CSA B Code Installation Code for Oil-Burning Equipment Yukon Housing Contractor s Breakfast March 2014 Presented by Ron Bramadat, Ken Alaric &

Similar documents
2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings

Recent Revisions and Proposed Key Changes to Fire Code

Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014

Large Family Daycare Guideline

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Short Term Accommodations Fire Code Requirements

CARBON MONOXIDE ALARM STANDARDS ACT - ENACTMENT Act of Dec. 18, 2013, P.L. 1229, No. 121 Cl. 35 An Act

Family Foster Home Fire Safety Evaluation Checklist Instructions

FAQ. (Frequently Asked Questions) What is required to convert my unfinished basement to finished space?

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

NCEHSA Conference. Carbon Monoxide Detector Regulations for Lodging Establishments (S.L )

C O D E S & A M M E N D M E N T S

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

FIRE PREVENTION STANDARDS

Winnipeg Fire Department Fire Prevention Branch

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August

NFPA 96, 2017 REVIEW SUMMARY

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

CHAPTER 1 ADMINISTRATION SECTION 101 (IFGC) GENERAL

Above Ground Fuel Tank Requirements

Major Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing

Section 42. Lead Paint Risk Factor NONE WATER HEATER STORAGE GAS

2012 NC Building Code Chapter 2, 602.4, , , Chapter 35 Cross-Laminated Timber. ( Item B-1)

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

OWNERS MANUAL MODEL DO110 & DO180 IS CERTIFIED TO: Unit Serial # Purchased From Company Address

PROTECTING AGAINST CARBON MONOXIDE. Questions and Answers about Carbon Monoxide (CO) and CO Alarms

about your house Assessing the Comfort and Safety of Your Home s Mechanical Systems

1.1 SECTION INCLUDES.1 Materials and installation for aboveground oil storage tanks..2 Section Waste Management and Disposal.

Certificate of Inspection CHECKLIST

EFFECTIVE DECEMBER 28, 2010 SECTION 610 CARBON MONOXIDE ALARMS

PROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)

FIRE PREVENTION AND SAFETY IN THE HOME. Provided to You by Lawrence Laviolette CD Fire Safety Officer

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

Fuel Oil Heating Installation Inspection Report #1 2008

BUTTE COUNTY PERMIT NO: DEPARTMENT OF DEVELOPMENT SERVICES BUILDING PERMIT APPLICATION* APN: Property Address. Policy Number. Carrier.

Inspection Checklist Mechanical Rough in

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

Photovoltaic (Solar) Array Installation Guide

Temporary LPG Heat for Construction Sites Work At Risk and Inspection Information Packet

BUILDING CODE GUIDELINE FOR MECHANICAL INSPECTIONS

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Electrical Tech Note 107

Rental Housing Inspection Guide

97 FCV 006 Page 2 of 16 EXPLANATORY MATERIAL

Residential-based Care Facility R-4 Guideline

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

THE TOWNSHIP OF CRANBURY

A GUIDE TO THE ROCK ISLAND HOUSING CODE. Prepared By: The City of Rock Island Inspection Division

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

2015 MECHANICAL CODE REQUIREMENTS

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS IMPORTANT

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

X-593 SOLID FUEL HEATING QUESTIONNAIRE

BALTIMORE CITY RENTAL LICENSE INSPECTION FORM RENTAL LICENSING INSPECTOR GUIDANCE

Temporary LPG Heat for Construction Sites Information Packet

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

Section 2, Reference publications: Updated the referenced publications to the current editions.

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

CHAPTER 8 CHIMNEYS AND VENTS

Building Department Informational Handout

CHANGES TO THE TEXT OF THE 2010 CODE BOOKS

Smoke Alarms and Carbon Monoxide Alarms

CHIMNEYS AND VENTS CHAPTER 8

Before selecting your stove, it is very important that you clearly identify what your needs are:

Flemington Borough Fire Safety 38 Park Ave Flemington, NJ 08822

Before selecting your wood heater, it is very important that you clearly identify what your needs are:

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

North Liberty Fire Department Permit Application Temporary Storage & Use of LPG

Before selecting your stove, it is very important that you clearly identify what your needs are:

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

MAINE FUEL BOARD MASTER OR JOURNEYMAN OIL TECHNICIAN APPLICATION TO ADD AN AUTHORITY

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

FIRE INSPECTION GUIDELINES FOR FOSTER GROUP HOME PARENTS Effective June 1, 2002, Update September 2011

