Temporary LPG Heat for Construction Sites Work At Risk and Inspection Information Packet

Similar documents
Temporary LPG Heat for Construction Sites Information Packet

North Liberty Fire Department Permit Application Temporary Storage & Use of LPG

Department of Public Safety

MOBILE FOOD VENDING Food Trucks & Trailers

Minimum Information Required to Process your Special Occasion Application. Parking area Access to site

Tents and Temporary Membrane Structures Permit Procedure

Tents and Temporary Membrane Structures Packet

SOUTH CAROLINA LIQUEFIED PETROLEUM GAS PROGRAM (LP-GAS)

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

Outdoor Festival and Special Event Guidelines

FIRE DEPARTMENT PERMIT GUIDELINES

Note: The event coordinator is responsible for compliance of all regulations.

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

SEMINOLE FIRE DEPARTMENT TENT PERMIT CONDITIONS

TENTS AND TEMPORARY MEMBRANE STRUCTURES PERMIT PROCEDURE

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

CHRISTMAS TREE LOT INFORMATION & REQUIREMENTS

Note: The event coordinator is responsible for compliance of all regulations.

SafetyNet FIRE MARSHAL S OFFICE. Food Booth and Vendor Regulations

All temporary special events held within the City of Orlando must be approved and inspected by the Orlando Fire Department prior to holding the event.

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

VENDOR AGREEMENT PACKET

OUTDOOR FIREWORKS DISPLAY

Mobile Food Units. A definition of mobile food unit added in OFC Rule 2 is as follows:

CORPUS CHRISTI FIRE PREVENTION MOBILE FOOD VENDOR REQUIREMENTS

To expedite the plan review and inspection processes, please refer to the information below.

GUIDELINES FOR INSPECTING GROUND BASED SPARKLING DEVICE (GBSD) RETAIL SALES FACILITIES

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

West Norriton Township

ksnow Model Rocket Launches Information Packet Colorado Springs Fire Department Division of the Fire Marshal

Exhibits and Trade Shows Permit Application

SPECIAL EVENTS INSTRUCTIONS AND REQUIREMENTS Must apply at least 2 weeks PRIOR to Event Date

Fire Safety Plan Information. For Construction and Demolition Sites

South Davis Metro Fire Agency

Dear Exhibitor, To assist in th. and safety issues that you may encounter with your booth.

ARKANSAS FIRE PROTECTION LICENSING BOARD ACT 743 OF 1977

Impairments to Fire Protection Equipment

South Elgin & Countryside Fire Protection District

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

Community Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007

Changes for the New Edition. Senior Engineer, NFPA NFPA

C i t y o f G r o v e r B e a c h ADMINISTRATIVE SERVICES DEPARTMENT

Jefferson Cocke County Utility District Marketing Plan (July 1, 2008 through June 30, 2019) Revised effective July 01, 2016 A) Identify commercial

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

CITY OF TOLEDO. Paula Hicks-Hudson. MAYOR Our Division s web-site can be accessed 24/7 at

ADMINISTRATIVE ORDER # CERTIFICATES OF USE AND OCCUPANCY FOR EXISTING BUILDINGS

GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE

Fire and Life Safety Requirements San Mateo City Special Events

30 DAY TEMPORARY TENT APPLICATION ON EXISTING COMMERCIAL PROPERTY

Oklahoma. 265: Incorporated national codes and standards The following national codes and standards are incorporated by reference:

CITY OF TOLEDO. MICHAEL P. BELL MAYOR Our Division s web-site can be accessed 24/7 at

CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION FIREWORKS 1.4G RETAIL STORAGE, DISPLAY, AND SALE

EXCELSIOR FIRE DISTRICT

FIREDEPARTMENT REGULATIONS AND GUIDELINES

FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD

ATTACHMENT B FIRE CODE REQUIREMENTS FOR EXHIBITS AND SPECIAL EVENTS

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

DATE: CHECK AMOUNT: CHECK NUMBER: RENEWAL APPLICATION. COMPANY CERTIFICATE OF REGISTRATION And INDIVIDUAL LICENSE RENEWAL

Township of Upper Providence Office of the Fire Marshal

Brighton Fire Rescue District

City of Leduc Fire Services Indoor Special Event Requirements

(d) (e) Section Dry cleaning. Section Exhibits and trade shows

REGULATIONS FOR OUTDOOR GATHERINGS AND EVENTS TENTS & MEMBRANE STRUCTURES

EXAMPLE FIRE PREVENTION AND PROTECTION PLAN WORKSHEET

Medical Gas and Vacuum Systems

with permit. and date. Signature: y including Water Heating Heaters Address: Permit Number CF 1R ALTT Climate Zone 12 Water Heater Type/Fuel 1,2

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS

SALT LAKE OFF-ROAD EXPO 2018 Sponsor Information Friday-Saturday April 27 th & 28 th 2018 South Towne Expo Center Hall 5 Off-Roaders Unite!

