Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Similar documents
Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Sprinkler Identification Numbers. TY3351 Horizontal TY3451 Vertical. Technical Data

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-B 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage General Description

Series TY-FRB 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Quick Response, Standard Coverage General Description

Sprinkler Identification Numbers

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Series TY-B 5.6 and 8.0 K-factor Upright and Pendent Intermediate Level Sprinklers Standard Response General Description

* Temperature rating is FIGURE K-FACTOR QUICK RESPONSE SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS

O-RING UPRIGHT SHIELD WRENCH FLATS WRENCH FLATS FIGURE 1 SERIES TY-B UPRIGHT (TY3153) AND PENDENT (TY3251) SPRINKLERS

Submittal Packages Detailed with Items and Reviewers

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application

Sprinkler Identification Number. Page 1 of 6 AUGUST 2018 TFP288. Worldwide Contacts.

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Horizontal Sidewall Wet Pipe and Dry Pipe Systems General Description

Sprinkler Identification Numbers

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

RAPID RESPONSE Series LFII Residential Sprinklers 5.6 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response)

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

Page 1 of 8 DECEMBER 2018 TFP408. Worldwide Contacts.

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

WRENCH FLATS 1/2" NPT. 7/16" (11,1 mm) NOMINAL MAKE-IN CENTERLINE OF WATERWAY ESCUTCHEON PLATE SEATING SURFACE

Model/Sprinkler Identification Numbers

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

Model TY-FRFS, TY-FS Special, and TY-FS 57, 80, and 115 K-factor Upright and Pendent Flat Spray Sprinklers General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Domed-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinkler 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe System General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Model TY-FRFS, TY-FS Special, and TY-FS Flat Spray Sprinklers, Upright and Pendent 57, 80, and 115 K-factor General Description

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Sprinkler Identification Number (SIN)

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential 4.9 K-factor Concealed Pendent Sprinkler Flat Plate, Wet Pipe and Dry Pipe Systems General Description

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Horizontal Sidewall Wet Pipe Systems

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

FIGURE 1 MODEL RFIII ECLH CONCEALED HSW SPRINKLER ASSEMBLY AND FEATURES. 5/16" (7,9 mm) MIN. 9/16" (14,3 mm) MAX.

RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General Description

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

The Series LFII (TY3596) Residential

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

5.6K Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

RAVEN 5.6K Institutional Sprinklers Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage General Description

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

G3/8" DIN ISO 228 THREAD SHOULDER AND DUST CAP MATING SURFACE. STYLE H ESCUTCHEON (SEPARATELY ORDERED) 85 mm DIA. (3-3/8")

Sprinkler Identification Numbers

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Series LFII Residential Flush Pendent Sprinklers 4.2 K-factor General Description

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe and Dry Pipe Systems

SENJU SPRINKLER CO.,LTD. Residential Flush Pendent Sprinkler Model ZN-RES,K=4.2 (SIN / SS4421) (PTFE gasketed orifice seal design) General Description

Model/Sprinkler Identification Number (SIN) Technical Data

Automatic Sprinklers

MODEL: FA003U FA004U FA005P FA006P STANDARD SPRAY, STANDARD QUICK RESPONSE, 5 3 mm BULB TYPE, K5.6, 1/2" CONNECTING THREAD

WFD Series Waterflow Detector

Automatic Sprinklers

SENJU SPRINKLER CO., LTD.

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Residential Flush Horizontal Side-Wall Sprinkler Model HF-RES,K=4.2 (SIN / SS4423) (PTFE gasketed orifice seal design)

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Worldwide Contacts.

Data Sheet 4.19 Issue C

Commercial Flat Concealed Sprinkler, Pendent, Quick Response, Standard Coverage, Model: RC-QR, K-Factor: 5.6, SIN: SS9561

Commercial Flat Concealed Sprinkler, Pendent, Quick & Standard Response, Standard Coverage, Model: CN-QR, K-Factor: 5.

