AE Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A

Similar documents
AE R20 January Cooling Requirements for Copelametic and Copeland Discus Compressors

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

September 2016 AE Application Guidelines for Copeland CS**KIE Compressors in Ice Machines AE4-1421

AE R8 March 2015

Application Guidelines for Glacier K3 Copeland Scroll Refrigeration Compressors

AE R17 November 2016

AE R4 July 2015 Guide for the Use of R-290 Refrigerant in Copeland Refrigeration Compressors

Application Guidelines for Low Temperature ZF**KAE 1-2.5HP Copeland Scroll Refrigeration Compressors

Application Guidelines for ZS**KAE Refrigeration Copeland Scroll Compressors HP

AE R13 August 2018 Economized Vapor Injection (EVI) for ZF*KVE and ZF*K5E Compressors TABLE OF CONTENTS

Copeland Scroll Condensing Units for the Food Service Market

AE R21 September 2017

Refrigerant Changeover Guidelines HFC R-404A/R-407A/C/F to R-448A/R-449A. Leading the Industry with Environmentally Responsible Refrigerant Solutions

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

AE R9. AE R9 May Application Guidelines For K4 Refrigeration Copeland Scroll Compressors Horsepower

Application Engineering

Refrigerant changeover guidelines

7 to 15 Ton ZR*KC and ZP*KC Copeland Scroll Compressors

Application Engineering

Application Guidelines

Scroll Compressors for Heat Pump Applications ZH12K4E to ZH11M4E, ZH06KVE to ZH48KVE

Digital Scroll Compressors for Air Conditioning

NO: 9-16 DATE: 2/11/16 EMERSON CLIMATE TECHNOLOGIES WHOLESALERS -EXECUTIVES -PRODUCT MANAGERS -EMERSON TM TECHNICAL SPECIALISTS -BRANCH PERSONNEL

Application Guidelines. Scroll Compressors for Air Conditioning ZR18K* to ZR380K*, ZP24K* to ZP485K*

Copeland Scroll. Product Information. Outdoor condensing units for refrigeration applications

Application Engineering

LIQUID REFRIGERANT CONTROL IN REFRIGERATION AND AIR CONDITIONING SYSTEMS

Application Engineering

horizontal air discharge outdoor discus condensing unit

Application Guidelines for ZB*KC/ZB*KCE Copeland Scroll Refrigeration Compressors 7 to 15 HP

Residential Piping and Long Line Guideline

Condensing Unit Installation and Operating Instructions

REFRIGERANT CHANGEOVER

Outdoor Condensing Unit - ZX Range. High Efficiency In Compact Design

Application Guidelines. Copeland Scroll Summit Series ZB50KCE to ZB114KCE & ZB66K5E to ZB114K5E ZF25K5E to ZF49K5E

Outdoor Refrigeration Unit - ZX Range High Efficiency In Compact Design

AE R1 Application Guidelines for ZB*KAU Copeland R-290. August Scroll Compressors

Digital. Application Guidelines Digital Scroll Compressors for Refrigeration ZBD21K* to ZBD114K* ZFD13KVE to ZFD25KVE ZFD41K5E

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Application Guidelines. Copeland Scroll Compressors for Refrigeration. ZB15K* to ZB220K*, ZS21K* to ZS11M* ZF06K* to ZF48K*, ZF13KVE to ZF48KVE

Copeland Scroll Outdoor Refrigeration Unit

AE ZJ36 to ZJ54KHE R410A Copeland Scroll Compressors

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

AE October 1965 Reformatted October Hot Gas Bypass Control Systems

AE R3. July 2016 AE R3. Replaces AE CR KQ, CR K6, CR_5, CR K7 Hermetic Reciprocating Compressors

Danfoss scroll compressors SH - In parallel installation

A Series Inertia Compressor Applications. Application Bulletin 115

PS SERIES PARALLEL RACK SYSTEM START UP GUIDE

APPLICATION DATA SHEET

PULSE WIDTH MODULATING VALVES

Service Step by Step Trouble-Shooting Check-List

Contour TM Screw Compressors

MACH N-407 Heat Pump Air-Cooled Chiller

June 2001 / BULLETIN Way Valves. The right solenoid valve for any job.

