYSTEMS

OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

The following information shall become and form part of the contract documents.

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

BY-LAW AMENDING THE BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL (RCG )

CAN/ULC-S E1. FIRE ALARM SYSTEM ANNUAL TEST & INSPECTION REPORT (Reference: Clause 5.1.2)

Unified Fire Authority - Fire Prevention Bureau

HIGH-RISE RETROFIT ORDINANCES - NO and NO

MODEL B2 INSTALLATION MANUAL

UEI-1 UNIVERSAL END-OF-LINE / ISOLATOR TESTER

SECTION ADDRESSABLE FIRE ALARM SYSTEM

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

NFPA Changes

BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm

CFAA Technical Seminar Ontario Building Code Updates to 2015

Operation & Maintenance Manual

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

SECTION : FIRE ALARM & DETECTION SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

rpsa FIRE PROTECTION ENGINEERS

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

11:00 to 12:00 Secrets to achieving code-compliant strobe installations. Ralph Coco, Potter Canada Paul Jewett, Mircom Group of Companies

3.1 Introduction. 3.1 Introduction

OAA Conference ,

RELEASE DEVICE CONTROLS

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Functional Performance Test

Florida Building Code 2010

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

COMMISSIONING OF LIFE SAFETY AND FIRE PROTECTION SYSTEMS: WHAT, WHERE AND HOW?

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Notification Appliance Circuit Module

Australian Standard. Automatic fire detection and alarm systems System design, installation, and commissioning AS

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

The EN54 Part 2 and 4 Fire System

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

Photovoltaic (Solar) Array Installation Guide

Fire Alarm System Inspection and Testing Report

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

BCBC 2012 CHANGES TO PART 3

ENERGY EFFICIENCY AFTER DECEMBER 31, 2016

COURSE SYLLABUS FIRE ALARM AND FIRE SUPPRESSION SYSTEMS CORRESPONDENCE COURSE

Major Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing

SECTION INTRUSION DETECTION

Model 17A00 Expansion Enclosure

NFPA Changes

Transcription:

Summary of Changes CAN/ULC-S524-06 Installation of Fire Alarm Systems Alan Cavers Area Manager Fire & Security Systems Group Course Title Rev Date: Summary of Changes Correct Deficiencies noted CAN/ULC-S524-01 Clarification S524-01 Edition Glossary of Terms Control Units and/or Transponders- Added New Section on Fault Isolation Modules Data Communication Links- Clarified and Expanded Slide 2 Summary of Changes Clarification To make this Standard easier to interpret. Slide 3

NBC Requirement 3.2.4.5.(1) Fire alarm systems, including the voice communication capability where provided, shall be installed in conformance with CAN/ULC- S524, Installation of Fire Alarm Systems. Slide 4 Requirements of Fire Alarm Systems 3.1.1 A fire alarm system shall consist of at least the following interconnected devices: a control unit, a manual station and an audible signal device. 3.1.2 A fire alarm system may include devices such as fire detectors, visible signal devices, annunciators and other equipment required to provide voice communication capability. Slide 5 Requirements of Fire Alarm Systems 3.1.3 (J) Devices and Equipment used in a fire alarm system, and the interconnection to the fire signal receiving centre shall comply with CAN/ULC-S561, The Standard for Installation and Services for Fire Signal Receiving Centres and Systems 3.1.4 All devices incorporated in a fire alarm system shall be compatible. 3.1.5 Ancillary devices connected to a fire alarm system shall not interfere with the operation of the fire alarm system. Slide 6

Requirements of Fire Alarm Systems 3.1.6 Where ancillary devices are powered by a fire alarm system, the primary power supply and emergency power supply of the fire alarm system shall be of sufficient capacity to operate both the fire alarm system and the ancillary devices. Slide 7 Requirements of Fire Alarm Systems 3.1.9 Receiving an alarm input normal to offnormal status change shall cause the fire alarm system to perform the required function. Slide 8 Requirements of Fire Alarm Systems 3.1.10 Control units and/or transponders arranged for single stage operation shall comply with the following: (Reference Table 2) 10 Second Response Time ( Audible & Visual Signal Devices, Interconnection to Signal Transmitting unit,releasing Devices, Annunciation, CACF, Ancillary Circuit) 90 Seconds - Trouble Slide 9

