Enhancing the performance of the domestic refrigerator with hot gas injection to suction line

Similar documents
Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Pure Butane as Refrigerant in Domestic Refrigerator Freezer

Technology Application of Environmental Friendly Refrigeration (Green Refrigeration) on Cold Storage for Fishery Industry

DEEPAK PALIWAL, S.P.S.RAJPUT

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Enhancement of COP using Nanoadditives in Domestic Refrigerator

Experimental Evaluation of Refrigerant Mixtures as Substitutes for HFC134a

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Part load performance analysis of vapour compression refrigeration system with hydrocarbon refrigerants

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

BUTANE, ISOBUTANE AND THEIR MIXTURES AS AN ALTERANTIVES TO R-134a IN DOMESTIC REFRIGERATOR

International Journal of Multidisciplinary Research and Modern Education (IJMRME) ISSN (Online): (

Study on a novel variable capacity technology and control strategy for refrigerated shipping container unit

Australian Journal of Basic and Applied Sciences. Investigation of New Eco Friendly Refrigerant Mixture Alternative to R134a in Domestic Refrigerator

Experimental study of hybrid loop heat pipe using pump assistance for high heat flux system

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

REVIEW ON HOT GAS DEFROSTING SYSTEM FOR VAPOR COMPRESSION REFRIGERATION SYSTEM

Study of Behavior of Refrigerant Mixtures in Domestic Refrigerator- Practical Research

Assessment of LPG as a possible alternative to R-12 in domestic refrigerators

Study of Performance of Binary Mixture of R134a and R161 as a Substitution of R134a in a Domestic Refrigerator

Environment Protection Engineering

Performance Study of Solar Heat Pipe with Different Working Fluids and Fill Ratios

Design Evolution: From Rolling Piston to Revolving Vane to Cross-Vane Expandercompressor

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Experimental study of R600a and R436a to replace R134a in a domestic refrigerator and freezer

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Thermal comfort investigation on a naturally ventilated two- storey residential house in Malaysia

THEORETICAL INVESTIGATION OF THE PERFORMANCE OF SOME ENVIRONMENT-FRIENDLY REFRIGERANTS IN A SUB-COOLING HEAT EXCHANGER REFRIGERATION SYSTEM

Performance Investigation of Domestic Refrigerator Using Pure Hydrocarbons and Blends of Hydrocarbons as Refrigerants

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

HFC/HC BLEND FOR CAR CLIMATE CONTROL WITH MINERAL OIL AS LUBRICANT

Effects of seawater flow rate and evaporation temperature on performance of Sherbet type ice making machine

Effects of evaporator load on vapour compression refrigeration system using ecofriendly hydrocarbon refrigerants with sub cooling

Building Coverage Ratio at the Eastern Corridor of Jalan Ir. H. Djuanda Bandung

Oyelami S., Bolaji B. O.

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

ENERGY PERFORMANCE ASSESSMENT OF R134A/LPG BLEND AS REPLACEMENT OF R134A IN VAPOR COMPRESSION REFRIGERATION SYSTEM

Effect of magnetic field on the performance of new refrigerant mixtures

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Thermodynamics I. Refrigeration and Heat Pump Cycles

Properties of a two stage adiabatic demagnetization refrigerator

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Design of solar adsorption refrigeration system with CPC and study on the heat and mass transfer performance

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

THERMODYNAMIC PERFORMANCE ANALYSIS OF R-600 AND R-600A AS REFRIGERANT

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Volume 2, Issue 4 (2014) ISSN International Journal of Advance Research and Innovation

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Evaluation of moisture content in drying of grated coconut meat using grain moisture meter

Chapter 10. Refrigeration and Heat Pump Systems

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Energy Performance Assessment of R32/R125/R600a Mixtures as Possible Alternatives to R22 in Compression Refrigeration Systems

Global Journal of Engineering Science and Research Management

U.G. Student, Department of Mechanical Engineering, J D Engineering College, Nagpur, Maharashtra, India

Department of MCE, Islamic University of Technology 2. Abstract

Brazed Plate Heat Exchanger for CO Applications

Experimental performance evaluation of vapour compression refrigeration system without nano particles