Model F1 LO K 8.0 (115 metric) Standard Response Sprinklers

Transcription:

Worldwide Contacts www.tyco-fire.com Series TY-B 2.8,.6, 8.0 K-factor Upright, Pendent, Recessed Pendent Sprinklers Stard Response, Stard Coverage General Description TYCO Series TY-B, 2.8,.6, 8.0 K-factor, Upright Pendent Sprinklers described in this technical data sheet are stard response, stard coverage decorative mm glass bulb type spray sprinklers designed for use in light, ordinary, or extra hazard, commercial occupancies such as banks, hotels, shopping malls, factories, refineries, chemical plants. The recessed version of the Series TY-B Pendent Sprinkler, where applicable, is intended for use in areas with a finished ceiling. It uses a two-piece Style 10 (1/2 inch ) or Style 0 (/ inch ) Recessed Escutcheon. The Recessed Escutcheon provides 1/2 inch (12,7 mm) of recessed adjustment or up to / inch (19,1 mm) of total adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion resistant coated sprinklers have passed the stard corrosion tests of the applicable approval agencies, the testing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level version of the Series TY-B Pendent Sprinkler can be obtained by utilizing the Series TY-B Pendent Sprinkler in combination with the Model S2 Shield. NOTICE The Series TY-B Sprinklers described herein must be installed maintained in compliance with this document, as well as with the applicable stards of the National Fire Protection Association (NFPA), in addition to the stards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system devices in proper operating condition. Contract the installing contractor or product manufacturer with any questions. Sprinkler Identification Numbers (SINs) TY111 Upright 2.8K, TY121 Pendent 2.8K, TY11 Upright.6K, TY21 Pendent.6K, TY11 Upright 8.0K, / TY21 Pendent 8.0K, / TY81 Upright 8.0K, TY91 Pendent 8.0K, IMPORTANT Always refer to Technical Data Sheet TFP700 for the INSTALLER WARNING that provides cautions with respect to hling installation of sprinkler systems components. Improper hling installation can permanently damage a sprinkler system or its components cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 NOVEMBER 201 TFP11

Page 2 of 8 1/2" ** 7/16" (11,1 mm) NOMINAL MAKE-IN 2-/16" (,6 mm) FLATS CEILING PLATE SEATING SURFACE 1-9/16" (9,7 mm) 2-1/" (7,2 mm) CROSS SECTION 7 1 2 6* 1 - Frame 2 - Button - Sealing Assembly - Bulb FIGURE 1 SERIES TY-B (TY111) AND (TY121) SPRINKLERS 2.8 K-FACTOR, 1/2 INCH, STANDARD RESPONSE * Temperature rating is indicated on Deflector. ** - Compression Screw 6 - Deflector * 7 - Bushing Pipe thread connections per ISO 7-1 can be provided on special request. * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on Deflector. special request. ESCUTCHEON PLATE SEATING SURFACE 1 - Frame 2 - Button - Sealing - Compression Assembly Screw - Bulb 6 - Deflector * 1 7/16" (11,1 mm) NOMINAL MAKE-IN 2-/16" (,6 mm) 1-1/2" (8,1 mm) 2-/16" (,6 mm) 2 1/2" ** STYLE 10 2-7/8" (7,0 mm) DIA. FLATS RECESSED ESCUTCHEON RECESSED CROSS SECTION FIGURE 2 SERIES TY-B (TY11) AND (TY21) SPRINKLERS.6 K-FACTOR, 1/2 INCH, STANDARD RESPONSE 6*

Page of 8 * Temperature rating ** Pipe thread connections per is indicated on ISO 7-1 can be provided on Deflector. special request. ESCUTCHEON PLATE SEATING SURFACE 1 - Frame 2 - Button - Sealing - Compression Assembly Screw - Bulb 6 - Deflector* 1 1/2" (12,7 mm) NOMINAL MAKE-IN 2-1/" (7,2 mm) 1-9/16" (9,7 mm) 2-/16" (8,7 mm) 2 /" ** STYLE 0 2-7/8" (7,0 mm) DIA. FLATS RECESSED ESCUTCHEON RECESSED CROSS SECTION FIGURE SERIES TY-B (TY11) AND (TY21) SPRINKLERS 8.0 K-FACTOR, / INCH, STANDARD RESPONSE 6* 7/16" (11,1 mm) NOMINAL MAKE-IN 2-/16" (,6 mm) 1/2" ** FLATS CEILING PLATE SEATING SURFACE 1-9/16" (9,7 mm) 2-1/" (7,2 mm) CROSS SECTION 1 2 6* 1 - Frame 2 - Button - Sealing Assembly - Bulb FIGURE SERIES TY-B (TY81) AND (TY91) SPRINKLERS 8.0 K-FACTOR, 1/2 INCH, STANDARD RESPONSE * Temperature rating is indicated on Deflector. ** - Compression Screw 6 - Deflector * Pipe thread connections per ISO 7-1 can be provided on special request.