Requirements of Fire Alarm Systems 3.1.11 Control units and/or transponders arranged for two stage operation shall comply with the following A. A first stage signal input normal to off-normal status change shall result in an alert signal. Activation of all or selected alarm signal devices connected to the system shall operate within the response time as detailed in Table 2; Slide 10 Requirements of Fire Alarm Systems B. All other functions, such as interconnection to the signal transmitting unit, releasing device service start of sequence, annunciation, central alarm and control facility annunciation and ancillary devices or circuit functions shall perform as intended within the response time as detailed in Table 2; and C. Initiation of a second stage signal input normal to offnormal status change, either manual or automatic, shall result in alarm signalling within response times as detailed in Table 2. Slide 11 Power Supply 3.2.1.1 Two independent power supplies shall be provided; one primary and one emergency, in accordance with the NBC Dedicated power source Continuous Supply under full load. Clarified- No real Change Slide 12

Primary Power Supply 3.2.2.1 Power supplied to the fire alarm system shall be provided from a separate dedicated circuit, except where a distributed type system is provided as described in Clauses 3.2.1.5 and 3.2.3.2. Label Stating One or more sources of power. 3.2.2.2 The primary power supply shall be capable of continuously supplying power for operating the fire alarm system under the installed full load condition. Slide 13 Emergency Power Supply 3.2.4.1 Where the emergency power supply is an engine-driven generator, it shall be installed in accordance with CSA C282, Emergency Power Supply for Buildings, or CAN/CSA-Z32, Electrical Safety and Essential Electrical Systems in Health Care Facilities. Clarification Slide 14 Emergency Power Supply 3.2.5.1 Batteries providing the emergency power supply shall conform to Clauses 3.2.5.2 through 3.2.5.4 and to CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for Electrical Installations, pertaining to batteries. Clarification Slide 15

Electrical Supervision 3.3.1.2 - Fire alarm system devices connected in an electrically supervised circuit shall be connected so that removal or disconnection of any device shall cause a trouble signal to be initiated. Clarification Slide 16 Separation of Primary and Alternate Wiring Circuit 3.3.1.3 In Class A circuit wiring, DCL style A and DCL style C wiring, the primary wiring circuit and the alternate wiring circuit shall be installed in separate raceways or cable assemblies having a minimum separation of 300 mm where the cables are installed vertically and 1200 mm where the cables are installed horizontally, except under the following conditions: Slide 17 A. Single conduit/raceway drops to individual field devices; or B. For a distance not to exceed 3000 mm where the primary and return conductors enter or exit the field devices, control unit or transponder enclosures; C. Single conduit/raceway drops to multiple field devices installed within a single room not exceeding 100m 2. Slide 18

Exceptions A. Single conduit/raceway drops to individual field devices; or B. For a distance not to exceed 3000 mm where the primary and return conductors enter or exit the field devices, control unit or transponder enclosures; C. Single conduit/raceway drops to multiple field devices installed within a single room not exceeding 100m 2. Slide 19 Trouble Signals 3.3.2.3 An audible trouble signal shall continue to sound until manually silenced or until the trouble condition is restored to normal. Reminder Defining Trouble Slide 20 Wiring Methods 3.4.10 Field wiring entry points for the various circuits and circuit separations shall in accordance with the manufacturer s installation instructions and CSA-C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations, Section 12, Wiring Methods. Explanation- Reinforcing this section Installations in field that do not meet code (No ground, No Conduit, etc.) Slide 21

Plans and Specifications 3.5.1.E The plans and specifications for the fire alarm system shall include a complete and detailed description of the connection to a fire signal receiving centre, if required by the NBC. Slide 22 Documentation of Fire Alarm System (FAS) 3.5.4 - Documentation for the FAS shall include the following description of the FAS A. Instructions for resetting the system and silencing the alarm signals; B. Instructions for silencing the trouble signal and action to be taken when the trouble signal sounds; C. Description of the function of each operating control and indicator on the fire alarm unit; Slide 23 Documentation of Fire Alarm System (FAS) Cont d D. Description of the area of fire zone protected by each alarm detection circuit (this may be in the form of a list or plan drawing); E. Description of the sequence of operation; F. Description of ancillary devices controlled by the fire alarm system; G. Equipment operating instructions or manuals; and H. Equipment maintenance or testing instructions. Slide 24

New Documentation Requirements 3.5.5 The documentation required by Clauses 3.5.1 to 3.5.4 shall be maintained on site. Requirement exists in S536 and S537. Fire Alarm System File. Slide 25 Installation of Fire Alarm Equipment 4.1.1 Clear space shall be maintained in front of control units and transponders equal to the width of the door, but not less than 1000 mm, to provide access for maintenance and testing. Slide 26 Installation of Fire Alarm Equipment 4.1.2 The top of control units and transponders shall be not more than 2400 mm above the finished floor level. 4.1.3 - Legend or operating controls shall be not more than 1800 mm above the finished floor level. Slide 27