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Implementation of Inverter-Driven Household Refrigerator/Freezer Using Hydrocarbon Isobutane for Refrigeration

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

AN EXPERIMENTAL INVESTIGATION INTO THE EFFECT OF THERMOSTAT SETTINGS ON THE ENERGY CONSUMPTION OF HOUSEHOLD REFRIGERATORS

Sarthak Thakar, 2 R.P.Prajapati 1

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Redesign 3 R Machine as a Refrigerant Waste Treatment Alternative in Environmental Rescue

Effect on air quality and flow rate of fresh water production in humidification and dehumidification system

Performance of an Improved Household Refrigerator/Freezer

Comparative Performance Analysis of Domestic Refrigerator using R12, R134a and R600a Refrigerants

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

A study of Transient Performance of A Cascade Heat Pump System

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

International Journal of Advance Engineering and Research Development

Energy Performance of Eco-friendly R152a and R600a Refrigerants as Alternative to R134a in Vapour Compression Refrigeration System

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

International Journal of Informative & Futuristic Research ISSN (Online):

To investigate the surface properties for increasing efficiency of solar water heater

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Performance Prediction of Domestic Refrigeration System using R436A Refrigerant as alternative Refrigerant to R134a with ANN

HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature

Transcription:

IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Enhancing the performance of the domestic refrigerator with hot gas injection to suction line Recent citations - Expansion Parallel Liquid Refrigerant On A Vapor Compression Systems With R-290 D Supriawan et al To cite this article: E T Berman et al 2016 IOP Conf. Ser.: Mater. Sci. Eng. 128 012028 View the article online for updates and enhancements. This content was downloaded from IP address 37.44.193.125 on 19/01/2018 at 08:23

Enhancing the performance of the domestic refrigerator with hot gas injection to suction line E T Berman*, S Hasan and Mutaufiq Department Pendidikan Teknik Mesin, FPTK Universitas Pendidikan Indonesia (UPI) *Corresponding author: egatb@upi.edu Abstract. The purpose of this study was to determine the increase in performance of a domestic refrigerator that uses hot gas injection (IHG) to the suction line. The experiment was conducted by flowing refrigerant from the discharge line to the suction line. To get performance data, measurements performed on the liquid brine as cooling load with various temperatures (range from 3 0 C to -3 0 C). The working fluid is used as a cooling medium is R-134a. The experimental results showed that the injection of hot gas to the suction line generates an increase in the coefficient of performance systems (COPs) of 7% and is able to lower the discharge temperature, causing the compressor to work lighter/easier, saving electric power needed by the refrigerator. 1. Introduction The use of refrigerators in households increases every year. It is because people increasingly do their activities outside their houses; they prefer to purchase their needs at one time and store them in refrigerators. The role of refrigerators in today s modern era occupies a primary position in people s lives [1]. In general, refrigerators use a vapour compression cycle that requires energy input from the outside in the form of electrical energy to drive the compressor motor. The energy required by refrigerators is quite big [2], as the refrigerators work for 24 hours. Therefore, energy saving measures are necessary as it would significantly impact on energy conservation efforts in the world [3][4]. In order to solve the problem of energy saving of refrigerators, some researchers have implemented various ways to reduce energy consumption and improve the efficiency of the refrigeration system, including: (i) replacing the synthetic refrigerant with natural refrigerants [5][6][7][8]; and (ii) installing suction-liquid heat exchangers (SLHX) [9][10]. However, some problems are still found. The natural refrigerants that are made from hydrocarbons have flammable properties and the advantages of SLHX installation rely on the combination of operating conditions and the properties of the fluid [10]. In general, the technique of hot gas injection is used to defrosting process on the evaporator [11][12][13]. Difference with other report, the technique of hot gas injection in this study is used to increase the cooling capacity and lowering the discharge temperature of the refrigerant. When the refrigeration system off cycling, the pressure of both low side and high side will be the same. However, when the refrigeration system starts running both pressure values will differ significantly. Therefore, the technique of hot gas injection to the suction line is needed to reduce the pressure difference on both sides. The purpose of this study was to determine the increase in performance of a refrigerator utilizing hot gas refrigerant from the compressor s discharge which was injected into the suction line. This method is adopted from the heat pump cycle [14][15], which useful to maintain the balance of the capacity of the evaporator and compressor when the pressure and temperature of refrigerant at the suction channel are low. Therefore, the application of this engineering method to domestic refrigerators is expected to reduce the load of the compressor when doing compression work; this will have an impact on the Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by Ltd 1

