QPM21 Series Duct CO 2 and Air Quality Sensors

Similar documents
Technical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application

Duct Air Quality Sensors

Room air quality sensors

Room Air Quality Sensors

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

for relative humidity and temperature

Use. In ventilating and air conditioning plants to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation.

QPA63... CO 2 /VOC Sensors. Siemens Building Technologies HVAC Products

QFM21... Duct sensors. Symaro. for relative humidity and temperature

for relative humidity and temperature

Duct Temperature Sensors

for relative humidity and temperature with calibration certificates

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Room Temperature Sensors

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Duct Temperature Sensors

Hygro Transducer / Hygrothermal Transducer and CO 2 Measuring Probe for Climate Monitoring

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies.

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Sensing & Inspection Technologies.

Differential pressure sensors

RAB10 Series Two-pipe Fan Coil Room Thermostat with Manual Changeover

Flush-mount room sensor KNX S-Mode / KNX LTE- Mode / KNX PL-Link

Room Temperature Controller

Hygro/hygrothermal transducers (hygrometric)

PRELIMINARY EDITION

SIMRAD GD10PE IR GAS DETECTOR

No. Icon Name Function

Hygro Transducer, Hygrothermal Transducer, and CO 2 Measuring Probe for Building Management and Climate Monitoring

Hygro/hygrothermal transducers (hygrometric)

Room Temperature Sensor

LC2200 Level Controller Installation and Maintenance Instructions

Semi flush-mount room thermostat

Datasheet: K-22 LO Sensor

Copying contents of this booklet or handing over to third party is strictly forbidden without written permission from Detector Oy.

Ventostat Wall Mount. Amphenol Advanced Sensors. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. Features:

Solid Core and Split Core 0-5, 0-10 Vdc Output Current Sensors CTS-05,10; CTP-05,-10

JBE LED2000 INDUSTRIAL SOLUTIONS FOR LED & INCANDESCENT MAINS LIGHTING FLICKER FREE TRAILING EDGE DIMMER

LC1350 Level Controller

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

HT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH

Indoor Air Quality Controller

Minimal maintenance requirements - No consumables and low cost of ownership. Rapid, accurate results - for safe operation of coal handling systems

SIMRAD GD10 IR GAS DETECTOR

RH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description

Room Temperature Controller

C7232A,B Sensor and Controller CARBON DIOXIDE SENSOR

Duct Humidity and Temperature Transmitter. Features. IP65 protection. Ordering

Hygro and Hygrothermo Transducers (capacitive) for climatic applications

Preliminary Release. Room Temperature

SET Installation and Operating Instructions. Level switch for one sensor

Technical Instructions Document No P25 ET September 28, ET 141 Electric Surface Mounted Thermostat.

OilSET Installation and Operating Instructions. Oil Separator Alarm Device with SET/DM3AL sensor

Two-Channel Gas Controller

RVL481. Heating Controller. including d.h.w. heating

UV Flame Supervision System

QVE1901U Flow Switch. Technical Instructions Document No September 20, Description. Features. Application.

Powers TM Controls ET 134 Line Voltage Room Thermostats

Immersion Temperature Controller

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

02/11/2015

Oxygen (O2) Single-Point Gas Detection System

Lamp Supply (Recommended)

Carbon Monoxide (CO) Gas Detector March 15 GCO 300

Air Quality Sensors. Particle Matter, CO 2, Humidity, Temperature and Dust Products. OEM Sensor Components for Air Quality and Environmental Control

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

Intelligent combined sensor for Air Quality (VOC) + Humidity (rh) + Temperature (T) with analogue outputs, Modbus and LCD display. Features.

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

Sensor unit MC2 with analog output for Freon gases and refrigerants

RVL480. Heating Controller

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25T EN0l-6091 February 2009

RVP310. Heating Controller. Building Technologies HVAC Products

SET-2000 Hi Level/Oil

Room controller. RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone.

