ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

Similar documents
ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE

FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK

PREMISES FIRE SAFETY HANDBOOK

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (Student Halls of Residences & Sleeping Accommodation)

EMERGENCY EVACUATION PLAN

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

EMERGENCY EVACUATION PLAN

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

GUARDIAN - SPECIALIST ESCAPE LOCKS

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

Evacuation Policy for People with Special Needs

Charlotte Building, 17 Gresse Street, London W1T 1QL

UNIVERSITY COLLEGE LONDON EMERGENCY PLAN. Regulatory Reform (Fire Safety) Order 2005 PART ONE - SPECIFIC INSTRUCTIONS & OTHER RELEVANT INFORMATION:

FIRE ALARM SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings - Excluding Sleeping Accommodation)

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

Guidance Note FIA Application Guidance on BS :2015

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

BUILDING FIRE STRATEGY (Operational & Fire Engineering Information)

Guidance for writing a Personal Emergency Evacuation Plan (PEEP)

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

BUILDING FIRE STRATEGY

Fire Evacuation Procedure Stroud Campus

SCHOOL EVACUATION POLICY

RELIGIOUS, FESTIVAL & OTHER DECORATIONS - FIRE SAFETY GUIDANCE

Fire Evacuation Procedure WISE Campus

Policy for Safe Evacuation of Persons with Disabilities

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures

(Fire) Emergency Evacuation Plan

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

BUILDING FIRE STRATEGY

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

Management Standard: Fire Safety

GROUP SR SPECIAL (ASSISTED SELF-PRESERVATION) OCCUPANCIES

GROUP SR SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

NFPA Changes

BUILDING FIRE STRATEGY

Security Considerations for Secure Workplaces

The DDA Explained ARROW ARCHITECTURAL

UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

Fire Evacuation Procedure WISE Campus

PERSONAL EMERGENCY EVACUATION PLANS (PEEP s)

GENERAL FIRE SAFETY TERMS & DEFINITIONS

Annemount School Fire Safety Policy This Policy is for the whole school including the EYFS

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

Fire Evacuation Procedure Filton Campus

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

Fire detection and alarm

The EN54 Part 2 and 4 Fire System

DORMA. Free Swing and Hold-open Solutions for Fire Doors. An alternative to Fire door keep shut

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY

STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL

Control Panel User Guide

LEICESTER GRAMMAR SCHOOL TRUST FIRE SAFETY POLICY

Wellsprings Primary School. Fire Emergency Evacuation Plan

NEWBATTLE ABBEY COLLEGE. Fire Safety and Emergency Evacuation Policy and Procedure

E-Flash Series. Electronic Door Locks

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SMARTair SOLUTIONS GUIDE. Providing complete specifications utilising ABLOY SMARTair. Page 1

EVACUATION PROCEDURES IN EDUCATION PREMISES

Regulatory Reform (Fire Safety) Order 2005

Design Guidelines Fire Safety in New and Refurbished Buildings

Health and Safety Services. Safety Guide 5. Fire drills

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Performance Specification for Rising Bollards Control Systems

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Fire Safety Protocol

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

Fire Risk Assessment 2016

Crown Woods College. Fire Safety Policy

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Element C3.5 Means of Escape

Unity DAU Voice Alarm System

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B

FIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018.

EMERGENCY EVACUATION PROCEDURE Temporary Instructions w.e.f 5 th September 2018

Control Panel User Guide (TO BE RETAINED BY THE USER)

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

Sir Christopher Hatton Academy A Member of Hatton Academies Trust

Installation, Operating and Maintenance Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Fire Risk Assessment Guide

SPECIAL AMUSEMENT OCCUPANCIES HAUNTED HOUSE, SCARE HOUSE OR MAZE

CARD ACCESS CONTROL SYSTEM

USER MANUAL & MAINTENANCE GUIDE OG OO

Dear Customer. Section Old F8 February 2014 Amendments to F8. Replace with new title page and document history pages 1 2B

Fire Evacuation Procedure Stroud Campus

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

Transcription:

Fire Safety Technical Note ACCESS SECURITY SYSTEMS (ELECTRONIC LOCKING) & ACCESSIBLE DOOR OPENING DEVICES ON MEANS OF ESCAPE Access Security & Accessible Door Opening Systems - what you need to know: Access and security controlled locking systems on doors or automatic sliding doors that form part of the Means of Escape (MoE) with opening ironmongery that does not have a mechanical override in the direction of escape, but relies on the release of Electro-magnetic lock or keep by a code / push button / reader device shall fail open/unlocked. Electronically controlled security barriers and turnstile systems or installations provided on escape routes must have emergency disconnection arrangements that shall fail open/unlocked (i.e. barriers drop out / unlock / release turnstiles free turn). Mandatory Where electronically controlled locking systems are provided on escape routes without a simple mechanical override in the direction of escape, then they shall fail open/unlocked (with the except of specialist secure areas) and be provided with a manual emergency override break glass to release the door or barrier. Accessible door opening devices - where doors are identified requiring automatic opening devices that electrically open and close doors with a time delay, then they shall not be fitted to stair enclosures or corridors forming protected fire routes without consultation with UCL Fire Safety. Prohibited Accessible Door Opening Devices on stairs forming part of the building s escape routes automatic door opening devices principally provided for Mobility Impaired Persons (MIP) to allow access through doors unaided, can, on activation of the fire alarm, remain open for longer than a normal selfclosing device and continue to open with movement of occupants or other reasons. This action potentially allows smoke to enter the escape route and therefore their installation on certain doors, may need to be prohibited, restricted or have input from the fire alarm system. This is to de-activate to door opening motor in emergencies to protect the escape routes for other building users. Acceptable Security Considerations - security in certain circumstances (including safety of the public) is to take precedence and therefore a variation from the requirement to release the door from electromagnetic locking on activation of the fire alarm system may be acceptable. These variations should be subject to a suitable assessment to confirm the adequacy of arrangements for safe egress of occupants in the event of fire and in discussion with UCL Fire Safety Manager. Consultation - before specifying or installing security systems or automatic opening devices for doors as reasonable adjustment, then UCL Fire Safety Manager should be consulted to ensure that basic fire safety standards are applied to meet the requirements of the Fire Safety Order 2005. Reference - BS 7273-4: 2015 Code of Practice for the Operation of Fire Protection Measures - Part 4: Actuation of Release Mechanisms for Doors. Date Last Amended: Dec 17 1. Issued by the Fire Safety Manager, Safety Services, UCL Estates, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of

Contents: UCL Fire Safety Technical Note - TN001 1.0. Introduction... 2 2.0. Normal Condition - Gallagher Access Control (Electromagnetic Locking Devices)... 2 3.0. Operational / Secure Conditions - Security Door Interfaces Electromagnetic Release Access Control Devices... 2 4.0. Break Glass Emergency Door Release Units... 3 5.0. Emergency Escape Lighting Requirement... 4 6.0. Mobility Impaired Persons (MIP) Accessible Auto Opening Door Devices - Escape Routes... 5 7.0. Residences - Accessible / Auto Opening Door Devices for Rooms & WCs... 5 8.0. Further UCL Advice... 6 1.0. Introduction This guidance note is provided for Design Engineers, Consultants, Project Managers, Contractors and UCL Staff to give general information on interfacing access security and accessible door release / opening systems with the fire alarm system, installed on doors and barriers used on the Means of Escape (MoE). 2.0. Normal Condition - Gallagher Access Control (Electromagnetic Locking Devices) 2.1. Where, electromagnetic locking devices are fitted to the routes forming part of the Mean of Escape (MoE) in case of fire from the building, they shall fail open / unlocked. 2.2. Gallagher / Fire Alarm Interface - fire alarm signals must be brought back to UCL s Security Control Room via the Gallagher system. This must include activation and fault. The fire alarm system interface module must be installed immediately adjacent to a Gallagher Controller, to minimise the reliance on non-fire rated cable. EOL resistors must be mounted inside the fire alarm interface module. 3.0. Operational / Secure Conditions - Security Door Interfaces Electromagnetic Release Access Control Devices Note - in some cased doors for operational reasons may be permitted to remain secure on operation of the fire alarm - these locations will generally be specialised and used by a small number of trained and familiar staff using the facilities. 3.1. Operational or Bio-Safety Requirements - may include: Containment Laboratories (CL) and GMP facilities; Biological Service Areas; External exit doors where potential security breaches an issue. Date Last Amended: Dec 17 2.

3.2. High Security Requirements - where Secure (SR) Security Doors (Stafford Bridge type) are installed. (a). (b). (c). Stafford Bridge security doors with the Safe and Secure locking solution must have a local fire alarm interface used to cut the power to the fail-locked locking mechanism, along with the local break glass; this then leaves the door secure, but with a free exit handle for easy escape in the event of fire; Important for specifiers and fire alarm installers - the fire alarm release must be direct-wired input to the security door via a separate IO interface for each security door; Note - usual fire alarm interfacing with the security system's software configuration at a central location is not acceptable where specialist Stafford Bridge door fitted; 3.3. Door Release / Unlock Requirements: (a). on operation of the fire alarm system - the locks shall release open / unlocked in all cases (with the exception of specialist, secure areassee item 3.2 above): (1). the fire alarm release may be a direct-wired input from the fire alarm system interface, or; (2). via the fire alarm system interfacing with the Gallagher security system's software configuration at a central location; (b) On the loss of electrical power - doors will unlock on loss of power supplies or disconnection of any relevant cable. Some doors may be fitted with battery backup for increased security, but shall still fail open / unlocked. 4.0. Break Glass Emergency Door Release Units Break glass door release units must be provided for all doors fitted with electronic locking that is not fitted with a mechanical physical override to open doors in an emergency such as a leaver handle. 4.1. Green break glass release units are to be positioned adjacent to the door, barrier or turnstile in all cases in the direction of travel of escape: Security drop out turnstiles or barriers at all entrances, libraries, receptions etc. Sliding, revolving doors or security gates etc. each emergency break glass unit shall: Date Last Amended: Dec 17 3.