New DCL Requirements 4.2.4 Where control units or transponders utilize DCLs, the loading requirements of Table 3 shall apply as follows (sub-clause A to D) Table 3 - Capacities of Systems Utilizing Data Communication Links within a Single Building has been revised. New figures, Figures 2-1, 2-2, 2-3, 2-4 and 2-5 that show schematics. Slide 28 Data Communication Link (DCL) Terminology change S524-01 DCLR has been changed in S524-06 to DCLC. DCL Style C A data communication link style with a primary wiring and an alternate wiring circuit with operational characteristics as detailed in Table 1 Performance of DCL. Slide 29 Table 1 Performance of DCL Abnormal operating condition in a link at the same location DCLA DCLB DCLC Single Open S T S Single Ground S S S Wire to wire short T T S1 Wire to wire short and ground T T S1 Open and ground S T S Loss of communication T T T T-Trouble indication at the control unit; S-Trouble indication at the control unit and alarm receipt capability during abnormal operation; S1-Trouble indication at the control unit and alarm receipt capability (beyond the isolated fault section of the link) during abnormal operation Slide 30

DCL Style A Redundant Loop- Class A Wiring Separate Loop for each zone Extra Wiring Multiple Trunks Slide 31 DSL Style A Slide 32 DCL Style B Class B Wiring Methods Use of EOL s No Back up or return loop Loose entire loop Slide 33

DCL Style B Slide 34 DCL Style C Class A with Isolators Separate/identify the problems Other circuits not affected Zone Separately Slide 35 DCL Style C Slide 36

New DCL Requirements 4.2.4.D The types of initiating devices to be considered when establishing the total number of connected devices shall include active field devices and supporting field devices. Conventional field devices monitored by a supporting field device are not considered in the maximum DCL capacity. DCL A = 300 DCL B = 200 DCL C = 300 Slide 37 Large Scale Networks 4.3 Requirements for Large Scale Network Systems revised. Operation in Degraded Mode Standalone capability Requirements for DCL between Control Units and Transponders Slide 38 Fire Separation 4.3.7 Each control unit and transponder shall be located in an electrical service room and/or central alarm and control facility separated from the remainder of the building by a 1 h fire separation. Note: Multiple control units or transponders installed in the same room within 18m of each other, which are interconnected to operate as a single unit, may be considered as a single control unit or transponder. Slide 39

Installation of Fire Alarm Devices Section Revised Better Directions for installation Clarification Slide 40 Installation of Fire Alarm Devices 5.2.1 Manual stations shall be installed not less than 1200 mm and not more than 1400 mm above the finished floor level measured from the centre of the manual station. REVISED 5.2.5 Manual stations shall be installed on both sides of a series of doors exceeding 12m in total width, and within 1500mm of each side of the opening. NEW Slide 41 Audible Signal Devices 5.4.1.1 Where ceiling heights allow, audible signal devices shall be installed so that the top of the device will not be less than 2300 mm above the finished floor level. Exception: This requirement does not apply to insuite signaling devices with integral silence means. Slide 42

Audible Signal Devices 5.4.1.2 Wall-mounted audible signal devices shall be installed at least 150 mm below the ceiling, measured to the top edge of the device. New Section Slide 43 Audible Signal Devices 5.4.1.7 Audible signal devices within a building shall generate similar sounds and sound patterns when activated. Section Reworded Slide 44 Visible Signal Devices Completely Revised 5.4.5.2 - Two or more visible signal devices in corridors or rooms in the same field of view shall flash in synchronization. 5.4.5.3 Wall-mounted visible signal devices shall be installed such that the entire lens is not less than 2000 mm and not more than 2400 mm above the finished floor. Slide 45

Mounting of Fire Detectors 5.6.1.3 - Each fire detector shall be accessible for periodic maintenance and testing. Where spot type fire detectors are not readily accessible due to safety considerations (e.g. continuous process operations, energized electrical equipment, radiation, and excessive height) alternate methods of detection shall by utilized (e.g. beam type smoke detector or aspiration type smoke detector). Updated Section- Takes in consideration where to install detectors. Slide 46 Mounting of Fire Detectors 5.7.2.2 A clear space of at least 450 mm shall be maintained between a spot type fire detector and any obstruction, except as specified in Clause 5.7.2.3. (Refer to Figure 4). Obstructions and protrusions not exceeding 100 mm from the ceiling need not by considered as impinging on this clear space. Slide 47 Slide 48

