EXHAUSTO Inc in North America In Atlanta since 1990 25,000 sq.ft. office and warehouse 86 authorized sales and service offices in USA and Canada.
The First Fan - 1957 The first chimney fan - a first worldwide and the foundation of EXHAUSTO s existence
A 50-year Old Company Founded in 1957 300,000+ sq.ft. of manufacturing and administration High-tech ISO 9001 certified manufacturing facilities
Certifications
Mechanical Draft Systems
Products RSV Fan Capacity: 6,000 MBH on CAT I Appliances 10,000 MBH on CAT IV Appliances 3/16 Cast aluminum housing Hinged for easy service and cleaning Direct drive Class H insulated motor Maintenance free 482 ºF Continuous Duty 575 ºF Intermittent Duty UL 378 Draft Equipment
Products RSV Fan The RSV fan can vent all appliance categories with or without barometric dampers Up to 6,000-10,000 MBH High temperature motor eliminates the need for secondary fan cooling Simple design with few components reduces the risk of failure and simplifies service
CASI Chimney Automation System
RSIB Power Venter Capacity: 8,000 MBH on CAT I Appliances 15,000 MBH on CAT IV Appliances SS316 construction Removable access door Direct drive Class A insulated motor - eliminates the need for secondary fan cooling Maintenance free Up to 575 ºF Duty The RSIB fan can vent category I, II, III & IV appliances Simple design with few components reduces the risk of failure and simplifies service RSIB is of Type B, Spark Resistant Construction UL 378 Draft Equipment
RSIF Power Venter Capacity: 1,800 MBH on CAT I Appliances Rated to 400 F non-condensing applications Forward inclined impeller. Statically and dynamically balanced. Insulated housing in galvanized steel Hinged fan housing easily opens to provide easy access to duct and impeller Direct drive, variable speed, TEFC motor located outside housing for easy access.
Modulating Overdraft Damper System
Controls EBC30 Modulating Pressure Control
Controls EBC30 Features 100% microprocessor based control Plug-and-Play initialization process Integrated PDS function with adjustable time delay Intermittent or continuous operation for all fans Field-adjustable PID loop Priority Operation function Bearing Cycle function Rotation Check for three-phase fans
Controls PDS Proven Draft Switch Differential pressure transducer Ensures proper draft before and during appliance operation Probe included Range: 0.04 to 0.60 W.C.
Controls VFD Variable Frequency Drive Pre-programmed from the factory 1 5 HP in 200 Volt Class input 1 7. All wiring is done externally conduits and wires are pre-installed Quick-menu for field adjustable Parameters NEMA 1 rating
Products Accessories SCA Steel Chimney Adapter Steel chimney adapter Used as transition between a round stack and the fan Made of 304 stainless steel
Products Accessories BBF Balancing Baffle Balancing baffle with flange connections For positive pressure stacks For balancing pressure drops on systems with multiple appliances
CASV Applications Stack Downsizing Hazen High School Renton, WA Soldier Field - Chicago, IL
CASV Applications - Aesthetics Getty Center Los Angeles Rigel San Francisco
MCAS Mechanical Combustion Air Supply Systems
MCAS Modulating Combustion Air Supply System
MCAS Components SFTA Fan Seven Models 1,500 30,000 cfm Fan can be mounted indoors Impeller cast aluminum. Housing in steel Direct drive, variable speed, TEFC motor located outside housing for easy access. Variable Frequency Drive is used on three phase models (VFD should be located inside the building).
MCAS Components BESF/BESB Fan Seven Models 450 5500 cfm Fan can be mounted indoors or outdoors. Impeller - statically and dynamically balanced. Insulated housing in galvanized steel Hinged fan housing easily opens to provide easy access to duct and impeller Direct drive, variable speed, TEFC motor located outside housing for easy access. Variable Frequency Drive is used on three phase models In-door or out-door installations (VFD should be located inside the building).
EBC30 Modulating Control Modulating Combustion Air Supply System Chimney Automation System
SBC Center San Antonio, TX Two 16 inch ducted combustion air inlets Instead of Two 10 foot high by 15 foot long Louvers
Lifetime Fitness Savage, MN
Marriott Waterfront Annapolis, MD One 24 inch ducted combustion air inlet Instead of One 90 ft.² louver
MDVS Mechanical Dryer Venting Systems
MDVS Mechanical Dryer Venting System
MDVS Components - BESB Fan Four Models 1200 5500 cfm ETL Listed to UL705 :"The product (BESB/MDVS) covered by this report is a modulating air exhaust system. The product consists of a box ventilator and a modulating control for permanent installation. Its intended use is exhausting of lint-laden air from single or multiple type I and type II residential and commercial clothes dryers whether electric or gasfired, exhausting commercial hoods, or for providing make-up air for laundries or mechanical rooms. The box ventilator can be installed indoors or outdoors."
MEC 18 Control Monitor draft in multi-story building exhaust applications Controls RSV, EFH, BESF and BESB EBC12 functions UL 508 and CSA C22.2 Standard for Industrial Control Equipment
Kitchen and Dryer Exhaust Madigral Lofts, MD
Applications Sports Arenas Hotels Hospitals Schools Fitness Facilities Apartments / Condominiums
Appliance Categorization Atmospheric Fan Assisted Forced Draft Scotch Marine Draft Hood Draft Diverter I III Negative Fan Assisted (high efficiency) II IV Condensing Positive
Z223.1-54 (Venting of equipment) 12.1 Minimum Safe Performance A venting system shall be designed and constructed so as to develop a positive flow adequate to remove flue or vent gases to the outside atmosphere. 12.4.1 Equipment Draft Requirement A venting system shall satisfy the draft requirement of the equipment in accordance with the manufacturer s instructions.
Common Code Violations (NFPA 54) Z223.1-2006 12.11.9.2 (Venting of Equipment) (NFPA 54) Z223.1-2006 13.2 (Sizing of Venting Systems)
Common Code Violations 3" 4" 5" 6" 7" 8" 9" 10" 12" 14" 16" 7" 10" 12" 14" 18" 22" 22" 26" 30" 36" 42" (NFPA 54) Z223 Sizing Tables (NFPA 54) Z223.1-2006 13.2.18 (Sizing of Venting Systems)
Mechanical Draft Systems Defined Z223.1-2006 Standard for Venting of Equipment 12.4.3.1 Mechanical draft systems shall be listed and shall be installed in accordance with the terms of their listing and both the appliance and the mechanical draft system manufacturer s instructions. 12.4.3.2 Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design. Exception: Incinerators 12.4.3.5 Where a mechanical draft system is employed, provision shall be made to prevent flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the equipment for safe performance
Commercial Laundry Radisson, Orlando, FL
Responsibility Reduce Emissions Environmentally friendly Low Energy Recyclable Materials Demand-Controlled
And Still Going Strong... Reliable 1990 1992 2001 2007 Disney Allstar Resorts Orlando, Florida 60 RSV installed 2 RSV replaced The White House Washington D.C 12 RSV installed Sample 3 xx RSV installed
Eliminates Potential Risks Seismological Safe
Eliminates Potential Risks Seismological Safe
Case: CBS Studio, Hollywood, CA Boiler replacement. Must meet air quality requirements and eliminate need for substantial stack work. Solution: Four condensing boilers installed in a modular system using a single common stack and a CASV system for venting. Benefits: Simple and Aesthetically pleasing Limited stack work using existing chase