Badger Universal Control Head

Similar documents
Badger Heat Detector Links and Housing Kits

FM-200 In-Cabinet Series

Agent Tanks PCL PCL PCL PCL - 600

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

Types of Detection. Fusible Link Detection - Most Common

SPECIFICATION: ARGONITE Engineered Fire Suppression System

Industrial Dry Chemical Fire Suppression System

PriceList Category PartNbr Part Description Weight (l MSRP

Product Alert September 20, 2012

SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SECTION FM-200 FIRE SUPPRESSION SYSTEM

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

ANSUL I-101 INDUSTRIAL FIRE SUPPRESSION SYSTEM TECHNICAL MANUAL VEHICLE PAINT SPRAY BOOTH PROTECTION MANUAL

DETECT-A-FIRE Heat Detectors

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Data/ Specification Sheet

AnaLASER II Detector. Protection Systems. A UTC Fire & Security Company. High-Sensitivity Smoke Detector (HSSD ) FEATURES DESCRIPTION

WFDE Series Waterflow Detector

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

MANUAL RESET ALARM RELEASE

CHECKFIRE 210 Detection and Actuation System

ECOJET EJ-10E & EJ-7E ELECTRIC CONVECTION STEAMER W/TWIN GENERATORS PARTS AND SERVICE MANUAL

Spark Electrodes/Flame Sensors

ANSUL AUTOMAN II-C EXPLOSION PROOF RELEASING DEVICE Installation, Operation, and Maintenance Manual

CABS/BLADES/ SPREADERS/ACCESSORIES

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

Linear Heat Detection for Coal Conveyors. Application Guide

Kitchen Fire Suppression Systems Post-Event Analysis

DAF DETECT-A-FIRE. DAF DETECT-A-FIRE Detection and Release Devices

PARTS LIST PL503 WVF-886 VENTLESS FRYER WITH OR WITHOUT ROLL WARMER CONTENTS

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

TotalPac X Single interlock SUREFIRE system

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

TECHNICAL DATA. 31a. September 18, (DN25 - DN50)

Carbon Dioxide Fire Suppression Systems

TotalPac X Firecycle III Preaction Double interlock system

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

CORE Protection Fire System Specification

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Basic Vehicle Fire Protection Manual

Service Bulletin No. 2930

TECHNICAL DATA. 319a. January 27, 2012

XRRS Specification Fire Ready Hood

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

The Marine Throne. Model TMT S/37045/X-Series QUIET - FLUSH ELECTRIC TOILET. "all the comforts of home" FEATURES SPECIFICATIONS INSTALLATION

Powers Controls Low Temperature Detection Thermostat

Specification/ Data Sheet

AlarmLine Linear Heat Detector

System Test Report CLEAN AGENT

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

Ventless Operation Supplement GBF-D-VH

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

AlarmLine Addressable Linear Heat Detector

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

Model Series. PumpAgents.com - buy pumps and parts online QUIET - FLUSH ELECTRIC TOILET. Model Series FEATURES SPECIFICATIONS INSTALLATION

R-102 RESTAURANT FIRE SUPPRESSION SYSTEM

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Hospitals and Major Medical Centers

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

MANUAL RESET ALARM RELEASE

Powers Controls Free Energy Band TH 193 HC Hesitation Room Thermostat

THE IDEAL SOLUTION FOR KITCHENS

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

TECHNICAL DATA OBSOLETE

Electric Automatic Carpet Extractor. Operator and Parts Manual. Model No.: Rev. 00 (11-99)

A B A B4

EHT/EHTD. Electromechanical Closer-Holder Release Devices

HOT WATER BOILER ( MBH)

PuraGuard. Maintenance Kit Rebuild Kit Replacement Drain Cock

INSTALLATION, OPERATION, SERVICE & PARTS SUPPLEMENT for

Installation Instruction. Puritan Bennett. Wall Air Water Trap For 800 Series Ventilator Basic Cart. Pla

B-14G. for series number with jm or j

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

2408/2900. Fire Guard

TECHNICAL DATA. model c-2

Model 4880 Status Output Display Module Manual

Technical Data. Sizes: ANSI Inches (DN) 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250)

Table of Contents. FETCO, and Driven To Pioneer Innovation are trademarks or trade names of Food Equipment Technologies Company.

