M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

Similar documents
National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. Technical Committee on Alternative Approaches to Life Safety. NFPA 101A First Draft Technical Committee FINAL Ballot Results (A2018)

Committee on NFPA 51A

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Report on First Revisions with Statement June 2014 NFPA 101

TECHNICAL COMMITTEE ON FIRE CODE

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

Circulation Report for SIG-TMS Comments Document # 72

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

Changes to NFPA 101A 2013 Edition for Health Care Facilities

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

Committee on NFPA 85

NFPA Technical Committee on Fire Tests

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

WORKING DRAFT OF COMMITTEE MEETING OUTPUT

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public Input No. 1-NFPA 90B-2015 [ Chapter 2 ]

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

MEMORANDUM. NFPA Technical Committee on Fire Code (FCC-AAA) Subject: NFPA 1 Proposed Tentative Interim Amendment (TIA) No.1045

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

MEETING MINUTES NFPA Technical Correlating Committee on Safety to Life January 6, 2011 ROC Meeting The Wyndham Phoenix, Phoenix, AZ

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Chapter 2: Definitions

C. None (No sprinkler system) K3 E. NUMBER OF BEDS CERTIFIED FOR MEDICAID

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. NFPA Technical Correlating Committee on Building Code. NFPA 5000 TCC Report on Proposals Letter Ballot (A2011)

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

M E M O R A N D U M. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. SUBJ: NFPA 72 Proposed TIA No FINAL CC BALLOT RESULTS

Report on First Revision June 2014 NFPA 5000

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

PROPOSAL BALLOT DUE BY: Thursday, September 18, 2008

First Revision No NFPA [ Section No ]

MEMORANDUM. NFPA Technical Committee on Solvent Extraction Plants. NFPA 36 First Draft TC FINAL Ballot Results (F2016)

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Diane D. Matthews, Administrator, Technical Projects. The September 19, 2013 date for receipt of the NFPA 5000 Second Draft Ballot has passed.

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Residential Sprinkler Systems

SAF-BCF SECOND REVISIONS WITH STATEMENTS

Report on First Revisions with Statement June 2014 NFPA 101

Page 1 of 6 10/19/2016 9:49 AM. Public Input No. 4-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

Agenda Technical Committee on Initiating Devices for Fire Alarm and Signaling Systems June 24-25, 2013 Saint Louis, MO

The Technical Committee on Commissioning and Integrated Testing

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

MEMORANDUM. Technical Committee on Notification Appliances for Fire Alarm and Signaling Systems

First Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

Report on First Revisions with Statement June 2014 NFPA 101

ROC MEETING AGENDA Technical Committee on Alternative Approaches to Life Safety Teleconference 10:00 a.m. Eastern Wednesday, September 14, 2011

Report on First Revision June 2014 NFPA 101

National Fire Protection Association

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

1 Batterymarch Park, Quincy, MA Phone: Fax: M E M O R A N D U M

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

Public. Mike Free Health. State of Alabama Department of

Public Health Fax: Web Site:

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #5

M E M O R A N D U M. NFPA 76 Second Draft TC FINAL Ballot Results (F2015 Cycle)

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS

<< COMPANY LETTERHEAD >>

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

TECHNICAL COMMITTEE ON FIRE PUMPS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

9/23/ :20 AM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

Chapter 43, Building Rehabilitation allows for degrees of compliance based on the work category such as the extent of work.

Agency for Health Care Administration

Report on Proposals A2006 Copyright, NFPA NFPA 150 Report of the Committee on

PERFORMANCE COMPLIANCE METHODS

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

MEMORANDUM. NFPA 51 First Draft Technical Committee FINAL Ballot Results (A2017 Cycle)

THE 2012 EDITION OF THE LIFE SAFETY CODE NURSING HOME EDITION SESSION #2

Questions for the HFD regarding Bill 69, Evaluation Worksheet for High-Rise Residential Buildings User s Guide ( New User s Guide or NUG )

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

M E M O R A N D U M. The Technical Correlating Committee on Boiler and Combustion Systems Hazards

Agency for Health Care Administration

Report on First Revision June 2014 NFPA 101

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

Transcription:

M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter ballot for NFPA 101A is attached. The ballot is for formally voting on whether you concur with the committee s actions on the proposals. Reasons must accompany all negative and abstention ballots. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. Please complete and return your ballot as soon as possible but not later than Friday, January 21, 2011. As noted on the ballot form, please return the ballot to Linda MacKay either via e-mail to lmackay@nfpa.org or via fax to 617-984-7110. You may also mail your ballot to the attention of Linda MacKay at NFPA, 1 Batterymarch Park, Quincy, MA 02169. The return of ballots is required by the Regulations Governing Committee Projects. Attachments: Proposals Letter Ballot ROP TC Initial Ballot Cover Memo March 24, 2010

PROPOSAL BALLOT DUE BY: Friday, January 21, 2011 NFPA 101A SAF-ALS Guide on Alternative Approaches to Life Safety Technical Committee on Alternative Approaches to Life Safety Staff Liaison: Ron Coté Due Date: 1/21/2011 Contact: Linda MacKay E-Mail: lmackay@nfpa.org Fax: 617-984-7110 Mail: One Batterymarch Park, Quincy, MA 02169 Committee Action Key: A = Accept R= Reject APA = Accept in Part APR = Accept in Principle APP = Accept in Principle in Part H = Hold With respect to the Committee Actions on the Proposals which accompanied the ballot, please record me as voting: (check one) Affirmative On All Items. I agree with all committee meeting actions without comment. Please return this Ballot Page only to NFPA. Affirmative With Exception(s)*: I agree with all committee meeting actions Except for the Affirmative with comment, Negative and /or Abstention checked below. *Reasons must accompany these votes. DATE: NAME: (Your printed name above acts as your signature) Proposal No Log No Section Committee Action Select the appropriate box below Affirmative with Comment* = Aff w-c Negative* = Neg Abstain* = Abs 101A-1 CP1 Entire Document APR Aff w/c Neg Abs 101A-2 CP6 Entire Document APR Aff w/c Neg Abs 1

Proposal No Log No. Section Committee Action Vote 101A-3 CP2 2.2 A Aff w/c Neg Abs 101A-4 CP3 2.3 A Aff w/c Neg Abs 101A-5 CP10 Chapters 4, 5, 7 and 8 A Aff w/c Neg Abs 101A-6 CP8 4.3.2.4 A Aff w/c Neg Abs 101A-7 1 4.5(5) Occupancy Risk (Worksheet R Aff w/c Neg Abs 101A-8 CP4 5.4.6.2, 7.2.4.6.2, 7.4.4.9.4, 7.6.4.9.1, A Aff w/c Neg Abs 101A-9 CP9 Chapter 7 (various) APR Aff w/c Neg Abs 2

Proposal No Log No. Section Committee Action Vote 101A-10 CP7 7.4.4.11.2 and Worksheet 7.5.2 A Aff w/c Neg Abs 101A-11 CP5 Worksheets 7.5.2, 7.5.4A, 7.5.4B, A Aff w/c Neg Abs 3

Report on Proposals June 2012 101A-1 Log #CP1 SAF-ALS NFPA 101A Review entire document to: 1) Update any extracted material by preparing separate proposals to do so, and 2) review and update references to other organizations documents, by preparing proposal(s) as required. To conform to the NFPA Regulations Governing Committee Projects. No further action required. The only extracted text in NFPA 101A is Table 5.4.1 of building construction types as taken from NFPA 5000. The version of the table shown in NFPA 101A-2010 is current with that shown in NFPA 5000. No updating is needed. No referenced publications of 2.3.1 from other organizations require updating of edition date. The withdrawal of NFPA 255 is addressed in a separate committee proposal. 101A-2 Log #CP6 SAF-ALS Throughout NFPA 101A, update the specific paragraph numbers of NFPA 101, Life Safety Code that are cited, to reflect accurately what those numbers will be in the 2012 edition of NFPA 101. The paragraph numbers cited in NFPA 101A-2010 are based on the numbering of NFPA 101-2009. The cited paragraph numbers need to be those current in the 2012 edition of NFPA 101 as NFPA 101A-2013 needs to track directly with NFPA 101-2012. Wait until the ROC period to make the updates. The paragraph numbers of what will appear in NFPA 101-2012 are not available at the time of preparation of the ROP for NFPA 101A. NFPA 101A is deliberately revised on a cycle that follows that of NFPA 101 by one year so as to permit the requirements of NFPA 101 to be reflected accurately in the FSES chapters of NFPA 101A. 101A-3 Log #CP2 SAF-ALS Revise 2.2 NFPA Publications by deleting NFPA 255 as follows: NFPA 255,, 2006 edition. NFPA 255 was withdrawn by the Association. The paragraphs of NFPA 101A that currently reference NFPA 255 as being revised by a separate committee proposal to reference ASTM E 84 and UL 723 in place of NFPA 255. Printed on 12/28/2010 1

