lindab we simplify construction Lindab Modular air handling units Transport and assembly manual

Similar documents
lindab we simplify construction Lindab Compact air handling unit compair CF Transport, installation, start-up, maintenance and service

lindab we simplify construction Lindab Compact air handling unit CompAir CF Transport, installation, start-up, maintenance and service

lindab we simplify construction Lindab Compact air handling unit COMPAIR CF Transport, installation, start-up, maintenance and service manual

lindab we simplify construction Lindab Modular air handling units Service and maintenance manual

lindab we simplify construction Lindab Modular air handling units Connection, start-up and commissioning manual

lindab we simplify construction AIR HANDLING UNITS INSTRUCTIONS FOR: TRANSPORT INSTALLATION COMMISSIONING OPERATION TESTING MAINTENANCE

Installer manual GreenMaster-HP

39 HQ Air Handling Units AiroVision

lindab we simplify construction LindabIndoorClimateSolutions Product overview Airborne Solutions

lindab we simplify construction LindabIndoorClimateSolutions Product overview Grilles

INSTALLATION & MAINTENANCE

Instructions for the BASIC Air Handling System, Sizes General 1.1 Description of the System

AHU INSTALLATION & OPERATION MANUAL

CENTRAL AIR CONDITIONER SPLIT SYSTEM

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

INSTALLATION INSTRUCTIONS

lindab we simplify construction LindabGarage doors Tailor-made with a five-year guarantee

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

C5.1. VERSO Pro S / R / P / RHP / PCF. EN Installation and Maintenance Service Manual

ACN SMOKE INSTALLATION AND MAINTENANCE

The power of ventilation

IMPORTANT INFORMATION. Revised Dishwasher Installation Instructions

DOMEKT ReCU 400VE(W)CF-EC-C4 Series Air Handling Units Installation and Maintenance Service Manual

Smoke extraction duct of sheet steel

We simplify construction

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

BELT DRIVEN STATIONARY AGITATOR

LindabCapella. Supply air beam

www. ElectricalPartManuals. com \/' INSTRUCTIONS WESTINGHOUSE RADIATORS DESCRIPTION '- INSTALLATION MAINTENANCE

VERSO Pro S / R / P / RHP / PCF. EN Installation and Maintenance Service Manual

UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

SECTION AIR HANDLING UNIT

We simplify construction

Indoor Unit Operation & Installation Manual

User manual for TIME. Air handling unit. Manual version Part number of this manual

XC-18. NOTE: *Machine shown without Lift-Up Safety Guard. This guard is included with machine. Machine should not be operated without this guard.

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

DOMEKT ReGO 400VE(W)-B Series Air Handling Units Installation and Maintenance Service Manual

Parts and Service Manual

Curb Inlet Filter INSTALLATION MANUAL. Bio Clean Environmental Services, Inc. 398 Via El Centro Oceanside, CA 92058

Installation Instructions

NTD-125-*, NTD-204-* & NTD-220-* Nuaire Round & Rectangular Thermal Ducting Installation Guide

U tube models PTU 09, 12, 15, 25, 30, 35, 40, 45. single linear tube models PTS 09, 12, 15, 25, 30, 35, 40, 45

RCF Closed Circuit Cooling Towers RCC Evaporative Condensers

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

ACTIVA SERIES ROOF TOP Air Conditioners 017/040

Single Wall Flue system. Installation manual WARNING. Installation Manual CoxDENS PPs MC-CG-105 EN_892054

Climaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB

ENTROPIE boiler TT100-01

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

Installation and Maintenance Instructions

WASHER INSTALLATION INSTRUCTIONS INSTRUCTIONS POUR L INSTALLATION DE LA LAVEUSE

DUCT COOLERS KWK KFK OPERATION MANUAL. KWK_KFK_v2(4)_EN.indd :35:29

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

MINIMUM TANK GAP. Greater of 3 or one-sixth of sum of adjacent tank diameters. one-half of sum of adjacent tank diameters 20

