WaterFurnace FX10 Application Guide Reversible Chiller

Similar documents
BACnet Points List for Single Compressor Water to Water PROSSWWE-01

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

I/O ZONE 560/583 USERS GUIDE

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

I/O ZONE 560/583 AND OPERATION MANUAL

Installation and Maintenance Manual OM

SPECIFICATION CATALOG. Console 0.75 to 1.5 Tons. Geothermal/Water Source Heat Pump

OPERATION INSTRUCTIONS DEMAND DEFROST CONTROL BOARD MODEL FOR USE WITH MODELS: AFFINITY, ECHELON, ACCLIMATE HEAT PUMP SERIES

Table of Contents. WSHP Open v3

BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller

York 25-Ton VAV Rooftop Unit

Pathfinder Air-Cooled Chillers

Pathfinder Air-Cooled Chillers

Reciprocating Chiller

Versatec Specification Catalog

MicroTech Series 200 Centrifugal Chiller

Introduction. What is the W2W Open controller?

Open Protocol Data Communications

GeneSys Air-Cooled Screw Compressor Chiller

Pioneer Gold Controller Technical Guide

SPECIFICATION CATALOG. NXW 10 to 50 Tons. Commercial Reversible Chiller - 60 Hz

Heating and Air Conditioning

SPECIFICATION CATALOG. Low Sill Console 0.75 to 1.5 Ton. Geothermal/Water Source Heat Pump

TWLC - Tempered Water Logic Controller. The Intelligent Control

SPECIFICATION CATALOG. NKW 30 to 150 kw. Commercial Reversible Chiller - 50 Hz

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

CONTROL PANEL OPERATING MANUAL AIR-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMAC00A10-12EN

water to water heat pumps

Trinity Tft High Efficiency Gas Condensing Boiler & Water Heater

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

Water Source Heat Pump Module Technical Guide

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Heat Pump Water Heater (Generation 4) Troubleshooting (Effective 1 Nov 2016)

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

1.0 Digital Controller

ASTON CONSOLE SERIES

SPECIFICATION CATALOG. NSW Commercial 1.5 to 6 Tons. Geothermal Hydronic Heat Pump

MicroTech Series-200 Flooded Screw Chiller

Siemens Thermostats. RDY2000BN Thermostat

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

Reference Guide for Microprocessor Controller

BasicTroubleshooting Information and Guidelines

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

Project Name: Location: Engineer: Contractor: I. GENERAL

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

RSMSD Technical Guide

GEOTHERMAL HYDRONIC HEAT PUMP 1.5 TO 6 TONS SPECIFICATION CATALOG

SPECIFICATION CATALOG. Commercial 7 to 25 Tons. Geothermal/Water Source Heat Pump

Water-Cooled Scroll Compressor Chillers

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

SPECIFICATION CATALOG. NSW 1.5 to 6 Tons. Commercial Geothermal Hydronic Heat Pump

FOR SERVICE TECHNICIAN S USE ONLY

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A07-16EN

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Heating and Air Conditioning

Service Manual Models: 1.0, 1.3, and 1.5

CONTROL PANEL OPERATING MANUAL WATER-COOLED SCREW CHILLER MICROTECH III CONTROLLER D EOMWC00A04-14EN

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

Pioneer Gold Controller Technical Guide. Pioneer Gold Controller Code: Version 1.1 Used with AAON WSHP WV Series Vertical and WH Series Horizontal

Digital Precise Air Control - DPAC

SPECIFICATION CATALOG. Commercial 7 to 25 Tons. Geothermal/Water Source Heat Pump

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Operating Functions Temperature Parameters