Page of 8 K SPRINKLER TYPE TEMPERATURE RATING BULB LIQUID COLOR NATURAL BRASS SPRINKLER FINISH (8) CHROME PLATED POLYESTER*** LEAD WAX WAX-OVER-LEAD 2.8.6 8.0 / 8.0 (TY111) (TY121) Figure 1 (TY11) (TY21) Figure 2 RECESSED (TY21)* Figure (TY11) (TY21) Figure RECESSED (TY21)* Figure 6 (TY81) (TY91) Figure 1, 2, N/A 286 F (11 C) Blue 60 F (182 C) Mauve 1, 2 1, 2,, 1, 2,, 1, 2,,,, 6, 7 1, 2,, 286 F (11 C) Blue 1**, 2**, **, ** 1**, 2**, **, ** 60 F (182 C) Mauve N/A 1, 2,,, N/A 286 F (11 C) Blue 1, 2 1, 2,, 1, 2, 1, 2,,,, 6, 7 1, 2, 286 F (11 C) Blue 1**, 2**, **, ** 1**, 2**, ** 60 F (182 C) Mauve N/A 1, 2,,, N/A 286 F (11 C) Blue 1, 2 1, 2,,,, 6 N/A 286 F (11 C) Blue 60 F (182 C) Mauve Notes: 1. Listed by Underwriters Laboratories, Inc. (UL) 2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL). Approved by FM Global (FM Approvals). Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/0). Approved by the City of New York under MEA -01-E 6. VdS Approved (For details contact Tyco Fire Suppression & Building Products, Enschede, Netherls, Tel. 1--28- / Fax 1--28-77) 7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 09a/0) 8. Where Polyester Coated, Lead Coated, Wax Coated, Wax-over-Lead Coated Sprinklers are noted to be UL C-UL Listed, the sprinklers are UL C-UL Listed as Corrosion- Resistant Sprinklers. Where Lead Coated, Wax Coated, Wax-over-Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as Corrosion-Resistant Sprinklers. * Installed with Style 10 ( ) or Style 0 (/ ) / Total Adjustment Recessed Escutcheon, as applicable ** 10 F (66 C) maximum ceiling temperature *** Frame deflector only N/A Not Applicable TABLE A SERIES TY-B AND SPRINKLERS LABORATORY LISTINGS AND APPROVALS

Page of 8 SPRINKLER FINISH K TYPE NATURAL BRASS CHROME PLATED POLYESTER* LEAD WAX WAX-OVER-LEAD 2.8 (TY111) (TY121) 17 psi (12,1 bar) N/A.6 (TY11) (TY21) RECESSED (TY21) 20 psi (17,2 bar) (a) OR 17 psi (12,1 bar) 8.0 / (TY11) (TY21) RECESSED (TY21) 17 psi (12,1 bar) 17 psi (12,1 bar) N/A 8.0 (TY81) (TY91) 17 psi (12,1 bar) Notes: a. The maximum working pressure of 20 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL), the Listing by Underwriters Laboratories, Inc. for use in Canada (C-UL), the Approval by the City of New York. * Frame deflector only N/A Not Applicable TABLE B SERIES TY-B AND SPRINKLERS MAXIMUM WORKING PRESSURE Technical Data Approvals UL C-UL Listed FM Approved LPCB Approved VdS Approved NYC Approved (Refer to Table A for complete approval information, including corrosion-resis-tant status.) Maximum Working Pressure Refer to Table B. Discharge Coefficient K=2.8 gpm/psi 1/2 (0, lpm/bar 1/2 ) K=.6 gpm/psi 1/2 (80,6 lpm/bar 1/2 ) K=8.0 gpm/psi 1/2 (11,2 lpm/bar 1/2 ) Temperature Ratings Refer to Table A. Finishes Sprinkler: Refer to Table C. Recessed Escutcheon: Signal or Pure White, Jet Black, Chrome Plated, or Natural Brass Physical Characteristics Frame... Bronze Button....Brass/Copper Sealing Assembly....... Beryllium Nickel w/teflon Bulb... Glass Compression Screw............ Bronze Deflector..................... Copper Bushing (K=2.8)............... Bronze Operation The glass bulb contains a fluid which exps when exposed to heat. When the rated temperature is reached, the fluid exps sufficiently to shatter the glass bulb, allowing the sprinkler to activate water to flow. Design Criteria TYCO Series TY-B, 2.8,.6, 8.0 K-factor, Upright Pendent Sprinklers are intended for fire protection systems designed in accordance with the stard installation rules recognized by the applicable Listing or Approval agency (e.g., UL Listing is based on the requirements of NFPA 1, FM Approval is based on the requirements of the FM Global Loss Prevention Data Sheets). Only the Style 10 or 0 Recessed Escutcheon, as applicable, is to be used for recessed pendent installations.

