Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

Similar documents
UNIVERSITY. Facilities Management

Fire System Impairment Policy

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

Date Issued: December 14, 2017 Revision: 2.1

Risk Management Services

Impairments to Fire Protection Equipment

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)

UNIVERSITY OF TOLEDO

Fire Protection System Impairment Procedure

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

Management Practices: Fire Protection Impairments November 2015

Austin Independent School District Police Department Policy and Procedure Manual

Chapter 4: Fire Protection Systems

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

BURN NOTICE: KEEP THE HEAT AWAY!

Evacuation Fire Safety Program

2010 FIRE CODE OF NEW YORK STATE

JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

OXNARD FIRE DEPARTMENT Fire Watch Guidelines

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS

HOT WORK PERMIT PROCEDURES

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch

FIRE PROTECTION PROGRAM

Vacant Building Loss Prevention Best Practices

Fire Watch Program. Building Administrators Building Administrators will inform building occupants about fire watch events and building evacuations.

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy)

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

ICC CODE CORNER 2015 International Fire Code

Iowa State Fire Marshal

Procedure DESCRIPTION/OVERVIEW

HUDSON VALLEY COMMUNITY COLLEGE BUILDING EMERGENCY ACTION PLAN FOR OUTSIDE EMERGENCY ASSISTANCE: DIAL 911 TO REACH THE SARATOGA CTY POLICE & FIRE

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

Phase 2 Security Response

Mount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

FIRE IMPAIRMENT NOTICE

IYRS School of Technology & Trades RCRA CONTINGENCY PLAN Bristol Facility 40 CFR 265 Subpart D 29 CFR Emergency Evacuation

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

FIRE PREVENTION PLAN EMERGENCY ACTION

Procedure for Performance of Fire/Emergency Evacuation Drills

Managing Fire Protection System Impairment

Written Fire Safety Plans

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

Agency for Health Care Administration

Emergency Action Fire Prevention Plan

Hot Work Policy and Procedures

Emergency Action Plan Program

Liberal Arts and Humanities. Building # 275. Emergency Evacuation Plan

Preparedness Committee Security and Life Safety Commercial Office Building Protective Measures

Muskogee Public Schools. Lockout/Tagout. Program

VICI. Emergency Evacuation Plan

MANUAL: ADMINISTRATIVE- Environment of Care Page 1 of 3 Effective Date: 10/00 Reviewed/Revised:12/13;04/14;6;15; 9/15;6/16;7/16

Electrical Safety Program

Contractor Safety. Workplace Safety & Environmental Division

Fire evacuation drill

Facilities Services Utilities Shutdown Request Form

Department of Fire Safety Policy and Procedures for Fire Watch, Preformed by Residence Education and Services Staff

FIRE SAFETY AND PREVENTION POLICY

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector

Narrative Reports As Regulated by 780 CMR, Section 903.0

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

Susquehanna University Annual Fire Safety Report 2015

F&S Control of Hazardous Energy Program

Hospice of Rutherford County Policies and Procedures

HOT WORK SAFETY PROGRAM:

Understanding and Applying NFPA 25

UNCONTROLLED IF PRINTED. Issued with the authority of the Chief Commissioner and General Manager of Scouts Australia NSW

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

Fire Prevention Plan

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

University of Maryland FIRE EVACUATION PLAN Columbus Center POLICE FIRE MEDICAL EMERGENCY - 911

Chapter 18 Welding Table of Contents

Safety & Security Services Services de Sûreté et Sécurité. Hot Work Protocol

TULANE UNIVERSITY EMERGENCY ACTION PLAN

Builders Risk - Fire Prevention Inspection Checklist

Facility Manager Training

Facilities Management

HIGH-RISE RETROFIT ORDINANCES - NO and NO

EC 5.10 FIRE PREVENTION MANAGEMENT

IIPP. Injury & Illness Prevention Program Hartog Drive San Jose CA Responsibilities. Workplace Hazards. Training. Incident Investigations

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

Initial Version Revision No. 0 Next Review Date: Preparation: Safety Mgr Authority: President Issuing Dept: Safety Page: Page 1 of 6

St. Vincent s Health System Page 1 of 6

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

SCALES NW EMERGENCY ACTION PLAN

Training Toolbox Series. ICA11v1.0 Information, Digital Media & Technology

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

ENERGY CONTROL LOCKOUT/TAGOUT PROGRAM PLAN

University of Maryland FIRE EVACUATION PLAN

For additional information please contact the Chesapeake Fire Prevention Office at or at

