MEV Ecosmart. Installation and Maintenance. Continuous Mechanical Extract Ventilation Units. 1.0 Introduction

Similar documents
MEV-DC. Continuous Mechanical Extract Ventilation Units Installation and Maintenance. Figure 3. Fixing screw hole.

MRXBOX95-WALL. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Extract air.

MRXBOX95B-LOFT. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Loft Mounting. Installation and Maintenance

AP-EH500-L/RQA9837. Installation Guide

Installation and Maintenance. Opus OK / Genie NKF1 Kitchen Extract Unit. Contents IMPORTANT WARNING IMPORTANT! Introduction WARNING!

Natural Ventilation. e-stack A-Series Ventilation System for Buildings with Atria. Installation and Maintenance. Palletised

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

MRXBOX95-LH1/LH2. Mechanical Ventilation Unit with Heat Recovery for Loft Mounting Installation and Maintenance. Spigot 4.

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Bracket

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

XB-EFA-8L-BK & XB-EFA-8R-BK

XBOXER 55. Supply & Extract Ventilation Unit with Heat Recovery Installation, Operating and Maintenance Instructions XB 55 - L - E

Installation and Maintenance. OPUS 30 and 60. Duct Mounted ('M' range) Domestic Extract Fans IMPORTANT WARNING

Ecosmart Boxer. AHU s (Fan Speed Control only) Installation and Maintenance. LPHW Heater

MRXBOX95-WM2H. Mechanical Ventilation Unit with Heat Recovery and Integral Humidistat for Wall Mounting Installation and Maintenance

OPUSXBOX - SMALL COMMERCIAL HEAT RECOVERY SYSTEM LOW DEPTH, HEAT RECOVERY UNIT WITH MULTIPLE SPIGOTS AND ECOSMART CONTROLS.

MRXBOX95-WM2. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

MRXBOX95AB-WH1. Mechanical Ventilation Unit with Heat Recovery & Summer Bypass for Wall Mounting. Installation and Maintenance

230V/24V DC SELV Surface and Semi-Recessed Mounted Domestic Fans INSTALLATION AND MAINTENANCE. n Wall mounting kit

DRIMASTER Anti-Condensation & Whole House Ventilation Unit Installation and Maintenance

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan with Humidity Enabler Installation Guide

MRXBOX95-WH1. Mechanical Ventilation Unit with Heat Recovery for Wall Mounting Installation and Maintenance. Intake air from outside

Installation and Maintenance

OPUS PLUS TWINFANS COMPACT & POWERFUL, IDEAL FOR LARGER ROOM APPLICATIONS WHILST MAINTAINING LOW NOISE LEVELS.

Decentralised Mechanical Extract Ventilation 2 Speed Axial Extract Fan Installation Guide. Fig. 2 Fan components.

FLAT2000L/R. Low Energy Positive Input Ventilation Unit. Installation and Maintenance. Alternative inlet position. 2.1 Spigot Inserts.

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

DAVE Supply Fans (ES Models) For Internal and External use

MRXBOX95AB-WH2 (with automatic summer bypass)

Installation and Maintenance

DRIMASTER 2000 and DRI S Anti-Condensation & Whole House Ventilation Unit Installation and Maintenance

Application and Installation Guide for sunwarm system (excluding Solar Air Collectors)

Sunwarm Air Solar Energy Ventilation System Installation and Maintenance Details for:

Application and Installation Guide for sunwarm140 AHU system (excluding Solar Air Collectors)

IMPROVING INDOOR AIR QUALITY IN NEW HOMES. MECHANICAL EXTRACT VENTILATION (MEV & dmev)

MRXBOX90S. Mechanical Ventilation with Heat Recovery. Installation and Maintenance

Installation and Maintenance

MRXBOX95-WH1 MECHANICAL VENTILATION WITH HEAT RECOVERY

Installation and Maintenance

Installation and Wiring Instructions

SQURBO XBOX. Units S1 - S6 - XB Supply & Extract fans with Heat Recovery Installation and Maintenance. Fresh air intake* Fresh air.