increased value of coefficient of performance systems (COPs) and the decrease of energy/power required as the driving force. 2. Materials and Experimental method Figure 1 shows the layout of a domestic refrigerator used for the experiement. The tes unit was a Sanyo refrigerator and designed to work with R-134a refrigerant. The main components of the domestic refrigerator consist of evaporator, compressor, condenser and refrigerant control. Components of the hot gas injection line consist of a 2 m capillary tube and a check valve. Two pressure gauges (Robin Air, USA) and two temperature sensors (Lutron, Taiwan) were placed on the inlet and outlet of the compressor to measure the suction and discharge pressures. On the inside of the refrigerator, a container of brine (salt water) weighing 500g was kept, serving as cooling load. A thermometer was placed in the brine container to determine changes in temperature every 1 0 C. At the beginning of the research, the system was operated under a normal condition to obtain baseline data of the performance of the refrigerator. After that, hot gas injection line was installed to the suction line. Before the second data retrieval, the system was flushed using nitrogen to eliminate dirt, moisture and other substances in the system which might affect its performance. Then, the system was filled with R-134a weighing 100g in accordance with the recommendation of the manufacturer. Data capture started when the temperature of the brine was 3 0 C, with the assumption that the system was steady. Next, changes were observed until the temperature of the brine reached -3 0 C. During the study, the temperature of the environment was kept at 28 0 C ± 2 0 C. The research procedure was implemented 3 times to obtain the average value. Figure 1. Layout of the domestic refrigerator 3. Results and Discussions The results were obtained from the performance testing of the domestic refrigerator in two operating conditions: normal and hot gas injection. Tests were carried out at an ambient temperature of 28 0 C in the refrigeration cycle operating mode under load conditions of 3 0 C to -3 0 C. 2

3.1. Work of compression Figure 2 shows the results of the compression works of the domestic refrigerator under two testing conditions. In general, the compression work generated by the system using hot gas injection has a lower value than that of the normal system. In the normal system, the compression generated when the brine was 3 0 C was 26.27 Btu/lb. Then, this increased gradually to 26.57 Btu/lb when the temperature of the brine was -1 0 C. After that, it feel back to to 26.48 Btu/lb when the temperature of the brine was -3 0 C. On the other hand, in the system which used hot gas injection, the compression work generated when the brine was 3 0 C was 25.25 Btu/lb. Further, this gradually decreased to 25.12 Btu/lb when the temperature of the brine was -3 0 C. Based on the results, there had been a 5% decrease of compression work in the system using hot gas injection. The effects of the use of the hot gas injection on the domestic refrigerator result in a smaller ratio of discharge and suction pressures, causing the compression work which compresses vapour from condensing pressure to evaporating pressure becomes shorter. Such results/values will contribute to the energy consumption of the compressor, which becomes smaller. Work of compression (Btu / lb) 27.00 26.50 26.00 25.50 25.00 24.50 24.00 3 2 1 0-1 -2-3 Brine temperature, 0 C Figure 2. The work of compression based on temperature changes of the brine 3.2. Coefficient of performance Figure 3 presents coefficient of performance data (Cop) of two conditions of the domestic refrigerator testing. In the normal system, the Cop decreased along with the decreasing temperature of the brine. At first, the obtained Cop was 2.15 when the temperature of the brine was 3 0 C; the Cop of 2.12 was obtained when the brine temperature was -3 0 C. Coefficient of performance (Cop) 2.35 2.30 2.25 2.20 2.15 2.10 2.05 2.00 3 2 1 0-1 -2-3 Brine temperature, 0 C Figure 3. Acquisition Cop value based on changes in temperature brine 3

