Case 8 Basic Performance of Screw Compressor

Similar documents
Case 6 Impact of Fouling Factor and Special Material for Heat Exchanger

Case 15 Refrigeration System for Chemical Fertilizer Plant Ammonia Storage

Cascade Refrigeration System for LPG Subcooling. Related Technical Data and Information for the Case:

Copy Right By: Thomas T.S. Wan

Partial Load Performance Of Refrigeration System

Chapter 4 Compressors Overview & System Annual Power Consumption

Case 13 Food Storage & Processing Center

Refrigerant Cycle. Performance Data 1) Electric. Acoustic Pressure Level. Compressor. Connections, Dimensions

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

A Treatise on Liquid Subcooling

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

APOGEE Open Processor with McQuay Microtech Driver: European Reciprocating Chiller (CR1)

PACKAGED AIR COOLED Product Data Catalog

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

FOR SERVICE TECHNICIAN S USE ONLY

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

Energy Use in Refrigeration Systems

THE FIVE W s SYSTEMES LMP MECHANICAL SUB-COOLING. I.G.A. GIRARD, TERREBONNE, Qc. INCREASED SYSTEM EFFICIENCY & LOWER ENERGY COSTS

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

Daikin VRV Service & Troubleshooting

REFRIGERATION AND AIR CONDITIONING RÉFRIGÉRATION ET CLIMATISATION POST-SECONDARY NIVEAU POSTSECONDAIRE

USING THE P-T CARD AS A SERVICE TOOL

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

Check valve Types NRV and NRVH

The Refrigeration Cycle

Superheat charging curves for technicians

SECTION 2 SAFETY, TOOLS AND EQUIPMENT, SHOP PRACTICES UNIT 10 SYSTEM CHARGING

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

4A6H5042G1000A 208/230/1/ DURATION - SCROLL 3/4 208/230/1/ NO (Use BAYKSKT263) YES YES PROPELLER DIRECT

SELF-CONTAINED VERTICAL AIR COOLED PACKAGE AIR-CONDITIONERS

Warm Case Troubleshooting Guide 9/18/2014

The Refrigeration Cycle

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Thermostatic Expansion valves, type TUA/TUAE REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Control of FGB (Flash Gas Bypass) in Start-Up and Transients. Mr. Nemanja Dzinic, Pega Hrnjak CTS, USA & MPG-KGH d.o.o., Serbia

Checking the Charge on a Heat Pump in the Winter

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

Sporlan Valve Division Parker Hannifan/CIC Group

Thermostatic expansion valves for ammonia Type TEA

JCseries EVAPORATIVE CONDENSER. engineering data

Split System Heat Pumps

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

208/230/1/60 5/8 5/8 5/8 5/8 5/8 20 CLIMATUFF /230/1/

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

Refrigerant Glide and Effect on Performances Declaration

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability

Application Engineering

Technical Bulletin (TB-0037)

Refrigerants and lubricants

A new concept at refueling CNG stations

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Transcritical CO2 Bottle Cooler Development

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

MAC-120HE-03 Air-Cooled Chiller

APOGEE Open Processor with McQuay Microtech Driver: Series 200 Centrifugal Chiller

McQuay BACnet Solution: Microtech II Water-Cooled Centrifugal Chiller Controller (WSC, WDC, WPV)

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

Service Step by Step Trouble-Shooting Check-List

Pump technology: Improved energy efficiency in refrigeration plants. Dr. R. Krämer

4A6H5049E1000B 208/230/1/ /8 7/8 7/8 7/8 DURATION 208/230/1/ /230/1/ SPINE FIN 13 LBS., 10 OZ. YES

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

2016 Annual Conference

MAC N-407 Air-Cooled Chiller

RSMV Technical Guide

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Chillers. Technical Data. EWYD-BZ 250~580 kw

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

FOR SERVICE TECHNICIAN S USE ONLY

TECHNICAL GUIDE HIGH EFFICIENCY, STANDARD ECM VERTICAL WALL MOUNT AIR HANDLERS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: EWX*18-36