MNEC NFPA 72 WHITE PAPER

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

Transcription:

Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire protection system is taken out of service due to construction, alteration, power outage, repair or an emergency condition. These procedures include measures taken during the impairment to ensure that increased risks are minimized and the duration of the impairment is limited. Procedures set forth in this policy do not apply to routine scheduled maintenance or testing. OVERVIEW The probability of a fire or explosion causing major damage is increased whenever a fire protection system is impaired. The longer the fire protection system is impaired, the greater the probability becomes. Therefore, it is necessary to minimize the duration and scope of any impairment or provide for an alternate protection system. A Fire Protection Impairment Program is an effective management program used to: Supervise the safe shutdown of fire protection systems Control potential fire hazards during the impairments Restore the fire protection system to service as soon as possible SCOPE This policy applies to all YC employees, outside contractors and their representatives, or any company representative hired by YC to provide services or any outside trade workers who will be w0rking on university property. DEFINITIONS Fire Protection Systems: Sprinkler systems, standpipe systems, fire hose systems, underground fire service mains, fire pumps, water storage tanks, water spray fixed systems, foam-water systems, special extinguishing systems, fire service control valves, fire alarms systems, and emergency lights.

Firewatch: A person or persons designated to physically patrol the area where the fire protection system is impaired. Impairment: a shutdown, in whole or part, of a fire protection system. 1. Emergency impairment: when a fire protection system is out of service due to an unexpected occurrence, such as a ruptured pipe or an unexpected power outage. Planned impairment: when a fire protection system is out of service due to work that has been planned in advance, such as revisions to the water supply or sprinkler piping system. 2. Level 2 impairment: when a limited number of components of a fire protection system are found defective or removed from service. A Level 2 impairment represents a minimal impact to the overall life safety of building occupants. 3. Level 1 impairment: a shutdown of an entire fire protection system, or major portion, significantly affecting occupant life safety. Impairment Coordinator (IC): The person who manages the impairment while system work is being performed and has overall responsibility for proper implementation of the Fire Protection Impairment Program. The Fire Protection Manager will be designated as the Impairment Coordinator.

RESPONSIBILITIES YC Employees Any employee who impairs a fire protection system, in whole or part, must first notify the Impairment Coordinator at facilities. If an impairment permit is required, the employee will attach the Fire & Life Safety System Permit/Impairment Tag (Schedule A) to the fire department connection for sprinkler system impairments or to the fire alarm annunciator/control panel for fire alarm systems. Contractors, Outside Workers, Outside Company Representatives Any Contractor/contractor s representative or outside worker who impairs a fire protection system, in whole or part, must first notify the Impairment Coordinator at facilities. If an impairment permit is required, the contractor, contractor s representative, or outside worker will attach the Fire & Life Safety System Permit/Impairment Tag (Schedule A) to the fire department connection for sprinkler system impairments or to the fire alarm annunciator/control panel for fire alarm systems. Impairment Coordinator (IC) The IC will determine the level of impairment due to a shutdown, in whole or part, of a fire protection system. The IC will be responsible for completion of the Impairment Worksheet (Schedule B) when authorizing Level 1 impairments. The IC will be responsible for issuing and verifying removal of fire & life safety system permit/impairment tags when authorizing Level 1 impairments. The IC will be responsible for coordination of the firewatch, if it has been determined that a firewatch is necessary. The IC will document firewatch activities on Schedule C, the Firewatch Log Sheet. The IC will be responsible for providing training to YC employees who will be utilized as firewatch personnel. IMPAIRMENT COORDINATION PROCEDURES LEVEL 2 Preplanned Impairments All level 2 impairments, both preplanned and emergency, must be reported to the impairment coordinator. YC facilities will be notified of a preplanned impairment of a fire alarm system. The fire alarm monitoring company, if utilized to monitor that particular fire alarm system, will be notified of a preplanned impairment of a fire alarm system. The impairment coordinator will ensure that level 2 impairments are satisfactorily remediated.