INSTALLATION INSTRUCTIONS TEC40 ELECTRONIC CONTROLLER

Verasys System Operation Overview Technical Bulletin

prestige Control Application Supplement - Type 5 MCBA WARNING

FOR SERVICE TECHNICIAN S USE ONLY

AHWG Remote Mount Hot Water Generator Module

INSTALLATION INSTRUCTIONS

Service Manual. w/con X US Interface Models: Series: & WARNING

B-40/B-41 Modulating Temperature Controller

prestige Control Application Supplement - Type 5 MCBA WARNING

1.0 Digital Controller

Reinventing Energy Efficiency

FieldServer Driver - Serial FS McQuay Microtech Open Protocol

NDW Installation Manual

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP 100% OUTSIDE AIR

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

KM-61BAH KM-101BAH KM-151BAH

AHWG Remote Mount Hot Water Generator Module for TTP Series Outdoor Split Unit

Table of Contents. W2W Open

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

prestige Control Application Supplement WARNING

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

GEOTHERMAL HEAT PUMPS AFFORDABLE RENEWABLE CLEAN

Heat Pump Defrost Board Replacement Kit

PERFECT SOLUTIONS WATERFURNACE COMMERCIAL PRODUCTS. Water Source/Geothermal Heat Pumps

CONTROL OPTIONS SPACE HEATING APPLICATIONS MAKEUP AIR HEATING APPLICATIONS PEH, PXH, RDH, REH, RXH, SDH & SHH. Horizontal Split System- Models PDH,

Service Manual. w/con X US Interface Models: WARNING

NXW Reversible Chiller Installation Manual

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

Commercial Series. Power switch & Nameplate location: NAMEPLATE: Single and Dual Section

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Introduction. What is the W2W Open controller?

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Transcription:

2011 WaterFurnace FX10 Application Guide Reversible Chiller

Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water to water heat pumps (8 to 50 tons nominal capacity). The manual describes the controller s components, input/output configurations and service procedures. While many WSHP s look and function in a similar manner, there may be significant internal differences that are defined by the model nomenclature. It is imperative that the specific model of the WSHP be properly identified prior to wiring, commissioning or servicing the unit controls. Failure to do so may cause damage to the unit. The FX10 WSHP controller contains a factory programmed microprocessor which has been tested for safe and reliable unit operation. The actual software programs will vary depending upon factory installed options or engineering specials in order to meet specific customer requirements. The software code is identified on each FX10 controller by a label (i.e. PRODCWWE-06). Each software program uses pre-determined factory fixed control parameters as well as network defined variables to maintain proper unit control. While nearly all of these are available to view over the building automation systems (BAS) network, only the network defined variables may be manipulated using a computer over the BAS network. There are NO INTERNAL SETPOINTS in the controller. Standard features of the FX10 WSHP controller include: Heating and cooling control input from external control system (Aquastat or BAS network) Monitoring of all equipment protection controls Sequencing and timing of compressor operation Status of all unit fault and lockout functions o High pressure refrigerant o Low pressure refrigerant o Water freeze protection Display Link Interface (DLI) board used in conjunction with the unit mounted Medium User Interface (MUI) local control display Input / Output expansion board (factory predefined I/O) Optional control inputs/outputs (predefined or network configurable) Optional features of the FX10 WSHP controller include: Open N2 (Metasys) communication board LON network communication board BACnet (MSTP 19,200 baud rate) communication board Page 2 of 7

Sequence of Operation When power is applied to the FX10, the processor executes a power-on start-up sequence that includes the generation of a random length program start delay which varies between 1 and 120 seconds. Upon the termination of the start delay timer, the thermostatic inputs of Y1, Y2 and O are examined to determine the specific mode of operation that is required. Temperature Monitoring The FX10 WSHP controller uses a Positive Temperature Coefficient (PTC) thermistor for temperature sensing. A thermistor chart, which provides voltage to temperature and resistance to temperature conversion data, is included on the last page of this manual. The network variables nvoentsource, nvolevsource, nvoentload and nvolevload will show the measured temperatures at the water connections of the WSHP over the network. Reversing Valve The position of the reversing valve is determined by a 24VAC external control input to the FX10 on the units low voltage terminal strip. If the reversing valve is de-energized (cooling mode), it will remain in this position until the O terminal of the low voltage terminal strip is energized with 24VAC indicating a need for heating. All applicable compressor timed delays are enforced to allow refrigeration pressures to equalize prior to a change in reversing valve position. Using the BAS the reversing valve can be commanded by writing to the REV VALVE CMD (Multistate Output 14.3) 1=cooling and 2=heating. Compressor Upon energizing the Y1 or Y2 terminals on the units low voltage terminal strip with 24VAC, the first indication of an eventual compressor operation is that the X1 (Accessory 1) output will be energized with 24 VAC. After a 90 second delay, the compressor will be energized if the internal safeties permit. Compressor operation will continue until the 24VAC control input is removed from the Y1 or Y2 terminals. Unit / Compressor Protection There are several conditions that will prevent or interrupt unit/compressor operation. There are also minimum operation times which are strictly enforced by the FX10 controller and are not adjustable or accessible. Minimum Run Once compressor operation is initiated, a fixed 120 second run time is enforced (start to stop). Only a high pressure fault, compressor start fault or an emergency stop command can halt the compressor during this period. This period is essential to ensuring proper oil return to the compressor. Minimum Off When compressor operation is terminated, a fixed minimum off time of 5 minutes is enforced (stop to start). This minimum off time is intended to allow time for the gas pressures to equalize and to minimize the starting load on the compressor as well as giving the compressor windings time to cool down from the heat experienced during start of a compressor and its high current draw. Page 3 of 7

