Orion-Opus LØV-R with Sirius

Similar documents
Orion-LØV LØV-R with Sirius

Orion-PTV LØV-R with Sirius

Orion-LØV LØV-R with Sirius

LØV-R. Svalbard-H. Chilled beam for corner installation between wall and ceiling

CONDOR. Supply air ceiling QUICK FACTS

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

CBC - Active Chilled Beam. Halton CBC. Active Chilled Beam

The swirl comfort unit is a compact air-conditioning unit providing swirl jet air supply.

Homepage > Products > Grilles and Diffusers > Ceiling diffusers > Design ceiling swirl diffusers > Type ADD. Type ADD

CHH - Active Chilled Beam. Halton CHH. Active Chilled Beam

CHILLED BEAM CASSETTE IQ STAR LYRA

iq Star LYRA II chilled beam cassette

Type TDF-SilentAIR WITH VERY LOW SOUND POWER LEVEL FOR COMFORT ZONES, WITH FIXED AIR CONTROL BLADES

TURBO HOODS. Product Brochure

HOTEL CHILLED BEAM IQ STAR SILENCIA

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION

Ceiling diffusers. Type DLQL

Homepage > Products > Decentralised ventilation systems > Vertical units > Type FSL-V-ZAB/SEK FSL-V-ZAB/SEK

Halton Rex 600 Basic R6B - Active chilled beam

Type PWX HORIZONTAL CHASSIS TYPE WATERSIDE FANCOILS FOR CONCEALED OR EXPOSED INSTALLATIONS

Ceiling swirl diffusers

CBH - Active Chilled Beam. Halton CBH. Active Chilled Beam

Ceiling swirl diffusers

Halton Rex for Vario R6O - Variable air volume chilled beam

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

Krantz. Multifunction exposed ceiling AVACS. Cooling and heating systems

UV-TURBO HOODS. Product Brochure

Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU

SERIES FAN VAV TERMINAL BOXES TYPE CVFB & SFTB

Fresh air unit ALB. ALB it s simple and so easy! Air supplied through a heater and filter in a single unit.

iq Star LYRA II chilled beam cassette

TTC. TTC Active supply air diffuser. Product description. Introduction SUPPLY AIR DIFFUSER - ACTIVE [CEILING MOUNTED] Simplicity

System architecture. Air treatment Index

CLN 3 ATTRACTIVE JOINABLE LINEAR PROFILE UP TO 8 SLOT TRACKS AVAILABLE HEATING AND COOLING TERMINAL REHEAT AVAILABLE

Swegon CASA R85. Ventilation unit with rotary heat exchanger HOME VENTILATION

Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU

WOLF VENTILATION SYSTEM PRICE LIST

Heat recovery unit RDKS

Puri-Drall PDK. Puri-Clean PCK. Puri-Inlet PEK. HEPA filter air outlet with pull-down outlet element

TopMaster Air Handling unit. Technical data

Bevent Rasch RABC-VAV. - Fire /03/2018

PARAGON. Compact comfort module. Key figures

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

66 on. Central ventilation system ZLS-DV EC according to DIN Central ventilation system ZLS EXTRACT AIR FIRE PROTECTION OUTSIDE AIR

Ceiling air diffuser INDULTHERM INDULTHERM-e

Units for suspended ceilings

Fan Coil Unit CULTRA

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

SECTION AIR DUCT ACCESSORIES

BSK-RPR Fire Damper. Additional operating instructions according to

CONTROL THE PERIMETER EFFECTIVELY HORIZONTAL/VERTICAL FLOW PATTERN ONBOARD/REMOTE SENSING EXCELLENT THROW & FLOW HEATING AND COOLING CHANGEOVER

Technology for life. Unit heater LH

Polaris-I-60. active chilled beam. the future of space conditioning

ELFODuct MP. Technical Bulletin. New generation horizontal and vertical built-in water-source ductable terminal for medium and large systems

TopMaster Air Handling Unit

KOMFORT EC DB Suspended heat recovery air handling units

Fire dampers. For diverse applications

QTS SELECTION TECHNICAL BOOKLET

TTC. TTC Active supply air diffuser. Product description SUPPLY AIR DIFFUSER - ACTIVE [CEILING MOUNTED] Introduction. Simplicity

Bypass Terminal Units. DUCT VENTILATION AIR CONDITIONING Co. (W.L.L.) BYPASS TERMINAL UNITS

FMC(Z) cartridge filter

EASY VOLUME ADJUSTMENT INCLUDED FLEX CLAMP EXCELLENT THROW & FLOW HEATING AND COOLING TERMINAL REHEAT AVAILABLE

Units for suspended cei lings

Air distribution systems. Rectangular displacement outlet VA-RN... with adjustment device VA-RV...