Liebert CRV Warranty Inspection Check Sheet

Tube-in-tube heat exchanger Type HE

Product Data. Features/Benefits. 38AH Commercial Air-Cooled Condensing Units 50/60 Hz. 20 to 130 Nominal Tons (63 to 390 Nominal kw)

Call us today! (800)

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

The Saturation process

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

THERMOSTATIC EXPANSION VALVES Part 1

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

MACH N-407 Heat Pump Air-Cooled Chiller

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Commercial High-Efficiency Condensing Units

MASS. MARITIME ACADEMY

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Danfoss scroll compressors SH- In parallel installation

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Pressure Enthalpy Charts

Refrigeration/Troubleshooting Manual

HVAC/R Refrigerant Cycle Basics

Transcription:

Case 8 Basic Performance of Screw Compressor Copy Right By: Thomas T.S. Wan ) June 24, 2010 All Rights Reserved Case Background: The basic rating and performance given by a compressor manufacturer is usually the bare rating of the compressor without any discharge and suction penalties, not even include the pressure drops of the standard option of the discharge valve, discharge check valve, suction valve suction strainer and etc. In order to understand the basic performance of the screw compressor, it is best to know the performance table published by the compressor manufacturer and make the compressor selection by using these performance table and curves. The followings are three different inquiry examples; each requires using the performance table to make screw compressor selection, by compare the selection results, it shall provide a better understanding of the basic performance of the screw compressor given by the manufacturer. Inquiry No. 1: Refrigeration capacity 252 TR, saturated condensing temperature is 105ºF, evaporative temperature is -15ºF, R-717, 380-3-50 power supply. Water cooled condenser with pre-lube oil pump. Water cooled oil cooling. 10ºF liquid subcooling in condenser. No economizing is allowed. 10ºF suction superheat. Use the information layout in the section of Rated Technical Data and Engineering Information for the Case; make a compressor selection to meet the operating conditions specified. What is (1) Compressor Size Selected, (2) Power Consumption in BHP and (3) BHP/TR. Inquiry No. 2: Refrigeration capacity 252 TR, saturated condensing temperature is 105ºF, evaporative temperature is -15ºF, R-717, 380-3-50 power supply.

Water cooled condenser with pre-lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. Flash type economizing is used. 10ºF suction superheat. Use the information layout in the section of Rated Technical Data and Engineering Information for the Case; make a compressor selection to meet the operating conditions specified. What is (1) Compressor Size Selected, (2) Power Consumption in BHP and (3) BHP/TR. Inquiry No. 3: Refrigeration capacity 252 TR, saturated condensing temperature is 105ºF, evaporative temperature is -15ºF, R-717, 380-3-50 power supply. Water cooled condenser with pre-lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. Flash type economizing is used. 20ºF suction superheat. Discharge external piping pressure drop is 3.7 Psi. External suction piping pressure drop is 1.3 Psi. Use the information layout in the section of Rated Technical Data and Engineering Information for the Case; make a compressor selection to meet the operating conditions specified. What is (1) Compressor Size Selected, (2) Power Consumption in BHP and (3) BHP/TR. Compare the compressor sizes, power consumptions and BHP/TR for the above three inquiries of 1.0, 2.0 and 3.0: Compressor Size Selected Power Consumption BHP BHP/TR Inquiry No. 1 Inquiry No. 2 Inquiry No. 3 No Economizing No ext. pres. drop With economizing No ext. pres. drop With economizing With ext. pres. drops

Related Technical Data and Engineering Information for the Case: Figure 8-1 Performance Table for WB-II-222E Compressor R-717 (Model with Economizer)

Figure 8-2 Performance Table for WB-II-270 Compressor R-717 (Model without Economizer)

Figure 8-3 Performance Table for WB-II-270E Compressor R-717 (Model with Economizer)

