Smoke and heat control systems - Part 10: Power supplies EN 12101-10 Classification according to operational and environmental class I.F.I. Institut für Industrieaerodynamik GmbH Welkenrather Straße 120 DE - 52074 Aachen Test engineer: Dipl.-Ing. Rolf Schauer I.F.I. Institut für Industrieaerodynamik GmbH Institut an der Fachhochschule Aachen Test report No. P-002/2008-10-E-I Client: Environment: Name/Type: Manufacturer: Trifte 72 DE-32657 Lemgo-Lieme Internal, clean, low temperature MZ2 Trifte 72 DE-32657 Lemgo-Lieme Tests in accordance with (DIN) EN 12101-10: 2005 and pren 12101-9:2004 Note: This test report consists of 5 pages and is based on the drawings, parts lists and descriptions given in table 1. It may be copied and published only if unabbreviated. Operational class: A Primary power source: X Electrical Type: Mains adapter Pneumatic Type:. Secondary power source: X Electrical Type: Battery Pneumatic Type:. Integral component of a control panel in accordance with pren 12101-9 X Yes No C o n t e n t s 1. Object of the tests 2. Test specimens 2.1 General 2.2 Description of the test specimens 3. Test procedure 4. Comments 5. Test results 6. Summary Classification of D Control panel: RE 11000 Aachen, 27/08/2009 Test engineer Dipl.-Ing. Rolf Schauer I.F.I. Institut für Industrieaerodynamik GmbH Geschäftsführung Tel.: +49 241 879708-0 Amtsgericht Aachen Welkenrather Straße 120 Dipl.-Ing. Bernd Konrath Fax: +49 241 879708-10 HRB 4518 DE - 52074 Aachen, Dipl.-Ing. Rolf-Dieter Lieb www.ifi-aachen.de
Page 2 of 5 Client: 1. Object of the tests The object of the tests is to confirm the classification determined on page 1 of this report. 2. Test specimens 2.1 General Name: Manufacturer: MZ2 Date of delivery to the test laboratory: Serial number 07040099: 07/2007 Serial number 08110042: 11/03/2009 Serial number 08110168: 11/03/2009 Manufacturer of the test specimens: Number of test specimens 3 Selection of the test specimens: Client 2.2 Description of the test specimens Dimensions: Weight: L * W * H= 600 mm * 800 mm * 210mm 26.45 Kg Details and equipment: see list of drawings and parts, table 1: MZ2 Softwaredokumentation.pdf Drawing/parts list no. Description Date 20081122 Circuit diagram, parts list 23/02/2009 20050716 Circuit diagram, parts list 21/07/2005 Ti_MZ2_general 20/06/2006 Ti-MZ2-configuration Installation 04/12/2006 Ti_MZ2_MCU 29/08/2005 Ti-MZ2_NM16A 13/09/2005 Ti_MZ2_MM2x8A 12/01/2007 Ti_MZ2_LM3G Technical information and instruc- 15/02/2007 tion Software description 29/05/2009 Table 1
Page 3 of 5 Client: 3. Test procedure The tests were performed on 3 production parts. The test procedures and equipment used correspond to the ones described in Chapter 11 and Chapter 12 of EN 12101-10. 4. Comments The environmental tests were started with the device serial number 07040099. Die EMC immunity test was not passed. As a result the device was modified by the client and two new units were submitted for testing. Since the components for the radiated emission and for the p.s.e. are of the same construction as the ones of the unmodified device these test results of the device number 07040099 were taken over for this report. The test for immunity was carried out on the device with serial number 07040101 by RS Schwarze Elektrotechnik, An der Heller 33 at 33758 Schloss Holte-Stukenbrock (). 5. Individual test results 5.1 Reliability test Date of the test: 12/03/2009 06/04/2009 Number of operating cycles: 11000 5.2 Functional test (electrical) Date of the test: 11/04/2008 22/04/2008 Serial number: 07040099 5.3 Test of the charger and secondary power source Date of the test: 11/04/2008 22/04/2008 SN: 07040099 5.4 Environmental test cold (operational) Date of the test: 23/03/2009 Temperature: -5 C Duration: 16h
Page 4 of 5 Client: 5.6 Environmental test impact (operational) Date of the test: 23/04/2009 Impact energy: (0.5 ± 0.04) J Number of points: 5 Number of impacts per point: 3 5.7 Environmental test vibration, sinusoidal (operational) Date of the test: 05/06/2009 Frequency range: 10 Hz to 150 Hz Acceleration amplitude: 0.981 m/s² Number of axes: 3 Number of cycles: 1 for each functional condition 5.8 Environmental test EMC immunity test (operational) 5.8.1 Radiated emission Date of the test: 05/05/2008, 31/05/2008 Serial number 07040099 - Interference voltage mains 150Khz 30Mhz - Radiated interference 30Mhz -1000Mhz 5.8.2 Immunity Date of the test: 30/09/2008 Serial number 07040101 - Immunity to electromagnetic fields - Immunity to conducted disturbances induced by high frequency fields
Page 5 of 5 Client: 6. Summary The MZ2 is a control panel with integrated power supply for the control of SHEV's. The control panel conforms to the characteristics of a control panel with detectors. The system can also be used for the control of the day to day ventilation. As primary power source, a mains adapter is used which is connected to a public electricity supply or equivalent system. The secondary power source consists of batteries which are controlled in their function by the control panel. The electrical tests were performed in accordance with DIN EN 12101-10:2005. The reliability test and the environmental tests were carried out in accordance with pren 12101-9:2004. The device conforms to the specifications according to environmental class 1.