Pneumatic Heat Press. Revision: 3 Operators Manual

PRODUCT MANAGEMENT BULLETIN# 171b

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED

AUTOMATIC WASHER HORIZONTAL AXIS. Product Type

MODEL CMA-180UC PARTS MANUAL Rev 1.16

MICRO SWITCH E6/V6 Series

DETCON MODEL AV2-C1D2C Hazardous Duty Class I. Div 2, Continuous Tone Alarm Station

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

Commercial and Light Industrial Fire Alarm Control Panel

PARTS LIST. SERVICE PARTS LIST WVG-136 Ventless Griddle with or without Roll Warmer CONTENTS

Twin-Agent Fire Fighting/Securing Systems Specifications

Explosion Proof Light Watt Metal Halide - Class 1 Div 1 & Class 2 Div 1

08/17/2011 Rev. 4 PULL STATION EXHAUST HOOD 10 TO 20 FEET FROM HOOD LOCATE ONE NEAR EVERY POINT OF EGRESS FROM HOOD

Transcription:

Badger Universal Control Head P/N: 60-120099-002 FEATURES For Use in: Range Guard Commercial Cooking Fire Suppression Systems Industry Guard Industrial Fire Suppression Systems Pneumatic Release of up to 20 Agent Cylinders Two Discrete Mechanical Detection Lines Cylinder or Wall Mount Up to 400 ft. Mechanical Detection Cable DESCRIPTION The Badger Universal Control Head is a compact, versatile unit used to actuate agent cylinders on Badger Range Guard and Industry Guard Pre-Engineered fire suppression systems. The control head can be operated via: Two Distinct Automatic Mechanical Detection Lines (fusible links or thermo-bulb links) Optional Electrical Solenoid Remote or Local Manual Mechanical Control Upon actuation, the Universal Control Head discharges the nitrogen System Cartridge, pressurizing the actuation lines and System Valve Actuators (SVA) mounted on the cylinder valve(s). The SVA(s) open the cylinder valve(s), Operates 2 Gas Valaves Available 24 V Electrical Actuation Multiple Remote Release Options Rugged, Die-Cast Aluminum Body Tamper/Lock Port for Cover Easy to Install and Maintain UL & ULC Listed FM Approved for Industry Guard Systems Effective: August 2013 B-87-027 discharging the Range Guard wet chemical or Industry Guard dry chemical suppression agent. The UCH can be mounted on a wall or directly to an SVA mounted on the cylinder. The Universal Control Head is UL and ULC Listed with Range Guard Wet Chemical and Industry Guard Dry Chemical Fire Suppression Systems. The UCH is FM approved with the Industry Guard Dry Chemical Systems. The UCH comes ready to install, with three EMT connectors, one System Valve Actuator (SVA), two microswitches, one nitrogen System Cartridge, and one nitrogen test cartridge. Figure 1. UCH Control System, P/N 60-120099-002

TECHNICAL DATA Table 1. Mechanical Cable Parameters for Range Guard & Industry Guard Systems UCH Cable Line Max. Cable Length Max. Corner Pulleys Max. Detectors Max. Tee Pulleys Detection and Manual Release-to-Trip Line 1 200 ft. (60.96 m) 50 40 * Detection and Manual Release-to-Trip Line 2 200 ft. (60.96 m) 50 40 * Pull-to-Trip Remote Manual Release Line 100 ft. (30.48 m) 30-1* Mechanical Gas Valve Line 100 ft. (30.48 m) 30-1* *Tee pulleys count as two Corner Pulleys. Maximum is from Universal Control Head, through the pulley, to each device. Table 2. Actuation Parameters for Range Guard Wet Chemical Systems Operating Temperature Range Number of Extinguishing System Cylinders Maximum Total Length Copper Actuation Tubing Minimum Total Length of Copper Actuation Tubing 0 F to 120 F (-18 C to 49 C) 1-12 106 ft. (32.30 m) 13-20 91 ft. (27.73 m) 5 ft. (1.52 m) Table 3. Actuation Parameters for Industry Guard Industrial Dry Chemical and Open-Face Spray Booth Systems Operating Temperature Range Number of Extinguishing System Cylinders Maximum Total Length Copper Actuation Tubing Minimum Total Length of Copper Actuation Tubing -40 F to 120 F (-40 C to 49 C) 1-14 166 ft. (50.60 m) 15-20 121 ft. (36.88 m) 5 ft. (1.52 m) Table 4. Actuation Parameters for Industry Guard Dry Chemical for Vehicle Spray Booths Operating Temperature Range Number of Extinguishing System Cylinders Maximum Total Length Copper Actuation Tubing Minimum Total Length of Copper Actuation Tubing 0 F to 120 F (-18 C to 49 C) 1-8 200 ft. (60.96 m) 9-15 160 ft. (48.76 m) 16-20 140 ft. (42.67 m) 5 ft. (1.52 m) NOTES 1. Braided high pressure nitrogen tubing (P/N 87-120045-00X), is required to connect the Universal Control Head to the System Valve Actuator (SVA) when the Universal Control Head is cylinder mounted. 2. Copper tubing shall be 1/4-inch O.D. x 0.031-inch wall high pressure tubing. 3. When Control System is cylinder mounted and two or more cylinders are being actuated, a minimum of 5 ft. (1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used for actuation lines. - 2 -

