Sensor OCS 100W Setup Guide The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dualtechnology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves. The PIR sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient room temperature. The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy output connections. Front Panel Features Ultrasonic Sensors Figure 1. Ultrasonic Sensors Green LED (status indicator) Infrared/Photocell Sensor and Green Lens LED (status indicator) Red LED (status indicator) Infrared/Photocell Sensor and Lens Removable Front Cover Red LED (status indicator) OCS 100W Front Panel Features Removable Front Cover Ultrasonic Sensors Detect movement in the room, based on ultrasonic waves. Green LED (status indicator) Flashes when the ultrasonic sensors detect occupancy. Infrared/Photocell Sensor and Lens Diffracts the incoming light and directs the light to the infrared/photocell sensor. Red LED (status indicator) Flashes when the infrared sensor detects occupancy. Removable Front Cover Conceals all controls and DIP switches. Control DIP Switches (A) DIP Switches (B) DIP Switches (A) DIP Switches (B) A B Timer Test Button Blue Dial Notch Red Dial Green Dial Timer Test Button Blue Dial Notch Red Dial Green Dial DIP Switches (A) A OPERATION OFF ON 1 Not used Not used* Not used 2 Not used Not used* Not used 3 LED indicators LEDs enabled* LEDs disabled 4 Automatic adjust reset Toggle to reset (Default: OFF) *Default Figure 2. OCS 100W Controls DIP Switches (B) B OPERATION OFF ON 1 Timer Setting (B1 and B2 switches must be set together) 8 minutes: OFF* 4 minutes: OFF 15 minutes: ON 2 OFF * ON OFF ON 3 Timer adjust Automatic Manual* 4 Sensitivity adjust Automatic Manual* *Default Blue Timer Test Button 30 minutes: ON Push in to enable 8 second timer test mode. This will last for 1 hour. Then automatically resets to the dip switch settings. Push and hold until the red LED flashes to return the 8 second timer to the dip switch timer settings. Red Infrared Sensitivity Dial Adjust this dial to increase or decrease infrared sensitivity. Turn counter clockwise (CCW) to decrease sensitivity. Turn clockwise (CW) to increase sensitivity. Factory default is 75%. 1
Sensor OCS 100W Setup Guide (Continued) Green Ultrasonic Range Dial (see figure 2 on the previous page) Adjust this dial to increase or decrease ultrasonic sensitivity. Turn counter clockwise (CCW) to decrease sensitivity. Turn clockwise (CW) to increase sensitivity. Factory default is 50%. Blue Photocell Dial Photocell prevents the sensor from triggering on when the area is adequately lit with natural light and when motion is detected. The sensor must be mounted directly over an area that is representative of the average, natural room lighting. Before setting the photocell control, wait until the natural light is brightest (optional). Adjust this dial to increase or decrease photocell sensitivity. Turn counter clockwise to decrease photocell sensitivity. Turn clockwise to increase photocell sensitivity. Factory default is 100% (full clockwise). Full counter clockwise Photocell is disabled. Range 10 to 1000 LUX Sensor Placement and Installation Options When placing the sensor in a room, be sure the sensor is not aimed out through a door. The sensor can detect hallway traffic, causing false triggers. PIR sensors trigger in response to changes in the amount of IR arriving from any of their segments of view within a direct line of sight from the sensor. US sensors trigger in response to changes in the frequency of reflected ultrasonic waves, caused by movement within the space. NOTE: See Troubleshooting on page 5 if you experience false triggers. Wrong 60 Ceiling Mount Wall Mount Top View Corner Mount Correct Hallway 80 Rotation Installation Options Figure 3. Sensor Placement Sensor Placement and Installation Diagrams Sensor Coverage 40' 32' 23' 20' 10' Mounting Height 23' 32' Sensor Coverage 40' Major Coverage 20' Minor Motion Coverage US Minor Motion IR Minor Motion US Major Motion IR Major Motion 2 Figure 4. Sensor Coverage Diagrams
OCS 100W Parts Mounting Bracket Pull Wiring Harness Bracket Cover Mounting Bolt, Washer and nut. (2) Cover Body Figure 5. OCS 100W Parts Installation 4 Snap Bracket Cover in place to conceal wiring and Mounting Bracket. Wiring Harness Building Wiring Wall 1 Insert wiring through Mounting Bracket. Bracket Cover 3 Wall Connect building wiring to Wiring Harness with included wire nuts. 2 Secure Mounting Bracket to the wall. Push POP 5 Snap sensor onto mounting post. 6 Loosen Tighten Position Locking Screw Plug Wiring Harness into connector located on the left side, opposite exit slot and place wiring under wire tabs. Align sensor and tighten position locking screw. SNAP 7 Replace Cover. Figure 6. OCS 100W Installation ATTENTION: All structural steps and electrical installation must be performed by qualified personnel in accordance with local and national building codes and electrical codes. Toute étape structurelle et installation électrique, doit être effectuée par un personnel qualifié, conformément aux codes du bâtiment, aux codes incendie et sécurité, et aux codes électriques, locaux et nationaux. 3
