EC3-X33 Stand-alone Superheat Controller Technical Data

Similar documents
EC3-X33 Stand-alone Superheat Controller

EC2-5x2 Series Condensing Unit Controllers

EXD-HP1/2 Stand-alone Superheat/Economizer Controller

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

Emerson Superheat Control. The smart solution for your application

EXD-SH1/2 Controller for EX/FX/CX with ModBus Communication Capability

OPERATING MANUAL Enertronic Control System 2

Danfoss gas detection units

Controller for operation of evaporator on water chiller EKD 316

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Process Alarm Module RTA 421

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

OPERATING MANUAL Enertronic Control System 2

Danfoss gas detection units

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

30GT FLOTRONIC AIR-COOLED CHILLERS

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Oxygen (O2) Single-Point Gas Detection System

Danfoss gas detection unit Type GD Heavy Duty

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Two-Channel Gas Controller

precision controlled industrial process chillers cooling capacity: ,255,668 BTU /hr ( tons) improved productivity & reduced costs

AE R1 October to 5 Ton ZPS*K6 Copeland Scroll Two-Stage Compressors

Bulletin , March Electric Hot Gas Bypass Valves

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

Air-Cooled Condensing Units with Compact Screw Compressors

Temperature Controllers

30GN FLOTRONIC II AIR-COOLED CHILLERS

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

MicroTech Series-200 Flooded Screw Chiller

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

ECO N DATE DESCRIPTION OF CHANGE CHG

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

ER65 - Mini Rack Controller Electronic Refrigeration Line

Analog Room Pressure Monitor RPC Series

Multi-Gas-Controller MGC2

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301

UDC100 Universal Digital Controller Specifications

Rectifier RC-series. Manual RC-series English MA doc. Manual Wall and 19 English

Air-Cooled Variable Speed Drive Screw Chillers. Super Efficient Super Quiet. Cooling Capacity Range kw R134a

DC 60 & DM 60 displays

Digital regulator for refrigeration and defrosting, 3 relays.

Process & TeMPerATUre UniversAl input DigiTAl MeTers

02/11/2015

AH3000 SERIES 180MM CHART PEN TYPE HYBRID RECORDER

WESTERN HTDM 90+ OMEGA 91% & 95% EFFICIENT INDIRECT FIRED HEAT EXCHANGER UP TO 60:1 TURNDOWN HEAT ONLY & HEAT / COOL UNITS

INSTALLATION & USER MANUAL

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

User Manual. Dryer Controller M720

WIO200 Water In Oil measuring instrument

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

I/A Series 716C 1/16 DIN Temperature Controller

Dryer Controller M720

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

User Manual Ichill 200 L/D (Firmware version 1.7)

WALLACE & TIERNAN CONTROLLERS & ANALYSERS CHEMTRIM DISINFECTION CONTROLLER PRODUCT SHEET

02/11/2015

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Chapter-8 Capacity Control of Refrigeration Systems

ROYCE SUSPENDED SOLIDS SYSTEM MODEL 7011A AND SENSORS MODELS 72A, 72P, 73B, 74A, 75A & 76A

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Model 1062 Environment Monitor

Intelligent addressable fire alarm control panel

Refrigerant valves. Valves for precise control and optimum energy efficiency in refrigeration systems. Answers for infrastructure.

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

ETO 2 - Controller for ice and snow melting

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

ET10 Series Stand-alone LCD Fan Coil Thermostat

Specification , July 2015

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

Controller for evaporator control AK-CC 750

Precise Temperature Control; Compact Footprint

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

Refrigeration Systems and Accessories

MAC N-407 Air-Cooled Chiller

Software Version 2.01 LEVEL MONITOR MODEL 220

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

The Book of AERMEC NRL Sequence of Operation

MicroTech Series 200 Centrifugal Chiller

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

Corporate Profile. needs and product demands. CON 08X /03 Rev 0

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

food-retail.danfoss.com Overview Brochure ADAP-KOOL Evaporator Controllers Achieve best-in-class energy efficiency and food safety