REQUIREMENTS & GUIDELINES

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada

Before selecting your stove, it is very important that you clearly identify what your needs are:

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

Maintence/Renewal Report

MONTECITO FIRE PROTECTION DISTRICT

Land Use and Environmental Services Code Enforcement. Table of Contents

ARCHIVED. Compliance Document for New Zealand Building Code Clause G4 Ventilation Second Edition. Prepared by the Department of Building and Housing

Frequently Asked Carbon Monoxide Questions

Econoburn Technical Datasheet

Requirements for Smoke / Carbon Monoxide / Fire Extinguisher Certification

Carbon Monoxide Detectors in New and Existing Buildings

Bold items are particular to the City of Euless

ML180UH SERIES GAS FURNACE WARNING WARNING

Protect Safety Alarms

SECTION 915 CARBON MONOXIDE DETECTION

PLAN NOW!! Plan your escape today Your life may depend on it tomorrow HOME ESCAPE PLAN EXERCISE

TABLE OF CONTENTS. Part I Administrative

Land Use and Environmental Service Agency (Code Enforcement) NC Mechanical Code. Table of Contents

Transcription:

Installation Code for Oil-Burning Equipment Yukon Housing Contractor s Breakfast March 2014 Presented by Ron Bramadat, Ken Alaric & Stan Dueck 1

CHANGES This presentation will addresses some changes to the 2009 Edition, now referenced in the 2010NBC as of Nov. 2013, and this is also the newest version of: CSA B139 Installation Code for Oil-Burning Equipment NOTE: This is not a comprehensive presentation of all the changes and the installer is responsible for acquainting themselves fully with the new edition of CSA B139-09. 2

CSA B139-09 - SCOPE CSA B139-09 Code Preface This is the eighth edition of CSA B139, Installation code for oilburning equipment. It supersedes the previous editions published in 2004, 2000, 1991, 1976, 1971, 1962, and 1957. http://shop.csa.ca/en/canada/fuel-burningequipment/b139-09/invt/27020552009 3

Scope 1.1 This Code applies to the installation of appliances, equipment, components, and accessories where oil is used for fuel purposes in applications that include (a) space heating; (c)power generation; and (b)service water heating; (d) process application. 4

Scope 1.2 CSA B139-09 Code This Code provides minimum requirements for installing or altering all stationary and portable oil-burning equipment, including (a) furnaces; (c) boilers; (e) vehicle heaters; (b) process furnaces; (d) water heaters; (f) construction heaters; and (g) internal combustion engines when used for power applications in buildings. Note: For installation of internal combustion engines for emergency power applications, see also CAN/CSA-C282 and CSA Z32. Both these Standards refer to CSA B139 for installation of accessories such as fuel tanks and piping. 5

Scope 1.3 CSA B139-09 Code This Code provides minimum requirements for installing or altering ancillary equipment, including (a) piping & tubing systems supplying fuel oil-burning equipment; (b) pumps; (d) venting systems; (c) control devices; (e) accessories; (f) heat distribution systems that affect the proper operation of the oil-burning equipment; For Residential Fuel Tank Restraints for Yukon Communities http://www.community.gov.yk.ca/buildingsafety/forms.html 6

Scope 1.3 (Cont.) CSA B139-09 Code (g) central oil distribution systems; and (h) above-ground storage tanks that have a maximum individual capacity of 2500 L (550 gal) and a maximum aggregate capacity of 5000 L (1100 gal). Note: Underground fuel oil tank installations of any size and above-ground installations over 2500 L (550 gal) are covered by the National Fire Code of Canada (NFC). These storage tank installations are governed by requirements of the Fire Marshal s Office. 7

Scope 1.4 This Code provides requirements for the maintenance of the most commonly used types of oil-burning equipment. Scope 1.5 This Code provides recommended precautions for filling tanks (see Annex G). Please be advised that in addition to the Residential Fuel Tank Restraints, there are also Installation Checklists which are to be submitted. 8

Scope 1.6 This Code does not apply to CSA B139-09 Code (a) process equipment installed in refineries; (b) appliances installed in mobile housing, recreational vehicles, and marine craft; (c) portable devices such as lamps, blowtorches, melting pots, and weed burners; or (d) integral fuel tanks on internal combustion engines. Note: For installation of oil-burning equipment in mobile housing and recreational vehicles, see CAN/CSA-Z240 MH Series. 9

Scope 1.7 In all CSA Standards: "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; "should" is used to express a recommendation or that which is advised but not required; "may" is used to express an option or that which is permissible within the limits of the standard; and "can" is used to express possibility or capability. 10

