Climate-Adapted Design

Similar documents
ASHRAE JOURNAL ON REHEAT

A New Approach to Museum HVAC Design ASHRAE TECHNOLOGY AWARD CASE STUDIES

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING

2014 ASHRAE TECHNOLOGY AWARD CASE STUDIES

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

Don t Turn Active Beams Into Expensive Diffusers

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Adding More Fan Power Can Be a Good Thing

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

Displacement Ventilation in Classrooms

Do All DOAS Configurations Provide the Same Benefits?

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

ASHRAE Illinois Chapter 2015 Excellence in Engineering Awards

Cold Weather Operation Of Cooling Towers

DIGI-VAV APPLICATIONS

Dehumidifying with Dedicated Outdoor Air

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

High-Performance VAV Systems

August 15, 2013 Page 1 of 19

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

4-Pipe VAV vs. Active Chilled Beams for Labs

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Summary Comparison of Simulation Program Features

4. OVERVIEW OF MECHANICAL SYSTEM

Technical Report Three

DESCRIPTION OF TECHNOLOGY

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Selected Laboratory Energy Efficiency Measures

Displacement Ventilation

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

COMcheck Software Version Review Mechanical Compliance Certificate

HVAC Controls Upgrades: Requirement Details ( )

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

CONSTRUCTION AND ENERGY COSTS FOR RADIANT VS. VAV SYSTEMS

IAQ: Re-tuning Commercial Buildings

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

Solana Ranch Elementary School

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

TECHNICAL REPORT 3 Mechanical Systems and Existing Conditions Northfield Mental Healthcare Center Northfield, Ohio

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

UNDERFLOOR PRODUCTS E3

Designing Energy Efficient Outdoor Air Systems

Best Practices for Condensing Boilers

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Designing Mega-AHUs BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

Paul McCown, PE, CEM, LEED AP, CxA Sr. Mechanical Engineer SSRCx, LLC Nashville, TN USA

SECTION HVAC TABLE OF CONTENTS PART 1 - SYSTEM DESCRIPTION / OUTLINE SPECIFICATIONS FILED SUB BID PROJECT OVERVIEW...

COMcheck Software Version Mechanical Compliance Certificate

Variable Air Volume with Indoor Air Quality

The Ed Roberts Campus

HVAC Controls Upgrades: Requirement Details ( )

Temperature Control and Zoning of UFAD Systems

2009 IECC Commercial Mechanical Requirements

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Daikin Blueprint: Delivering Hot Water with a Chiller

1 - This title will copy onto other forms Date

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

APPLICATION GUIDE BEAMS

Radiant Exchange in Stratified Environments: Considerations and Challenges for Hourly Energy Simulation of UFAD, DV, and Radiant Cooling Systems

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

CALIFORNIA MECHANICAL CODE OVERVIEW OF 2016 UPDATES CHANGES AND RAMIFICATIONS

Worried aboutthe air quality in your schools?

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Executive Summary. OA/person (cfm/p) Private and open offices, Classrooms, Building as designed

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Underfloor Air Distribution:

1. Packaged Variable Air Volume (VAV) Rooftop Units (RTU) with Hot Water Reheat. 2. Geothermal Heat Pump VAV Rooftop Units with Hot Water Reheat

Chapter 6 ALL-AIR HVAC SYSTEMS 6.1 CONTEXT

Making UFAD Systems Work BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

Job Name Control Systems Description Date

RE: Phase 2 Improvements DATE: July 1, 2016 New Administration Building Wernle Youth & Family Treatment Center 2000 Wernle Road Richmond, Indiana

ASHRAE/IESNA Standard

Strategies for Building Energy Efficiency

Challenges and Methods of Estimating a Conceptual HVAC Design

Technical Assignment 3

Transcription:

This article was published in ASHRAE Journal, May 2014. Copyright 2014 ASHRAE. Posted at www. ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. The Oakland Unified School District, La Escuelita Education Center maintains comfort using a multi-pronged conditioning strategy that relies on local climate, thermal mass and sophisticated controls. HONORABLE MENTION EDUCATIONAL FACILITIES, NEW Climate-Adapted Design For California School BY BRENT EUBANKS, P.E., MEMBER ASHRAE; AND GLENN FRIEDMAN, P.E., MEMBER ASHRAE BUILDING AT A GLANCE OUSD La Escuelita Educational Center Location: Oakland, Calif. Owner: Oakland Unified School District Principal Use: K 8 school, district administrative functions Includes: classrooms, two-story great room, offices, data center, kitchen, health clinic, TV studio Employees/Occupants: 1,850 Gross Square Footage: 71,500 Conditioned Space Square Footage: 54,900 Substantial Completion/Occupancy: August 2012 Occupancy: 100% National Distinctions/Awards: 2014 C.A.S.H./ AIACC Leroy F. Greene Design + Planning Awards Program; Award of Excellence, New Built Category; 2011 C.A.S.H./AIACC Leroy F. Greene Design + Planning Awards Program; Award of Merit, Project-in-Design Design Architect and Architect of Record: MVE Institutional The Oakland Unified School District (OUSD) is one of the largest in California with more than 80 schools and 36,000 students, primarily from low income communities. Funded by a bond, the La Escuelita Education Center (LEEC) project replaces an outdated campus consisting primarily of decrepit portable classrooms with a modern facility. OUSD-LEEC Phase 1 includes a kindergarten and elementary school, as well as district support facilities. The new LEEC campus meets the requirements of the California Collaborative for High Performance Schools (CA-CHPS), including compliance with ASHRAE Standards 55 and 62.1 (2010 versions), while maintaining the long-standing district policy of avoiding compressor-based cooling for classrooms and administrative offices. Brent Eubanks, P.E., is a mechanical engineer and certified permaculture designer and Glenn Friedman, P.E., is a principal at Taylor Engineering in Alameda, Calif. Both are members of the Golden Gate ASHRAE Chapter. 72

PHOTOS COURTESY OF NW ARCHITECTURAL PHOTOGRAPHY ABOVE AND LEFT Large ceiling fans in each classroom provide comfort cooling on the hottest days. COURTESY OF NW ARCHITECTURAL PHOTOGRAPHY These goals were achieved by a combination of building orientation, careful lighting and daylighting design, and an HVAC strategy that capitalizes on Oakland s Mediterranean climate with its reliable breezes and significant diurnal temperature swings. Systems Description While the data center, clinic, and TV studio use a highefficiency, single-duct VAV HVAC system, the classrooms do not use compressor-based cooling. Maintaining comfort required a multi-pronged conditioning strategy that relies on local climate, thermal mass and sophisticated controls. The classrooms and offices have operable windows (with switches that disable HVAC), allowing for occupant control and passive natural ventilation. When windows are closed these spaces are cooled by unconditioned 100% outdoor air from central AHUs. Displacement diffusers deliver air to the classrooms, which improves ventilation effectiveness and IAQ, and also rejects occupant heat from the space rather than mixing it into the rooms air mass. Air supply is controlled by demand and outdoor air temperature, delivering large volumes when the weather is cool but reducing to ventilation minimum when weather is warm. Additional cooling is provided by thermal mass: a 4 in. (25 mm) concrete floor slab and a 2 in. (25 mm) thick cement plaster layer on interior walls. Thermal mass is charged (cooled) at night by a high volume purge cycle, leveraging a cooling season diurnal temperature swing of 20 F (11 C) or more. This cycle is controlled based on outdoor air temperature, room temperature, and thermal mass temperature from sensors embedded in the floor and walls to minimize fan energy and avoid overcooling. This provides a thermal flywheel effect to maintain comfort even on warm days. A final element of the classroom cooling strategy is automatically controlled high volume, low speed (HVLS) ceiling fans. The fans are off during the first stage of cooling, when the supply air is cool, so that displacement ventilation provides beneficial stratification in the occupied zone. As the outdoor temperature (and, thus SAT) rises, the ceiling fans activate to provide up to 4 F (2 C) additional effective cooling. The ceiling fans also assist in heating, which is by parallel fan-powered VAV (FP-VAV) boxes with hot water coils in each room. Heated air is delivered via the same displacement diffusers used for cooling, while the ceiling fan operates at low speed to destratify the space and ensure uniform heating. These cooling and heating strategies are also applied in the great room, which has a dedicated single-zone AHU with economizer to provide heating, ventilation and 100% outdoor air cooling. However, the great room is periodically subject to high occupant densities, up to 10 ft 2 (0.9 m 2 ) per person. This exceeds what outdoor air cooling and thermal mass alone can support, so a pair of passive evaporative downdraft towers ( cool towers ) is employed to address these loads. The towers are 40 ft (12 m) tall and 12 ft (3.7 m) square with high-pressure fogging nozzles at the top that inject a modulated volume of very finely atomized water. The water evaporates and cools the air, which drops under buoyancy pressure, cooling the space and then relieving through automatic louver/dampers installed near the ceiling. Each tower also has a wind scoop that faces west into the prevailing wind to provide cooling and ventilation without evaporation when the weather is suitable. Tower and AHU controls are integrated so that the towers provide natural ventilation and respond first to a high CO 2 signal, energizing the AHU for mixed mode MAY 2014 ashrae.org ASHRAE JOURNAL 73