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

Inverter scroll compressors VZH

AL3000 SERIES 100MM CHART MULTI-POINT TYPE HYBRID RECORDER

Inverter scroll compressors VZH hybrid manifold

3.2 E1 Outdoor Unit PCB Abnormality E4 Actuation of Low Pressure Sensor E5 Compressor Motor Lock 3 52

Heat Link. Technical Guide

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

Gas Controller Module GC-06

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Parts introduction FRONT BACK

Dual Column Dehydrating Breather Manual

Transcription:

Technical Data EC3-X33 is a stand-alone universal superheat controller for air conditioning, refrigeration and industrial applications such as chillers, industrial process cooling, rooftops, heat pumps, package unit, close control, cold room, food process and air driers. The optional ECD-002 Display/keypad Unit is necessary for setup but not for operation of the controllers. ECD-002 can be connected or disconnected to EC3-X33 at any time. Features EC3-X33 Superheat control in conjunction with Emerson stepper motor driven Electrical Control Valves EX4 EX8 Limitation of evaporating pressure (MOP) Low superheat alarm Feed through of 4 20mA signal from evaporator pressure sensor to analogue output. This may also be connected to pressure input of any other controller to avoid need for multiple pressure sensors Monitoring of sensors and sensor wiring and detection of sensor and wiring failures Intelligent alarm management in order to protect the compressor i.e fail safe operation Integral rechargeable battery to close Electrical Control Valve in case of power loss Electrical connection via plug-in type screw terminals Aluminum housing for DIN rail mounting EC3-X33 with ECD-002 Features ECD-002 2½ digit LED display with automatic decimal point Indicator LEDs for valve opening/closing, external demand and alarm Connection to EC3 Series via ECC-Nxx or standard CAT5 patch cord with RJ45 connectors Typical ordering package: Description Type Emerson PCN Part No. Superheat Controller EC3-X33 097707 807 783 Terminal kit K03-X32 097709 807 644 Temperature sensor ECN-N60 097714 804 497 Electrical Control Valve EX4, EX5, EX6, EX7 or EX8 * * * Pressure sensor for R-22/R-124/R-134a/R-404A/R-407C/R-507C for R-410A for R-744 PT5-07M PT5-18M PT4-30M 097748 097749 097728 802 350 802 851 802 334 Plug and cable assembly for pressure sensor PT4-M60 097717 804 805 *For further details refer to: EX4, EX5, EX6, EX7, EX8 Electrical Control Valves datasheet FC-TD/ EX4-8 Accessories (required for setting at start-up only): Description Type Emerson Part No. PCN Optional display/keypad ECD-002 097712 807 657 Cable connection between EC3-X33 and ECD-002 ECC-N30 or any standard Cat 5 patch cord with RJ45 connectors 097713 807 861 Replacement Battery for EC3 097693 807 790 Application EC3-X33 as superheat controller can be applied for the following: Superheat control of conventional evaporators such as shell and tube, plate heat exchanger, air coil etc. Superheat control of subcoolers or economizers connected to suction pressure of compressor or intermediate pressure of screw/scroll compressors having vapor or liquid injection connection Superheat control of intermediate gas in two stage compressors Superheat control of suction gas in conjunction with hot gas bypass Superheat control of flooded evaporators FC-TD/ EC3-X33 1 / 6 July 2011

