Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

Similar documents
Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Series. Access Power Controllers. Installation Guide

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

Installation Guide for models:

Installation Guide for models:

AL600ULX Series. Power Supply/Charger. Installation Guide

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

AL600ULADA. NAC Power Extender. Installation Guide

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

ACM8 & ACM8CB. Access Power Controllers Installation Guide. - Fused Outputs - Fused Outputs. - PTC Outputs - PTC Outputs. Models Include: Rev.

Rack Mount Series Installation Guide

AL800ULADA. NAC Power Extender. Installation Guide

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

Access Power Controllers with Power Supplies

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

SP-1000X. Panic Device Power Controller Installation Guide. Rev

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

more than just power! Altronix is the professional security industry s leading manufacturer

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Securitron Magnalock Corporation S. 51 st St., Ste. 102 Phoenix, AZ Phone: (800) MAGLOCK

TECHNICAL DATA OBSOLETE

IP Access FACP Adapters. Installation Guide. Entrada2DMK - IP Access FACP Adapter Kit. Kit Includes: Entrada2DMR - IP Access FACP Receiver

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

PDD-8PCI. Power Distribution Board With Supervised Interface. Installation and Specifications Manual

GENERAL STANDARD FEATURES. ISO-9001 Engineering and Manufacturing Quality System Certified to International Standard ISO-9001 PATENT PENDING

4100U City and Relay Cards Installation Instructions

Power Supplies. Overview

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

June 10, 2002 DF C S2424

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

July 14, 1999 DF C-100.

PSN-1000 & PSN 1000(E) Installation Manual

I TS-12 1 Y K DO WHAT THEY DON T. Model. INSTALLATION lnstrljctlons. FIRE BURGLARY lnstrumentsrn INC.

Booster Power Supply Manual

Remote NAC Power Supply D7038

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

FireNET Plus Wiring Instructions

Commercial and Light Industrial Fire Alarm Control Panel

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

AL602ULADA AL802ULADA AL1002ULADA

MODEL B2 INSTALLATION MANUAL

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

30.45 Electric Release PDRP-2001

MR-2602 Two Zone Fire Alarm Control Panel

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Conventional Releasing Control Panel

This wiring diagram describes circuit connections for all models of the Series Quaestor-SZU Releasing Fire Control

RDM LOCK G Series Electromagnetic Lock. Listings. Standard Features. Ordering Information:

PDD-FT-3. Fire Panel Interface With EOL Trigger. Installation and Specifications Manual

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

Public Safety DAS Annunciator Panel

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

Specification/ Data Sheet

Model 17A00 Expansion Enclosure

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

TECHNICAL DATA SHEET CONVENTIONAL FIRE ALARM SYSTEMS Conventional Fire Alarm Control Panel

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

TrueAlert Addressable Notification

Wiring Instructions (01-09)

LifeAlarm Fire Alarm Controls

Remote Booster Power Supplies

MANUAL RESET ALARM RELEASE

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Addressable NAC Output Module D327A

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

RGM 75 B - C4P N Z Articulating Z Bracket for wire management

Power Supply Display Module PSDM. Installation and Operation Manual

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

Fire Safety. Installation Instructions Model SMB-2 Main Control Board OPERATION INSTALLATION

RELEASE DEVICE CONTROLS

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

1200-HCM DIN RAIL MOUNTING FIRE SYSTEM MODULE Fire Detection & Extinguishant Control A R T PATOL LIMITED SUPPLY FAULT SOUNDER

Battery charger modules

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

Transcription:

M Series Multi-Output Access Control Power Supply Charger Installation Guide Models Include: AL300ULM AL400ULM - 2.5 amp @ 12VDC or 24VDC. - 4 amp @ 12VDC or 3 amp @ 24VDC. AL600ULM AL1012ULM - 6 amp @ 12VDC or 24VDC. - 10 amp @ 12VDC. AL1024ULM - 10 amp @ 24VDC. For a red enclosure, add an R suffix to the part # e.g. AL300ULMR Rev. 111103