ventilation only when the towers cannot provide sufficient fresh air. FIGURE 1 Cooling by displacement ventilation (cool weather). Energy-Efficient Design Features OUSD-LEEC is intended to be a showcase green project, so minimizing energy use is a key priority. Strategies employed include: Classroom cooling strategy is based on thermal mass, natural and mixed mode ventilation, and ceiling fans rather than compressors. Cool towers provide as much as 50,000 cfm (24 L/s) and 90 tons (317 kw) of cooling without fans or coils on hot days, and natural ventilation on mild days. Ceiling fans use efficient direct drive electronically commutated (EC) motors, drawing 80 W to provide 4 F (2 C) of perceived cooling. AHUs use high-efficiency variable-speed fan arrays, with demandbased static pressure setpoint reset to minimize fan energy. FP-VAV boxes use efficient variable-speed EC motors. VAV-reheat boxes use dualmaximum control sequences and supply air temperature control, with demand-based supply air and static pressure resets to minimize reheat and fan energy. Cool Air Enters The Room at Low Velocity & Cascades Along Floor FIGURE 2 Cooling by automatic ceiling fan (warm weather). Warm Air Enters the Room at Low Velocity. Airflow Is Ventilation Minimum. FIGURE 3 Heating with automatic ceiling fan assistance (cold weather). Heated Supply Air Enters the Room at Low Velocity and Rises Toward The Ceiling Data center AHUs have digital scroll compressors and custom control programming to maximize airflow when economizer is available, and minimize fan energy, favoring DX cooling, when economizer is locked out. The system is 100% redundant with both units running to minimize fan power. Kitchen exhaust hood uses a variable-speed fan controlled by heat and smoke sensors to minimize exhaust when not actively cooking. Heating hot water is by condensing boilers with variable-speed pumping, with supply water temperature reset to maximize condensing operation. A 203 kw photovoltaic array provides an estimated 280,000 kwh per year. Hot Air Rises For Passive Relief Ceiling Fan Operates at High Speed For Comfort Cooling Ceiling Fan Operates at Low Speed To Destratify Room Solar hot water panels provide hot water for the kitchen and bathrooms. Classrooms and offices are designed for daylighting: oriented for southern exposures with overhangs and daylighting windows, orientation specific glazing, and automatic dimming controls. The design easily beats Title 24, with EnergyPro models showing savings of 29.9% in TDV energy use. When modeled according to CA-CHPS rules, which permit the inclusion of on site renewable energy, savings were 48.5% TDV energy and 55.6% energy cost relative to a baseline building. The data center was modeled separately, for a utility rebate program. Third-party analysis showed 72% energy savings relative to baseline. 74