High Pressure If the high pressure switch opens at any time, the compressor is immediately disabled. Three high pressure events within a 60 minute period will result in a manual reset lock-out. An alarm is generated for this condition. Low Pressure If the low pressure switch is open prior to compressor start, it is deemed a loss of charge condition and the compressor will not start. An alarm is generated for this condition. Once the compressor is started, the low pressure switch is ignored for the first 2 minutes. Thereafter, if the low pressure switch is open for 30 continuous seconds, compressor operation is halted. Three low pressure events within a 60 minute period will result in a manual reset Lock-out. An alarm is generated for this condition. Low Temperature To prevent freeze damage to the brazed plate heat exchangers, the refrigerant temperature is monitored after the minimum run time has expired. If the refrigerant temperature is below the low limit for 30 seconds continuously, compressor operation is halted. Three low temperature events within a 60 minute period will result in a manual reset Lock-out. An alarm is generated for this condition. The temperature sensor is located on the low pressure refrigerant line in close proximity to the leaving water outlet of the heat exchanger. The FX10 automatically converts the refrigerant temperature to a corresponding leaving water temperature for comparison to the freeze protection set point. The refrigerant temperature is utilized as it responds more quickly to changes in temperature and is less susceptible to errors caused by changes in water flow or sensor installation. Laboratory testing has proven that the error rate in the temperature between the refrigerant and water while in the heating mode is less than 1 F (less than 2 F in cooling mode). Reversing Valve change If the compressor is operating and the minimum run timer has expired, a commanded change in the reversing valve position will halt the compressor. The compressor will not be started until the minimum off timer has expired and all safeties have been satisfied. Internal Compressor Control Module Reads a thermister chain within the compressor to protect against excessive motor and discharge temperature. A problem in either area will cause the module to interrupt the control circuit. Phase Guard Control Module The phase guard module monitors the supply voltage to the unit. If any of the points it monitors are outside of the range the phase guard will remove power to the control board until the condition is corrected. The points it monitors are under/over voltage, phase imbalance, phase loss, and phase reversal. Additional Features Advanced Freeze Protection Freeze protection uses the leaving water temperature and the refrigerant temperature to determine if a freeze condition is possible, and will disable the compressor associated with the freeze condition. If both Page 4 of 7