Overview: These multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. These units convert a 115VAC / 60Hz input into five (5) individually protected 12VDC or 24VDC outputs (see specifications). Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form C dry output relay enables HVAC Shutdown, Elevator Recall or may be used to trigger auxiliary devices. M Series Power Supply Configuration Reference Chart: Altronix Model Number 12VDC Total Output Current (amp) 24VDC Total Output Current (amp) Outputs Class 2 Rated Power Limited AL300ULM 2.5 2.5 5 Yes 1.45 AL400ULM 4 3 5 Yes 1.9 AL600ULM 6 6 5 Yes 2.5 AL1024ULM - 10 5 Yes 4.4 AL1012ULM 10-5 Yes 1.9 115VAC 60Hz Input (current draw/amp) Input: Power input 115VAC 60Hz (see reference chart above). Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C. supervised trigger input and polarity reversal trigger input (4mA draw from FACP). Output: Five (5) individual power limited class 2 rated outputs. Current limit is 2.5 amp @ 12VDC or 24VDC per output (12VDC only for AL1012ULM and 24VDC only for AL1024ULM). Filtered and electronically regulated outputs. Thermal and short circuit protection with auto reset. Overload protection. Output relay energizes when unit is triggered (form C contact rated 1 amp @ 28VDC). Power Supply Board Input Fuse Rating 3.5 amp 250VAC 3.5 amp 250VAC 3.5 amp 250VAC 10 amp 250VAC 3.5 amp 250VAC - 2 - Agency Lisitings NYC Dept. of Buildings California State Fire Marshal Specifications: UL Listings and File Numbers UL File # S4707 UL 1481 UL Listed Power Supply for Fire Protective Signaling Systems UL 294 UL Listed Access Control System Unit. UL 603 UL Listed for Burglar Alarms Systems. UL 1069 UL Listed Hospital Signaling and Nurse Call Equipment. Signal Equipment Evaluated to CSA 22.2 N205-M1983 UL File # S4707 UL 1481 UL Listed Power Supply for Fire Protective Signaling Systems UL 294 UL Listed Access Control System Unit. Signal Equipment Evaluated to CSA 22.2 N205-M1983 UL File # BP617 UL 294 UL Listed Access Control System Unit. Signal Equipment Evaluated to CSA 22.2 N205-M1983 Battery Backup: Built-in charger for sealed lead acid or gel type batteries. Automatic switch over to stand-by battery when AC fails. AL300ULXB, AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current.7 amp. AL1024ULXB (Power Supply Board) maximum charge current 3.6 amp). Zero voltage drop when switching over to battery backup. AL300ULM, AL400ULM and AL600ULM enclosure accommodates up to two (2) 12VDC/7AH batteries. AL1012ULM and AL1024ULM enclosure accommodates up to two (2) 12VDC/12AH batteries.