Report on Proposals June 2012 101A-4 Log #CP3 SAF-ALS Add two new numbered paragraphs to 2.3 as follows: NFPA 101A ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. www.astm.org ASTM E 84,, 2010. Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096. www.ul.com ANSI/UL 723,, 2008, Revised 2010. NFPA 255 was withdrawn by the Association. In each place where NFPA 255 was previously referenced, new references are being made to ASTM E 84 and ANSI/UL 723 by a separate committee proposal as these ASTM and UL standards are equivalent to NFPA 255. The references, complete with contact information for ASTM and UL and the edition date need to appear in Section 2.3. 101A-5 Log #CP10 SAF-ALS 1. Revise Worksheet 4.7.11 Conclusions (for health care) to read the same as Worksheet 9.6.7 Conclusions (for educational) - but change the Chapter 9 references to Chapter 4 references. 2. Revise Worksheet 5.5.8 Conclusions (for detention/correctional) to read the same as Worksheet 9.6.7 Conclusions (for educational) - but change the Chapter 9 references to Chapter 5 references. 3. Revise Worksheet 7.3.7 Conclusions (for small board and care) to read the same as Worksheet 9.6.7 Conclusions (for educational) - but change the Chapter 9 references to Chapter 7 references. 4. Revise Worksheet 7.5.7 Conclusions (for large board and care) to read the same as Worksheet 9.6.7 Conclusions (for educational) - but change the Chapter 9 references to Chapter 7 references. 5. Revise Worksheet 7.7.7 Conclusions (for board and care apartment building suitability) to read the same as Worksheet 9.6.7 Conclusions (for educational) - but change the Chapter 9 references to Chapter 7 references. 6. Revise Worksheet 8.6.7 Conclusions (for business) to read the same as Worksheet 9.6.7 Conclusions (for educational) - but change the Chapter 9 references to Chapter 8 references. The Chapter 9 FSES for educational occupancies is the newest of the FSES chapters. It explains what to do with the results of the Facility Fire Safety Requirements Worksheet which covers considerations not otherwise evaluated by the FSES. The Conclusions worksheets of Chapters 4, 5, 6 and 7 do not tell the user what to do if items are Not Met in the Facility Fire Safety Requirements Worksheet. The wording of the Conclusions worksheet in Chapters 4, 5, 6 and 7 tell the AHJ that equivalency has been achieved based solely on getting all Yes entries in the Equivalency Evaluation worksheet. A footnote states that the considerations in the Facility Fire Safety Requirements Worksheet must be considered separately but doesn't tell the AHJ not to accept the equivalency or how to consider those items separately. If the Chapter 9 approach is not correct, it needs to be adjusted. In any case, the language in Chapters 4, 5, 6 and 7 needs revision to clarify what effect the results of the Facility Fire Safety Requirements Worksheet need to have on the overall equivalency determination. The NFPA 101A technical committee has formed a task group to study the issue and report back at the ROC-preparation meeting. Printed on 12/28/2010 2