Installation and Maintenance

EVG Extractors. Manual for Installation, Use and Maintenance

Installation and Maintenance

DAVE Supply (DS) Fans For Internal & External Use Installation and Maintenance

MRXBOXAB-ECO4 100% and Opposite Handed version. Typical Installation

Installation and Maintenance

Intake air from outside. Supply air to house. Extract air. from house. Extract air from house. Exhaust air from house to outside

Application and Installation Guide (excluding Solar Air Collectors)

FAITH (dmev) 230V / 24V DC SELV Flush Mounted Domestic Continuous Extract Fans

Lo-Carbon MULTIVENT MVDC-MS & MVDC-MS H VENTILATION SYSTEMS V~50Hz. Installation and Wiring Instructions IP22. Stock Ref.

MRXBOXAB-ECO3 MRXBOX-ECO3

MRXBOXAB-ECO2 MRXBOX-ECO2

Integra. Integra Plus EC MVHR. Installation & Commissioning. Stock Ref. N EC Integra Plus EC PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.

isense & isense-ht 230V Flush Mounted Domestic Continuous Extract Fans

Centrif Duo & Centrif Duo Plus

MRXBOXAB-ECO-LP1 100% Typical Installation. (including opposite handed versions)

Lo-Carbon Quadra Centrifugal Fan

ONE FAN FITS ALL CYFAN CENTRIFUGAL EXTRACT FAN

MECHANICAL VENTILATION WITH HEAT RECOVERY (MVHR) NEW ECO RANGE

Internal/External Wall/Window Fan Range GX6. Installation and maintenance instructions Retain for future use

SQURBO XBOX. (Pre-packaged heat recovery unit) Installation, Operating and Maintenance Instructions. Intake. Exhaust. Extract. Supply. Intake.

MEV SPIDER INSTALLATION GUIDE FOR ENGINEER / INSTALLER

CREATING A HEALTHY INDOOR ENVIRONMENT POSITIVE INPUT VENTILATION (PIV)

SUNWARM AIR SOLAR PRE-HEAT VENTILATION SYSTEM

EVP61/91/101/121. Extractor. Installation, use and maintenance.

CTE9. Extractor. Installation, use and maintenance.

EST 19H & 20H 3ph Run & Standby, Roof & Plantroom Twinfans

Wind. Service instruction

EVX101 Extractor Installation, Use and Maintenance

T-SERIES. Window & Roof Models. Installation, Set-up and Operating Instructions. 230V/1/50Hz

HR100R. Mini Air Handling Unit - For Ducted Ventilation With Heat Recovery. Installation and Servicing Instructions

airooncentre.co.uk irconcentre.co.uk Xpelair Low Energy Wall/Window Fan Range GX6 EC2 GXC6 EC2 Quick Order Hotline or

Titon CME1 Q Plus Mechanical Extract Ventilation Unit

Installation and Operating Manual Drying Cabinet

Xpelair Simply Silent DX150

MECHANICAL VENTILATION WITH HEAT RECOVERY (MVHR)

Genie-DC and DCE 12V and 230V

SLIMAIRE 230V & 12V SINGLE SPEED FANS

DRI-ECO-LINK-HC 1.0 INTRODUCTION 4.0 DIFFUSER INSTALLATION 2.0 IMPORTANT NOTES TO INSTALLERS 3.0 LOFT INSPECTION

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions

Simply Silent Contour 4 (100mm) Axial Extraction Fan

Long Case Axial Fan. Installation and Wiring Instructions V/1/50Hz & V/3/50Hz

Constant Pressure, Belt Drive Run & Standby, Roof & Plantroom Single & Twinfan Units Installation and Maintenance

PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

Lo-Carbon Quadra Centrifugal Fan

Centair CMEV.4 / CMEV.4e / CMEV.4eHT Mechanical Extract Ventilation (MEV) System Installation Instructions

MODEL: DV72 R & L. Mechanical Ventilation with Heat Recovery Installation Instructions and User Manual

EKF. EC kitchen extract fan range. Installation and Wiring Instructions. Stock Ref. N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3