Visual Indicators: DC output indicator. s indicate condition of power outputs. Power & input trigger s. Supervision: AC fail supervision (form "C" contact). Low battery supervision (form "C" contact). Specifications (cont d): Installation Instructions: The unit should be installed in accordance with The National Electrical Code, as well as NFPA 72 and all applicable Local Regulations. 1. Mount the unit in desired location. It is recommended to first review the following tables for screw terminals, switch selection and status indications. This will greatly facilitate installation hook-up. Carefully review: Output Voltage & Stand-by Specifications (pgs. 3 & 4) Terminal Identification Table (pg. 7) Diagnostics (pg. 6) Typical Application Diagrams (pgs. 8 & 9) 2. Set output voltage: AL300ULM, AL400ULM and AL600ULM set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board. AL1012ULM is 12VDC only and AL1024ULM is 24VDC only. (Output Voltage and Stand-by Specification Charts below and pg. 4). 3. Secure green lead to earth ground. Connect AC power (115VAC 60Hz to terminals marked [L, G, N] on power supply board (Fig. 1, pg. 5). Use 18 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting). 4. Measure output voltage before connecting devices. This helps avoid potential damage. Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires). Minimum.25 spacing must be provided. 5. Connect Fail-Secure type locking hardware (e.g. door strikes and electronic dead bolts) positive leads to terminals marked [1 through 5 POS DC OUTPUT (ALARM)] on MOM5 board (Fig. 1, pg. 5) and the negative leads to terminals marked [NEG 1 through NEG 5] on MOM5 board (Fig. 1, pg. 5). 6. Connect Fail-Safe type locking hardware (e.g. mag locks, door strikes and door holders) positive leads to terminals marked [6 through 10 POS DC OUTPUT (STAND-BY)] on MOM5 board (Fig. 1, pg. 5) and negative leads to terminals marked [NEG 1 through NEG 5] on MOM5 board (Fig. 1, pg. 5). 7. To trigger the unit from a FACP connect signaling circuit of FACP to terminals marked [- INPUT +] on MOM5 board (Fig. 1, pg. 5). Polarity is shown in alarm condition. For latching fire alarm interface (Fig. 5, 6, 7, pg. 9). Note: A 2.2K EOL must be installed across terminals marked [] on MOM5 board or the unit will remain in an alarm condition. 8. To trigger the unit using a supervised dry contact connect the 2.2K resistor in series for a N.C. trigger input and in parallel for N.O. trigger input (Fig. 2, pg. 8). 9. Connect auxiliary devices triggered by the unit to the terminals marked [DRY OUTPUT N.O. & C] on MOM5 board for normally open output or terminals marked [DRY OUTPUT N.C. & C] on MOM5 board for normally closed output (Fig. 1, pg. 5). Note: This relay will energize when the unit is triggered. 10. For Access Control applications batteries are optional. When batteries are not used a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type if used. Connect one (1) 12VDC battery to terminals marked [+ BAT--] on power supply board (Fig. 1, pg. 5) for 12VDC operation. Use two (2) 12VDC batteries connected in series for 24VDC operation. (Battery leads included). 11. Connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] (Fig. 1A, pg. 5) and [Power Fail] (Fig. 1, pg. 5) supervisory relay outputs marked [N.O., C, N.C.] on power supply board. Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting. Note: When used in fire alarm, burglar alarm or access control applications, AC Fail relay must be used to provide a visual indication of AC power on. 12. Please insure that the cover is secured with the provided Key Lock. - 3 - Supervision (cont d): Battery presence supervision (form C contact). Power fail supervision relay (form C contact rated 1 amp @ 28VDC). Power supply is complete with enclosure, cam lock, transformer and battery leads.

Output Voltage and Stand-by Specification Charts: AL300ULM Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by & Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm 12VDC / 40 AH Battery Closed Stand-by = 2.5 amp Stand-by = 1.0 amp Stand-by = 300mA Alarm = 2.5 amp Alarm = 2.5 amp Alarm = 2.5 amp 24VDC / 12 AH Battery Open Stand-by = 200mA Alarm = 2.5 amp 24VDC / 40 AH Battery Open Stand-by = 2.5 amp Stand-by = 1.0 amp Stand-by = 300mA Alarm = 2.5 amp Alarm = 2.5 amp Alarm = 2.5 amp AL400ULM Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by & Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm 12VDC / 40 AH Battery Closed Stand-by = 4.0 amp Stand-by = 1.0 amp Stand-by = 300mA Alarm = 4.0 amp Alarm = 4.0 amp Alarm = 4.0 amp 24VDC / 12 AH Battery Open Stand-by = 200mA Alarm = 3.0 amp 24VDC / 40 AH Battery Open Stand-by = 3.0 amp Stand-by = 1.0 amp Stand-by = 300mA Alarm = 3.0 amp Alarm = 3.0 amp Alarm = 3.0 amp AL600ULM Output Switch 4 hr. of Stand-by & 24 hr. of Stand-by & 60 hr. of Stand-by & Position 5 Minutes of Alarm 5 Minutes of Alarm 5 Minutes of Alarm 12VDC / 40 AH Battery Closed Stand-by = 6.0 amp Stand-by = 1.0 amp Stand-by = 300mA Alarm = 6.0 amp Alarm = 6.0 amp Alarm = 6.0 amp 24VDC / 12 AH Battery Open Stand-by = 200mA Alarm = 6.0 amp 24VDC / 40 AH Battery Open Stand-by = 6.0 amp Stand-by = 1.0 amp Stand-by = 300mA Alarm = 6.0 amp Alarm = 6.0 amp Alarm = 6.0 amp AL1012ULM Output 12VDC / 12 AH Battery 15 Minutes of Stand-by @ 10 amp AL1024ULM Output 15 mins. Stand-by / 4 hr. Stand-by / 24 hr. Stand-by / 60 hr. Stand-by / 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm 5 mins. Alarm 24VDC / 12 AH Battery 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp ------------------------- ------------------------- 24VDC / 65 AH Battery ------------------------- 7.7 amp / 9.7 amp 1.2 amp / 9.7 amp 200mA / 9.7 amp - 4 -

Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level (Output Voltage and Stand-by Specification Charts, pg. 3 & 4). Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery terminals and at the board terminals marked [+ BAT-- ] to insure that there is no break in the battery connection wires. Note: AL300ULXB, AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply Board) maximum charge current is.7 amp. AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp. Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary. Fig. 1 CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard replace fuses with the same type and rating (see marking on the board). Replace fuse cover before energizing. Do not expose to rain or moisture. Fuse Cover Fig. 1A Door Wire Strap (from Enclosure to Door) Green Lead 115VAC power mains non-power limited Class 1 BAT FAIL L G N AC FAIL Power Supply Board Divider NEG1 NEG2 NEG3 NEG4 NEG5 -- DC INPUT + Fire Alarm Interface Power Limited 1 2 3 4 5 POS DC OUTPUT (ALARM) NC C NO FAIL NC C NO DRY OUTPUT 6 7 8 9 10 POS DC OUTPUT (STANDBY) BAT FAIL AC FAIL DC Output to devices (power limited) Battery & AC Supervision Circuit (power limited) + BAT --- --- DC + non-power limited Battery connection (non power limited) Battery 1 Battery 2 Keep power limited wiring separate from non-power limited. Use minimum.25" spacing. - 5 -

Power Supply Board Diagnostics: Red (DC) Green (AC) Power Supply Status ON ON Normal operating condition. ON OFF Loss of AC, Stand-by battery supplying power. OFF ON No DC output. Short circuit or thermal overload condition. OFF OFF No DC output. Loss of AC. Discharged battery. MOM5 - Output Module ON OFF Power (Green) Normal operation. Power failure. Trigger (Green) Input is triggered (alarm condition). No input trigger (non-alarm condition). Outputs (Red) Output tripped due to a Normal operation. short circuit or overload condition. - 6 -

Power Supply Board Terminal Identification Tables: Terminal Function/Description Legend L, G, N Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground. - DC + AL300ULM - 12VDC/24VDC @ 2.5 amp to MOM5 board (power limited). AL400ULM - 12VDC @ 4 amp or 24VDC @ 3 amp to MOM5 board (power limited). AL600ULM - 12VDC/24VDC @ 6 amp to MOM5 board (non-power limited). AL1012ULM - 12VDC @ 10 amp to MOM5 board (non-power limited). AL1024ULM - 24VDC @ 10 amp to MOM5 board (non-power limited). AC FAIL Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay N.C., C, N.O. normally energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 6 hrs., cut AC delay jumper and reset power to unit. BAT FAIL Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally N.C., C, N.O. energized when DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute. Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULM), 24VDC output threshold set @ approximately 21VDC. + BAT - Stand-by battery connections. AL300ULXB, AL400ULXB and AL600ULXB (Power Supply Board) maximum charge current is.7 amp. AL1024ULXB (Power Supply Board) maximum charge current is 3.6 amp. MOM5 - Output Module Terminal Legend Function/Description - DC INPUT + 12VDC or 24VDC from power supply. Dry normally open (N.O.) or normally closed (N.C.) supervised (2.2K EOL resistor) input trigger. A short or open circuit will transfer power from terminals marked [POS. DC OUTPUT (STAND-BY)] to terminals marked [POS DC OUTPUT (ALARM)]. - INPUT + Wet (5-30VDC) input trigger. Applying voltage to these terminals in the polarity shown will transfer power from terminals marked [POS. DC OUTPUT (STAND-BY)] to terminals marked [POS DC OUTPUT (ALARM)] (e.g. fire alarm control panel indications circuit).. NEG 1 THRU NEG 5 Supplies constant negative (-) voltage. POS DC OUTPUT Supplies positive voltage when dry trigger input or fire (ALARM) 1-5 alarm wet trigger input is applied. POS DC OUTPUT Supplies positive voltage in normal condition. (STAND-BY) 6-10 Power is removed when dry trigger input or fire alarm wet trigger input is applied. N.C., C., N.O. When the MOM5 is triggered the C and N.O. terminals will open and the DRY OUTPUT C and N.C. terminals will close. This output is used to trigger auxiliary devices. (e.g. HVAC Shutdown, Elevator Recall etc.) Contact rating 1 amp @ 28VDC. N.C., C, N.O. Form C contacts used for reporting no voltage is present at [-- DC input +] FAIL terminals. Under normal conditions, terminals N.O. and C are open, N.C. and C are closed. A loss of power causes N.O. and C to close and N.C. and C to open. Contact rating 1 amp @ 28VDC. - 7 -