Report on Proposals June 2012 101A-6 Log #CP8 SAF-ALS NFPA 101A Revise text as follows: A floor... (4) Zones not involving housing, treatment, or customary access for patients four or more inpatients simultaneously who are incapable of self-preservation; such zones should be evaluated as follows: The change in text proposed for 4.3.2(4) reflects changes being made to NFPA 101 for the 2012 edition. If the NFPA 101A technical committee needs to tweak the wording further for agreement with NFPA 101, it can do so during the ROC-preparation stage which will occur once the language of NFPA 101-2012 is finalized. 101A-7 Log #1 SAF-ALS Robert Trotter, Tennessee Code Development Committee / Rep. Tennessee Fire Safety Inspectors Association & Tennessee Fire Chiefs Association Add a new subitem (5) to 4.5 as follows: (5) In the measurement of occupancy risk factors for Patient Mobility, Patient Density, Ratio of Patients to Attendants, and Patient Average Age, a risk factor at 1.0 is assessed for any zone not involving housing, treatment or customary access by patients. Such zones might include, but are not limited to, business use areas, storage and industrial use areas. The Guide is silent on which risk factor to select for zones with no patients in regards to Worksheet 4.7.2. This language provides direction to completing the worksheet in accordance with NFPA staff response to the question, For Worksheet 4.7.2 which risk factor value is selected for zones with no patients? The Rationale is that there are various areas of a health care occupancy that are evaluated as a zone and do not house patients. The subject is already adequately addressed in 4.3.2(4) where the user is directed to set F = L without having to perform any calculations for exactly the case that the submitter described. Also, per 4.3.2(4)(b), where a 2-hr fire resistance-rated separation is provided to separate nonpatient spaces from health care spaces, Chapter 4 is not the correct FSES to use for such nonpatient spaces. 101A-8 Log #CP4 SAF-ALS In 5.4.6.2, 7.2.4.6.2, 7.4.4.9.4, 7.6.4.9.1, 7.6.4.9.4, 8.5.7.1, 8.5.7.2, 9.5.7.1 and 9.5.7.2 replace the words "NFPA 255, " with the words "ASTM E 84, or ANSI/UL 723 NFPA 255 was withdrawn by the Association. In each place where NFPA 255 was previously referenced, new references are being made to ASTM E 84 and ANSI/UL 723 by this committee proposal as these ASTM and UL standards are equivalent to NFPA 255. Printed on 12/28/2010 3

Report on Proposals June 2012 101A-9 Log #CP9 SAF-ALS NFPA 101A Correlate the use of terminology related to smoke detectors so as to use the terms "smoke alarms" and "single station" where appropriate. The terminology for smoke detection in 7.2.4.4, the 7.4.4.4s, and 7.6.4.4 is inconsistent and incorrect in places. Make the necessary edits/fixes at the ROC stage. The NFPA 101A technical committee was not able to address the issue fully during its ROP-preparation meeting. It formed a task group to develop needed changes for action at the ROC-preparation meeting. 101A-10 Log #CP7 SAF-ALS Add text to 7.4.4.11.2 as follows: Smoke barriers consist of installations conforming to the requirements of 32.3.3.7 and 33.3.3.7 (NFPA 101), as appropriate. The full value for the presence of smoke barriers is awarded where an existing separation is by smoke partitions complying with Section 8.4 (NFPA ) on stories used for sleeping by not more than 30 residents. In Worksheet 7.5.2 Safety Parameter 11 Smoke Control, revise the value for the Smoke Barriers column as follows: 2 (2) u In Worksheet 7.5.2, add a new footnote "u" below the table to read: " u Use (2) if an existing separation is by smoke partition on stories used for sleeping by not more than 30 residents." NFPA 101-2012 is being revised in Chapter 33 to permit existing large residential board and care facilities to satisfy the smoke barrier requirement via an existing separation consisting of a smoke partition on stories used for sleeping by not more than 30 residents. The change is being reflected in the NFPA 101A FSES for large residential board and care occupancies in the text of 7.4.4.11.2 and in Worksheet 7.5.2, lest the user miss the new exemption. Printed on 12/28/2010 4