EASY VOLUME ADJUSTMENT INCLUDED FLEX CLAMP EXCELLENT THROW & FLOW HEATING AND COOLING TERMINAL REHEAT AVAILABLE

Unit heater with accessories

Smoke extraction duct of sheet steel

Product is subject to and complies with Regulation (UE) N.327/2011. cert. n Fan Coil Unit Cassette SkyStar Jumbo ECM. technical catalogue

42AM. Air heaters PRODUCT SELECTION DATA

Others ( 50Hz areas ) ADVANCED SUBJECT DATE: May-08 PRODUCT NEWS. Advanced Product News: Launching of New KPI-(502~2002)E1E & KPI-3002H1E units

Fan heater SWT Ceiling mounted fan heater with water heat

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

EXPAIR. Use. Precision air handling cabinets. Reducted footprint Dual-wall construction

ESAR SMOKE CONTROL DAMPER» TECHNICAL CATALOGUE

Heat Recovery Unit HERU. web-version

ADRIATIC VF. Active chilled beam with cooling, heating and ventilation QUICK FACTS

Premium Efficiency Heat Recovery Unit. D-AHU Modular L. Air Handling Units

Supply air unit VEKA Installation & Maintenance

Axial fans The right fan for every house

Air distribution systems. Opticlean OC-Q...

The Silent Range Pure Elegance & Tranquillity. The widest range of ultra quiet silent fans

KLIMA Active Chilled Beams

PARASOL EX. Suspended comfort modules QUICK FACTS

VEX100 series Air handling units with cross-flow heat exchanger

CONFIGURABLE CROSS-FLOW HEAT RECOVERY UNITS ENERGY-BOX HE

Bevent Rasch BSKC6. - Fire /06/17

ADAPT Parasol EX. Energy-saving, suspended comfort module QUICK FACTS

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

Extraction systems for the electronic industry. Soldering workstations Soldering smoke extraction systems

VAV DIFFUSERS PREVENT DUMPING VAV DIFFUSERS SAVE FAN ENERGY ENERGY SAVING - LOW PRESSURE LOSS REHEAT, OCCUPANCY, FLOW MEASUREMENT

Series VENTS VUT R WH ЕС

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

Cooling Strip Model SPB

Fire damper actuators. Selection and integration.

TECHNICAL MANUAL YEFB HIGH PRESSURE DUCTED UNIT

CONTENTS. Page 1. THE DRYPAC SYSTEM - CUSTOM MADE 1 2. PRINCIPLE OF OPERATION 2 3. CONTROLS 4 4. FLEXIBILITY 6 5. DRYPAC OPTIONS 7

TECHNICAL SPECIFICATION

THERMA FUSER SIDEWALL LINEAR VAV DIFFUSER

BKA-EN Fire Damper. Additional operating instructions according to

Transcription:

GB0653 09.17 Orion-Opus LØV-R with Sirius VAV box for supply diffuser Unique damper function Extensive working range Belimo MP-Bus Modbus LONWORKS Belimo KNX TROX Trox Norge AS PO Box 100 NO-2712 Brandbu Telephone +47 61 31 35 00 Fax +47 61 31 35 10 e-mail: firmapost@auranor.no www.trox.no