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

Danfoss scroll compressors SH- In parallel installation

Condensing Unit Installation and Operating Instructions

2 shp 13 lc 1 36 t - 1 a

INDEXING AND CLASSIFICATION SYSTEM

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

MAC N-407 Air-Cooled Chiller

Suction Accumulators. Introduction. Suction Accumulators

H29A Series Compressor Applications. Application Bulletin 139

Technical Information

Danfoss Inverter scroll compressor, VRJ

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

TECHNICAL SPECIFICATIONS

Air-Cooled Condensing Units with Bitzer Compressors

Publication # RD-0003-E Rev 1, 10/17 SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Application Guidelines Semi-Hermetic Stream CO 2 Compressors 4MTL-05_to 4MTL-30_ 4MSL-03_ to 4MSL-15_

Nominal Capacity 024 = 7 kw (2 tons) 036 = 10.5 kw (3 tons) 048 = 14 kw (4 tons) 060 = 17.5 kw (5 tons)

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Danfoss scroll compressors In parallel installation SM/SY/SZ

NEWGATE TECHNOLOGIES, INC.

Kramersaver Air Cooled Condensing Units

The Digital Scroll Dryer

AIR COOLED PACKAGED CHILLER

Application Engineering

Technical Information

Performer Heat Pump scroll compressors 50 Hz - R407C Selection & application guidelines

R-407A R-448A R-449A

APPROVAL SHEET SPECIFICATIONS OF HERMETIC SCROLL COMPRESSOR C-SBR180H16A

Maneurop reciprocating compressors NTZ

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

XC16. ELITE SERIES R 410A Two Stage Compressor SilentComfort Technology A I R C O N D I T I O N E R S

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Inverter scroll compressors VZH hybrid manifold

MAC-120HE-03 Air-Cooled Chiller

MAKING MODERN LIVING POSSIBLE. Residential and light commercial scroll compressors Hz R-407C / R-22 / R-410A SELECTION & APPLICATION GUIDELINES

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Danfoss scroll for refrigeration LLZ Evolution A (with POE oil) Low temperature

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

AIR COOLED CONDENSING UNITS IMPORTANT DESIGN FEATURES

DEHYDRATORS AND FILTERS

R410A Air-Conditioning Scroll Compressors, Tandem ZPT180 KCE... ZPT590KCE ZPU415KCE... ZPU530KCE

Liebert CSU3000 Chiller

Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s) Description Model(s) Page(s)

Transcription:

AE4-1392 July 2014 Application Guidelines for Refrigeration Copeland Discus Compressors with R-410A Section TABLE OF CONTENTS Page Safety Safety Instructions...2 Safety Icon Explanation...2 Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons...3 Safety Statements...3 Introduction Nomenclature...4 Coresense Protection...4 Discus Digital Technology...4 Operating Envelope...4 Motor Protection...4 Compressor Charge...4 Oil Types...4 Oil Charges...5 Oil Management...5 Copeland Discus with Demand Cooling...5 Discharge Temperature Protection...5 Internal Pressure Relief Valve...5 Crankcase Heater...5 Power Supply...5 Multiple Compressor Applications...5 Accumulators...6 Discharge Line Mufflers...6 Contaminant Control...6 Screens...6 Compressor Bolt Torque Values...6 Compressor Tubing and Mounting...6 Figures and Tables Medium Temperature (3PA*R) R-410A Operating Envelope...7 Low Temperature (3PA*F) R-410A Operating Envelope...7 Mounting Kit for R-410A Discus...8 R-410A Copeland Discus Compressor Models...8 Pressure Control Settings...8 R-410A Discus Mounting Kit Part Numbers...9 Accessory Kits for R-410A Discus...9 1

Safety Instructions Copeland Scroll compressors are manufactured according to the latest U.S. and European Safety Standards. Particular emphasis has been placed on the user's safety. Safey icons are explained below and safety instructions applicable to the products in this bulletin are grouped on page 3. These instructions should be retained throughout the lifetime of the compressor. You are strongly advised to follow these safety instructions. Safety Icon Explanation DANGER WARNING CAUTION NOTICE CAUTION DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE is used to address practices not related to personal injury. CAUTION, without the safety alert symbol, is used to address practices not related to personal injury. 2