Mounting of Fire Detectors 5.7.2.3 Spot type fire detectors shall be installed on the ceiling not less than 100 mm from the wall, measured to the edge of the detector, except as permitted in clause 5.7.5.1.1. Slide 49 Mounting of Fire Detectors 5.7.2.4 Spot type fire detectors shall not be located in a direct airflow or closer than 450 mm from an air supply outlet or from an air exhaust outlet measured to the edge of the detector. Slide 50 Spot Type Smoke Detectors 5.7.5.1.1 - Spot type smoke detectors may be installed on the wall 100 to 300 mm from the ceiling, measured to the edge of the detector. Slide 51

Spot Type Smoke Detectors 5.7.5.3.3 Interior horizontal exit passageways forming exit stair shafts exceeding 18 m in height shall be provided with spot type smoke detectors in accordance with Clause 5.7.1.1 and Subsection 5.7.3.7, Corridors. Slide 52 Spot Type Smoke Detectors 5.7.5.3.4 When spot type smoke detectors cannot be used due to abnormally low ambient temperature, below 0 C, appropriate fixed temperature spot type heat detectors may be installed. Slide 53 Fault Isolation Modules 5.14 New Section 5.14.2 - Fault isolation modules shall be utilized when entering and leaving each fire alarm zone, as required by the National Building Code of Canada. Slide 54

Fault Isolation Modules SIEMENS - Model HLIM Slide 55 Fault Isolation Modules 5.14.3 Except as noted in 5.14.4, fault isolation modules, shall be located in a separate enclosure, installed so as to be visible and accessible at all times, and located beyond the last device in the data communication link serving that floor area. Slide 56 Fault Isolation Modules 5.14.4 Fault isolation modules incorporated in a field device shall be mounted in accordance with the requirements of the field device. Note: Field devices incorporating fault isolation modules complying with Clause 5.14.2 do not require additional dedicated fault isolation modules. Slide 57

Fault Isolation Modules 5.14.5 Where a fire separation is provided, fault isolation modules required by Clause 5.14.2 shall be installed on each side of that fire separation. Slide 58 Fault Isolation Modules 5.14.6 Fault isolation modules installed on opposite sides of the same fire separation shall be offset horizontally to a minimum of 400 mm, and not located within the same stud space. Slide 59 Fault Isolation Modules 5.14.7 Where no fire separation is provided between each NBC required fire alarm zone, a single fault isolation module shall be utilized when isolating zones within the same floor area. Note: This Clause would be applicable to large horizontal buildings. For example, warehouses, shopping malls, factories, etc. Slide 60

Fault Isolation Modules 5.14.8 Fault isolation modules serving a single field device in an exit or vertical service space shall be installed on the floor area side. Note: Fault isolation modules are not required on the exit or vertical service space side. Slide 61 Fault Isolation Modules 5.14.9 Fault isolation modules shall have an identifying mark or label on the cover plate or field device. The identifier shall be visible after installation. Where field devices incorporating fault isolation modules are used to comply with Clause 5.14.2, the first field device entering and the last field device leaving each fire alarm zone shall be marked. Slide 62 Requirements of Fire Alarm Systems New fire alarm system requirement 3.1.3.(J) Devices and equipment used in a fire alarm system, and the interconnection to the fire signal receiving centre, shall comply with CAN/ULC-S561, Installation and Services for Fire Signal Receiving Centres and Systems. Slide 63

Interconnection to the Fire Signal Receiving Centre 5.15 New section 5.15.1 - The interconnection wiring from the fire alarm control unit or transponder to the fire signal receiving centre shall comply with CAN/ULCS561, Installation and Services for Fire Signal Receiving Centres and Systems. Refer to Appendix E, Responsibility Demarcations, for examples of responsibility demarcations. Slide 64 Typical S561 Installation Protected Premises Slide 101 Copyright 2006 Underwriters Laboratories Inc. All rights reserved Slide 65 Improper Installation Slide 66

Ordering ULC Standards ULC publications including Standards, Directories and ORDs are available via the ULC Online Store. Payment is accepted by VISA, MasterCard, or American Express. All products on the ULC Online Store are available in hardcopy only. http://www.ulc.ca/about_ulc/order_stand ARDS.asp Slide 67 Questions Slide 68 Thank You For Attending For more information on a private or public seminar on this topic or many other topics please go to: http://uluniversity.com/ca Or call 1-888-503-5536 Or Contact Linda Savo Manager, Customer Training 416-757-5250, Ext. 61222 Slide 69