Page 6 of 8 /8±1/" (1,9±6, mm) FACE OF SPRINKLER FITTING MOUNTING SURFACE 2-7/8" DIA. (7,0 mm) 2-1/" DIA. (7,2 mm) /" (19,1 mm) 1/" (6, mm) MOUNTING PLATE 1/8" (,2 mm) RECESS (END "A" USED FOR 1/2" MODELS) RECESS (END "B" USED FOR /" MODELS) FIGURE 7 W-TYPE 6 SPRINKLER CLOSURE SERIES TY-B 1-1/" (1,8 mm) /" (19,1 mm) FIGURE SERIES TY-B RECESSED SPRINKLER ASSEMBLY WITH TWO-PIECE / INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON.6 K-FACTOR, 1/2 INCH RECESS /8±1/" (1,9±6, mm) FACE OF SPRINKLER FITTING 2-7/8" DIA. (7,0 mm) 2-1/" DIA. (7,2 mm) /" (19,1 mm) 1/" (6, mm) MOUNTING PLATE 1/8" (,2 mm) PUSH IN TO ENSURE ENGAGEMENT WITH SPRINKLER ING AREA FIGURE 8 W-TYPE 7 RECESSED SPRINKLER MOUNTING SURFACE CLOSURE SERIES TY-B 1-/16" (, mm) 1/16" (20,6 mm) FIGURE 6 SERIES TY-B RECESSED SPRINKLER ASSEMBLY WITH TWO-PIECE / INCH TOTAL ADJUSTMENT STYLE 0 RECESSED ESCUTCHEON 8.0 K-FACTOR, / INCH Installation TYCO Series TY-B, 2.8,.6, 8.0 K-factor, Upright Pendent Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 1 F (7 C) to /2 inch (2, mm) for the 60 F (182 C) temperature ratings. A leak-tight 1/2 inch sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 1 ft.-lbs. (9, to 19,0 Nm). Obtain a leak-tight / inch sprinkler joint by applying a minimum to maximum torque of 10 to 20 ft.-lbs. (1, to 26,8 Nm). Higher levels of torque may distort the sprinkler inlet cause leakage or impairment of the sprinkler. Do not attempt to make-up for insufficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit.

Page 7 of 8 Upright Pendent Sprinklers The Series TY-B Upright Pendent Sprinklers must be installed in accordance with the following instructions: Note: Install pendent sprinklers in the pendent position; install upright sprinklers in the upright position. Step 1. With pipe thread sealant applied to the pipe threads, h-tighten the sprinkler into the sprinkler fitting. Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 7). For wax-coated sprinklers, use an 8 or 10 inch adjustable wrench. With reference to Figures 1 through, the W-Type 7 Recessed Sprinkler Wrench or an adjustable wrench, as applicable, is to be applied to the sprinkler wrench flats. When installing wax-coated sprinklers with an adjustable wrench, exercise care to prevent damage to the wax coating on the sprinkler wrench flats or frame arms, consequently, exposure of bare metal to the corrosive environment. Open the jaws of the wrench sufficiently wide to pass over the wrench flats without damaging the wax coating. Before wrench tightening the sprinkler, adjust the jaws of the wrench to contact only the sprinkler wrench flats. After wrench tightening the sprinkler, loosen the wrench jaws before removing the wrench. After installation, inspect the sprinkler wrench flats frame arms retouch (repair) the wax coating whenever the coating has been damaged bare metal is exposed. Retouch the wax coating on the wrench flats by gently applying a heated 1/8 inch diameter steel rod to the damaged areas of wax, to smooth it back over areas where bare metal is exposed. NOTICE Only retouching of the wax coating applied to the wrench flats frame arms is permitted, the retouching is to be performed only at the time of the initial sprinkler installation. The steel rod should be heated only to the point at which it can begin to melt the wax, appropriate precautions need to be taken when hling the heated rod in order to prevent the installer from being burned. Recessed Pendent Sprinklers The Series TY-B Recessed Pendent Sprinklers must be installed in accordance with the following instructions: Step A. After installing the Style 10 or 0 Mounting Plate, as applicable, over the sprinkler threads with pipe thread sealant applied to the pipe threads, h-tighten the sprinkler into the sprinkler fitting. Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 8). With reference to Figure or, the W-Type 7 Recessed Sprinkler Wrench is to be applied to the sprinkler wrench flats. Step C. After the ceiling is installed or the finish coat is applied, slide on the Style 10 or 0 Closure over the Series TY-B Sprinkler push the Closure over the Mounting Plate until its flange contacts the ceiling. Care Maintenance TYCO Series TY-B, 2.8,.6, 8.0 K-factor, Upright Pendent Sprinklers must be maintained serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities notify all personnel who may be affected by this action. The owner must assure that the sprinklers are not used for hanging any objects that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inadvertent operation may result. Absence of an escutcheon, which is used to cover a clearance, may delay the time to sprinkler operation in a fire situation. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, after installation. Sprinklers damaged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Refer to Installation Section.) The owner is responsible for the inspection, testing, maintenance of their fire protection system devices in compliance with this document, as well as with the applicable stards of the National Fire Protection Association (e.g., NFPA 2), in addition to the stards of any other authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions. Automatic sprinklers are recommended to be inspected, tested, maintained by a qualified Inspection Service in accordance with local requirements /or national codes.