M -S G L www.extron.com Sensor OCS 100W Setup Guide (Continued) OCS 100W Wiring 5A MAX IPCP PRO 550 Control Processor Dual Zone 100-240V ~ 50-60Hz Sensor w/ 12 VDC Power Supply BUS ID Single Zone S B +V +S 24 G S B ebus + V OUT 1 1 2 3 7 2 PWR OUT = 9W SWITCHED 12 VDC 40W MAX TOTAL Tx Rx G TxRxG Tx Rx G TxRx G RTSCTS S G S G S G S G +V +S -S G ebus 3 4 4 5 6 8 5 6 7 8 5 6 7 8 G 12 VDC ECM DIO8 ECM DIO8 ebus Control Module Sensor w/ 24 VDC Power Supply Figure 7. DIGITAL I/O G 5 6 7 8 G Tx Rx G TxRxG Tx Rx G TxRx G RTSCTS COM Ground (Black) +12V (Red) 1.5 A MAX S G S G S G S G IR/SERIAL E t Power Module Ground (Black) Control Signal #1 (Blue) Ground (Black) +24V (Red) 12V IN 33-2665-01 B RELAYS Control Signal #1 (Blue) 24V OUT 12V OUT 1.25 MAX A 75 ma MAX +24V (Red) Ground (Black) OCS 100W Wiring Diagram FLEX I/O IPCP PRO 550 LAN 00-05-A6-XX-XX-XX MAC: 00-05-A6-XX-XX-XX S/N: ####### E###### OCS 100W Sensor 1 NOTE: The Ground dash line is optional. Control Signal #2 (Blue) OCS 100W Sensor 2 OCS 100W Sensor Black Red Blue Gray Connections Ground +24 VDC control output and photocell control output NOTE: Gray wire is used when the control system needs to know when the area is adequately lit with natural light and when motion is detected (for example, automatic lighting through control system). Blue/ White Black/ White Yellow/ White Relay Contacts Common Normally closed when unoccupied Normally open when unoccupied NOTE: Relay contacts could be used to trigger third party devices, such as HVAC, based on occupancy. Wiring ATTENTION: Do not connect power until you have read the ATTENTIONS: notices on the next page. Ne branchez pas l alimentation avant d avoir lu les mises en garde «ATTENTIONS» de la page suivante. Remove power from the system before making any connections. Mettez le système hors tension avant d effectuer tout raccordement. The OCS 100W requires 24 VDC. If the sensors are connected to a device that does not provide 24 VDC: 1. Connect a 12 VDC power source to the 12 VDC input on the supplied power converter, using a 2-pole captive screw connector (see image on the right). 2. Wire the 24 VDC 2-pole captive screw connector to the black and red wires on the OCS 100W. A 12 VDC pass-through is available to power additional 12 VDC devices. 12V Power Source 1.5 A MAX 12V IN 33-2665-01 B www.extron.com 24V OUT 12V OUT 1.25 MAX A 75 ma MAX Sensor Additional Devices Power Module 4
Troubleshooting Problem Possible Cause Test Solution Sensor remains on. Constant noise. Reduce both green and red knobs by 15% and remove noise source. Move sensor to a less noisy area within the room. Sensor remains on too long. Timer setting too high. Check dip switch settings. Reduce timer setting. Hallway traffic turns sensor on. Infrared sensor can see into the hallway. Put sensor in timer test mode and walk the hallway. Move sensor, so it cannot see into the hallway. Safety Instructions For information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Safety and Regulatory Compliance Guide, part number 68-290-01, on the website. FCC Class A Notice This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. The Class A limits provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause interference. This interference must be corrected at the expense of the user. NOTE: For more information on safety guidelines, regulatory compliances, EMI/EMF compatibility, accessibility, and related topics, see the Safety and Regulatory Compliance Guide on the website. Power Attentions ATTENTIONS: These products are intended for use with a UL Listed LPS type power source. Ces produits doivent être utilisés avec une source d alimentation de type LPS certifiée UL. Use of a non-lps or unlisted power supply will void all regulatory compliance certification. L utilisation d une source d alimentation non-listée ou non-listée LPS annulera toute certification de conformité réglementaire. Unless otherwise stated, the AC/DC adapters are not suitable for use in air handling spaces or in wall cavities. The power supply is to be located within the same vicinity as the AV processing equipment in an ordinary location, Pollution Degree 2, secured to the equipment rack within the dedicated closet, podium, or desk. Sauf mention contraire, les adaptateurs CA/CC ne conviennent pas à une utilisation dans les espaces d aération ou dans les cavités murales. La source d alimentation doit être placée à proximité de l équipement dans un emplacement ordinaire soumis à un degré de pollution de catégorie II, solidement fixé au rack d équipement d une baie technique, d un pupitre, ou d un bureau. The installation must always be in accordance with the applicable provisions of National Electrical Code ANSI/NFPA 70, article 725 and the Canadian Electrical Code part 1, section 16. Cette installation doit toujours être conforme aux dispositions applicables du Code américain de l électricité (National Electrical Code) ANSI/NFPA 70, article 725, et du Code canadien de l électricité, partie 1, section 16. The power supply shall not be permanently fixed to building structure or similar structure. La source d alimentation ne devra pas être fixée de façon permanente à la structure de bâtiment ou à d autres structures similaires. 5
Headquarters +800.633.9876 Inside USA/Canada Only USA - West USA - East +1.714.491.1500 +1.919.850.1000 +1.714.491.1517 FAX +1.919.850.1001 FAX Europe +800.3987.6673 Inside Europe Only +31.33.453.4040 +31.33.453.4050 FAX Asia +65.6383.4400 +65.6383.4664 FAX Japan +81.3.3511.7655 +81.3.3511.7656 FAX China +86.21.3760.1568 +86.21.3760.1566 FAX Middle East +971.4.299.1800 +971.4.299.1880 FAX Australia +61.8.8113.6800 +61.8.8351.2511 FAX India 1800.3070.3777 (Inside India Only) +91.80.3055.3777 +91.80.3055.3737 FAX 6 2017 Electronics All rights reserved. All trademarks mentioned are the property of their respective owners. www.extron.com 68-3155-50 Rev. C 09 17