4. When Control System is wall mounted, a minimum of 5 ft. (1.52 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used in the overall actuation line. 5. High pressure nitrogen tubing (P/N 87-120045-00X) may be used in place of copper tubing, not to exceed a maximum length of 30 feet (9 m). 6. In every system, either single cylinder or multiple cylinder, a 1/8-inch NPT plug or vent check (P/N WK-877810-000) shall be used in the outlet port of the last System Valve Actuator(s) in the actuation line. 7. A maximum of 2 Pressure Switches (P/N 486536) may be used in the actuation line. SYSTEM NITROGEN CARTRIDGE, P/N 87-120043-001 The Universal Control Head uses a nitrogen cartridge for actuating the system cylinders and is charged with dry nitrogen (see Figure 2). The cartridge is mounted inside the Universal Control Head to protect it from tampering and provides the date of manufacturing and space (gray band) for recording the installation date. 5-1/8 in. (130 mm) 1-9/16 in. (40 mm) GRAY BAND Figure 2. System Nitrogen Cartridge, P/N 87-120043-001 TEST CARTRIDGE, P/N 87-120044-001 The Test Cartridge is used for functional testing of the Badger Range Guard Wet Chemical System and Industry Guard Dry Chemical System*. The cartridge has a red band and is labeled TEST CARTRIDGE as shown in Figure 3. *Note: The System Nitrogen Cartridge P/N 87-120043-001 is required for actuation and full discharge or "puff" tests, and when a time delay is included (as in systems protecting Vehicle Spray Booths). 4 in. (102 mm) 1 in. (25 mm) Figure 3. Test Cartridge, P/N 87-120044-001-3 -

SYSTEM VALVE ACTUATOR (SVA), P/N 87-120042-001 A System Valve Actuator (SVA) must be mounted to every system cylinder valve assembly (see Figure 4). The SVA has ports for low profile tubing runs, and is also equipped with a spring loaded plunger that locks the piston in the discharged position, ensuring complete discharge of the cylinder(s) contents. 5/16-18 UNC THROUGH (TYP) (NOT SHOWN) 1/8 in. NPT PORT 1-3/4 in. (44 mm) 1/8 in. NPT PLUG (IF APPLICABLE) SVA PISTON IN SET POSITION PISTON IN ACTUATED POSITION (TOWARDS CYLINDER VALVE) Figure 4. System Valve Actuator (SVA), P/N 87-120042-001 SPRING LOADED PLUNGER HIGH-PRESSURE NITROGEN TUBING, P/N 87-120045-00X The High-Pressure Nitrogen Tubing is used to connect the Universal Control Head to the SVA on all installations in which the Universal Control Head is mounted to a wet or dry chemical cylinder. (see Figure 5). A 1/8-inch NPT (male) x 3/8-24 JIC Adapter is included with the High Pressure Nitrogen Tubing. 1/8 in. NPT THREAD SEAT 1/2 in. HEX, 1/4 in. 37 DEGREE FLARE, SWIVEL A (END TO SEAT) 1/8 in. NPT (MALE) x 3/8-24 JIC ADAPTER Figure 5. External Tubing for Universal Control Head, P/N 87-120045-00X Table 5. External Tubing for Universal Control Head Part Number Length "A" 87-120045-001 7-1/2 in. (191 mm) 87-120045-002 24 in. (610 mm) 87-120045-003 60 in. (1524 mm) - 4 -