Page 8 of 8 P/N 7 XXX X XXX SIN SPRINKLER FINISH TEMPERATURE RATING 0 2.8K ( ) TY111 1 NATURAL BRASS 1 1 F (7 C) 1 2.8K ( ) TY121 PURE WHITE (RAL9010) * POLYESTER 1 1 F (68 C) 70.6K ( ) TY11 SIGNAL WHITE (RAL900) POLYESTER 17 17 F (79 C) 71.6K ( ) TY21 JET BLACK (RAL900) ** POLYESTER 200 200 F (9 C) 90 8.0K (/ ) TY11 6 WAX 286 F (11 C) MAX 286 286 F (11 C) 91 8.0K (/ ) TY21 7 LEAD 60 60 F (182 C) 60 8.0K ( ) TY81 8 WAX-OVER-LEAD 286 F (11 C) MAX 000 OPEN*** 61 8.0K ( ) TY91 9 CHROME PLATED Notes: * Eastern Hemisphere sales only ** Available in only 8.0K, 1 F (68 C) or 200 F (9 C); requires lead time to manufacture *** Available only for 8.0 K-factor TY11 TY21 for use in deluge systems ( OPEN indicates sprinkler assembly without glass bulb, button, sealing assembly) Limited Warranty For warranty terms conditions, visit www.tyco-fire.com. TABLE C SERIES TY-B AND SPRINKLERS PART NUMBER SELECTION Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name Part Number (P/N). Sprinkler Assemblies with Thread Connections Specify: Series TY-B (specify SIN), (specify K-factor), (specify Upright or Pendent) Sprinkler with (specify) temperature rating, (specify) finish or coating, P/N (Refer to Table C) Recessed Escutcheon Specify: Style (10 or 0) Recessed Escutcheon with (specify) finish, P/N* * Refer to Technical Data Sheet TFP770 Sprinkler Wrenches Specify: W-Type 6 Sprinkler Wrench, P/N 6-000-6-87 Specify: W-Type 7 Sprinkler Wrench, P/N 6-80--001 Wax Sticks (for retouching wrench-damaged wax coating) Specify: (specify color, below) Colored Coded Wax Stick for retouching (specify temperature rating) temperature-rated Series TY-B Sprinklers, P/N (specify) Black for 1 F (7 C)...P/N 6-06-1-1 Red for 1 F (68 C)...P/N 6-06-1-1 Yellow for 17 F (79 C)...P/N 6-06-1-17 Blue for 200 F (9 C) 286 F (11 C)...P/N 6-06-1-286 Note: Each wax stick is suitable for retouching up to 2 sprinklers. Note: The wax used for 286 F (11 C) sprinklers is the same as for 200 F (9 C) sprinklers,, therefore, the 286 F (11 C) sprinkler is limited to the same maximum ceiling temperature as the 200 F (9 C) sprinkler (i.e., 10 F [66 C]). GLOBAL HEADQUARTERS 100 Pennbrook Parkway, Lansdale, PA 196 Telephone +1-21-62-0700 Copyright 201 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of the DuPont Corporation.