Residential Carbon Friendly Ventilation SAP Q Eligible. ventilation

EDD61 & EDD91 Extractors

Model: Kair Whole House Ventilator Model Number: KHRVWH2000

READ AND SAVE THESE INSTRUCTIONS GENERAL SAFETY INFORMATION

Lo-Carbon Quadra SELV

HR200WK Through the wall Heat Recovery Ventilator

VA100 SELV 12 RANGE. Installation and Wiring Instructions IPX7

Transcription:

MEV Ecosmart Continuous Mechanical Extract Ventilation Units Installation and Maintenance ICUDIG MEV-SVS 1.0 Introduction uaire's MEV Ecosmart units are designed to provide continuous mechanical extract ventilation to homes in accordance with BRE digest 398. Coding: Two units are available as standard. Unit codes/descriptions are as follows: ES-MEV Single fan unit. ES-MEV-H Single fan unit with internal adjustable humidistat. The case is constructed in aluminium/zinc coated steel. Internal faces of the casing are acoustically lined with flame retardant acoustic foam. The full length access cover which is located on the underside of the unit, on the opposite side to the mounting bracket, is retained by four M5 screws. Figure 1. It is assumed that a solid non-reverberant mounting position has been selected and the electrical mains wiring and any optional control wires have been made ready. It is also assumed that compatible ductwork is already installed and ready to be connected to the 125mm dia. discharge spigot and also the chosen 100mm dia and/or 125mm dia. inlet spigots. ote the unit is not fitted with a backdraught shutter. (When using the continuous background vent facility a backdraught shutter is not needed). However a backdraught shutter is available from uaire if required. An integral fixing bracket with a single bolt fixing allows easy mounting and removal of the unit when necessary. The unit is supplied with the 125mm dia. discharge spigot for fitting during installation. 2.1 Unit fixing The integral mounting bracket supplied can be offered up to position, the fixing points marked through and the bracket installed with screws (by others). See figure 2. Offer the unit into position and locate the bracket into the slots in the case before fixing with the single bracket fixing screw. Figure 3. Figure. 2.0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming to all statutory and governing regulations. The fan must be fitted indoors, away from sources of water spray or steam generation. The fan can be installed at any angle using the integral mounting bracket supplied (Figure 2). Figure 2. Bracket tongues engage with casing slots, then unit rotated up to align with fixing screw hole. Slots in casing either side of unit to allow alternative mounting option. 2 rubber cable entry grommets either side of casing for external wiring. Fixing screw hole. Cut through the acoustic foam round the circumference of the damper. Damper can be swivelled on the 2 body casing hinges. When spigot is in position, damper can be adjusted using a screwdriver. Various damper/inlet spigot positions can be utilised as required to suit the system ductwork and extract grilles. All inlet dampers are closed as knockouts when delivered but can be opened using a sharp knife. (See figure 3). After the spigot has been fixed adjust the damper with a screwdriver. (See figure ). uaire imited Western Industrial Estate Caerphilly United Kingdom CF83 1A T: 029 2088 5911 F: 029 2088 7033 E: info@nuaire.co.uk W: www.nuaire.co.uk 1 eaflet umber 671266 July 2007

Installation and Maintenance MEV Ecosmart Continuous Mechanical Extract Ventilation Units The spigot locations are as follows: Two x 125mm inlet end spigots. Two x 100mm inlet spigots on H side of case. Two x 100mm inlet spigots on RH side of case. One x 125mm discharge end spigots. Any, or all of these inlets can be utilised with individual volume control being available via the relevant damper. A filter frame with a replaceable filter is push fit located inside the case which is easily removed for cleaning following removal of the case cover. Please note a clear space of at least 70 x 320mm is required to allow the cover to be removed and provide sufficient access for maintenance. The fan is designed to be wired direct to the mains supply through a fused spur (by others) and run continuously in the ORMA mode (which is the low speed, background or trickle ventilation setting) with occasional BOOST airflow (high speed setting) as and when required. The degree of extract from each room served can be adjusted with the inlet balancing spigots. The unit is provided with adjustment for the low speed (ORMA) and high speed (BOOST) ventilation rate as required. 2.2 Electrical connection With the unit fixed in position and working from underneath the installation bring the external wiring through the chosen rubber cable entry grommet (two either side, see figure 2). The unit MUST be Earthed. Isolation - Before commencing work make sure that the unit, and uaire control are electrically isolated from the mains supply. 3.0 Dimensions Figure 5. Dimensions in mm. SIDE VIEW 10 Mounting bracket Single screw unit fixing 125 dia 186 x Spigot knockouts 100 dia. Cable entry 20mm ED VIEW 1 x Spigot knockout 125 dia. VIEW WITH COVER REMOVED 50 MOUTIG BRACKET TOP VIEW 10 30 2 x Spigot knockouts 125 dia. Bracket fixing holes 7.5 dia. 170 70 2 eaflet umber 671266 July 2007