Welcome! Today s topic: Small Home Repairs. November 14, 2015

4. The above safety devices should be electrically connected to the `startconditions' circuit of the burner.

COMMERCIAL GAS AND ELECTRIC STACKED WASHER/ DRYER INSTALLATION INSTRUCTIONS

1.1 This section applies to air handling units for HVAC Systems.


The equipment for storage and transportation of grain

PLEASE READ ALL SECTIONS OF THIS GUIDE BEFORE COMMENCING YOUR INSTALLATION AND IN CONJUNCTION WITH YOUR DRAWINGS.

Installation Instructions

INSTALLATION, OPERATION & MAINTENANCE MANUAL WING FRESH AIR SUPPLY UNIT Steam & Hot Water

InterSeptor Centrifugal Separators Operating & Maintenance Manual

ENRGY CURB APPLICATION GUIDE FOR TPO ROOFING SYSTEMS

Alfa Laval Arctigo ID

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

Installation Instructions

InverterFlex Series Multi-Zone Ducted Indoor Unit B-VFH09DA-1 B-VFH12DA-1 B-VFH18DA-1 B-VFH24DA-1

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Inspection Checklist Mechanical Final

Turning Air Into Solutions. TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS. Model TCBS

MIST MAX MODEL MM2400. Important: Installation and Operation Manual

DUKE UNIVERSITY CONSTRUCTION STANDARDS

l i nda b we si mpl i f y c onstr u ction Conforms ErP Ecodesign Lot 6 Residential and non-residential air handling units

HE120, HE160 Humidifier Installation Kit

Installation Operation Maintenance

We simplify construction

lindab we simplify construction LindabGarage doors Customised and backed by a 5-year guarantee

Installation Instructions

PAC, NQAC, HQAC, SQAC, EQAC AIR-COOLED CONDENSERS OPERATING AND INSTALLATION INSTRUCTIONS

Installation Instructions

EAGLE 2000B EAGLE 2000BE EAGLE 2000EBT MUST READ MANUAL PRIOR TO INSTALLING MACHINE

OUTDOOR DISHWASHER INSTALLATION INSTRUCTIONS

INSTALLATION AND MAINTENANCE MANUAL MINI AIR HANDLING UNIT «MISTRAL»

Air Handling Units. T F E.

Installation GUIDE VDWU524SS VDWU524WSSS FDWU524WS FDWU524 VDWU324SS FDWU324

Flue & Flue Kits for NVx, VPC & NVS

173 Index of Materials

Riva Studio Dedicated Sealed External Air Kit

DUCTING FOR HRV SYSTEMS The distribution of airflows

Air handling unit. X-CUBE compact. GB/en. Transport and installation manual. including X-CUBE compact accessories

Installation manual. Tumble dryers T4130. Compass Control

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

WM-4510HZD Installation Instructions

Transcription:

lindab we simplify construction Lindab Modular air handling units Transport and assembly manual

Transport and assembly manual 1 General... 3 2 Warnings & Tips... 3 3 Transportation... 3 3.1 Truck loading and forklifting... 3 3.2 Hoisting with crane... 4 3.3 Transportation of disproportional sections... 4 4 Assembly and Installation... 5 4.1 Assembly and servicing area... 5 4.2 Construction of a foundation... 5 4.3 Mounting of an AHU on legs... 6 4.4 Air handling unit assembly... 7 4.4.1 Assembly checklist... 8 4.5 Outdoor installation of air handling units... 9 4.6 Duct connection... 9 4.6.1 AHU delivered with flexible rectangular duct connections... 9 4.6.2 AHU delivered with fixed rectangular duct connections... 9 4.6.3 AHU delivered with fixed round duct connections... 9 4.6.4 AHU delivered with duct mounted on unit casing... 10 4.7 Siphon installation... 11 4.7.1 Siphon sizing... 11 2 February 2017