Instructions Pertaining to Risk of Electrical Shock, Fire, or Injury to Persons WARNING ELECTRICAL SHOCK HAZARD Disconnect and lock out power before servicing. Discharge all capacitors before servicing. Use compressor with grounded system only. Molded electrical plug must be used when required. Refer to original equipment wiring diagrams. Failure to follow these warnings could result in serious personal injury. WARNING PRESSURIZED SYSTEM HAZARD System contains refrigerant and oil under pressure. Remove refrigerant from both the high and low compressor side before removing compressor. Never install a system and leave it unattended when it has no charge, a holding charge, or with the service valves closed without electrically locking out the system. Use only approved refrigerants and refrigeration oils. Personal safety equipment must be used. Failure to follow these warnings could result in serious personal injury. WARNING BURN HAZARD Do not touch the compressor until it has cooled down. Ensure that materials and wiring do not touch high temperature areas of the compressor. Use caution when brazing system components. Personal safety equipment must be used. Failure to follow these warnings could result in serious personal injury or property damage. CAUTION COMPRESSOR HANDLING Use the appropriate lifting devices to move compressors. Personal safety equipment must be used. Failure to follow these warnings could result in personal injury or property damage. Safety Statements Refrigerant compressors must be employed only for their intended use. install, commission and maintain this equipment. All valid standards and codes for installing, servicing, and maintaining electrical and refrigeration equipment must be observed. 3

Introduction The refrigeration Copeland Discus compressor product offering has expanded to include the higher pressure refrigerant R-410A. These new models include low temperature and medium/high temperature models with capacity of 29,000 to 45,000 Btu/hr at -25/105 F ARI condition and 85,000 to 130,000 Btu/hr at 20/120 ARI condition using 60 Hz electrical power. Only threecylinder Discus compressors have been released at this time. This bulletin covers the application parameters recommended for operating these compressors properly. Nomenclature The high pressure refrigerant Discus compressor has a model designation as follows, with the second digit shown as a 'P': 3PA3R85KL-TFD-C00. The model numbers include the nominal capacity for R-410A at ARI conditions (20/120 F for medium temperature and -25/105 F for low temperature). 3 P A 3 R 85K L TFD - C00 1 2 3 4 5 6 7 8 9 1. 3 = Number of Cylinders 2. P = High Pressure Refrigerant Discus (R-410A) 3. A = Bore Size 4. 3 = Fixed Capacity Control; D = Discus Digital 5. R = Medium Temperature; F = Low Temperature 6. 85K = Nominal capacity (Btu/hr) at ARI Condition, where 'K' is for 1,000 multiplier and 'M' is for 10,000 multiplier 7. L = Less Oil; E = Polyolester Oil 8. TFD = Electrical Code ( 460V -3Ø-60Hz) 9. C00 = Build of Material Table 1 at the end of this bulletin shows the nominal capacity (Btu/hr) for each model with R-410A refrigerant at ARI conditions. For additional performance data, refer to the Online Product Information at www. emersonclimate.com or through Emerson Climate Technologies Product Selection Software, PSS. CoreSense Protection CoreSense Protection will be provided on all R-410A Copeland Discus compressors. CoreSense Protection is noted by a 'C' in the build of materials, e.g. 3PA3R85KL- TFD-C00. The Coresense Protection module for Discus compressors combines oil and motor protection into one module, as well as offering optional protection against high discharge temperature and communication compatibility with MODBUS communication devices. Display LEDs clearly indicate the operational status of the compressor and whether or not there are any active compressor warnings, trips, or lockouts. Discus Digital Technology Each of the 3P R-410A Discus compressors are also available with Copeland Discus Digital technology. Digital capacity control is achieved by using a proven internal unloading method, blocked suction. By varying the percentage of duty cycle that the compressor is loaded and unloaded, capacity control between 10 and 100% can be achieved. During blocked suction operation, the flow of suction gas is blocked to all cylinders on a single bank; therefore there is no gas to compress and the power consumption is significantly lower. The unloader piston mechanism that controls flow of suction gas into the cylinders is driven by a high life digital solenoid valve. The digital models are indicated by a 'D' in the 4th character of the model number, e.g. 3PADR10ML-TFD. For more information on Copeland Discus Digital compressors, refer to AE21-1355, Digital Capacity Control for Copeland and Intelligent Store Discus Refrigeration Compressors. Operating Envelope See Figures 1 and 2 at the end of this bulletin. All 3PA* Discus models are approved for use with refrigerant R-410A. All models may be operated within the entire operating envelopes shown in Figures 1 and 2. Use of refrigerants other than R-410A voids the UL listing and warranty of these models since they could affect the motor protector setting. Motor Protection Conventional inherent internal line break motor protection is provided in the R-410A Discus compressor. Refrigerant Charge For single compressor applications, 3P* Copeland Discus compressors have a maximum recommended charge of 17.5 lbs. Some system configurations may contain higher-than-normal refrigerant charges either because of large internal coil volumes or long line sets. If such a system also contains an accumulator, then the permanent loss of oil may become critical. Accumulator manufacturers should be consulted for a pre-charge recommendation. Additional oil may need to be added to wet the system prior to start up. 4