Installation and Maintenance MEV Ecosmart Continuous Mechanical Extract Ventilation Units.0 Electrical Wiring (basic) Figure 6. Unit serving Bathroom only Unit Unit serving Kitchen and two Bathrooms Unit MAIS Fuse 2A Remote/light Optional lamp S MAIS Fuse 2A ight es (Double Pole) Room lights S Unit serving Kitchen and Bathroom MAIS Fuse 2A ight (Double Pole) Kitchen Room light Unit S Kitchen All field wiring, es and s, by others..1 Electrical Wiring (options) Figure 7. Circuit Board Connections. Do not use To OPUS-SPD speed control To remote fail indicator ES-MEV-AVI Internal humidity adj. VT ET TR Calibration S 30 50 60 Run-on (mins) 0 90 Max Airflow (l/s) 10 50 90 Min Airflow (l/s) 10 Status The unit is normally designed to ventilate the property continuously to give between 0.5 and 0.7 air changes per hour. A facility is included which boosts the duty as required. The boost can be achieved by the following methods: For good EMC engineering practice, any sensor cables or ed live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables. a) Switched ive (S) Connection of mains to S terminal. b) Optional Remote Speed Control (OPUS-SPD) The speed control will mimic the speed between the max and min settings selected at the fan. Connect OPUS-SPD to V terminal. c) Internal Humidistat (on the ES-MEV-H unit only) The internal humidistat can be found on the base of the fan case. The adjustment dial gives a range of 50-80% @ 20 0 C. (See figure 8). Setting to mid position gives 65% which should be acceptable for most circumstances. 3 eaflet umber 671266 July 2007

Installation and Maintenance MEV Ecosmart Continuous Mechanical Extract Ventilation Units If the unit boosts at unacceptable times, this dial should be turned clockwise by a small amount. Figure 8. 5.0 Volume Control J1 To control the volume of air the unit is equipped with two control dials, for trickle and boost duties. In order to comply with the BRE Digest the unit should be set to give a minimum of the 0.5 air change/hour for the dwelling continuously, plus 25% boost. To achieve this the volume of the property should be measured (in m 3 ) and this figure divided by 7.2. This gives the duty required in l/s. The table below is intended as a guide to achieve the correct duty (based on 0.5 ACH with 25% boost). o. of Bedrooms Typical Trickle/ Boost volume ormal duty l/s l/s 1 10m 3 19 2 2 200m 3 28 35 3 260m 3 36 5 320m 3 56 5.1 Run-on Timer 50% 80% U1 The Run-on timer adjustment is from 0-60 mins. Run-on is only available from the ed live (S) signal. 5.2 Start-up Routine TH1 On power up or and after power failure the unit goes through a 2 minute set-up period. During this period the unit: 1. Starts at full speed 2. Ramps down to off 3. Restarts at 25% speed. Resumes normal operation H1 D2 5. Calibration By pressing the calibration button the unit re-sets itself by ing off for 30 seconds then re-starts at full speed before ramping down to the desired duty. Whilst running at full speed the status light flashes to indicate if the duty set on the adjustment dials can be achieved (green for yes, amber for no). Checks can be carried out in both the trickle and boost modes. If the light flashes amber check the resistance of the ducting, grilles etc. or turn down the adjustment dial. 6.0 Maintenance It is inevitable that even with filtered extract grilles as recommended in BRE digest 398 some dust, fluff etc. will pass through the filter, and which, if allowed, will build up internally on motors and impellers, shortening the life of the unit and, in severe cases, leading to overheating of the motors. Consequently, it is strongly recommended that all units are inspected and cleaned every six months. To clean the filter, remove from the unit and wash in tepid water to which a little mild detergent has been added. Shake out excess water and allow to dry naturally. Replace when dry. 7.0 Cleaning Remove covers and carefully clean out interiors as necessary. Check for damage and security of components. Refit covers. 8.0 Replacement of Parts Should any component need replacing uaire keep extensive stocks for quick delivery. Ensure that the unit is electrically isolated, before carrying out any work. When ordering spare parts, please quote the serial number of the unit and the ARC number of the purchase if possible. (This information will be available on the fan label). 9.0 Service Enquiries uaire can assist you in all aspects of service. Our service department will be happy to provide any assistance required, initially by telephone and If necessary arrange for an engineer to call. Customer Services Department on 08705 002 555 5.3 Status ight Green light - running Red light - failure Flashing green light - Set-up period Flashing red light - Electronics failure eaflet umber 671266 July 2007