1 General The air handling unit can be supplied in several shipment units, which are factory protected with wooden beams or pallets, protective foil, props and other aids to ensure safe transportation. Check the packing list for a complete inventory and check for transportation damage. Please note that some components are not factory mounted in the air handling unit, but are transported with as separate packages. Each separate component is supplied with a manual provided by the manufacturer of the component. Prior to assembly, please remove the packaging and follow the installation instructions for each component. Please note that certain components, such as fans, are transported with blockers, which must be removed prior to the assembly. Prior to performing any work on the air handling unit, please read the transport and assembly manual. Prior to installation, store the air handling unit in a roofed and dry area. Always place the air handling unit on even ground. Lift the air handling unit by applying the hoisting procedure described in this manual. 2 Warnings & Tips The air handling unit may only be installed, checked, commissioned and maintained by trained personnel, who must observe engineering standards and local safety regulations. When installing, commissioning or maintaining functional components produced by manufacturers other than Lindab, the instructions provided by the manufacturer of the component must be followed. The air handling unit shall only be used for the purpose and under the operating conditions specified in the technical sheets, generated by the selection software AirCalc++. The air handling unit manufacturer shall not be held liable in cases of failure to observe the information provided in the instructions, or in cases of alteration of electrical or mechanical components without prior approval by the manufacturer. Figure 1 Figure 2 wooden pallets (unit without support base frame), see Figure 2 When loading or unloading with a forklift always transport the air handling unit on the wooden beams or pallet provided (Figure 3). When loading or unloading with a crane always use the lifting tubes as shown in Figure 4. Figure 3 3 Transportation 3.1 Truck loading and forklifting Protect each unit to prevent damage during loading, transportation and unloading, due to tumbling, sliding or uncontrolled release from the vehicle. Futhermore, protect staff against any health and safety hazards. During delivery at the installation site, each air handling unit must remain secured with all guards and protective means (diagonal restraints, wooden supports, pallets under the structural frame, protective foil etc.). During transportation, any manipulation of the air handling unit must be carried out by means of the structural frame. Do not apply pressure to the housing! All shipment units are factory protected by: wooden beams (unit with support base frame), see Figure 1 or Figure 4 February 2017 3

Always observe the weight and the position (centre of gravity) of the packaged shipment. Pay special attention not to excert any pressure to the bottom cover of the air handling unit or to the components attached under the cover (e.g. the ground drain pipes Figure 6) Forklifts may excert pressure only to the bottom frame of the air handling unit. The fork should reach beyond the outermost part of the structural frame Figure 5. through the circular leads in the structural frame. For lifting, apply steel hoisting cables or chains; in all cases, apply two spacer supports (Figure 7, detail A). Appropriate guards must be applied to both ends of the tubes (Figure 7, detail B). Hoisting without spacer supports (Figure 8) is not allowed, as this may damage the housing. Figure 5 Figure 7 1 - wooden beams or palette 2 - forks 3 - transport unit Figure 8 Figure 6 3.2 Hoisting with a crane Any crane hoisting of packaged components is to be performed by means of the structural frame provided underneath the component. Insert appropriate tubes (thick wall tube of outside diameter ø 48.3 mm and wall thickness of 10 mm) 3.3 Transportation of disproportional units In the case of functional units with short and disproportionately high section combinations, the transport packaging must be constructed so as to prevent the hazard of tumbling during transport or storage, and to add to the safety of exposed persons. If the rotary wheel or plate heat exchanger are delivered separately, refer to the additional manufacturer s instructions. 4 February 2017