OilSET-1000 (12 VDC)

HTO-45 HUMIDITY TEMPERATURE PROBE INSTRUCTION MANUAL

VMX DEMAND CONTROLLED VENTILATION FOR NON RESIDENTIAL BUILDINGS

MANDÍK MEASUREMENT AND CONTROL SYSTEM

Room thermostats with LCD for wall mounting

Room Temperature Controller with LCD

Room controllers with manual forced ventilation function

CMT MANUAL 6. NMC SENSORS

HVAC Sensors Catalogue

Flush-mounted room thermostat

Product Test report. Security Systems TO WHOM IT MAY CONCERN. Bosch Security Systems Torenallee 49 Eindhoven 5617 BA The Netherlands AT18-Q1616

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

RVL479. Heating Controller. for use with a partner unit

DESIGN MANUAL. The information in this doucment is applicable to sensors built in September, 2009 or later (Firmware 3.0)

REA 105 Arc Protection Module. Operator s Manual

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

SET-2000 Oil/Sludge. Alarm Device for Oil Separators. Installation and Operating Instructions

Transcription:

Document No. CE1N1962 QPM21 Series Duct CO 2 and Air Quality Sensors Description Features Application The Carbon Dioxide (CO 2 ) Duct Sensors are directly wired to the controller via twisted pair and/or three conductor cables (18 to 22 AW). The number and type of cables required depends on the model selected. All field wiring is terminated in a terminal block on the sensor body. All CO 2 duct sensors deliver a 0 to 1dc output signal. Maintenance-free CO 2 sensing element based on optical infrared absorption measurement, Non Dispersive Infrared (NDIR). CO 2 temperature and CO 2 humidity-temperature multisensor. No recalibrations required. Operating voltage 24 Vac. Signal outputs 0 to 1dc. For use in air ducts of ventilation and air conditioning applications to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation. The sensor acquires: CO 2 concentrations. VOC concentrations as an indication of odors in the duct air, such as tobacco smoke, body odor, or material fumes. The relative humidity of the duct air. The duct air temperature. The QPM21 Series Sensors can be used as a: Control sensor in the supply or exhaust air duct. Transmitter for building automation and control systems and/or display units. Typical use: Acquisition of CO 2 and VOC concentrations: In party rooms, lounges, fair pavilions and exhibition halls, restaurants, canteens, shopping malls, sports gymnasiums, sales rooms, and conference rooms. Acquisition of CO 2 concentrations: In ventilation applications of rooms with varying occupancy levels where smoking is prohibited, such as museums, theaters, movie theaters, auditoriums, office spaces and school rooms.

QPM 21 Series Duct CO 2 and Air Quality Sensors Application, Continued NOTES: The QPM21 Series Sensors are not suited for use as safety devices, such as gas or smoke warning devices. Do not install outdoors. Product Numbers Table 1. Product Number CO 2 Measuring Range VOC Sensitivity Temperature Measuring Range Humidity Measuring Range QPM2100 QPM2102 Low (R1) 0 to 2000 ppm Normal (R2) High (R3) QPM2160 32 F to 122 F/-31 F to 95 F QPM2162 (0 to 50 C/-35 to 35 C) 0 to 100% Ordering When ordering, specify product number and description. For example: Duct air quality sensor QPM2102 The sensor is supplied complete with mounting flange and cable entry gland M16. Equipment Combinations Mode of Operation CO 2 Concentrations The QPM21 Series Air Quality Sensors are suited for use with all types of systems and devices capable of acquiring and handling the 0 to 1dc output signal delivered by the sensor. The QPM21 Series Air Quality Sensors acquire the CO 2 concentration by infrared absorption measurement (NDIR). Due to an additional integrated reference light source, the measurement is always accurate. This reduces service costs as no service or recalibration is needed. The resulting output signal of 0 to 1dc is proportional to the CO 2 content of the ambient air. U1 [V] 10 8 6 4 SEN0440R1 2 0 0 400 800 1200 1600 2000 CO 2 [ppm] Figure 1. Function Diagram CO 2 (Output U1). Page 2