Fig. 2 MOM5 module shown with wet and/or dry normally closed trigger inputs (Non-Latching): Typical Application Diagrams: MOM5 module shown with wet and/or dry normally open trigger inputs (Non-Latching): (-) DC VOLTAGE INPUT SIGNALING OUTPUT OR ACCESS N.C. INPUT FROM FACP OR ACCESS (-) DC VOLTAGE INPUT SIGNALING OUTPUT OR ACCESS N.O. INPUT FROM FACP OR ACCESS Fig. 3 - Two (2) or more MOM5 modules shown with wet and/or dry normally closed trigger inputs (Non-Latching): (--) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS N.C. INPUT FROM FACP OR ACCESS ON ON TO INPUT OF NEXT MOM5 Fig. 4 - Two (2) or more MOM5 modules shown with wet and/or dry normally open trigger inputs (Non-Latching): MOM5_S (--) DC VOLTAGE INPUT SIGNALING OUTPUT OR ACCESS MOM5_S ALTRONIX CORP. BROOKLYN, NY 11220 MADE IN USA ALTRONIX CORP. BROOKLYN, NY 11220 MADE IN USA N.O. INPUT FROM FACP OR ACCESS ON ON TO INPUT OF NEXT MOM5-8 -

Fig. 5 Typical Application Diagrams (cont d.): MOM5 module shown with with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset): MOM5 module shown with with wet and/or dry normally open fire alarm trigger inputs (Latching with Manual Reset): NEG (-) INPUT POS (+ (-) DC VOLTAGE INPUT SIGNALING OUTPUT (-) DC VOLTAGE INPUT SIGNALING OUTPUT ON N.O. INPUT SIGNALING OUTPUT ON N.C. INPUT SIGNALING OUTPUT N.C. RESET N.O. RESET Fig. 6 - Two (2) MOM5 modules shown with wet and/or dry normally open fire alarm trigger inputs (Latching with Manual Reset): (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS N.C. INPUT FROM FACP ON ON N.O. RESET Fig. 7 - Two (2) MOM5 modules shown with wet and/or dry normally closed fire alarm trigger inputs (Latching with Manual Reset): (-) DC VOLTAGE INPUT FROM FACP SIGNALING OUTPUT OR ACCESS (-) N.O. INPUT FROM FACP ON ON N.C. RESET - 9 -

AL300ULM AL400ULM AL600ULM 13 H x 13.5 W x 3.25 D 3.25" Enclosure Dimensions: TOP ONLY 1.1875" 3.25" 1.1875" 0 0 0 0.75" 1.5" 6.25" 11" 11.75"12.5" 0 1.1875" 3.25".81" 1.4" 1.4" 5.5" 6.5" 11.66" 12.1" 13" - 10 -

AL1012ULM AL1024ULM 15.5 H x 12 W x 4.5 D Enclosure Dimensions: 4.5" TOP & BOTTOM 1.25" 4.5" 1.25" 0 0 0 0.875" 1.5" 6" 10.5" 10.75" 12" 0 1.25" 4.5" 1" 2" 6.625" 10" 13.5" 14.25" 15.5" - 11 -

Notes: Altronix is not responsible for any typographical errors. Altronix Corp. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. IIM series H25D MEMBER - 12 -