APPLICATION Orion-Opus with Sirius is a diffuser unit with VAV function, and is used as volume flow controller and diffuser in ventilation systems to enable air flow rates to be set as per requirements. Orion-Opus offers excellent induction, and is ideal for variable air flow rates. FUNCTION Orion-Opus with Sirius has a built-in VAV controller for adjustment of air flow rate. The damper solution will choke the pressure at high flow rates and will maintain a low sound level. This may reduce the need for additional dampers and sound attenuators in a duct system. Orion-Opus with Sirius is delivered with Belimo MP-Bus, LON, Modbus or belimo KNX for direct BUS communication to SD systems. Deviation for working range 10-20% of V nom :±25% 20-40%: of V nom <±10% 40-100%: of V nom <±4% If T-pipes are used, a spacing of at least 5 x ØD is recommended in order to maintain the measurement accuracy. The diffusor front can be supplied with integrated motion sensor. Product sheet for Motion sensor can be found on our website: www.trox.no ORDER CODE, diffuser - Orion-Opus Sirius Orion-Opus-Sirius R TA B 200 0 Nozzle settings, front: SL=Special finish Dim: Ø200,Ø250,Ø315,Ø400 R = Rotation 1 = 1-way 2A = 2-way 180 2B = 2-way 90 B=Motion sensor Modular ceiling system: TA=A-flange DC=Dampa Clip-In DG=Dg-flange DS=Ds-flange EK 24=E-flange-T24 EK 15=E-flange-T15 Orion-Opus-Sirius-R-TA-B-200/0 Explanation: Orion-Opus-Sirius supply diffuser with rotational nozzle setting at front. A flange for T-profile ceiling system, motion sensor diffuser front, spigot Ø200 ORDER CODE, Sirius DESIGN Orion-Opus with Sirius is a complete measuring and control unit where the air flow rates in ventilation systems can be set as required. At the measuring station, the differential pressure is measured by using measuring rods integrated in the unit. Sirius is equipped with LHV-D3 VAV controller from Belimo. Controller specifications are provided in the table below. Full technical documentation can be downloaded from www.belimo.eu. Orion-Opus with Sirius features a removable front panel, and is available with 4 different nozzle settings: rotational, 1-way, 2-way 180 or 2-way 90. It is suitable for a range of ceiling systems. Dim: 125-200 160-250 200-315 250-400 Sirius - 125-200 - 1 Connection: 0 = MP-Bus 1 = MP-Bus with Winsta plug 2 = LON-Bus 3 = MOD-Bus 7 = Belimo KNX 8 = MOD-Bus for XAC 9 = MOD-Bus for XAC-ZM Actuator LHV-D3-MP/MOD/LON Operating voltage AC 24 V 50/60 Hz, DC 24 V Power drain 2,5W Dim. effect 4.5VA (max.8 A @5 ms) Sirius-125-200-1 Explanation: Sirius with Ø125 inlet and Ø200 outlet, with MP-Bus with Winsta plug. Table 1: Technical specifications, Belimo VAV controller MATERIALS AND SURFACE COATING Sirius comes in a galvanised steel design. The measurement unit is in aluminium, and hoses and nipples are in plastic. The damper is equipped with polyester material, and the connection collar is fitted with EPDM rubber gasket 2 2

QUICK SELECTION, Orion-OPUS with Sirius [Open] m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 175 221 280 160 306 367 440 200 374 446 529 250 478 575 692 (75Pa) m³/h Sirius dim. 25dB(A) 30dB(A) 35dB(A) 125 158 223-160 252 353 432 200 360 450 558 250 360 526 677 Table 2: Quick selection, Orion-Opus with Sirius DIMENSIONS AND WEIGHT, Orion-Opus with Sirius Dim. D DA B H L L1 Weight Weight Sirius Sirius with valve [kg] [kg] 125-200 124 202 325 175 645 386 8 12 160-250 159 252 360 210 645 402 9 13 200-315 199 317 400 240 645 435 10,5 14,5 250-400 249 402 450 290 645 392 12 16 Table 4 Sirius (m³/h) ØD. Minimum Maximum 125 26 265 160 43 434 200 70 700 250 106 1060 Table 3: Adjustment range for VAV controller, air flow rate in m3/h. See calculation diagram for sound power level and pressure drop. ORDER CODE, Orion-Opus with Sirius Fig. 1: Dimensions, Orion-Opus with Sirius Orion-Opus-Sirius R TA B 200 SK 0 SL=Special finish Nozzle settings front: R = Rotational 1 = 1-way 2A = 2-way 180 2B = 2-way 90 Modular ceiling system: TA=A-flange DC=Dampa Clip-In DG=Dg-flange DS=Ds-flange EK 24=E-flange-T24 EK 15=E-flange-T15 B=Motion-sensor Dim: Ø200 Ø250 Ø315 Ø400 SK - 125-200 - 1 SK=Sirius Inlet - outlet 125-200 160-250 200-315 250-400 Connection: 0 = MP-Bus 1 = MP-Bus with Winsta plug 2 = LON-Bus 3 = MOD-Bus 7 = Belimo KNX 8 = MOD-Bus for XAC 9 = MOD-Bus for XAC-ZM Orion-Opus-Sirius-R-TA-B-200-SK-125-200-1/0 Explanation: Orion-Opus-Sirius supply diffuser with rotational nozzle setting at front, A flange for T-profile ceiling system, motion-sensor at front, spigot Ø200, Sirius box inlet Ø125 and outlet Ø200, with MP-Bus with Winsta plug. 3 3