SOLENOID, P/N 83-100034-001 An optional solenoid can be installed into the Universal Control Head, just under the actuation latch. The solenoid operates directly on the actuation latch to activate the system. This installation allows simultaneous usage of mechanical detection lines, or the lines can be locked out. The solenoid includes two mounting bolts, the bracket and a push plate which mounts onto the solenoid body (Figure 6). The solenoid coil is 24 Vdc at 1.5 Amp and at 70 F (21 C). Refer to Figure 7 for Release Wiring with Terminal Type Microswitch. When actuating the Universal Control Head with an optional solenoid, a UL Compatible and Listed fire control panel with a supervised power supply is required, such as the Kidde AEGIS or Kidde ARIES. PUSH PLATE (DO NOT REMOVE) 9/64 in. ALLEN SCREWS (2) BRACKET (DO NOT REMOVE) WIRE TYPE KEY RELEASING CIRCUIT IN COMPATIBLE CONTROL PANEL ( 24 VDC ONLY) UCH SOLENOID P/N 83-100034-001 24 VDC ONLY SPLICE SOLENOID LEAD TO RELEASING CIRCUIT ALARM WIRES TO UCH SOLENOID AND/OR OTHER DEVICES MICROSWITCH (INTERNAL) ALARM WIRES FROM CONTROL PANEL OPEN TERMINAL 2 TERMINAL 2 NOT USED ATTACH RELEASING CIRCUIT TO TERMINAL 4 OF MICROSWITCH CLOSED TERMINAL 4 FLAG ENGAGED BY UCH ATTACH SOLENOID LEAD TO TERMINAL 1 OF MICROSWITCH COMMON TERMINAL 1 SWITCH POSITION WHEN UCH FLAG/CAM IS IN SET POSITION Figure 7. Release Wiring with Terminal Type Microswitch SOLENOID BODY ELECTRICAL LEADS 24 in. (610 mm) Figure 6. Solenoid, P/N 83-100034-001 Note: Where electric detection and/or actuation is provided, supervision shall be provided in accordance with NFPA 72, National Fire Alarm and Signaling Code. Alarms and indicators, along with a supervised power source, shall be provided in accordance with NFPA 72. Electrical wiring and equipment shall be provided in accordance with NFPA 70, National Electric Code. All installations are subject to the approval of the Authority Having Jurisdiction (AHJ). KEEPER PIN, P/N 60-9197108-000 The Keeper Pin (P/N 60-9197108-000) is used to prevent actuation while installing the system. Figure 8. Keeper Pin, P/N 60-9197108-000-5 -

ORDERING INFORMATION Description Part Number Universal Control Head includes: (1) 87-120042-001 System Valve Actuator (1) 87-120043-001 System Nitrogen Cartridge (1) 87-120044-001 Test Cartridge (1) 87-120058-001 EMT Connector Kit (1) 87-120039-001 Microswitch Kit (1) 87-120039-501 Microswitch Kit 60-120099-002 System Valve Actuator 87-120042-001 System Nitrogen Cartridge 87-120043-001 Test Cartridge 87-120044-001 High Pressure Hose for Cylinder Mount 87-120045-001 EMT Connector Kit 87-120058-001 Solenoid Electric Actuator Kit 83-100034-001 Microswitch Kit (SPDT), Solid Color Leads 87-120039-001 Microswitch Kit (SPDT), Striped Color Leads 87-120039-501 Terminal Type Microswitch Kit (SPDT) 87-120047-001 REFERENCE INFORMATION Range Guard Systems designed and installed according to manual P/N 60-9127100-000. Industry Guard Systems designed and installed according to manual P/N 60-900000-001. Vehicle Spray Booth Systems designed and installed according to manual P/N 60-900007-001. 5-1/2 in. (140 mm) 7-5/8 in. (194 mm) TO OPERATE PULL PIN TURN HANDLE 9-3/4 (248 mm) FIRE SUPPRESSION SYSTEM 3/4 in. (19 mm) 1-5/16 in. (34 mm) 4-3/8 in. (112 mm) 3-3/4 (95 mm) 8-1/2 (216 mm) Figure 9. Universal Control Head Dimensions Kidde and Range Guard are registered trademarks of Kidde-Fenwal, Inc. AEGIS, and ARIES are trademarks of Kidde-Fenwal, Inc Badger is a registered trademark of Badger Fire Protection. Industry Guard is a trademark of Badger Fire Protection. B-87-027 Rev AE This literature is provided for informational purposes only. BADGER FIRE PROTECTION assumes no responsibility for the product s suitability for a particular application. The product must be properly applied to work correctly. 2013 Badger Fire Protection Badger Fire Protection 944 Glenwood Station Lane Suite 303 Charlottesville, VA 22901 Ph: (434) 964-3200 Toll Free: (800) 446-3857 www.badgerfire.com Kidde Canada, Inc. 340 Four Valley Drive Vaughan, Ontario L4K 5Z1 Ph: (905) 695-6060 Toll Free: (800) 565-1976 www.kiddecanada.com