o be coloured green; o position at a suitable height of between 1200 mm & 1400 mm (with the exception of dropout barriers at a height to suite); o be in a prominent position suitable for escape i.e. adjacent to door; 4.2. Emergency Release Provision it is important that the emergency release is a double / triple pole type and 'in line' so that both Pos & Neg imputes are broken by operation of green box thus escape cannot be prevented by: failure of the control system; earth or frame faults in the control circuit; failure of relays through doors sticking in the closed position; not re-locking the device until a reset of the fire panel and on replacement / reset of the glass in the break glass unit; 4.3. Under no circumstances is an electronic door release to be connected to a local fire alarm sounder circuit. In all cases, the recommendations indicated within BS 5839-1 and BS 7273-4 are to be observed. 4.4. Doors with Battery Backup - where a battery backup is proposed to maintain the security in the event of power failure then, an override facility (i.e. green break glass call point) must be installed so that the power supply to the electronic door-locking device can be interrupted in all cases. 4.5. Signage - all break glass units associated with egress systems for emergency use shall be GREEN in colour. 4.6. Be clearly labelled, e.g. BREAK GLASS TO OPEN DOOR IN EMERGENCY and be placed adjacent to green release box. 4.7. In addition, a specific sign is necessary with a minimum letter size of 20 mm lettering (white letters on a green background) indicating Break Glass to Open Door. Width 100 mm x Length 250 mm wording & letter height (minimum of 20 mm high) iaw Reference A 5.0. Emergency Escape Lighting Requirement 5.1. Escape Lighting - emergency escape lighting shall be provided within two metres (2m) of the emergency green break glass door or barrier device units (see UCL Fire Safety Technical Note TN020). Date Last Amended: Dec 17 4.

6.0. Mobility Impaired Persons (MIP) Accessible Auto Opening Door Devices - Escape Routes 6.1. Accessible door opening devices specifiers and contractors installing automated self-opening door mechanisms on UCL doors shall be installed and configured to respond in the following way on activation of the fire alarm: Close on activation of fire alarm or interruption of mains power - door motor drive will close and movement sensors, push buttons and connections to other systems deactivate on receiving a signal from the fire alarm; the door may then be pushed or pulled manually; Opening sequence - doors are to be wired so that on fire alarm input signal, they do not open or cycle through any opening sequence; External opening doors - on external opening doors that form part of the escape from the premises the door motor drive will close and movement sensors, push buttons and connections to other systems deactivated on receiving a signal from the fire alarm, the door may then be pushed or pulled manually this will assist in the rapid movement of evacuees through the doors during an emergency evacuation without door movement sensors impeding movement; In most cases, MIPs will have had a Personal Emergency Evacuation Plan (PEEP) or a Generic Emergency Evacuation Plan (GEEP) and/or a Buddy or a Fire Evacuation Marshal (FEM) allocated to assist in their evacuation. 7.0. Residences - Accessible / Auto Opening Door Devices for Rooms & WCs 7.1. Where it is proposed to fit auto-opening doors to bedrooms, rooms or kitchens, is subject to discussions with students and other persons requiring assistance with these devices: The door-opening device operates by means of a suitable controller with open and close/locked unit on both sides of the door. It is to be positioned so that it can be easily operated by MIP users; Care that any Red or Green lights door controller are hidden particularly in bedrooms, so as not to distract occupants; That the doors are fitted with large D type handles to allow ease of opening and closing of doors by all persons including MIPs; Date Last Amended: Dec 17 5.

The door opening and controllers can be switched off and only activated when there is a need for their use; this will also assist with the maintenance of the mechanisms; The door-opening device can be switched off on room doors if the user of the room does not require the opening facility so the door reverts to manual opening, closing and locking arrangement; All connections to designated fire doors are interfaced so as door motor driver will close and movement sensors, push buttons and connections to other systems deactivated on receiving a signal from the fire alarm, the door may then be pushed or pulled manually; In all cases, there may be need for further reasonable adjustment to assist providing specific need of the users; Automatic doors would normally operate on a key fob or proximity card and any deadlock arrangement will conflict with operation of the automatic operator. Where there is a requirement to lock doors with powered opening devices, this should be done using either electronic access control, or by installing a mechanical deadlock with a switched strike to defeat the operator when the door is locked. Powered openers must not be used on doors with mechanical latches. Specification will be provided by UCL Security Systems section; 7.2. Considerations: Ease of access for disabled users; Door operator to fail in closed position in the event of fire alarm activation (as fire may be in this room); Privacy and ability to lock door from within room; Security of room against unauthorised access; Lock over-ride for carer / emergency access; Key over-ride switch; Important Note - we should provide as much assistance, help and reasonable adjustment as practicable for MIPs to access and use our facilities to the full. However, we must be mindful that these arrangements DO NOT compromise escape routes or place other occupants at risk through our desire to assist disabled persons. Sometimes, clear management and other practical changes need to be developed, over the use and reliance of technology 8.0. Further UCL Advice Further advice from UCL Security Systems and locking devices should be obtained from the UCL Security Systems Manager [Tel: 020 7679 7735 / Internal: 37735 or securitysystems@ucl.ac.uk ]. Date Last Amended: Dec 17 6.