Scope 1.7 (Cont.) CSA B139-09 Code Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application. 11

Scope 1.8 CSA B139-09 Code The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only. 12

You may notice that some of the clauses are written slightly different than the Code to enable a better understand of them. NOTE: Some code reference numbers have changed: 1) Section 3 is now definitions which was housed under 2.2. 2) Section 4 in the 2004 code is now section 5, 6 is 7 etc. 13

4.1.4 - is a new clause that states that appliances (furnaces/ boilers/water heaters) shall be installed on a firm, level, NON-COMBUSTIBLE floor or support except where it is approved (CSA, ULC, etc.) for installation on a combustible floor or is installed using a manufacturers certified base. 14

Note: It has often been the practice to have a metal liquid tight pan made and to install an appliance on brick or blocks inside the pan when installing on a combustible floor. This is no longer an accepted practice, as the code states that it must be a manufacturers certified base. 4.11.3 is a new clause that refers to pre-heated fuels (bunkerc oil) 15

VENTING: 5.2.5.11 is a new clause that states when an oil- fired appliance is vented via the same chimney as a gas-fired appliance, the gas appliance must be installed through a separate flue opening above the oil into the flue (double base tee on a prefabricated chimney or separate flue opening in a brick chimney) or into a shop fabricated branch fitting (Y-branch). In a dwelling the branch fitting must be within 30 of the chimney flue or as close as possible in any other type of building. 16

TANKS: 7.4.6 has changed to combine the 2004-6.4.6 & 6.4.7 7.4.10 is a new clause that states unless otherwise protected by its location, the tank and anything attached to it must be protected from possible vehicular movement, in accordance with good engineering practices. Note: Although protection from vehicular movement was in the previous editions, it was included in an annex and as such, was not a mandatory requirement. Good engineering practices means the protection must be capable of stopping a moving vehicle and prevent possible damage to the tank or anything attached to it. (oil lines etc.) 17

TANKS: (Cont.) 7.5.5 This is a very important new clause and refers to tanks installed outdoors. It states that any steel outdoor single tanks of 550 gals. or less, or any combination of connected outside STEEL tanks up to 1100 gals. capacity, shall have secondary containment. 18

TANKS: (Cont.) All outside steel residential tanks will have to be double bottom with interstitial monitoring (signal device to indicate tank bottom failure), be double wall tanks, or be installed in an approved secondary container designed for outdoor use. (ie. covered tank) Note: Although not clearly stated in the code, a combination of two 200 gal tanks, which would be less than 550 gals., or any combination of outside tanks up to 1100 gals will require secondary containment. Any tanks installed before Nov. 2013 will be under the 2004 code. This clause also refers to nonmetallic tanks being approved for this purpose. 19

TANKS: (Cont.) 7.5.7 Outside tanks shall be located and maintained so that the temperature of the oil will not exceed 100 degrees F. Note: Although this clause has been in effect for inside tanks, it is new for outside storage and as noted, could be relevant for tanks with a direct southern exposure and dark colour paint. Consider a cover to avoid direct sunlight & always paint with a light reflective colour. 7.8.3 Fill pipes shall be installed to drain towards the tank ¼ to the foot and be without sags or traps in which liquid can collect. This clause is new for fill pipes but has been used for vent pipes for some time. 20

TANKS: (Cont.) 7.8.12 New clause for tanks supplying generators that states if they have an electrically powered overfill protection device, it must be provided with continuous power. 7.8.13 New clause that states when a fuel transfer pump is used to fill a used-oil supply tank, automatic overfill protection shall be provided. 21

TANKS: (Cont.) 7.9.1.1 - This clause looks new, but is a re-write of two previous clauses so nothing has changed here from the old code. Tanks over 10 gal capacity must be vented in accordance with clause 9.3 (piping and tubing) and cannot exceed 13 ½ ft in height. (A 13 ½ ft. vent pipe full of oil would exceed the allowable pressure at the tank outlet or bottom) 7.9.1.2 in this clause (c) has been moved elsewhere. 22

TANKS: (Cont.) 7.9.1.3 New clause stating if a tank is not certified under ULC - S602 (aboveground steel tanks) or ULC ORD-C80.1 (aboveground non-metallic tanks) the tanks must be vented in accordance with manufacturer s instructions. 7.9.1.10 Clauses on venting two or more supply tanks have been removed and must now conform to 7.6 and 7.7 as shown in Figure 10 A & B and 11 pg.90 92. 23