Report on Proposals June 2012 101A-11 Log #CP5 SAF-ALS NFPA 101A 1. In Worksheet 7.5.4A, in the Stories in Height column, change 1 Story to 1 Story and change 2 Stories to 2 Stories 2. In Worksheet 7.5.2 Safety Parameter 2 Hazardous Areas, revise the value for the column for None, or No Deficiency as follows: 0 (-1) t 3. In Worksheet 7.5.2, add a new footnote t below the table to read: t Use (-1) if evacuation capability is impractical and fire-rated hazardous area separation barriers are not also smoke partitions 4. In Worksheet 7.5.4B, change the title as follows: WORKSHEET 7.5.4B MANDATORY SAFETY REQUIREMENTS EXISTING LARGE FACILITY WITH PROMPT OR SLOW EVACUATION CAPABILITY 5. In Worksheet 7.5.4C, change the title as follows: WORKSHEET 7.5.4C MANDATORY SAFETY REQUIREMENTS EXISTING, SPRINKLER PROTECTED, LARGE FACILITIES FACILITY WITH PROMPT OR SLOW EVACUATION CAPABILITY 6. Add a new Worksheet 7.5.4D MANDATORY SAFETY REQUIREMENTS EXISTING LARGE FACILITY WITH IMPRACTICAL EVACUATION CAPABILITY as follows (underscoring omitted as entire table is new and underscoring makes it more difficult to read the table): **** Insert Table Here**** NFPA 101 Chapter 33, Section 33.3 for existing large residential board and care facilities is being revised for the 2012 edition to include requirements for large, impractical to evacuate facilities. In prior editions, the user was sent to the health care occupancies chapters and told to protect the large, impractical to evacuate facility as a limited care facility. NFPA 101A Chapter 7 is being revised by this committee proposal to reflect the changes being made to NFPA 101. The requirements being added to NFPA 101 to recognize existing, impractical to evacuate, large board and care facilities include the following: 1. Corridor must be 44-in. minimum width. No change is needed as the subject is adequately covered via the choice of the value of -2 for a Deficient Multiple Routes in Safety Parameter 7 Exit System. 2. Emergency lighting required. No change is needed as the subject is not directly measured by the FSES. 3. Hazardous area separation must be a smoke partition in addition to being a 1-hr fire resistance-rated barrier. Subject addressed by items (2) and (3) in above recommendation. The net effect is to require, in the fire-rated partitions, that the penetrations resist the passage of smoke. 4. Fire alarm system is required. Subject addressed via the calibration calculations that went into the development of the mandatory values in new Worksheet 7.5.4D via the choice of a value of 2 for manual alarm without fire department notification in Safety Parameter 3. 5. Smoke detection required in all living areas. Subject addressed via the calibration calculations that went into the development of the mandatory values in new Worksheet 7.5.4D via the choice of a value of 3 for interconnected system detectors with single station smoke alarms in bedrooms/suites in Safety Parameter 4. 6. Sprinkler system required. Subject addressed via the calibration calculations that went into the development of the mandatory values in new Worksheet 7.5.4D via the choice of a value of 8 for total building sprinklering in Safety Parameter 5. 7. Smoke barriers required. Subject addressed via the calibration calculations that went into the development of the mandatory values in new Worksheet 7.5.4D via the choice of a value of 2 for smoke barriers in Safety Parameter 11. The changes being made to Worksheet 7.5.4A (i.e., changing 1 Story to 1 Story and changing 2 Stories to 2 Stories ) correct errors as a building cannot have fewer than 1 story, and an the entry marked " 2 Stories" is meant to apply to 2-Story only and not to 1-Story. To help record the history of the changes made, the mandatory value calculation sheets that led to the values shown in Worksheet 7.5.4D follow: See ROP pages xx through yy for PDF printouts of the six calculation sheets Printed on 12/28/2010 5

WORKSHEET 7.5.4D MANDATORY SAFETY REQUIREMENTS EXISTING LARGE FACILITY WITH IMPRACTICAL EVACUATION CAPABILITY Stories in Height Control Requirement (S a ) Egress Requirement (S b ) Refuge Requirement (S c ) General Fire Safety Requirement (S d ) 1 Story 6 6.5 8.5 8 2 Stories 2 6.5 4.5 4 3 6 Stories 6 6.5 8.5 8 >6 Stories 8 6.5 6.5 10 NFPA 101A 2013 ROP Proposal 101A (Log #CP5)

Report on Proposals June 2012 NFPA 101A INSERT calculation sheets HERE Printed on 12/28/2010 6

1-STORY IMPRACTICAL LARGE B&C FACILITY PARAMETER EXISTING FACILITIES 1.CONSTRUCTION V(000) (POINTS) -2 2. HAZARDOUS AREAS NO DEF.S 3. MANUAL F.A. WO/F.D. NOTIF 4. SMOKE DETEC. InterSglStaBR/Suite (POINTS) 3 5. SPRINKLERS TOTAL (POINTS) 8 6. SEPERATION OF SMK.REST. SLEEPING ROOMS W/O CLOSER 7. EXIT SYSTEM W/O HORZ. 8. EXIT ACCESS 150 FT 9. INTERIOR FINISH CLASS C (POINTS) -3 10. VERTICAL OPG.S 1/2-HR 11. SMOKE CONTROL BARRIERS S1 6 S2 6.5 S3 8.5 S4 8