4 Assembly and installation 4.1 Assembly and servicing area To allow maintenance interventions and operation (e.g. withdrawal of a heat exchanger), always provide a clear area with a minimum width of 1.3 x unit width on the air handling unit servicing side. To facilitate the assembly, a clearance area with a minimum width of 0.5 m should be provided on the non-servicing side (Figure 9). In case of installation on an elevated platform, provide safe access to the platform and the necessary servicing area on the platform. If the total height of air handling units exceeds 2 m, provide for unimpeded and safe access by maintenance personnel to elevated parts of the air handling unit. Figure 9 4.2 Construction of a foundation Mount the air handling unit onto an appropriately high, levelled and flat concrete or steel foundation. The minimum foundation height is determined by the elevation of the drain siphon. The foundation must be dimensioned according to the dimensions and masses of the devices listed in the technical calculation. IMPORTANT: air handling units with widths of 2 m or more must be additionally equipped with a longitudinal support bar under the center of the air handling unit in the entire unit length, as shown in Figure 10. If in doubt, consult the local Lindab service provider. Figure 10 February 2017 5

4.3 Mounting of an air handling unit on legs The foundation may be substituted by mounting the air handling unit onto Lindab type base legs, fitted with a structural noise and vibration insulation bolt, allowing levelling within a range of 30 mm (Figure 13). The legs are to be mounted on site. Mount the legs to the base frame from the inner side with M10x20 bolts, as shown in Figure 13. To level each leg within the 30 mm range use a wrench for M16 bolts. The height of the leg can be adjusted with the lower nut, see Figure 13. After reaching the correct level, tighten the upper nut. For additional vibration and noise insulation we can offer Mafund type insulation pads as an option. Figure 11 Figure 12 Figure 13 6 February 2017

4.4 Air handling unit assembly Remove the protective foil, guards, diagonal restraints, wooden supports, pallets under the structural frame, etc. and ensure that the foundation is in level and flat. Figure 14: Apply self-adhesive EPDM rubber sealing tape with a 20 x 8 mm cross-section (supplied with the air handling unit) onto the contact front faces (housing frame), when connecting the sections with aluminium profile. Figure 17: The sections are equipped with clamps on both the vertical and horizontal sides and both inside and outside. Figure 15: The sealing tape must overlap at the corners. When connecting two sections, apply the sealing tape only on one of the sections. Figure 18: Draw the individual sections together by means of the tightening clamps, which are mounted in the structural frame openings. Do not apply pressure to the housing! Figure 16: For sections with a steel profile (e.g. plate heat exchanger or rotary wheel section), additional EPDM rubber sealing tape with a 15 x 5 mm cross-section is used, see also blue marked tape. The self-adhesive EPDM rubber sealing tape with a 20 x 8 mm cross-section is applied where the tape is marked red. Figure 19: After having drawn the sections together, join them by means of eccentric clamps fitted on the section frames. The eccentric clamps are fitted on both vertical and horizontal sides either inside (Figure 20) or outside (Figure 19) on the frame. February 2017 7

Figure 20: Connect outside type clamps with standard M8x40 screws. Screws are included as separate delivery. Figure 22: The overpressure doors and de-mounting service covers are attached to the housing by blockers. To remove / attach the blockers use a 4 mm imbus key. Figure 21: Connect inside type clamps with special eccentric M8x25 screws. Screws are included as separate delivery. Figure 23: All overpressure door are additionally secured with a locking chain. 4.4.1 Assembly checklist Remove packaging. Ensure that the foundation is in level and flat. Apply rubber sealing tape onto the contact front faces of sections Draw the individual sections together. Join sections by means of clamps fitted on the section frames. Mount legs. Open all sections and remove transportation blockers. Remove instructions attached to components inside sections. Store instructions at a safe place. Close sections. 8 February 2017