24

25

26

27

28

29

30

VENTING of AUXILIARY SUPPLY TANKS: 7.9.2.2 7.9.2.4 and 7.9.2.5. Are new clauses for venting overhead auxiliary tanks (day-tanks) used on some booster pump systems. (Commercial/Industrial applications normally) Fuel tanks for engines: 7.9.3 New clause states that if a tank (over 10 gal) is supplying an engine and is in the same trailer, shed, or building, the fill and vent pipes must terminate outdoors. 31

FUEL CONTAINING DEVICES: 9.1.3 This new clause refers specifically to the installation of a fuel oil de-aerator. Must be installed to manufacturer s instructions. A fusible link shut-off valve must be installed just upstream of the device and have a melting point lower than the de-aerator s. The de-aerator must be designed to prevent any foam or liquid from escaping through its vent. Oil temperature must be kept below 100 F. Must be installed indoors. Fuel supply must be filtered. 32

FUEL CONTAINING DEVICES: (Cont.) 9.3.1.5 New clause has been expanded to include piping and tubing protection from damage such as foot and vehicle traffic, grass cutting and snow damage. 9.3.1.9 New clause that states tubing or piping that passes through an exterior wall must be watertight and sleeved (in a plastic pipe) or double wrapped with a waterproof wrap. 33

FUEL CONTAINING DEVICES: (Cont.) 9.3.1.10 Same as 9.3.1.9 (above) but refers to interior masonry or concrete walls. 9.3.1.11 New clause says that materials used to sleeve copper tube must protect the tube from damage and galvanic action. (be non-conductive) 34

FUEL CONTAINING DEVICES: (Cont.) 9.3.1.12 New clause states that piping (threaded pipe) must have at least 1 of unthreaded pipe extended through a finished ceiling or finished wall and at least 2 through a floor. (threaded part of pipe must be at least 1 or 2 from the surface ) 9.3.1.13 New clause that states any piping installed in an area with a corrosive atmosphere must be protected from the corrosive atmosphere (painted, wrapped or coated). 35

VALVES: (pressure relief valves) 9.4.2.3 New clause states that a means to relieve pressure shall be installed between any two automatic shut-off devices. Field Installation of Burners: This was under section 9 in the 2004 code and is section 10 in the new code and states: Site installation of burners, other than those certified for the unit, shall be acceptable to the authority having jurisdiction. 36

Central oil distribution systems (Oil Safety Valves / Anti-Siphoning Valves) 11.5.2. In a central oil distribution system; A certified device (oil safety valve) shall be provided on each oil service pipeline to automatically shut off the oil supply if the supply line between this device and the appliance leaks. This device shall be (a) located on the appliance side of the manual shut-off valve; (b) not more than 1 m (3 ft) from the entry of the oil service pipe into the structure or from the takeoff point from an oil distribution main; (c) installed in accordance with its certification; and (d) solidly supported and protected from damage. As a safety measure it is recommended that this oil safety valve, should be installed on the oil line, inside every dwelling or building. 37

Central oil distribution systems (Oil Safety Valves / Anti-Siphoning Valves) As a safety measure it is recommended that this oil safety valve, should be installed on the oil line, inside every dwelling or building. 38

Annex H:- Is new and refers to tanks for engines (mostly generators or sprinkler pumps). An annex is not normally a mandatory part of the code but may be adopted by the authority having jurisdiction either the Building Safety Branch or the City of Whitehorse Building Inspection Department. 39

RE: Requirements for the Installation of Smoke and Carbon Monoxide Alarms The 2010 Edition of the National Building Code requires the installation of smoke alarms and carbon monoxide (CO) alarms. Smoke Alarms conforming to CAN/ULC-S531, Smoke-Alarms, shall be installed in conformance with CAN/ULC-S553; In each sleeping room; not within a dwelling unit, and In each sleeping room within a care occupancy, and In each sleeping room within a dwelling unit, and 40

Requirements for the Installation of Smoke Alarms (Cont.) In a location between the sleeping rooms, and remainder of the storey, & if the sleeping rooms are served by a hallway, the smoke alarm shall be located in the hallway, and There shall be at least one smoke alarm installed on each storey, of a dwelling unit, including basements, and Ancillary spaces and common spaces not in dwelling units in a house with a secondary suite, and Smoke alarms shall be installed on or near the ceiling, and 41