QPM 21 Series Duct CO 2 and Air Quality Sensors Technical Instructions CO 2 /VOC Concentration (QPM2102 Only) The sensor acquires and evaluates the CO 2 /VOC concentration and converts it to a ventilation demand signal. It represents the result of maximum selection of the CO 2 measuring signal and the filtered VOC measuring signal. With maximum selection, the two demand signals are compared and depending on the result and the selected VOC sensitivity delivered as the common air quality demand. The ventilation demand signal is delivered via output U2 as a 0 to 1dc signal to be fed to the ventilation controller. U2 [V] 10 8 6 4 2 0 SEN0441R1 0 400 800 1200 1600 2000 Max (CO 2, VOC) [ppm] Figure 2. Ventilation Demand Diagram (Output U2). VOC Sensitivity Using the jumper on the setting element for the measuring range, the impact of VOC ventilation demand on maximum selection against CO 2 ventilation demand can be changed. The position in the middle (R2) produces normal sensitivity of the VOC signal (factory setting). The other two positions are used for increasing (R3) or decreasing (R1) VOC sensitivity (see Figure 3). Response Time VOC Signal Relative Humidity (QPM2162 Only) Before the processor handles a change of the measured VOC value for maximum selection, there is a delay in response time of three minutes for every Volt the signal value changes. The sensor acquires the relative humidity in the room with a capacitive humidity sensing element whose capacitance changes as a function of the relative humidity. An electronic measuring circuit converts the signal from the sensing element to a continuous 0 to 1dc signal, corresponding to a relative humidity range of 0 to 100%. Temperature (QPM2160 and QPM2162 Only) The sensor acquires the air duct temperature with a sensing element whose electrical resistance changes as a function of the temperature. The change is converted to an active 0 to 1dc output signal ( 32 F to 122 F [0 C to 50 C] or -31 F to 95 F [-35 C to 35 C]). Page 3

Mechanical Design QPM 21 Series Duct CO 2 and Air Quality Sensors The duct air quality sensor consists of housing, printed circuit board, connection terminals, mounting flange and immersion rod with measuring probe. The two-sectional housing is comprised of base and removable cover (snap-on design). The measuring circuit and the setting elements are located on the printed circuit board inside the cover, the connection terminals on the base. The humidity and temperature sensing elements are located at the end of the measuring probe and are protected by a filter cap. Cable entry is made via the cable entry gland M16 (IP 54) supplied with the sensor, which screws into the housing. Immersion rod and housing are made of plastic and are rigidly connected. The sensor is fitted with the mounting flange supplied with the sensor. The flange is placed over the immersion rod and then secured at the required immersion length. Setting Elements 1 2 3 Measuring range R1 R2 R3 Test function active U1 U2 1 QPM2100/2102/2160 1 X17 Measuring range R1 R2 R3 Test function active U1 U2 U3 X17 U1 U2 U3 1 1 1 2 3 X17 QPM2162 1 SEN0461R2 Figure 3. NOTE: The setting elements are located inside the cover. Page 4

QPM 21 Series Duct CO 2 and Air Quality Sensors Technical Instructions Measuring Range QPM2100 QPM2102 QPM2160 and QPM2162 Active Test Function Meaning of the different jumper positions: For the CO 2 measuring range: Jumper in the middle position (R2) = 0 to 2000 ppm (factory setting). For CO2/VOC weighting: Jumper in the upper position (R1) = VOC sensitivity "low". Jumper in the middle position (R2) = VOC sensitivity "normal" (factory setting). Jumper in the lower position (R3) = VOC sensitivity "high". For the temperature measuring range: Jumper in the upper position (R1) = -31 F to 95 F (35 to 35 C). Jumper in the middle position (R2) = 32 F to 122 F (0 to 50 C) (factory setting). Jumper for the measuring range in the horizontal position: The signal output delivers the values according to table "Test function active". Fault In the event of CO 2 failure, 10V will be present at signal output U1 (after 60 seconds). All Models QPM2102 In the event of CO 2 or VOC failure, 10V will be present at signal output U2 (after 60 seconds). QPM2160 If the temperature sensor becomes faulty, 0V will be present at signal output U2. QPM2162 If the temperature sensor becomes faulty, 0V will be present at signal output U3, and the humidity signal at signal output U2 will increase to 10V (after 60 seconds). If the humidity sensor becomes faulty, 10V will be present at signal output U2 (after 60 seconds), and the temperature signal will remain active. Accessories AQF3101 Filter cap (for replacement) Engineering Notes Cable Routing and Selection The sensor must be powered by a transformer for Safety Extra Low-Voltage (SELV) with separate windings, suited for 100% duty. It must be sized and fused in compliance with local safety regulations. When sizing the transformer, the power consumption of the sensor must be taken into consideration. For information about wiring, see the Technical Instructions of the devices with which the sensor is used. Observe maximum permissible cable lengths. When laying the cables, it should be considered that electrical interference increases the longer the cables run parallel and the smaller the distance between them. Use shielded cables on applications with EMC problems. For the secondary power lines and signal lines, use cables with twisted pairs. Page 5