For racks and other applications that use multiple compressors see the section titled Multiple Compressor Applications. Oil Types All 3PA* Discus models are approved for use with polyolester oil (POE). See Form 93-11 for a complete list of all Emerson-approved lubricants. Oil Charges The recommended initial oil charge for these compressors is 125 ounces and the recommended recharge is 115 ounces. The oil level of the R-410A Discus compressor should be adjusted to the mid-point of the compressor sightglass during normal operation. Oil Management The R-410A Discus compressors are each equipped with electronic oil pressure protection using CoreSense Protection technology. Insufficient oil pressure time for the compressor is stored and accumulated in the CoreSense module memory. Once the total time accumulated for low oil pressure (a reading less than 7-9 PSID) exceeds 120 seconds, the module will shut the compressor off and a low oil pressure lockout will be reported. The compressor will turn back on once the reset has been activated either manually or remotely through the communication network, or when power has been cycled to the CoreSense Protection module. For more information on CoreSense Protection for Copeland Discus compressors, refer to AE8-1367. Copeland Discus with Demand Cooling R-410A can be used as a low temperature refrigerant in a properly designed and controlled refrigeration system. However, experience has shown that R-410A can present problems as a low temperature refrigerant because under some conditions the internal compressor discharge temperature exceeds the safe temperature limit for long term stability of the oil (similar to what is seen when using R-22 or R-407A in low temperature applications). The Demand Cooling system uses modern electronics to provide a reliable cost-effective solution to this problem. It is required for all low temperature Discus R-410A applications with saturated suction temperatures below -10 F. The Demand Cooling module uses the signal of a discharge head temperature sensor to monitor discharge gas temperature. If a critical temperature is reached, the module energizes a long life injection valve which meters a controlled amount of saturated refrigerant into the compressor suction cavity to cool the suction gas. This process controls the discharge temperature to a safe level. If for some reason the discharge temperature rises above a preset maximum level, the Demand Cooling module will turn the compressor off (requiring a manual reset) and actuate its alarm contact. To minimize the amount of refrigerant which must be injected, the suction gas cooling process is performed after the gas has passed around and through the motor. Performance data for Demand Cooling compressors includes the effects of injection when it is required. The approximate conditions where injection occurs are shown in Figure 2. For more information on Copeland Discus Demand Cooling refer to AE4-1287. NOTE! When Demand Cooling is applied, a head fan is not required. When Demand Cooling is not utilizedduring low temperature applications, a head fan is required. Part numbers for Discus head fans can be found in Table 4. Discharge Temperature Protection Another method of protecting against high discharge temperature is the use of a discharge probe. Coresense Protection has the option of adding discharge temperature protection. The probe can be installed into the head of the compressor and wired to the Coresense module. Figure 4 shows multiple locations for installing the discharge temperature probe. Coresense Protection will open the control circuit and shut the compressor off if the probe senses too much resistance (280 F). NOTE! When applying Demand Cooling, the optional discharge temperature probe for CoreSense Protection is not required. Internal Pressure Relief Valve R-410A Copeland Discus compressors are not equipped with an internal pressure relief valve. To provide safe operation, a high pressure control set no higher than 577 psig must be used in all applications (See Table 2.) Crankcase Heater If the compressor will be exposed to low ambient conditions, refrigerant migration may become an issue during the off cycle. To prevent migration during the off cycle of the compressor, a crankcase heater is 5