Further, when the system employed hot gas injection, Cop increased significantly. When the temperature of the brine was 3 0 C, the obtained Cop was 2.27. Then, the value fluctuated to 2.29 when the brine temperature was -3 0 C. These results indicate that the use of hot gas injection on the refrigeration system results in the increase value of Cop, which is 7%. The great value of Cop indicates that the system worked properly. The value of Cop is influenced by the amount of heat which can be absorbed by the refrigerant flowing in the evaporator (refrigeration effect), and the compression work performed by the compressor when it compressed the low temperature-pressured refrigerant vapour to high temperature-pressured refrigerant vapour. If the value of the refrigeration effect is big and the value of compression work are small, the Cop obtained will be large. The bigger the value of the refrigeration effect and the smaller the value of the compression work, the value of Cop obtained will be better. 4. Conclusions Research on the use of hot gas injection to improve the performance of domestic refrigerators has been conducted. To demonstrate the performance improvement of refrigerators, we tested the refrigeration system in two different conditions. The results indicate that hot gas injection to the suction line generates an increased value of coefficient of performance (Cop) and lowers the temperature discharge. This has a significant implication for the lighter work of the compressor and low electrical power needed by the refrigerator. Acknowledgement The author would like to thank the Rector of UPI for funding this research through PPDKI program 2011-2015, on research scheme penguatan kompetensi. References [1] Sari O, Balli M. From conventional to magnetic refrigerator technology. International Journal of Refrigeration. 2014. p. 8 15. [2] Geppert J, Stamminger R. Do consumers act in a sustainable way using their refrigerator? The influence of consumer real life behaviour on the energy consumption of cooling appliances. Int J Consum Stud [Internet]. Blackwell Publishing Ltd; 2010;34(2):219 27. [3] Ueno T, Sano F, Saeki O, Tsuji K. Effectiveness of an energy-consumption information system on energy savings in residential houses based on monitored data. Appl Energy. 2006;83(2):166 83. [4] Hasanuzzaman M, Saidur R, Masjuki HH. Effects of operating variables on heat transfer and energy consumption of a household refrigerator-freezer during closed door operation. Energy. 2009;34(2):196 8. [5] Tashtoush B, Tahat M, Shudeifat MA. Experimental study of new refrigerant mixtures to replace R12 in domestic refrigerators. Appl Therm Eng. 2002;22(5):495 506. [6] Sekhar SJ, Lal DM, Renganarayanan S. Improved energy efficiency for CFC domestic refrigerators retrofitted with ozone-friendly HFC134a/HC refrigerant mixture. Int J Therm Sci. 2004;43(3):307 14. [7] Wongwises S, Chimres N. Experimental study of hydrocarbon mixtures to replace HFC-134a in a domestic refrigerator. Energy Convers Manag. 2005;46(1):85 100. [8] Sattar MA., Saidur R, Masjuki HH. Performance investigation of domestic refrigerator using pure hydrocarbons and blends of hydrocarbons as refrigerants. Waset. 2007;23(2002):223 8. [9] Mastrullo R, Mauro AW, Tino S, Vanoli GP. A chart for predicting the possible advantage of adopting a suction/liquid heat exchanger in refrigerating system. Appl Therm Eng. 2007;27(14-15):2443 8. [10] Klein SA, Reindl DT, Brownell K. Refrigeration system performance using liquid-suction heat exchangers. Int J Refrig. Elsevier Science Ltd; 2000;23(8):588 96. [11] Cho H, Kim Y, Jang I. Performance of a showcase refrigeration system with multi-evaporator during on-off cycling and hot-gas bypass defrost. Energy. 2005;30(10):1915 30. [12] Dopazo JA, Fernandez-Seara J, Uhía FJ, Diz R. Modelling and experimental validation of the hotgas defrost process of an air-cooled evaporator. Int J Refrig. 2010;33(4):829 39. [13] Yaqub M, M. Zubair S, Khan J-R. Performance evaluation of hot-gas by-pass capacity control 4

schemes for refrigeration and air-conditioning systems. Energy. 2000. p. 543 61. [14] Dutta AK, Yanagisawa T, Fukuta M. An investigation of the performance of a scroll compressor under liquid refrigerant injection. Int J Refrig. 2001;24:577 87. [15] Hu B, Wang X, Cao F, He Z, Xing Z. Experimental analysis of an air-source transcritical CO2 heat pump water heater using the hot gas bypass defrosting method. Appl Therm Eng [Internet]. 2014;71(1):528 35. 5