Measured Energy Use The project includes extensive energy metering, independently measuring HVAC, lighting and plug energy. However, challenges during the controls installation and commissioning meant that no useful data was recorded in the first year of operation. While these issues have been corrected, going forward, detailed historical energy use data is not available. Campus-wide energy use intensity, calculated from utility bills, was found to be 41.7 kbtu/ft 2 (131.5 kwh/m 2 ) per year. For comparison, a baseline EUI was developed from CBECS data, weighted based on building areas used for different purposes (e.g., classroom, kitchen, datacenter, etc). With a weighted baseline of 57.8 kbtu/ft 2 (182.3 kwh/m 2 ), the project demonstrates a savings of 28% over baseline. In addition, a number of energy-wasting installation and controls issues were corrected during the commissioning process, so future savings are expected to be higher. 270 FIGURE 4 Evaporative downdraft cool tower. Prevailing Winds: Intake As the Mist Cools the Air, The Air Drops and Causes Airflow Pressurized Waterline FIGURE 5 Cooling season prevailing winds. Indoor Air Quality Per CHPS, low-emitting materials were used throughout the project to minimize pollutants. Classroom and office indoor air quality (and ASHRAE Standard 62.1 compliance) is ensured by 100% outdoor air ventilation and cooling with MERV 11 filters. Displacement diffusers enhance ventilation effectiveness, but ventilation minimums were not reduced. CO 2 demand-controlled ventilation is used in all classrooms, common areas, and conference rooms. Thermal Comfort ASHRAE Standard 55 compliance is a CHPS requirement, and cooling densely occupied (30 ft 2 to 45 ft 2 /person [3 m 2 to 4 m 2 ]) classrooms on an 89 F/66 F (32 C/19 C) design day without the use of compressors was one of the principal design challenges. Simulation demonstrated that high mass floors (145 lb/ft 3 [2323 kg/m 3 ]) and walls (95 lb/ft 3 [1522 kg/m 3 ]), coupled with night 300 240 330 210 360 10% 5% 12% Calm 180 Frequency by Direction 30 150 Mist Sprayers Exhaust Warm Air 60 120 90 270 300 240 330 210 Photovoltaics on All South Facing Sloped Roofs 360 15 kts 10 kts 5 kts 12% Calm 180 30 Average Speed by Direction cooling ventilation, maintains the worst-case room at or below 74 F (23 C) for 88% of a TMY-3 weather year. (Simulations assumed a conventional mixed-air system. Due to budget constraints, displacement was not modeled, but is understood to improve both ventilation and cooling performance, providing an additional margin of safety to the design.) For 12% of the year indoor temperatures are expected to range up to 85 F (29 C). During these periods the ceilings fans will operate automatically to provide up to 220 fpm (1 m/s) of cooling via air movement, maintaining comfort for lightly clothed individuals as shown in Figure 6. Adjustable thermostats and manual override 150 60 120 90 76