recommended. For systems that exceed the refrigerant charge limit (17.5lbs) and are without a suction accumutor a crankcase heater is recommended. Power Supply All 3P* Copeland Discus compressors have electrical code 'TFD' and are rated for 460V -3Ø-60Hz. Voltage should be maintained within +/- 10% of nominal to ensure reliable operation. Multiple Compressor Applications 3P* Copeland Discus compressors are approved for use in multiple compressor applications. When using an OMB for oil management the system pressures may exceed the solenoid maximum operating pressure differential (MOPD) of 350psig. If the MOPD is exceeded, the solenoid may not open and the compressor could be starved of oil. This would result in a 'Low Oil Trip' fault from the CoreSense Protection module. To avoid low oil faults, a pressure reducing valve located on the oil suction line may be needed for high pressure oil systems. Another valid option would be the use of a low pressure oil system. Accumulators The use of a suction accumulator is very dependent on the application. A suction accumulator is recommended to prevent liquid refrigerant from returning to the compressor. When liquid refrigerant returns to the compressor, the oil can become diluted to a point that bearings are inadequately lubricated. To determine if refrigerant is returning to the compressor, determine the superheat reading on the suction line 6 inches from the compressor. If the superheat is low, then an accumulator is recommended to ensure liquid does not return to the compressor. To prevent refrigerant floodback in systems that do not use an accumulator, it is recommended that a minimum of 20 F superheat is maintained. Systems with scheduled defrost cycles or greater than 17.5 lbs refrigerant charge should use a suction accumulator. Discharge Line Mufflers Discharge line mufflers are not required for the R-410A Discus compressor. If a discharge pulsation is unacceptable then a muffler may be added to reduce vibrations and or sound. Contaminant Control A filter drier is required on all R-410A and POE lubricant systems to prevent solid particulate contamination, oil dielectric strength degradation, ice formation, oil hydrolysis and metal corrosion. It is recommended that a liquid line filter drier be installed. In some cases a suction line filter drier may also be necessary. It is the system designer s responsibility to make sure the filter-drier is adequately sized to accommodate the contaminants from system manufacturing processes that leave solid or liquid contaminants in the evaporator coil, condenser coil, and interconnecting tubing plus any contaminants introduced during the field installation precess. Molecular sieve and activated alumina are two filter-drier materials designed to remove moisture and mitigate acid formation. A 100% molecular sieve filter can be used for maximum moisture capacity. A more conservative mix of molecular sieve and activated alumina, such as 75% molecular sieve and 25% activated alumina, should be used for service applications. Screens Screens finer than 30X30 mesh (0.06mm openings) should not be used anywhere in the system. Field experience has shown that finer mesh screens used to protect thermal expansion valves, capillary tubes, or accumulators can become temporarily or permanently plugged with normal system debris and block the flow of either oil or refrigerant to the compressor. Compressor Bolt Torque Values The compressor bolt torque values for a R-410A Copeland Discus compressor are equivalent to those applied on a standard 3D Copeland Discus compressor. Refer to AE4-1219, Torque Values for Copeland Brand Products, for more details. Compressor Tubing and Mounting Compressor mounting must be selected based on application. Consideration must be given to sound reduction and tubing reliability. Some tubing geometry or shock loops may be required to reduce vibration transferred from the compressor to external tubing. The mounting kit required for single condensing unit applications is shown in Table 3. The mounting diagram in Figure 3 shows how the mounting kits should be applied. For multiple compressor systems such as parallel racks, solid spacers are recommended. 6