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

THE TOWNSHIP OF CRANBURY

Builders Risk - Fire Prevention Inspection Checklist

FIRE PREVENTION CODE

HEALTH DEPARTMENT Environmental Health, Mosquito Control, Neighborhood Protection, Stormwater, and Animal Services

Demolition Permit Application (Please print and complete ENTIRE form)

PLACES OF ASSEMBLY CHAPTER 17

FORM MUST BE SIGNED AND RETURNED FOR VENDOR PARTICIPATION

Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa

Saturday, September 29, 2018

Brandon Fire and Emergency Services

Above Ground Fuel Tank Requirements

CITY OF PETALUMA FIRE DEPARTMENT. FIRE PERMIT AND HAZARDOUS MATERIALS (CUPA) FEE SCHEDULE (September 2002)

9S / 9E Inspection Worksheets. The fire department should complete the following sheets prior to inspection date

Residential Rebate Program Available to NYSEG and RG&E residential natural gas and electric customers.

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

CITY OF DANIA BEACH Local Business Tax Receipt Division 100 W Dania Beach Blvd. Dania Beach, FL Phone: ext 3644 / Fax

REQUIREMENTS FOR TENTS, CANOPIES & MEMBRANE STRUCTURES

FIRE DEPARTMENT SYSTEM PERMIT APPLICATION

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

ST. LUCIE COUNTY FIRE DISTRICT FIRE PREVENTION CODE

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau. Permit fees shall be assessed in accordance with the Permit Fee Schedule

Welcome to the Keys to a Successful Fire / Life Safety Inspection and Sustained Tenant & Building Safety

Family Foster Home Fire Safety Evaluation Checklist Instructions


THE MAURITIUS FIRE AND RESCUE SERVICE ACT. Regulations made by the Minister under sections 18, 19 and 27 of the Mauritius Fire and Rescue Service Act

Transcription:

Temporary LPG Heat for Construction Sites Work At Risk and Inspection Information Packet Colorado Springs Fire Department Division of the Fire Marshal December 2013 W:\Packets\Haz Mat\IFC2009_Work_At_Risk_Temp_LPG_Heat DEC2013.doc

TEMPORARY LPG HEAT The CSFD Office of the Fire Marshal has implemented a Temporary LPG Heat- Work At Risk program in order to assist propane contractors with facilitating an efficient response to a client that requests an LPG-fueled temporary heating assembly for a construction site on short notice. This program allows a propane contractor to obtain a Work At Risk Permit to install such an assembly upon receipt of the permit without the need to wait for a CSFD OFM inspection of the assembly and site prior to use. The fees for this permit and inspection shall be assessed in accordance with the CSFD Permit Fee Schedule and the permit/inspection fees shall be due upon receipt of the permit. The permit shall be applied for, paid for and obtained (and the inspection scheduled) the next business day following installation. This program is subject to the provisions as outlined in this packet. PERMIT APPLICATION Any application for a Temporary LPG Heat Work At Risk Permit shall be filled out in its entirety and shall be accompanied by a detailed site plan showing: The installed location of the LPG tank, including distances with respect to structures, public ways, property lines and overhead utilities. A declaration of the size of the tank (in gallons of water capacity, 1000 gallon max, one tank max) and the heat release rate of the appliance that it fuels (in btu/hr). The location of the appliance being fueled as well as any associated valving, piping, and/or gas lines. The building intended to be heated and the location/size of the nearest required fire extinguisher. Any/all associated vehicular protection devices around the tank as well as any protective device installed to protect gas piping and/or lines. The permit application shall be submitted and fees paid on the business day following installation. Failure to obtain the permit, pay the required fees and schedule the inspection on this day will be considered as Work Without A Permit and fees shall be assessed as such in accordance with the CSFD Fee Schedule. See section Work Without a Work At Risk Permit at the end of this packet for further penalties regarding all situations deemed as Work Without A Permit. INSTALLATION No temporary LPG-fueled heating assembly with a tank in excess of the exempt size requiring a permit in accordance with the 2009 International Fire Code, as Amended by the City of Colorado Springs shall be installed without first obtaining a permit (125 gallons water capacity). All LPG-fueled heating appliances and assemblies shall be installed in accordance with all applicable provisions of the 2009 International Fire Code, as Amended by the City of Colorado Springs as well as all applicable provisions of NFPA 58, Liquefied Petroleum Gas Code. 2