compressors are running at the time of this, only the compressor associated with the freeze condition will be shut down. If there is only one compressor running it will shut down this compressor and not allow the other compressor to start until the temperature is above a value that is determined by the freeze setpoint. It takes three failures within a 60 minute period to create a lockout condition, which will generate a manual reset alarm. Alarm Reset In the event of a manual reset lockout, the condition may be reset by turning off primary power for a minimum of 20 seconds. The lockout can also be reset over the BAS network by commanding the variable nvialarmreset from an uncommanded or Off value to a Low_ST_On value. In the event that the network is not available, but a Medium User Interface (MUI) is connected; simultaneously pressing of the Return and ESC keys on the display will also reset the alarm. Emergency Shutdown DI-2 on the FX10 controller has been predefined as the emergency shutdown input. In the event that it is necessary to disable operation of the WSHP unit, DI-2 recognizes a voltage free contact closure as a command to cease unit operation. The compressor and blower contactors are interlock with DI-2 internally and will drop out 24VAC to the contactors and thereby disabling unit function. The unit will operate normally when a normally open circuit is detected by the controller. Compressor delay timers are restarted at this time. Motorized Solenoid Valve Located on the WSHP low voltage terminal board, X1 (Accessory 1) is wired to DO-7 of the FX10 controller, which is cycled with the operation of the compressor. The X1 terminal is energized (24VAC) when the compressor is operating (factory default selection), and is field adjustable to accommodate alternative valve actuation. General Fault When an alarm condition is actively preventing compressor operation, the L terminal located on the low voltage terminal board and wired to DO-6 of the FX10 controller will be energized (24VAC). Network Alarm Variable The network variable nvoalarms has a numeric output that shows the alarm condition of the WSHP. The Alarm values for the NXW are as follows: 0=No alarms 13=Bad Sensor Load Compressor 2 1=Load Flow Switch 14=Hi Pressure Compressor 2 2=Compressor 1 Low Suction Pressure 15= Compressor 1 Start Fail alarm 3=Source Low Temp alarm Compressor 1 16=Low temp cutoff Comp 1 4=Source Predictive Freeze alarm Compressor 1 17= Low temp cutoff Comp 2 5=Source Flow Switch 18=Compressor 2 Start Failure alarm 6=Hi Pressure Compressor 1 19=Load Low Temp alarm Compressor 1 7=Bad Source Sensor Compressor 1 20=Load Predictive Freeze alarm Compressor 1 8=Bad Load Sensor Compressor 1 21=Load Low Temp alarm compressor 2 9=Compressor 2 Low Suction Pressure 22=Load predictive Freeze alarm compressor 2 10=Source Low Temp alarm Compressor 2 23=Compressor 1 charge loss 11=Bad Sensor Source Compressor 2 24=compressor 2 charge loss 12= Source Predictive Freeze alarm Compressor2 Page 5 of 7

Brownout Protection The FX10 has been designed to protect the compressor contactors from low voltage or brownout conditions. If the supply voltage to the WSHP is below 85% of the nameplate rating, the FX10 deenergizes the compressor and blower contactors. When proper power has been restored the WSHP resumes normal operation. Lead-Lag When the unit receives a Y1 or Y2 call, the processor will determine which of the two compressors was last to run and then it will enable the other compressor, the unit does not care which Y1 or Y2 signal it receives, lead lag is determined by using a the theory of the first on is the first off and the last off is the last on. Commissioning The following commissioning procedures pertain to Water Source Heat Pumps (WSHP) with the factory applied FX10 unitary controller. These procedures must be performed in addition to the mechanical, electrical and plumbing procedures outlined in the installation and operations manuals of each specific WSHP. Before a unit has power applied to it, a technician must visually inspect the control box to verify that all wire connections are tight, and that all Molex plugs are properly and fully seated on the control board. After this step is complete the technician can apply power to the unit and begin to fill out the startup sheet. Once the unit is up and operational, the technician will need to record all the readings and verify that they are within the unit specifications. Communication WaterFurnace offers three different communication protocols, LONworks, N2 Open, BACnet. Points list are available for download from the Commercial page of the Waterfurnace website. Page 6 of 7

A99 Sensor Chart Voltage to Temperature to Resistance Voltage DC Temperature C Temperature F Resistance Ω -40-40 613-35 -31 640 1.170-30 -22 668 1.207-25 -13 697 1.245-20 -4 727 1.284-15 5 758 1.323-10 14 789 1.362-5 23 822 1.402 0 32 855 1.443 5 41 889 1.483 10 50 924 1.522 15 59 960 1.562 20 68 997 1.603 25 77 1035 1.642 30 86 1074 1.682 35 95 1113 1.722 40 104 1153 1.760 45 113 1194 1.792 50 122 1236 1.840 55 131 1279 1.878 60 140 1323 1.917 65 149 1368 1.955 70 158 1413 1.993 75 167 1459 2.031 80 176 1506 2.069 85 185 1554 2.106 90 194 1602 2.142 95 203 1652 100 212 1702 105 221 1753 A99 sensors are only used in Units that have the FX10 Controller. Page 7 of 7