Introduction The EC3-X33 controls the opening of an electrical control valves according to desired superheat. As Emerson Electrical Control Valves (ECV) are able to a provide positive shut-off function better than conventional solenoid valves, there will be no flow through Emerson ECV as long as the compressor is not running. In the event of cooling request and compressor startup, EC3-X33 needs to be informed. This can be achieved by a digital input. EC3-X33 will start to control the refrigerant mass flow stand alone by precise positioning of the ECV under different operating conditions such as compressor start-up, start of further compressor, high head pressure, low head pressure, high load, low load and partial load operation. EC3-X33 is capable for diagnostics and alarm. The alarm can be received via relay output as well as optical LED/alarm code on ECD-002. Algorithm The superheat control algorithm is self-adapting, so that it automatically adjusts itself to the characteristics of the evaporator at regular intervals. This guarantees optimal superheat control performance for different types of evaporators, as well as when the operating conditions of the evaporator change over time. Superheat Control function By receiving two measured values from Emerson pressure sensor PT4 and Emerson temperature sensor ECN-N60, EC3- X33 calculates the actual superheat and compares with preset superheat. EC3-X33 operates the Electrical Control Valve in order to keep superheat at desired setpoint under various operating conditions. The superheat setpoint is adjustable between 6 F and 60 F. If low superheat alarm function is disabled, it is possible to adjust the superheat set point below 6 F down to 1 F for special applications such as flooded evaporators. MOP function To avoid overload of the compressor motor, the MOP function of the EC3-X33 limits the evaporating pressure to a predetermined value. This can be adjusted to match the safe operating envelope of the compressor. MOP setpoints are entered as saturation temperature values to match published safe operating data of compressor manufacturers and to avoid unnecessary manual conversions from temperature into pressure values. The MOP function may be totally disabled, when not needed. Low superheat alarm Liquid flooding may lead to serious damage of compressors and must be avoided. The built-in low superheat alarm function of the EC3-X33 detects low superheat conditions and deactivates the alarm relay. If the alarm relay is wired into the serial safety loop, the compressor will be switched off when a low superheat alarm occurs. Digital input status The digital input is the interface between EC3-X33 and system controller. The digital status depends on the system s compressor/thermostat. Commander Operating condition Digital input status Compressor Compressor starts Closed / 24V (Start) Compressor stops Open / 0V (Stop) Thermostat Demand (compressor Closed / 24V (Start) must be ON) No demand Open / 0V (Stop) Shut-off function When digital input is open (0V), the EC3-X33 will drive the electrical control valve to the closed position. Due to the positive shut-off capabilities of the EX4/5/6/7/8 valves a separate liquid line solenoid valve is not required. The shut-off function is guaranteed in case of power loss due to built-in internal battery. Analogue output (4-20mA signal) function EC3-X33 requires the outlet pressure level of the evaporator for superheat and MOP control. The output signal from PT4 is used by EC3-X33 and again provided as a 4...20mA signal (galvanized) for the connection to any other third party controller, which can receive a 4...20mA signal. Please see the wiring diagram for more details. If the system controller does not have the capability of using this signal, the terminal will not be wired to any other device. Pump down function Emerson Electrical Control Valves can be driven to close position while the compressor is running for pump down function. There are two possibilities to achieve this function: 1) The valve will be driven to close position by interruption of the digital input. The compressor can be turned off by a pressure switch and / or a timer. 2) By using 4 to 20 ma analogue output connected to system controller. In both cases, the initiation and termination of pump down is under the system controller functionality/responsibility. Safety / internal battery function In the event of a power failure to the entire system, a stepper motor driven valve would not be able to move. Due to the differential pressure between condenser and evaporator, the refrigerant would continue to flow through the valve if the valve is open. The compressor must be protected after power recovery against flood- back. The EC3-X33 contains an internal rechargeable battery and smart battery charge control. Optimum battery life is achieved through temperature compensated charge cycles. Alarm and maintenance functions EC3-X33 provides several alarms to facilitate diagnosis as well as shut down of compressor/system if the alarm relay is wired into the serial safety loop. Built-in diagnostic routines constantly monitor battery health and sensors the Electrical Control Valve and the associated wiring for open and short circuits. When such errors are detected, the controller goes into an alarm condition and closes the valve. In addition to hardware errors, the EC3-X33 will monitor the minimum operating superheat. If the superheat drops below 1 F for a continuous period of one minute, the low superheat alarm will occur. The low superheat alarm can be disabled for applications such as a flooded evaporator, where a lower operating superheat is required. In the case of an alarm, the EC3-X33 will close the valve, and the alarm relay will be deactivated. Alarm codes such as alarm LED will be available if the optional display/keypad, ECD-002, is connected to EC3-X33 All alarms are automatically cleared after correction. Battery alarm and low superheat alarm can be modified for manual reset. Alarm relay function Alarm relay contains a SPDT contact. If the relay is wired to the system controller, it is possible to stop the compressor/system. The alarm relay is activated during normal operation and FC-TD/ EC3-X33 2 / 6 July 2008