DECARATIO OF ICORPORATIO AD IFORMATIO FOR SAFE ISTAATIO, OPERATIO AD MAITEACE We declare that the machinery named below is intended to be assembled with other components to constitute a system of machinery. The machinery shall not be put into service until the system has been declared to be in conformity with the provisions of the EC Council Machinery Directive. Designation of machinery: Machinery Types: Relevant EC Council Directives: ES-MEV Continuous Extract Ventilation Unit 98/37/EC, 98/79/EC (Machinery Directive) Applied Harmonised Standards: BS E ISO 12100-1, BS E ISO 12100-2, E29, E6020-1, BS E ISO 9001 Applied ational Standards: BS88 Parts One, Two and Five Signature of manufacture representatives: ame: Position: Date: 1) C. Biggs Technical Director 20. 07. 07 2) W. Glover Manufacturing Director 20. 07. 07 DECARATIO OF COFORMITY We declare that the machine named below conforms to the requirements of EC Council Directives relating to Electromagnetic Compatibility and Safety of Electrical Equipment. Designation of machinery: Machinery Types: Relevant EC Council Directives: ES-MEV Continuous Extract Ventilation Unit 200/108/EC (EMC) 2006/95/EC (ow Voltage Directive) Applied Harmonised Standards: E5501-1, E5501-2, E60335-2-80 Basis of Self Attestation: Quality Assurance to BS E ISO 9001 BSI Registered Firm Certificate o. FM 19 Signature of manufacture representatives: ame: Position: Date: 1) C. Biggs Technical Director 20. 07. 07 2) W. Glover Manufacturing Director 20. 07. 07 IFORMATIO FOR SAFE ISTAATIO, OPERATIO AD MAITEACE OF UAIRE VETIATIO EQUIPMET To comply with EC Council Directives 73/23/EEC ow Voltage Directive To be read in conjunction with the relevant Product Documentation (see 2.1) 1.0 GEERA 1.1 The equipment referred to in this Declaration of Incorporation is supplied by uaire to be assembled into a ventilation system which may or may not include additional components. The entire system must be considered for safety purposes and it is the responsibility of the installer to ensure that all of the equipment is installed in compliance with the manufacturers recommendations and with due regard to current legislation and codes of practice. 2.0 IFORMATIO SUPPIED WITH THE EQUIPMET 2.1 Each item of equipment is supplied with a set of documentation which provides the information required for the safe installation and maintenance of the equipment. This may be in the form of a Data sheet and/or Installation and Maintenance instruction. 2.2 Each unit has a rating plate attached to its outer casing. The rating plate provides essential data relating to the equipment such as serial number, unit code and electrical data. Any further data that may be required will be found in the documentation. If any item is unclear or more information is required, contact uaire. 2.3 Where warning labels or notices are attached to the unit the instructions given must be adhered to. 3.0 TRASPORTATIO, HADIG AD STORAGE 3.1 Care must be taken at all times to prevent damage to the equipment. ote that shock to the unit may result in the balance of the impeller being affected. 3.2 When handling the equipment, care should be taken with corners and edges and that the weight distribution within the unit is considered. ifting gear such as slings or ropes must be arranged so as not to bear on the casing. 3.3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants..0 OPERATIOA IMITS.1 It is important that the specified operational limits for the equipment are adhered to e.g. operational air temperature, air borne contaminants and unit orientation..2 Where installation accessories are supplied with the specified equipment eg. wall mounting brackets. They are to be used to support the equipment only. Other system components must have separate provision for support..3 Flanges and connection spigots are provided for the purpose of joining to ductwork systems. They must not be used to support the ductwork.. In the event of RF interference the fan may increase in speed or make high pitched noises. This is normal and will have no adverse effect on the fan. The speed and noise will return to normal once the interference has subsided. 5.0 ISTAATIO REQUIREMETS In addition to the particular requirements given for the individual product, the following general requirements should be noted. 5.1 Where access to any part of equipment which moves, or can become electrically live are not prevented by the equipment panels or by fixed installation detail (eg ducting), then guarding to the appropriate standard must be fitted. 5.2 The electrical installation of the equipment must comply with the requirements of the relevant local electrical safety regulations. 6.0 COMMISSIOIG REQUIREMETS 6.1 General pre-commissioning checks relevant to safe operation consist of the following: Ensure that no foreign bodies are present within the fan or casing. Check electrical safety. e.g. Insulation and earthing. Check guarding of system. Check operation of Isolators/Controls. Check fastenings for security. 6.2 Other commissioning requirements are given in the relevant product documentation. 7.0 OPERATIOA REQUIREMETS 7.1 Equipment access panels must be in place at all times during operation of the unit, and must be secured with the original fastenings. 7.2 If failure of the equipment occurs or is suspected then it should be taken out of service until a competent person can effect repair or examination. (ote that certain ranges of equipment are designed to detect and compensate for fan failure). 8.0 MAITEACE REQUIREMETS 8.1 Specific maintenance requirements are given in the relevant product documentation. 8.2 It is important that the correct tools are used for the various tasks required. 8.3 If the access panels are to be removed for any reason the electrical supply to the unit must be isolated. 8. A minium period of two minutes should be allowed after electrical disconnection before access panels are removed. This will allow the impeller to come to rest. B: Care should still be taken however since airflow generated at some other point in the system can cause the impeller to windmill even when power is not present. 8.5 Care should be taken when removing and storing access panels in windy conditions. Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and dimensions of equipment and the right is reserved to make such changes without prior notice. 5 eaflet umber 671266 July 2007