150 140 130 120 Condensing Temperature 110 100 90 80 70 60 50 40-20 -10 0 10 20 30 40 50 Evapora ng Temperature Figure 1 Medium Temperature (3PA*R) R-410A Operating Envelope 140 130 120 Demand Cooling Required* 110 Condensing Temperature 100 90 80 70 65 F Return Gas Demand Cooling Injec on Line 60 50 40 Head Cooling Fan Required** 30-45 -40-35 -30-25 -20-15 -10-5 0 Evapora ng Temperature Figure 2 Low Temperature (3PA*F) R-410A Operating Envelope * Demand Cooling is required when using low temperature R-410A Discus models above the dotted line. ** A head cooling fan is required for low temperature R-410A Discus models when demand cooling is not used and operation is below the dotted line. 7

Mounting Stud Leave 1/16 inch space after installation Mounting Nut (Upper) Rubber Spacer Mounting Nut (Lower) Mounting Spring Mounting Base Lockwasher Mount is shown in properly adjusted position. (Shipping retainer has been removed.) Figure 3 Condensing Unit Spring Mounting Kit for R-410A Discus Front (Oil Pump End) Figure 4 - Top View of 3D Discus Cylinder Head with Possible Temperature Probe Locations 8

Table 1 R-410A Copeland Discus Compressor Models Application Model Number HP Medium Temperature 20/120/65RG/0SC F Low Temperature -25/105/65RG/0SC F Compressor Capacity (Btu/hr) 3PA3R85KL-TFD 10 85,000 3PA3R10ML-TFD 10 100,000 3PA3R12ML-TFD 15 120,000 3PA3R13ML-TFD 15 130,000 3PA3F29KL-TFD 7.5 29,000 3PA3F35KL-TFD 7.5 35,000 3PA3F41KL-TFD 10 41,000 3PA3F45KL-TFD 10 45,000 Table 2 Pressure Control Settings Application Low Temperature (3PA*F*) Medium Temperature (3PA*R*) Low Pressure Cutout High Pressure Cutout 6 psig min. 508 psig max. 32 psig min. 577 psig max. Table 3 R-410A Discus Condensing Unit Spring Mounting Kit Part Numbers Model Number Mounting Kit 3PA3R85KL-TFD 527-0009-00 3PA3R10ML-TFD 527-0009-00 3PA3R12ML-TFD 527-0045-00 3PA3R13ML-TFD 527-0045-00 3PA3F29KL-TFD 527-0009-00 3PA3F35KL-TFD 527-0009-00 3PA3F41KL-TFD 527-0045-00 3PA3F45KL-TFD 527-0045-00 9

Table 4 Accessory Kits for R-410A Discus Part Description Kit Number CoreSense Protection Optional Discharge Temperature Probe 985-0109-50 Demand Cooling Kit, 120V, 60Hz 998-1000-13 Demand Cooling Kit, 240V, 60Hz 998-1000-24 Crankcase Heater, 120V, 100W 918-0028-00 Crankcase Heater, 240V, 100W 918-0028-01 Heater Sleeve 030-0187-00 Head Cooling Fan Assembly, 460V 998-0550-01 Head Cooling Fan Assembly, 230V 998-0550-00 Head Cooling Fan Assembly, 115V 998-0550-02 Head Cooling Fan Mounting Kit 998-0574-10 Digital Compressor Controller (3D) 943-0086-02 XC643 Digital Compressor Controller 998-0189-00 Discus Digital 24V Coil 923-0084-00 Discus Digital 120V Coil 923-0084-01 Discus Digital 240V Coil 923-0084-02 High Discharge Temperature Protection Probe 985-0109-50 Model Number Table 5 Service Valve Part Numbers Discharge Service Valve Suction Service Valve 3PA3R85KL-TFD 998-0510-02 998-0510-11 3PA3R10ML-TFD 998-0510-02 998-0510-11 3PA3R12ML-TFD 998-0510-02 998-0510-07 3PA3R13ML-TFD 998-0510-02 998-0510-07 3PA3F29KL-TFD 998-0510-02 998-0510-11 3PA3F35KL-TFD 998-0510-02 998-0510-11 3PA3F41KL-TFD 998-0510-02 998-0510-11 3PA3F45KL-TFD 998-0510-02 998-0510-11 The contents of this publication are presented for informational purposes only and are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies, Inc. and/or its affiliates (collectively "Emerson"), as applicable, reserve the right to modify the design or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson product remains solely with the purchaser or end user. 10