deactivated during alarm conditions such as supply power interruptions. Start-up configuration function Built-in valve opening (%) at start-up for a certain period of time helps the compressor s start-up and prevents erratic low pressure cut-out for the following cases: Operation of systems with air cooled condensers in low ambient temperatures Compressor start-up after a long standby time in a low ambient environment Start-up of very large single stage compressor capacity Emerson Pressure Sensor PT4 function The pressure sensor measures the saturation pressure at the outlet of the evaporator. The output signal is 4 to 20 ma corresponding to a pressure range. Based on the type of refrigerant and system, different types of pressure sensors are needed. PT4-07M for evaporators operating with refrigerants R- 22/R-124/R-134a/R-404A/R-407C PT4-18M for evaporators operating with R-410A PT4-30M for evaporators operating with R744 Every type of pressure sensor is calibrated in a temperature range for the above specified applications. The feature set and performance of the PT4 Series is a perfect match for the EC3- X33. Other pressure sensors are not released for use with EC3-X33 and when applied, may lead to poor performance. Emerson temperature sensor ECN-N60 The temperature sensor measures the refrigerant temperature at the outlet of the evaporator. It is important to use only this particular temperature sensor because the ECN-N60 has the right performance such as desired time constant and tolerance compensation within the specific working range. The use of other temperature sensors is not recommended. The sensor is hermetically sealed for high reliability and long lifetime and has metal housings for optimal thermal conductivity. Optional ECD-002 display/keypad unit The ECD-002 is required to set a parameter during start-up. After completion of start-up, it may be left connected or removed from EC3-X33. The display unit can be switched from K/bar/ C to R/psig/ F. Indicator LEDs show the status of valve opening, valve closing, demand and alarm. Blinking: Valve is opening ON: Valve is fully open Blinking: Valve is closing ON: Valve is fully close ON: Demand OFF: No demand ON: Alarm OFF: No alarm Parameters setting/saving Next parameter/value (higher) Wiring Diagram A: White wire B: Black wire C: Blue wire D: Brown wire E: Plug cable assembly EX5-Nxx for connection to EX4/EX5/EX6/EX7/EX8 F: Remote control panel, system controller G: Alarm relay, dry contact. Relay coil is not energized at alarm condition or power off H: Digital input (0V/open = Stop; 24V/closed = Start) I: Transformer Class II, 24VAC secondary / 28VA J: Third party controller (can use the analog output signal from EC3) Note: The internal resistor of a third party controller must fulfill the following conditions: Supply voltage 12VDC: R 200Ω Supply voltage 24VDC: R 800Ω Manual reset for blinking alarm codes (press 5 sec together) Selecting/confirming Next parameter/value (lower) FC-TD/ EC3-X33 3 / 6 July 2008

Ordering, main parts Description Type Part Code Nr. Controller EC3-X33 EC3-X33 807 783 Terminal Kit for EC3-X33 K03-X32 807 644 Pressure Sensors -11.6 101.5 psi 0 261.1 psi 0 435.1 psi PT4-07M PT4-18M PT4-30M 802 332 802 333 802 334 Cable Assembly for PT4 20 ft cable length PT4-M60 804 805 NTC Temperature sensors 20 ft cable length ECN-N60 804 497 Display/keypad unit (need for set-up only) ECD-002 807 657 Connection cable EC3 to ECD-002 10 ft ECC-N30 807 861 Ordering, accessories, spare part Transformer Emerson PCN Type Part Code Nr. Primary:120/208/240VAC 60 Hz Secondary: 24V 40VA 097724 T2 90-T40F3 Suitable valves for connection to EC3-X33 Valve Capacity range Tons * EX4 0.6 5.7 EX5 1.4 14.2 EX6 3.4 34.1 EX7 10 93.8 EX8 25.6 250.2 EX4 0.6 6 EX5 1.4 15.1 EX6 3.7 35.8 EX7 10 98.7 EX8 28.4 263 EX4 0.6 4.3 EX5 1.1 11.1 EX6 2.8 26.4 EX7 7.1 72.5 EX8 19.9 193.4 EX4 0.6 4 EX5 1.1 10 EX6 2.6 23.9 EX7 6.8 65.4 EX8 17.6 174.3 Refrigerant R-22 R-407C R-134a R-404A/ R-507 Capacity regulation 10-100% Valve Capacity range Tons* EX4 0.9 6.5 EX5 1.7 16.5 EX6 4 39.8 EX7 11.4 109.5 EX8** 28.4 292 EX4 1.1 11.7 EX5 2.8 29 EX6 7.1 69.4 EX7 19.9 190.8 EX8** 51.2 508.7 EX4 0.3 3.1 EX5 0.9 8 EX6 1.7 19.1 *) Nominal rating conditions: Refrigerant Refrigerant R-410A R-744 R-124 Evaporating Temperature Capacity regulation 10 to 100% Condensing Temperature R-22, R-134a, R-404A, R-407C, R-410A +39.2 F +100.4 F R-23-76 F -13 F R-744-40 F 14 F R-124 68 F 176 F **) MWP: 508 psi FC-TD/ EC3-X33 4 / 6 July 2008