QPM 21 Series Duct CO 2 and Air Quality Sensors Mounting Notes Mounting Location and Orientation Installation Instructions Commissioning Notes To ensure degree of protection IP54, mount the sensor with the cable entry pointing downward. Mount the sensor in a location where it can be easily accessed for service. If used in connection with steam humidifiers, the distance to the humidifier must be a minimum of 9.8 feet (3 m). If permitted by the installation, the distance should be as great as possible, but no more than 32.8 feet (10 m). Handle carefully; the sensing elements in the immersion rod are susceptible to impact and shock. The sensor must not be mounted in a ventilation application on top of a building (impact of solar radiation). To ensure correct operation, the sensor s ambient temperature must be between 23 F to 113 F ( 5 C to 45 C). Installation Instructions are included in the packaging. Check the sensor s functions 30 minutes after applying power. Checking the CO 2 function: In well-ventilated spaces, the sensor shows the CO 2 concentration of the outside air. Typically, this is 360 ppm (depending on the sensor s measuring accuracy). Also, a basic functional check can be made by exhaling on the sensor. Note that the sensor s rate of response has been purposely delayed (time constant t 90 = 5 minutes). Checking the VOC function: Touch the sensor with a cotton ball dowsed in alcohol. Specifications Power supply Cable length for measuring signal Ventilation should start when the preset switching level of the connected controller is reached. Operating voltage (SELV) 24 Vac ±20% Frequency 50/60 Hz at 24 Vac Power consumption 2 VA Permissible cable length See the Technical Instructions of the device handling the signal Functional data, CO 2 Measuring range (MV = measured value) 0 to 2000 parts per million (ppm) Measuring accuracy @ 73 F (23 C) < + (50 ppm + 2% MV) and 1013 hpa Temperature dependency in 23 F to 113 F + 2 ppm/ C typically (-5 C to 45 C) range Long-time drift < + 20 ppm per year Time constant t 90 <5 minutes Output signal, linear (terminal U1) 0 to 1dc 0 to 2000 ppm, maximum + 1 ma Recalibration-free 8 years Page 6