Installation and Maintenance MEV-SVS Continuous Mechanical Ventilation /Extract Units 11.0 MEV-SVS units uaire's MEV-SVS units are designed to provide continuous mechanical supply/extract ventilation to homes enabling each room to be individually ventilated. Figure 9. Typical installation. Coding: MEV - SVS Comprising a supply fan unit, an extract fan unit and a unique multi-spigoted distribution box. Attenuators to be specified and supplied seperately. 1 2 3 Unit Extract Unit Air Distribution Box Extract Points Wet Rooms Fresh filtered air into habitable rooms 3 1 2 12.0 Electrical Wiring (MEV-SVS) MEV-SVS control wiring using remote speed control (Opus-SPD) The extract fan operates continuously in trickle mode. The supply fan will operate in trickle mode when activated by the supply fan. The remote boost will set both extract and supply fans to boost if they are operating in trickle mode. If the supply fan is ed off, only the extract fan will operate. fan boost airflow should be set to fully clockwise. The supply fan will only operate on boost speed from the boost if the speed control is set to off. Extract fan airflows should be set to meet Part F requirements. Figure 10. 1 Ph 3A Boost S Extract T V To remote speed control MEV-SVS wiring using light/remote es The extract fan operates continuously in trickle mode. The supply fan will operate in trickle mode when activated by the supply fan. The remote boost will set both extract and supply fans to boost if they are operating in trickle mode. If the supply fan is ed off, only the extract fan will operate. fan boost airflow should be set to fully clockwise. Extract fan airflows should be set to meet Part F requirements. Figure 11. 1 Ph 3A ight Room light S Extract fan S For good EMC engineering practice, any sensor cables or ed live cables should not be placed within 50mm of other cables or on the same metal cable tray as other cables. Extract fan boost fan All es by others S 6 eaflet umber 671266 July 2007