IMPAIRMENT COORDINATION PROCEDURES LEVEL 1 YC facilities will be notified of a preplanned impairment of a fire alarm system. The fire alarm monitoring company, if utilized to monitor that particular fire alarm system, will be notified of a preplanned impairment of a fire alarm system. The maintenance supervisor for the affected building will be notified of the preplanned impairment. The impairment coordinator will complete the Impairment Worksheet (Schedule B). The impairment coordinator will complete the fire & life safety system permit/impairment tag (Schedule A). The IC will authorize the preplanned impairment and verify that the following procedures have been implemented: 1. The extent and expected duration of the impairment have been determined. 2. The areas or buildings involved have been considered and the increased risks determined. 3. When a required automatic sprinkler system is out of service for an extended duration, the impairment coordinator will arrange for one of the following: a) Evacuation of the building or portion of the building affected by the system out of service, or b) A fire watch for all portions of the building left unprotected by the shutdown until the fire alarm or sprinkler system has been returned to service. A fire watch utilized for a fire alarm or automatic sprinkler system shutdown will be composed of individuals beyond normal staffing, assigned to walk the areas affected. The number of fire watch personnel utilized will be determined by the impairment coordinator. Firewatch personnel used for fire alarm shutdowns must be specially trained in fire prevention and in occupant and fire department notification techniques. Fire watch personnel used for automatic sprinkler system shutdowns must be specially trained in fire prevention and in the use of fire extinguishers, and in occupant and fire department notification techniques. 4. When a required fire alarm system is out of service for an extended duration, the impairment coordinator will arrange for one of the following: a) Evacuation of the building or portion of the building affected by the system out of service, or b) Implementation of mitigating measures for the period that the system is impaired. This considers the building occupancy type, nature and duration of impairment, building occupancy level

during the impairment period, active work being conducted on the fire alarm system during the impairment, condition of other fire protection systems and features, and hazards and assets at risk. Appropriate mitigating measures range from simple occupant notification to full-time fire watch. 5. Sprinkler systems: the impairment coordinator will complete or authorize a Fire & Life Safety System Permit/Impairment Tag (Schedule A), making sure it is located at the fire department connection, indicating which system, or part thereof, has been removed from service. 6. Fire alarm systems: the impairment coordinator will complete or authorize a Fire & Life Safety System Permit/Impairment Tag (Schedule A), making sure it is located at the fire alarm annunciator or fire alarm control panel. Emergency Impairment Procedures When an emergency impairment occurs, emergency action will be taken to minimize potential injury and damage. The impairment coordinator will implement items 1 through 6 of section Preplanned Impairments with the following exception: o Any damage to fire protection systems caused by the contractor will be repaired by a licensed fire protection company at the contractor s expense. Any required firewatch activities due to damage of the fire protection equipment will be supplied by the contractor. Contractor must supply their own firewatch activities to ensure compliance with this policy and other YC policies, i.e. Hot Work Permit Policy. Restoring Systems to Service When all impaired equipment is restored to normal working order, the impairment coordinator will verify that the following procedures have been implemented: Any necessary inspections and tests have been conducted to verify that affected systems are operational. Maintenance supervisors for the affected buildings have been advised that protection is restored. If a fire alarm system is involved, YC facilities and monitoring company (if any) have been advised that protection is restored. The Fire & Life Safety System Permit/Impairment Tag has been removed. REFERENCES NFPA 1 13.3.4 (2003 ed.), Uniform Fire Code NFPA 25 14 (2003 ed.), Maintenance of Water Based Fire Protection Systems NFPA 72 4.6 & 10.2.1.2, National Fire Alarm Code NFPA 101 9.6.1.7 & 9.7.6 (2003 ed.), Life Safety Code International Fire Code, 2003 ed. Schedule A

Building Fire & Life Safety System Impairment Permit/Tag (Please attach tag to Fire Department Connection or Fire Alarm Annunciator/Control Panel) Name: Type of system impaired: Reason for Extent of Date system impairment: impairment: shutoff: Expected date of restoration: Impairment authorized by:

Schedule B Impairment Worksheet Core Information Today s date: Bldg: Type of system impaired: Extent of impairment: Reason for impairment: Date impairment to begin: Estimated completion date: Person(s) conducting work: Person responsible for mounting impairment tag: Firewatch required? If yes, number of persons: Reminders Area inspected and risks determined? Prohibitions involved?_ Building evacuated? Impairment tag issued? Notifications Has campus police been notified of the impairment? Has monitoring company, if any, been notified of the impairment? Has the maintenance supervisor for the affected building been notified of the impairment? Restoration Has the affected system been inspected and tested operational? Has the impairment tag been removed? Has the campus police been notified of the restoration, if a fire alarm system? Has the fire alarm monitoring company(if any) been notified of the restoration? Has the maintenance supervisor for the affected building been notified of the restoration? Schedule C

Firewatch Log Sheet Date Name(s) Time Area Checked Please return this form to Fire Protection Manager at Facilities Management.