Technical Data EC3-X33 ECD-002 Display Unit Supply voltage 24VAC ±10%, 50/60Hz Supply From EC3 Series Controller via connecting cable Digital input 24V AC ±10%, 50-60HZ 24V DC ±10% LED indicators Valve opening, valve closing, alarm, demand Power consumption Internal battery charging time 25VA max. including connected ECV and display/keyboard Approximately 2 hours if battery is fully empty Plug-in connector size Removable screw version wire size 12-20 AWG Display LED Numeric segmental display, 2½digits, red, with automatic decimal point betw. ±19.9, switchable between C and F Connecting cable ECC-Nxx or standard CAT5 patch cord with RJ45 connectors Temperature storage operating -4 +149 F +32 +140 F Ground connection 1/4 in spade earth connector Humidity 0 80% r.h. non condensing Applied directive EMC LVD EN 61326, EN 50081, EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN Protection class IP 65 (front protection with gasket) RoHS 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11 Marking CE Weight ~ 1.8oz Protection class IP 20 Mounting Panel mount (2.8 x 1.1 in cutout) Vibration 4g, 10-1000Hz Temperatures storage operating Humidity Protection class Weight Mounting -4 +149 F +32 +140 F 0 80% r.h. non condensing IP20 ~28.2oz DIN rail mounted Input and Output, EC3-X33 Controller Description Temperature input Pressure sensor input Analog output (evaporating pressure fed-through signal) Digital input Output relay Stepper motor output Connection to ECD-002 List of adjustable parameters Superheat set point Low superheat function MOP function and set point Type of refrigerant and required pressure sensor Type of Electrical Control Valve Valve start opening and duration Unit conversion Value to display Battery error management Password Specification ECN-N60 10k @ +77 F, Range: -58 +122 F PT4-07M/18M 24VDC, 4 20mA 4 20mA Requires 12 or 24 VDC 0/24 VAC/DC SPDT contacts, AgCdO, 24VAC/DC Inductive 2Amp, Resistive 8 Amp For EX4 EX8 Electrical Control Valves RJ45 FC-TD/ EC3-X33 5 / 6 July 2008

Dimensions (in) EC3-X33 Controller ECD-002 Display Unit Emerson is not to be held responsible for erroneous literature regarding capacities, dimensions, applications, etc. stated herein. Products, specifications and data in this literature are subject to change without notice. The information given herein is based on technical data and tests which Emerson believes to be reliable and which are in compliance with technical knowledge of today. It is intended only for use by persons having the appropriate technical knowledge and skills, at their own discretion and risk. Since conditions of use are outside of Emerson control we can not assume any liability for results obtained or damages occurred due to improper application. This document replaces all earlier versions. www.emersonclimate.com/flowcontrols 11911 Adie Road P.O. Box 411400 St. Louis, MO 63141 USA CUSTOMER SERVICE (314)-569-4666 FC-TD/ EC3-X33 6 / 6 July 2008