INSTALLATION (Cont.) The LPG tank(s) installed for temporary heat at a construction site under a Work At Risk Permit may not exceed 1000 gallons (water capacity) for a single tank or 1000 gallons total (water capacity) for an aggregate of tanks regardless of the number of heat-producing devices used on the site. For the purposes of this permit only, the CSFD defines a site as a single street address. Should the installation contractor require an LPG tank in excess of 1000 gallons (water capacity) the contractor shall be subject to normal permit application, plan review and inspection processes. INTERIOR USE The installation of LPG containers may be installed indoors, only if in accordance with the following provisions of the 2009 International Fire Code, as amended by the City of Colorado Springs and NFPA 58, Liquefied Petroleum Gas Code: Limited to conditions where indoor use is necessary and locating cylinders outdoors is impractical (subject to the discretion of the CSFD Inspector) (NFPA 58). Containers shall be specifically allowed for indoor use (NFPA 58). 125 gallons water capacity (530 lb.) single container or aggregate of all containers, maximum (NFPA 58). LP-Gas containers shall NOT be used in a basement, pit or similar location where heavier-than-air gas might collect. Shall not be used in an above-grade underfloor area unless provided with an approved means of ventilation (subject to the discretion of the CSFD Inspector). INSPECTION Upon receipt of the Work At Risk Permit, the installation contractor shall schedule a code compliance inspection through the CSFD Office of the Fire Marshal for the installed assembly and use site. This inspection shall be scheduled for a time during the period declared for use on the permit application. The site and assembly will be inspected to insure that the installation and use of equipment is in accordance with all applicable provisions of the 2009 International Fire Code, as amended by the City of Colorado Springs and NFPA 58, Liquefied Petroleum Gas Code. REINSPECTIONS If, upon inspection, the CSFD Inspector identifies any issues that do not conform to all applicable provisions of the 2009 International Fire Code, as amended by the City of Colorado Springs and NFPA 58, Liquefied Petroleum Gas Code that cannot be immediately corrected, a Cease and Desist Order Notice will be issued by the Inspector for the use of the temporary heat operation at the site. A re-inspection will be required and a re-inspection fee will be assessed in accordance with the CSFD Fee Schedule. The Cease and Desist Order Notice will remain effective until relieved by the Inspector after a successful re-inspection. 3

MORE THAN TWO REINSPECTIONS IN A CALENDAR YEAR Should any contractor receive more than two Cease and Desist Order Notices for temporary LPG heat installations installed under a Work at Risk permit during a single calendar year, that contractor will not be granted another Temporary LPG Heat- Work At Risk permit until the next calendar year. Any further LPG installations by that contractor that will utilize a tank in excess of the exempt size requiring a permit in accordance with the 2009 International Fire Code, as Amended by the City of Colorado Springs will be subject to normal application, review, inspection and permit procedures. WORK WITHOUT A WORK AT RISK PERMIT Should any contractor be found to have installed any LPG-fired temporary heat assembly with a tank in excess of the exempt size requiring a permit in accordance with the 2009 International Fire Code, as Amended by the City of Colorado Springs, without a permit, that contractor will not be granted a Temporary LPG Heat- Work At Risk permit until the next calendar year. Any further LPG installations by that contractor which utilize a tank in excess of the exempt size requiring a permit in accordance with the 2009 International Fire Code, as Amended by the City of Colorado Springs will be subject to normal application, review, inspection and permit procedures. I have read and understand the above installation and use requirements, and with my signature guarantee no changes will be made after the Fire Inspector s inspection. I understand that all applicable provisions of the 2009 International Fire Code, as amended by the City of Colorado Springs and NFPA 58, Liquefied Petroleum Gas Code apply. Installer s Representative (Printed) Company Name Installer s Representative (Signature) Date User s Representative (Printed) Company Name User s Representative (Signature) Date 4

Colorado Springs Fire Department TEMPORARY LPG HEAT WORK AT RISK CONTRACTOR PERMIT APPLICATION USER INFORMATION Business Name: Business Address: City, State, Zip: Daytime Phone: After-hours Phone: Fax Number: INSTALLER INFORMATION Business Name: Business Address: City, State, Zip: Contact Person: Daytime Phone: After-hours Phone: _ Fax Number _ After-hours Phone: _ TEMPORARY LPG HEAT INSTALLATION LOCATION INFORMATION Business Name: Installation Address: City, State, Zip: Location on Property: Number of Tanks: Size of Tanks Tank Serial Numbers Date(s) planned for Temp LPG Heat Date(s) planned for Temp LPG Heat Date(s) planned for Temp LPG Heat Installation: _ Use: Removal: For Office Use Only Date: Permit Fee Permit #(s) _ Receipt # A COPY OF THIS APPLICATION FORM SHALL REMAIN ON SITE WITH THE PERMIT 5