ACOUSTIC DATA The diagrams provide a summary of the A-weighted sound power level from diffuser, L WA. Correction factors in table 5, page 5, are used to calculate emitted sound power level at the respective frequencies, L W = L WA + KO. A room with absorption equivalent to 10m² Sabine will have a sound pressure level which is 4 db below the sound power level emitted. Sirius 160 with Orion-Opus supply diffuser, desired volume flow 90 l/s. From diagram 2, we find that L WA = 27 db(a) with open damper and 45 Pa total pressure drop. The aim is to find the following data: a) Emitted sound power level at 250 Hz with open damper. b) A-weighted total sound pressure level from diffuser in an office with 4dB room attenuation. c) A-weighted sound pressure level in an office at 75 Pa total pressure loss, i.e. 20 Pa choking with the unit s damper. a) The correction factor for 250 Hz is -0 db. Emitted sound power at 250 Hz is then: L W = L WA + KO = 27 + 0 = 27 db b) With room attenuation equivalent to 4 db, A-weighted sound pressure level is: 27-4 = 23 db(a) c) At the operating point of 90 l/s and 75 Pa total pressure loss, the diagram indicates 28dB(A). With 4dB room attenuation the sound pressure level in the room will be: 28-4 = 24 db(a) CALCULATION DIAGRAM Diagram 1, Orion-Opus w/sirius Ø125 Diagram 2, Orion-Opus w/sirius Ø160 Diagram 3, Orion-Opus w/sirius Ø200 Diagram 4, Orion-Opus w/sirius Ø250 4 4

Right pressure drop line (open) KO [db] Left pressure drop line (heavily choked) Sirius dim. 63 125 250 500 1k 2k 4k 8k 63 125 250 500 1k 2k 4k 8k 125 7 3 1-3 -7-13 -12-8 3-6 -7-13 -10-9 -4-7 160 7 3 0-2 -6-13 -13-10 3-2 -4-7 -7-9 -7-7 200 6 4-1 -3-5 -13-13 -10 2-1 -2-5 -5-11 -9-8 250 5 3-1 -2-5 -15-14 -9 3 1-1 -3-6 -12-10 -7 Table 5: Correction factor, Orion-Opus with Sirius THROW LENGTH FLOW PATTERN Diagram 5, Orion-Opus with Sirius - throw length Fig. 2: Flow pattern - Orion-Opus - 1-way Orion-Opus with Sirius Attenuation [db] Dim. 63 125 250 500 1k 2k 4k 8k 125 21 9 13 18 12 11 12 17 160 17 6 10 15 11 11 12 17 200 13 5 11 12 10 10 12 16 250 14 4 12 9 10 10 12 15 Table 6: Static sound attenuation incl. end reflection, Orion-Opus with Sirius 450 400 125 160 200 250 Fig. 3: Flow pattern - Orion-Opus - rotation 350 300 Pt(Pa) 250 200 150 100 50 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 q (l/s) Diagram 6, Sirius, leakage at closed damper 5 5

INSTALLATION The Orion-Opus diffuser can be installed in a range of modular ceiling systems as well as in fixed ceilings. Sirius is attached by means of threaded rod or strap (fig. 5). In order to maintain the system s measurement accuracy, it is important to install units with spacing as shown in fig. 6. A A-kant flange Dampa Clip-In DG Dg-kant flange COMMISSIONING Orion-Opus with Sirius uses Belimo PC-tool or ZTH-GEN in order to make the requisite adjustments. MAINTENANCE No specific maintenance requirements.. ENVIRONMENT Enquiries regarding product declaration can be directed to our sales team, or information can be found at our website: www.trox.no DS Ds-kant flange E E-kant flange T24/T15 Fixed Fast himling ceiling Fig. 4: Installation Fig. 5: Installation Orion-Opus with Sirius is developed and manufactured by: Fig. 6: Installation The company reserves the right to make amendments without prior notice. www.tintkom.no 6 6 Head Office: TROX Auranor Norge AS, PO Box 100, NO-2712 Brandbu Telephone: +47 61 31 35 00 Fax: +47 61 31 35 10 www.trox.no 6