Requirements for the Installation of Smoke Alarms (Cont.) Smoke alarms shall be installed with permanent connections to an electrical circuit, have no disconnect switch between the overcurrent device and the smoke alarm, be provided with a battery as an alternative power source that can continue to provide power to the smoke alarm for a period of no less than 7 days in the normal condition, followed by 4 minutes of alarm, and 42

Requirements for the Installation of Smoke Alarms (Cont.) Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound, and A manually operated device shall be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more than 10 min, after which the smoke alarm will reset and sound again if the level of smoke in the vicinity is sufficient to re-actuate it. 43

Requirements for the Installation of Smoke Alarms (Cont.) Smoke alarms in a house with a secondary suite shall be wired so that the activation of any smoke alarm causes all smoke alarms within the house & secondary suite to sound. If a building is not supplied with electrical power, smoke alarms are permitted to be battery-operated. 44

Requirements for the Installation of Smoke Alarms (Cont.) If instructions are necessary to describe the maintenance and care required for smoke alarms to ensure continuing satisfactory performance, they shall be posted in a location where they will be readily available to the occupants. Residential suites are permitted to be equipped with smoke detectors in lieu of smoke alarms, provided a fire alarm system has been installed in conformance with CAN/ULC- S524, Installation of Fire Alarm Systems. 45

RE: Requirements for the Installation of Smoke and Carbon Monoxide Alarms The 2010 Edition of the National Building Code requires the installation of smoke alarms and carbon monoxide (CO) alarms. Carbon Monoxide (CO) Alarms conforming to CAN/CSA-6.19, Residential Carbon Monoxide Alarming Devices, shall be installed in every building with a residential or care occupancy that contains a fuel-burning appliance or an attached garage; 46

Requirements for Installing Carbon Monoxide Alarms (Cont.) Have no disconnect switch between the overcurrent device and the CO alarm, where the CO alarm is powered by the dwelling unit s electrical system, and Be mechanically fixed at a height recommended by the manufacturer. 47

Requirements for Installing Carbon Monoxide Alarms (Cont.) Where a room contains a solid-fuel-burning appliance, a CO alarm shall be mechanically fixed: at the manufacturer s recommended height where these instructions specifically mention solid-fuelburning appliances, or in the absence of specific instructions related to solidfuel-burning appliances, on or near the ceiling. 48

Requirements for Installing Carbon Monoxide Alarms (Cont.) Where a fuel-burning appliance is installed in a suite of residential or care occupancy, a CO alarm shall be installed: inside each bedroom, or outside each bedroom, within 5m of each bedroom door, measured following corridors and doorways. 49

Requirements for Installing Carbon Monoxide Alarms (Cont.) Where a fuel-burning appliance is installed in a service room that is not in a suite of residential or care occupancy, a CO alarm shall be installed: either inside each bedroom, or if outside, within 5 m of each bedroom door, measured following corridors and doorways, in every suite of residential occupancy that shares a wall or floor/ceiling assembly with the service room, and in the service room. 50

Requirements for Installing Carbon Monoxide Alarms (Cont.) For each suite of residential or care occupancy that shares a wall or floor/ceiling assembly with an attached garage or that is adjacent to an attic or crawl space that is adjacent to an attached garage, a CO alarm shall be installed: inside each bedroom, or outside each bedroom, within 5m of each bedroom door, measured following corridors and doorways. 51

Requirements for Installing Carbon Monoxide Alarms (Cont.) Where CO alarms are installed in a house with a secondary suite including their common spaces, the CO alarms shall be wired so that the activation of any one CO alarm causes all CO alarms within the house with a secondary suite including their common spaces to sound. Battery-operated carbon monoxide alarms are permitted, but they must be mechanically fixed to a surface. 52

When a a fuel-fired appliance is installed or replaced in a building with a residential or care occupancy, the National Building Code (NBC) also requires that smoke alarms and carbon monoxide (CO) alarms be installed in conformance with the NBC. 53

When a a fuel-fired appliance is installed or replaced in a building with a residential or care occupancy, the National Building Code (NBC) also requires that smoke alarms and carbon monoxide (CO) alarms be installed in conformance with the NBC. 54

http://www.housing.yk.ca/pdf/1_designer_builder_information_package.pdf 55

56

57

58

59

Q&A s REGARDING TANK INSTALLATION & B139-09 The following is a list of possible questions and answers that may arise in reference to the TANK section of the new B139-09, accompanied by comprehensive answers that might be helpful while in the field. Also included are a number of other questions surrounding proper tank installation in general. If clarification is needed on any of the code changes in B139-09, please contact the appropriate authority having jurisdiction. 60