INSTALLER CERTIFICATION OF COMPLIANCE I will install the assembly in full conformance with the applicable provisions of the 2009 International Fire Code, as amended and NFPA 58. I will instruct the User of the assembly in the daily use of the Installation Checklist as well as of proper emergency shut-off procedures. I will document this instruction by obtaining a duly executed User Certification of Compliance form as outlined in this Packet. A copy of this signed form will be posted with the Colorado Springs Fire Department Permit. I will explain each of the checklist requirements and the appropriate corrective actions. I understand that this certification is being made in conformance with the 2009 International Fire Code, as amended and NFPA 58. I understand that installation of an assembly that does not comply with the requirements of the 2009 International Fire Code, as amended and NFPA 58 is a violation of local law. I have instructed and trained a minimum of 2 individuals employed by the User" to perform shutdown of propane equipment and tanks in the event of an emergency. Signed: Date Official of Installing Company Printed Name: USER CERTIFICATION OF COMPLIANCE I have read and understand the applicable installation and periodic surveillance requirements as outlined in the 2003 International Fire Code, as amended and NFPA 58. I agree to abide by the policies, codes, and standards as outlined in the 2009 International Fire Code, as amended and NFPA 58. I agree to conduct, or have conducted by a designated employee, a daily self-inspection of the installation utilizing the Installation Checklist provided in this Information Packet. I agree not to use the assembly unless it fully meets the requirements for installation and passes the Installation Checklist without exception. I have provided a minimum of 2 individuals, employed by my organization that have received proper instruction and training from the Installer to perform shutdown of propane equipment and tanks in the event of an emergency. Signed: Date Official of Installing Company Printed Name: 6

SITE MAP A B C D E F G H I J K L M N 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 16 16 17 17 A B C D E F G H I J K L M N BUSINESS: ADDRESS: DATE: PAGE _ OF _ 7

SYSTEM SETUP AND DAILY CHECKLIST YES Item to Verify NO Corrective Action Indoor tanks (if necessary) do not exceed 525lb / 125 gallon water capacity. Move tank outside to appropriate location in accordance with code-required clearances. Indoor tanks are not within 6 feet of a heating appliance. Move cylinder more than 6 feet away from heating appliance. Forced-air or radiant heating appliances are not Move cylinder more than 20 feet from appliance. directed toward a tank within 20 feet. Tank is not located in a basement or pit. Move tank to an above-grade location. Outdoor tank does not exceed 4500 lb / 1000 gal water capacity. Remove tank and replace with tank of less than 4500 lb / 1000 gal water capacity. Outdoor tanks up to 500 gal water capacity are Move tank to a proper location. at least 10 feet from buildings, property lines and/or vehicular traffic. Outdoor tanks to 501-1000 gal water capacity Move tank to a proper location. are at least 25 feet from buildings, property lines and/or vehicular traffic. All tanks are farther than 6 away from a vertical plane below overhead electrical lines. Move tank outside of a 6 distance from below electrical lines (applicable when lines carry greater than 600V). Proper required No Smoking / No Open Place signage. Flame and NFPA 704 placards installed on, or in the immediate vicinity of tanks. Weeds, grass, brush, trash, other combustibles Remove combustibles or relocate tank. kept a minimum of 10 feet from tank. Vehicular protection has been installed around Install vehicular protection or relocate tank. tanks exposed to proximate traffic. Tank shows no signs of denting, bulging, Replace tank. Gouging or corrosion. Hose is continuously marked LP-GAS, Replace with proper hose. PROPANE, 350 PSI WORKING PRESSURE. Portable heaters are equipped with an Replace heater. operational automatic shutoff device. Portable heater is self supporting or cylinder- Replace heater. mounted. Aboveground piping is supported and Properly support and protect. protected against physical damage (shielded or in a conduit). Buried piping is below a minimum of 12- Properly bury. inches of cover. Approved fire extinguisher(s) provided that Obtain & place proper extinguisher. contain a minimum of 18 pounds of dry chemical. Minimum Rating: 80-B:C Dist.: 10-50 ft. Minimum Rating: 40-B:C.Dist.: 10-30 ft. At least 2 individuals, properly instructed and trained to perform shutdown of propane equipment and tanks in the event or an emergency are present on this site. Obtain proper instruction and training from Installer. Inspection Performed by: Date: _ 1