fan controls in every classroom give occupants local control of their space. There have been no too-hot comfort complaints. There were some too-cold complaints. These were traced to an incorrect boiler installation resulting in low hot water supply temperatures, which has now been corrected. Air Speed (fpm) Maintenance and Operations Construction was financed by a municipal bond, but operating expenses are paid out of general school district funds, so controlling operating costs was a design priority. Design features that minimize ongoing maintenance include: The fundamental cooling system thermal mass walls and floor does not require mechanical service and never breaks down. Classroom AHUs are very simple: just fans in a box, with no heating coil, cooling coil, compressors, pumps or economizer to maintain. Most fans use direct-drive motors, eliminating belt replacement. Ceiling fans are a robust industrial design with a 10-year warranty. The cool tower fogger system avoids water recirculation and evaporative media, eliminating periodic cleaning and most routine maintenance. Extensive power metering via the energy management and control system allows operators to observe energy use trends and identify loads that would otherwise be hidden. Cost Effectiveness Per our office standard, details such as duct and pipe sizes were determined by life-cycle cost analysis. However, due to client requirements and project funding structure, cost effectiveness calculations were not performed for the project as a whole. Client requirements dictated a high performance building without compressors, so a traditional HVAC system was not an alternative. The project itself is funded by a bond, while operating costs will be paid from the district budget two separate pools of money. As such, minimizing operating FIGURE 6 Design condition for ceiling fan cooling, from the Standard Effective Temperature chart (ASHRAE Standard 55). 276 197 118 39 1.1 met Local Control of Air Speed Local Control Not Required Still Air Comfort Zones In This Figure t r = t a PMV 0.5 Equal SET Contour 1.0 clo 0.5 clo PMV 0.5 PMV +.5 PMV +.5 0 64 68 72 73 75 79 82 86 90 Operative Temperature ( F) and maintenance costs was prioritized over construction costs. That said, the mechanical system ultimately cost $43/ft 2 ($463/m 2 ) within 10% of the schematic design cost estimate for a conventional HVAC system. Environmental Impact As a CHPS project, a number of non-mechanical design features reduce the project s environmental impact, including daylighting, water efficient fixtures, storm water control via bioswales populated with native plants, and rapidly renewable, recycled, and low emissions materials. A grant-financed 203 kw photovoltaic system will provide an estimated 280,000 kwh per year, offsetting 66.5 metric tons of CO 2 every year. Solar thermal panels provide for all domestic hot water use. The mechanical design serves to reduce environmental impact chiefly through the energy efficiency measures described above. In addition, the elimination of compressors and coils from the primary AHUs reduces the embodied energy of the mechanical system, while the use of foggers rather than evaporative media in the cool towers eliminates the water waste associated with sump blowdown. Innovation Some of the most innovative elements of the HVAC system reflect a very old idea: the principal of designing around local climatic conditions. During early SD, a study of local weather patterns identified the significant cooling season diurnal temperature swing, which enables the thermal mass/night purge cooling strategy. 78

It also identified a prevailing west wind in the cooling season, which allows the cool towers to provide natural ventilation and eliminate great room AHU operation for much of the year. Finally, this study highlighted the coincidence of low humidity with high dry-bulb temperatures, which makes evaporative cooling a practical option during the peak of the cooling season. The project embodies high technology innovations as well. The cool towers are an ancient concept from vernacular architecture, but their implementation relies on a modern DDC system and complex programming to harness natural forces while avoiding overcooling and drafts. The use of the high-pressure (2,000 psi [14 MPa]) atomizing foggers in this context is also unprecedented to the best of our knowledge. Similar towers on other projects have relied on evaporative media, which require maintenance and create air-side pressure drop (limiting its usefulness Advertisement formerly in this space. In the great room, louver/dampers provide a relief path for the cool tower, while ceiling fans provide additional cooling. on windless days), or low-pressure sprayers that can create dripping and blow through due to incomplete evaporation. The ceiling fans also represent innovation on several fronts. They were developed in collaboration with a well-known manufacturer as a new product specifically for schools. At our request, the manufacturer constructed a mock-up classroom to test a variety of blade sizes and configurations, and was able to provide air velocity profile data using a three-axis anemometer. This enabled us to optimize the design for uniform air velocities (avoiding under-cooling and drafts) and to have confidence in ASHRAE Standard 55 compliance, which was later validated by field tests in the completed building, in collaboration with the manufacturer and an independent research university. Automatic control of ceiling fans is also unusual, and enables several innovative features. Although a manual override allows the teacher to control the fan directly, no occupant interaction is required. The multi-mode cooling strategy automatically activates the ceiling fans when supply air temperatures rise enough that the displacement diffusers no longer provide beneficial stratification. In heating the ceiling, fans automatically mix and destratify, which allows the displacement diffusers to deliver heating air, avoiding the need for a separate heating system as is typical with displacement cooling systems. The ceiling fans also operate automatically during the night purge cycle to improve heat transfer to the thermal mass. 80