QPM 21 Series Duct CO 2 and Air Quality Sensors Technical Instructions Functional data, maximum selection of CO 2 and VOC with QPA2002 and QPA2002D Functional data, rh with QPM2162 Functional data, temperature with QPM2160 and QPM2162 Measuring range VOC 0 to 2000 ppm VOC sensitivity See Table 1 Output signal, linear (terminal U2) 0 to 1dc 0 to 2000 ppm, maximum + 1 ma Response time, VOC signal t voc 3 minutes/v Range of use 0 to 95% rh (non-condensing) Measuring range 0 to 100% rh Measuring accuracy @ 73 F (23 C) and 24 Vac 0 to 30/70 to 95% rh + 5% rh 30 to 70% rh + 3 rh (typically) Temperature dependency < 0.1% rh/ C Time constant Approximately 20 s in moving air Output signal, linear (terminal U2) 0 to 1dc 0 to 100% rh, maximum + 1 ma Environmental temperature range for 23 F to 113 F (-5 C to 45 C) electronics Measuring range 32 F to 122 F (0 C to 50 C) (R2, R3) -31 F to 95 F (-35 C to 35 C) (R1) Measuring element NTC 10K Ω Measuring accuracy 59 F to 95 F (15 C to 35 C) + 0.8 K -31 F to 59 F/95 F 122 F + 1 K (-35 C to 15 C/35 C to 50 C) Time constant Approximately 20 s in moving air Output signal, linear (terminal U2 or U3) 0 to 1dc 32 F to 122 F (0 C to 50 C)/-31 F to 95 F (-35 C to 35 C), maximum + 1 ma Protective data Degree of protection, housing IP 54 to IEC 529 Safety class III to EN 60 730 Electrical connections Screw terminals for 1 12 AW or 2 16 AW Transport Climatic conditions Temperature Humidity -13 F to 158 F (-25 C to 70 C) < 95% rh Materials and colors Base Polycarbonate, RAL 7001 (silver-gray) Cover Polycarbonate, RAL 7001 (light-gray) Immersion rod Polycarbonate, RAL 7001 (silver-gray) Filter cap Polycarbonate, RAL 7001 (silver-gray) Mounting flange PA66 F35 (black) Cable entry gland PA, RAL 7035 (light-gray) Sensor (complete assembly) Silicone-free Packaging Corrugated cardboard Page 7

Standards Weight (including packaging) Electromagnetic compatibility Immunity (QPM2162) EN 61 000-6-1 Immunity (QPM2100, QPM2102, EN 61 000-6-2 QPM2160) Emissions EN 61 000-6-3 QPM 21 Series Duct CO 2 and Air Quality Sensors conformity EMC directive 89/336/EEC conformity to Australian EM framework Radio Communication Act 1992 Radio Interference Emission Standard AS/NZS 3548 UL Listed UL 873 cul Listed Canadian Standard C22.2 No. 24-93 QPM2100, QPM2102 Approximately 8.71 oz (0.247 kg) QPM2160, QPM2162 Approximately 8.89 oz (0.252 kg) Wiring Connections 0 CO 2 U1 CO 2 CO 2 / VOC 0 U1 U2 SEN0427R1 0 0 to 1dc SEN0428R1 0 0 to 1dc 0 to 1dc Figure 3. QPM2100. Figure 4. QPM2102. SEN0429R1 0 0 CO 2 U1 0 to 1dc R1 = -35F to 95F (-35C to 35C) R2 = 32F to 122F (0C to 50C) U2 0 to 1dc SEN0430R1 0 0 CO 2 U1 r. h. U2 R1 = -35F to 95F (-35C to 35C) R2 = 32F to 122F (0C to 50C) U3 0 to 1dc 0 to 1dc 0 to 1dc Figure 5. QPM2160. Figure 6. QPM2162., 0 System potential 24 Vac (SELV) 0 System neutral and measuring neutral U1 Signal output 0 to 1dc U2 Signal output 0 to 1dc U3 Signal output 0 to 1dc Page 8

QPM 21 Series Duct CO 2 and Air Quality Sensors Technical Instructions Dimensions 3.15 (80) 2.36 (60) 1.10 (28) QPM2160, QPM2162: 10.79 (274) 1.50 (38) QPM2100, QPM2102: 9.60 (243) 3.19 (81) 0.98 (25) ł 0.59 (ł 15) 3.03 (77) 2.17 (55) 3.15 (80) min. 2.76 (70), max. 5.31 (135) min. 3.94 (100), max. 6.50 (165) 1.92 (49) 1.65 (42) 1.97 (50) 2.20 (56) M16 x 1,5 SEN0463R1 SEN0462R1 0.67 (17) 2.36 (60) Figure 8. Dimensions in Inches (Millimeters). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Products or company names mentioned herein may be the trademarks of their respective owners 2007 1000 Deerfield Parkway Buffalo rove, IL 60089-4513 U.S.A. Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com Document No. CE1N1962 Country of Origin: US Page 9