2-STORY IMPRACTICAL LARGE B&C FACILITY PARAMETER EXISTING FACILITIES 1.CONSTRUCTION V(000) (POINTS) -6 2. HAZARDOUS AREAS NO DEF.S 3. MANUAL F.A. WO/F.D. NOTIF 4. SMOKE DETEC. InterSglStaBR/Suite (POINTS) 3 5. SPRINKLERS TOTAL (POINTS) 8 6. SEPERATION OF SMK.REST. SLEEPING ROOMS W/O CLOSER 7. EXIT SYSTEM W/O HORZ. 8. EXIT ACCESS 150 FT 9. INTERIOR FINISH CLASS C (POINTS) -3 10. VERTICAL OPG.S 1/2-HR 11. SMOKE CONTROL BARRIERS S1 2 S2 6.5 S3 4.5 S4 4

3-STORY IMPRACTICAL LARGE B&C FACILITY PARAMETER EXISTING FACILITIES 1.CONSTRUCTION III(200) (SHEATHED) (POINTS) -2 2. HAZARDOUS AREAS NO DEF.S 3. MANUAL F.A. WO/F.D. NOTIF 4. SMOKE DETEC. InterSglStaBR/Suite (POINTS) 3 5. SPRINKLERS TOTAL (POINTS) 8 6. SEPERATION OF SMK.REST. SLEEPING ROOMS W/O CLOSER 7. EXIT SYSTEM W/O HORZ. 8. EXIT ACCESS 150 FT 9. INTERIOR FINISH CLASS C (POINTS) -3 10. VERTICAL OPG.S 1/2-HR 11. SMOKE CONTROL BARRIERS S1 6 S2 6.5 S3 8.5 S4 8

4-STORY IMPRACTICAL LARGE B&C FACILITY PARAMETER EXISTING FACILITIES 1.CONSTRUCTION III(200) (SHEATHED) (POINTS) -2 2. HAZARDOUS AREAS NO DEF.S 3. MANUAL F.A. WO/F.D. NOTIF 4. SMOKE DETEC. InterSglStaBR/Suite (POINTS) 3 5. SPRINKLERS TOTAL (POINTS) 8 6. SEPERATION OF SMK.REST. SLEEPING ROOMS W/O CLOSER 7. EXIT SYSTEM W/O HORZ. 8. EXIT ACCESS 150 FT 9. INTERIOR FINISH CLASS C (POINTS) -3 10. VERTICAL OPG.S 1/2-HR 11. SMOKE CONTROL BARRIERS S1 6 S2 6.5 S3 8.5 S4 8

5/6-STORY IMPRACTICAL LARGE B&C FACILITY PARAMETER EXISTING FACILITIES 1.CONSTRUCTION III(200) Sheathed (POINTS) -2 2. HAZARDOUS AREAS NO DEF.S 3. MANUAL F.A. WO/F.D. NOTIF 4. SMOKE DETEC. InterSglStaBR/Suite (POINTS) 3 5. SPRINKLERS TOTAL (POINTS) 8 6. SEPERATION OF SMK.REST. SLEEPING ROOMS W/O CLOSER 7. EXIT SYSTEM W/O HORZ. 8. EXIT ACCESS 150 FT 9. INTERIOR FINISH CLASS C (POINTS) -3 10. VERTICAL OPG.S 1/2-HR 11. SMOKE CONTROL BARRIERS S1 6 S2 6.5 S3 8.5 S4 8

MORE THAN 6-STORY IMPRACTICAL LARGE B&C FACILITY PARAMETER EXISTING FACILITIES 1.CONSTRUCTION IV(2HH) 2. HAZARDOUS AREAS NO DEF.S 3. MANUAL F.A. WO/F.D. NOTIF 4. SMOKE DETEC. InterSglStaBR/Suite (POINTS) 3 5. SPRINKLERS TOTAL (POINTS) 8 6. SEPERATION OF SMK.REST. SLEEPING ROOMS W/O CLOSER 7. EXIT SYSTEM W/O HORZ. 8. EXIT ACCESS 150 FT 9. INTERIOR FINISH CLASS C (POINTS) -3 10. VERTICAL OPG.S 1/2-HR 11. SMOKE CONTROL BARRIERS S1 8 S2 6.5 S3 6.5 S4 10