4.5 Outdoor installation of air handling units Mount the air handling unit on a foundation of adequate height. Construct the foundation, so as to protect the air handling unit and its components from sliding or tumbling due to wind gusts. The roof of the air handling unit is factory mounted. However, when assembling sections on site, roof joints must be sealed and watertight. Mount the ridge tiles on the joints with rust-proof rivets (Figure 24) and seal (watertight) all the vertical joints between sections. 4.6.2 AHU delivered with fixed rectangular duct connections The fixed connection is attached to the rectangular duct either by means of RJFP clamps, as shown in Figure 26 or, by means of RJFP profile, as shown in Figure 27. For a more detailed duct mounting instruction please see Lindab document»rectangular duct system.pdf«, available on www.lindab.com. Figure 26 Figure 24 4.6 Duct connection The different types of duct connections are described below. In case of outdoor air handling units, all joints between the connections and the intake and outflow air ducts must be sealed and watertight. If the intake and exhaust air run to/from the air handling unit via ducts, the joints between the connections and the ducts must be sealed and watertight. 4.6.1. AHU delivered with flexible rectangular duct connections The flexible connection is attached to the duct by means of M8 bolts in the corners and, additionally with ø 4,8x19 mm bolts along the flange, as shown in Figure 25. Figure 27 4.6.3 AHU delivered with fixed round duct connections 2 1 1 - Round duct 2 - Lindab Safe connection Figure 28 Figure 25 The duct system is connected to the unit according Lindab document»assembly instruction Lindab Safe«, available on www.lindab.com. February 2017 9

4.6.4 AHU delivered with duct mounted on unit casing Fixing of the duct directly to the air handling unit s casing is shown in Figure 29. Figure 30 Figure 29 4.7 Siphon installation All sections, where condensation is likely to occur, are equipped with a drip tray and a drain. It is important, that the siphon mounted on the drainpipe is designed correctly and has correct dimensions. Both positive and negative pressure may occur in sections that require draining. The siphon assures the water drainage and prevents escaping of conditioned air through the drain or unconditioned air being dragged into the unit. In case of negative pressure a siphon type with ball shown on Figure 31 is normally used. In case of positive pressure in the section, a siphon similar to Figure 30 is to be used. Make sure to flood the positive pressure siphon with water. All drain pipes are size ø40, with smooth pipe connection. Figure 31 NOTE: In case of outdoor installed air handling unit the drainpipe and siphon should be insulated and equipped with a heating cable. Please always assure, that the rubber sealing of the siphon is mounted tightly around the drain pipe see Figure 32. Do not connect the drain directly to the sewer system. Condensate must be able to flow freely from the siphon to the sewer through an open funnel. The drain pipe should be installed with a minimum 2% slope in the drain direction. IMPORTANT: ensure an adequate height of foundation and thus a proper height of the water trap. Is the column of liquid (H) in the siphon too small, water may build up inside the drip tray. Figure 32 10 February 2017

4.7.1 Siphon sizing The height of the siphon must be larger than the total negative or positive pressure inside the air handling unit section being drained. Please take into account the increased pressure loss generated during normal operation. Below the installation of positive pressure siphon (Figure 33) and the installation of negative pressure siphon (Figure 34) is shown. Section pressure (Pa) H (mm) Positive pressure / negative pressure 300 40 600 75 900 110 1200 140 1500 175 1800 210 2100 240 Please note, that the piping from driptray under plate heat exchangers is run below section see Figure 35. Figure 33 Please assure for a 10 mm lower outlet bend, preventing water build up inside the drip tray. Figure 35 Figure 34 For quick selection the minimum dimension H is shown in the following table. February 2017 11

At Lindab, good thinking is a philosophy that guides us in everything we do. We have made it our mission to create a healthy indoor climate and to simplify the construction of sustainable buildings. We do that by designing innovative products and solutions that are easy to use, as well as offering efficient availability and logistics. We are also working on ways to reduce our impact on our environment and climate. We do that by developing methods to produce our solutions using a minimum of energy and natural resources, and by reducing negative effects on the environment. We use steel in our products. It s one of few materials that can be recycled an infinite number of times without losing any of its properties. That means less carbon emissions in nature and less energy wasted. We simplify construction www.lindab.com