Q - Can I install a steel tank outdoors? A Any single-wall steel tank installed outdoors must have a secondary containment designed for outdoor use (ie. Covered tank) or be a double- bottom with interstitial monitoring. This requirement does not apply to non-metallic tanks. 61

Q- Must I install a double wall steel tank indoors? A NO. This requirement is only for tanks installed outdoors. 62

Q What about existing outdoor steel tank installations? A If the tank was installed prior to November 2013, and it was installed, inspected and approved to the code of the day of when it was installed, then you should check with your insurance company. Also any steel tank, regardless of age, should be checked annually to ensure that there are no signs of oil leaking from the tank or from the oil lines. 63

Q How long can a home/business owner keep an existing steel tank? A All equipment shall be maintained at least once per year. Tanks shall be visually inspected and replaced if necessary. Tanks in unconditioned spaces and outdoors shall be tested for water and pumped if necessary. (15.2.1 15.2.3) 64

Q In the past, insurance companies have stated outdoor steel tanks are good for 15 years. Does this still hold? A Insurance companies set internal company policies for oil tank installations. Homeowners should check with their individual agents for their specific policy details. A tank still must be inspected on an annual basis. If a tank is deemed unfit, the age is irrelevant. 65

Q When a new tank is being installed, does it have to be filled? A The installer has to test the tank and connections for leaks. They can pressure test for a minimum of 10 minutes or hydrostatic test during the first fill. It is the installers responsibility to test the new installation. (7.12.2) 66

Q Can old product be transferred into a new steel tank? A- The transfer of contaminated oil can significantly shorten the life span of a new steel tank and may affect tank warranty. There are various methods to reduce the likelihood of contamination during product transfer, but the only sure thing is no product transfer. The Installation requirements for above-ground domestic oil tanks states transfer should be avoided and recommends only new fuel be introduced into the new tank after replacement. (7.12.4) 67

Q Indoor or outdoor installations; which is preferred? A- Indoor installations are always preferred by the industry. The house offers protection from the environment and from vandalism. As well, small leaks can be detected sooner, less condensation takes place, and fuel atomizes better at room temperature. 68

Q Should a home/business owner be able to detect an oil odour from an oil tank that s installed indoors? A Absolutely not. Fuel has offensive aromatics that should alert you to a problem. If an odour is detected, there must be (1) a leak in the fill and vent piping or (2) a leak in the tank itself or (3) a leak in the line/filter from tank to burner or (4) a leak involving the fuel pump. Property owners need not get used to the smell of heating oil. 69

Q If an oil tank is located inside a garage, does it need to have posts installed to protect it from vehicular movement? A YES. The new code states that unless the tank is protected by its location, the tank and anything attached to the tank (piping, oil lines etc.) must be protected from vehicular movement/traffic. If an automobile can hit the tank, it needs protection. (7.5.6) (7.4.10) 70

Q When replacing an existing outside oil tank that is currently located on the property line, can the new tank be installed in the same location? A No. There are no grandfather rules that allow for new installations on the property line. Code requirements state the tank must be at least 5 from the property line. (7.5.4) 71

Q When installing a new tank indoors, do the fill and vent pipes need to be replaced? A Fill and vent pipes are part of the tank storage system and must meet the code of the day. Today s code states Fill pipes shall be steel (black iron) or galvanized (zinc Coated black iron), however, no cast 90 s are allowed. The fill and vent must drain 1/4 per foot, and the vent cap must be screened. The likelihood of existing fill and vent pipes meeting all code requirements today, is very slim. It s better to count on replacement.(7.8.12) 72

Q - What is the right way to pipe together two fuel tanks? A Figure 10a, 10b and 11 in the new B139-09 show the only acceptable configuration to pipe-out multiple tanks. The main concerns are overfills and pressurization of the vessels. Failure to install tanks according to these methods could lead to product spills. 73

Q Does a top connected fuel line require a de-aerator? A When fuel oil is subjected to a vacuum, air in the oil will be extracted and cause problems not only with the pump, but also after drip and carbon deposits. 74

75

76

77

78

79

80

81

82

Chimney in a chase without sleeve, sleeve had to be installed, Inspection of a chimney chase that has already been enclosed requires a Letter of Declaration from the installer stating that; if required a sleeve has been installed, all clearances to combustibles have been met, floor and ceiling support kits and required fire stopping at each floor have all been installed. 83

84

85

86

87

88

89

90

91

92

93

94

95

96

97

98