Figure 8-4 Performance Table for WB-II-316 Compressor R-717 (Model without Economizer)

Figure 8-5 Performance Table for WB-II-316E Compressor R-717 (Model with Economizer)

Figure 8-6 Performance Table for WB-II-399 Compressor R-717 (Model without economizer)

Figure 8-7 Typical Part Load Power Input Constant Condensing Temperature for High Stage Compressor

Figure 8-8 Typical Part Load Power Input with Falling Condensing Temperature for High Stage

Figure 8-9 Standard Pre-Lube System Limit for High Stage

Clarifications for Performance Ratings of WB-II Compressor Units 1.0 Standard Conditions for the High Stage Ratings: 2.0 Selection Procedure for High Stage Compressors: 3.0 Condenser Liquid Subcooling Correction Factors for High Stage Compressors:

4.0 Suction Superheat Correction Factors for High Stage Compressors:

Cogitation: 1.0 Inquiry No. 1: Refrigeration capacity: 252 TR Saturated condensing temperature: 105 F (CT) Saturated suction temperature: -15 F (Same as ET) Refrigerant: R-717 Power 380-3-50. compressor speed: 2,950 RPM Pre-Lube oil pump. Water cooled oil cooling. 10 F Liquid subcooling in condenser. 10 F Suction superheat. No economizing. This shall be a standard rating for high stage compressor except that the compressor is driven by a 50 Hz motor at 2,950 RPM compressor speed. (See No. 1 and No. 2 of the Clarifications for Performance Ratings of WB Compressors): Capacity and power consumption correction factor is 0.833. Converting the capacity to 60 Hz, 3,550 RPM compressor speed rating, it shall be 252/0.833 = 302.5 TR. From the compressor performance table Figure 8-6, compressor without economizer: WB-II-399 at CT 105 F and ET of -15 F at 60 Hz: Capacity Power consumption = 359.6 TR = 831.7 BHP Correction Factor Capacity and power consumption is 0.833 for 50 Hz of 2,950 RPM compressor speed: Corrected Capacity = 0.833 x 359.6 Corrected Power consumption = 0.833 x 831.7 = 299.7 TR = 690.3 BHP At the rated capacity of 252 TR as specified, the compressor is actually at partial load; refer to Figure 8-7, the partial load power input with constant condensing temperature at evaporative temperature of 15 F, the power consumption is calculated as the following: Percent of capacity = (252/299.7) = 0.841 The power consumption correction factor = 0.88 Therefore, power consumption at 252 TR is calculated:

= 690.3 x 0.88 = 607.5 BHP Conclusion: Compressor selected: Capacity at rated conditions: Power consumption: WB-II-399 252 TR 608 BHP 2.0 Inquiry No. 2. Refrigeration capacity: 252 TR Condensing temperature: 105 F Evaporative temperature: -15 F Refrigerant: R-717 Power 380-3-50. compressor speed: 2,950 RPM Pre-Lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. 10 F Suction superheat. Flash type economizing is used. Capacity Correction Factor for 0 F liquid subcooling for condenser: (See No. 3 of the Clarifications for Performance Ratings of WB Compressors): S.C.C.F. = 1 + (S.C. - 10 F) x 0.0025 = 1 + (0 10) x 0.0025 = 0.975 Correction Factors for 50 Hz of 2,950 RPM compressor speed: Capacity Correction Factor: 0.833 Power Consumption Correction Factor: 0.833 The capacity of the compressor at 60 Hz 252 = -------------------------- = 310.3 TR 0.975 x 0.833 From the Figure 8-5, the standard ratings for WB-II-316E compressor, the compressor model with economizer at condensing temperature of 105 F and evaporative temperature of -15 F at 60 Hz:, the capacity and power consumption for the compressor are as the following:

Capacity Power consumption = 340.6 TR = 713.3 BHP Correct the capacity and power consumption for 50 Hz operation: Corrected Capacity = 340.6 x 0.975 x 0.833 Corrected Power consumption = 713.3 x 0.833 = 275.6 TR = 594.2 BHP At the rated capacity of 252 TR as specified, the compressor is actually at partial load; refer to Figure 8-7, the partial load power input with constant condensing temperature at evaporative temperature of 15 F, the power consumption is calculated as the following: Percent of capacity = (252/275.6) = 0.914 The power consumption correction factor = 0.93 Therefore, power consumption at 252 TR is calculated: = 594.2 x 0.93 = 552.6 BHP Therefore: Compressor selected: Capacity at rated conditions: Power consumption: WB-II-316E 252 TR 553 BHP 3.0 Inquiry No. 3 Refrigeration capacity: 245 TR Condensing temperature: 105 F Evaporative temperature: -15 F Refrigerant: R-717 Power 380-3-50, compressor speed: 2,950 RPM Pre-Lube oil pump. Water cooled oil cooling. No liquid subcooling in condenser. 20 F Suction superheat. Flash type economizing is used. Discharge external piping pressure drop is 3.7 Psi. External suction piping pressure drop is 1.3 Psi.

The condensing pressure at 105 F is 214.2 Psig, discharge external piping pressure drop is 3.7 Psi. Compressor discharge pressure: = 214.2 + 3.7 PSI = 217.9 PSIG The saturated evaporative pressure at 6.2 F is 6.2 Psig, the external piping pressure drop is 1.3 Psi Compressor suction pressure: = 6.2 + 1.3 PSI = 4.9 PSIG From the compressor performance table of Figure 8-5, model with economizer: WB-II-316E at condensing pressure of 217.9 Psig and suction pressure of 4.9 Psig: Capacity Power consumption = 319.7 TR = 706.6 BHP Correction for 50 Hz of 2,950 RPM compressor speed: Capacity Correction Factor: 0.833 Power Consumption Correction Factor: 0.833 Capacity Correction Factor for 0 F liquid subcooling for condenser: (See Selection Guide, Rule No. 3: S.C.C.F. = 1 + (S.C. - 10 F) x 0.0025 = 1 + (0 10) x 0.0025 = 0.975 From No. 4 of the Clarifications for Performance Ratings of WB Compressors, Suction Superheat Correction Factors for for 20 F suction superheat: 1 SHCF = ----------------------------------------- 1 + (S.H. 10 F) x (0.0027) 1 = -------------------------------------- 1 + (20 10 F) x (0.0027) = 0.9737 Corrected capacity = 319.7 x 0.833 x 0.975 x 0.9737 = 252.8 TR

Corrected Power consumption = 0.833 x 706.6 Therefore: Compressor selected: Capacity at rated conditions: Power consumption: = 588.8 BHP WB-II-316E 252 TR 587 BHP Comparisons: Compare the compressor sizes, power consumption and BHP/TR for the above Inquiries of 1.0, 2.0 and 3.0: Question No. 1 Question No. 2 Question No. 3 No economizing No ext. pres. drop With economizing No ext. pres. drop With economizing With ext. pres. drop Compressor Size Selected WB-II-399 WB-II-316E WB-II-316E Power Consumption BHP 608 553 587 BHP/TR 2.41 2.19 2.33 Conclusion; (A) (B) (C) (D) Inquiry No. 1: The compressor is without economizer. The compressor is larger and having higher power consumption, even no external piping pressure drops are included. Inquiry No. 2 is the compressor with economizer, but, without external piping pressure drops being considered. The selection results in smaller size compressor and lower power consumption than the Inquiry No. 1. The compressor size of Inquiry No. 3 has higher power consumption than the Inquiry No. 2, because external piping drops and superheat are included in the operating conditions; yet the compressor size and the power consumption are smaller than the compressor for Inquiry No. 1. The operating conditions for Inquiry No. 1 and No. 2 are idea cases; it does not reflect the actual working condition. In an actual system design, discharge, suction external piping pressure drop and suction superheat must be included.