Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description

Similar documents
VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

Technical Data. Installation

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

Model CV-1FR Riser Check Valves 2 to 12 Inch (DN50 to DN300) General Description. Installation. Technical Data. Page 1 of 6 OCTOBER 2010 TFP950

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Design Criteria. Installation

ILLUSION 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

Series TY-B 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Standard Response, Standard Coverage General Description

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

The Series LFII (TY3596) Residential

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

Model CHEC 8.0 K-factor Concealed Horizontal Extended Coverage Quick Response Light Hazard, Sidewall Sprinklers General Description

Technical Data Approvals UL Listed and FM Approved. Refer to Tables 1, 2, and 3, as applicable.

DOUBLE INTERLOCK, PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC RELEASE

Series TY-B & TY-FRB, 10 mm Orifice, ISO 7/1-R3/8 Upright, Pendent, and Recessed Pendent Sprinklers Standard and Quick Response General Description

TECHNICAL DATA. 319a. January 27, 2012

TECHNICAL DATA SINGLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA OBSOLETE

Model/Sprinkler Identification Numbers

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH ELECTRIC RELEASE

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

Pre-Pack INTEGRATED PRE-ACTION SYSTEM

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Model ELOC 11.2 K-factor Extra Large Orifice Concealed Pendent Sprinklers Quick and Standard Response, Extended Coverage

SINGLE INTERLOCK, SUPERVISED PREACTION SYSTEM WITH WET PILOT ACTUATION

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Sprinkler Identification Numbers

Series LFII Residential Pendent Sprinklers 4.9 K-factor General Description

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Series LFII Residential Flush Pendent Sprinklers 4.2 K-factor General Description

Series LFII Residential Sprinklers Flat-Plate Concealed Pendent 4.9 K-Factor General Description

Series RFII 5.6 K-factor. Flush II Concealed Pendent Sprinklers

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Worldwide Contacts.

TECHNICAL DATA 1. SYSTEM DESCRIPTION 2. SYSTEM OPERATION 3. INSTALLATION. Page 1 of 5

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Series LFII Residential Horizontal Sidewall Sprinklers 4.4 K-factor General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Sprinkler Identification Number TY ECLH HSW, 8.0K, 3/4"NPT

TOTALPAC2 Integrated Fire Protection System

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

Series LFII Residential Horizontal Sidewall Sprinklers 4.2 K-factor General Description

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-Factor General Description

Technical Data. Minimum Inlet Supply Pressure All MCC Models...0 psi. Minimum Inlet Supply Capacity Match system design calculations

Datasheet. Dry-pipe Vacuum Sprinkler System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Datasheet. Vacuum Double-interlock Preaction System, Electric Release Self contained unit. Features. FIREFLEX VACTEC description

Sprinkler Identification Number (SIN) TY4234. Page 1 of 8 APRIL 2012 TFP Technical Services

Model WS TM 5.6 K-factor Specific Application Window Sprinklers, Horizontal and Pendent Vertical Sidewall General Description

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

AQUAMIST Mist Control Center (MCC) Pump Skid Unit. General Description. Technical Data. Page 1 of 8 JANUARY 2016 TFP2270. Worldwide Contacts

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, Dual-Purpose Water Supply, Domestic and Fire Sprinkler System General Description

Instructions for Installation, Operation, Care and Maintenance

as required for residential sprinklers intended for use in dry pipe systems.

5.6K Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

TECHNICAL DATA DELUGE SYSTEM CONTROLLED BY ELECTRIC RELEASE

Becoming an Expert on Dry-pipe, Preaction, and Deluge Sprinkler Systems

Advanced Integrated Fire Protection Systems TOTALPAC 2. Owner's Operation and Maintenance Manual FIRECYCLE III. September 2009 FM-086G-0-5E

Nitin Ventures FZE. (A Division of Nitin Fire Protection Industries Ltd.)

Model/Sprinkler Identification Number (SIN) Technical Data

Deluge & Preac tion Systems

TotalPac X Firecycle III Preaction Double interlock system

Series DS-1 Stainless Steel Dry-Type Sprinklers 5.6K Pendent, HSW, and Extended Coverage HSW Standard and Quick Response General Description

TotalPac 3 Double interlock Preaction, Electric/PneuLectric release Self-contained system

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

Specification/ Data Sheet

GG-VL-R REFRIGERANT VENT LINE SENSOR. Installation and Operation Manual

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

TotalPac X Single interlock SUREFIRE system

GASGUARD LEL 3 OPERATING & INSTALLATION MANUAL

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

mechanical. OPERATION Rapidrop Global

TotalPac 3 Firecyle III Deluge Remote controlled system

Instructions for. Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure. Single Interlock

TECHNICAL ASSISTANCE TOLL FREE TELEPHONE NUMBER TECHNICAL ASSISTANCE FAX:

GG-CO-EXP CARBON MONOXIDE SENSOR. Installation and Operation Manual

GG-NO2 NITROGEN DIOXIDE GAS SENSOR. Installation and Operation Manual

CD6102 / CD6102 OC / CD6102-2

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

BERMAD Fire Protection

GG-H2S HYDROGEN SULFIDE GAS SENSOR. Installation and Operation Manual

GASGUARD VENT LINE3. Ammonia Sensor OPERATING & INSTALLATION MANUAL

GASGUARD Cl 2. Chlorine Sensor OPERATING & INSTALLATION MANUAL

GASGUARD H2S EXP. Hydrogen Sulfide Sensor OPERATING & INSTALLATION MANUAL

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

TotalPac 3 Single interlock Firecyle III Preaction Self-contained system

Model CV-1F Grooved End Swing Check Valves. General Description. Technical Data. Installation. Page 1 of 6 FEBRUARY 2016 TFP1550. Worldwide Contacts

RAPID RESPONSE Series LFII Residential Sprinklers 4.4 K-factor Horizontal Sidewall, Dry Type Wet Pipe and Dry Pipe Systems

GASGUARD O 2. Oxygen Sensor OPERATING & INSTALLATION MANUAL

Transcription:

Technical Services: Tel: (800) 81-912 / Fax: (800) 91-00 Model QRS Electronic Accelerator (Quick Opening Device) For Dry Pipe or Preaction Systems General Description The Tyco Model QRS Electronic Accelerator is a quick opening device intended to reduce the operating time of a dry pipe valve in a dry pipe system or an automatic control valve (deluge valve) in a double interlock electric/electric preaction system. The control panel for the QRS may be used with up to four QRS switches for one to four system risers using of the following dry pipe valves: TFSBP & inch (DN100/10) Model DPV-1 Dry Pipe Valves. Central inch (DN80) Model AF or Central & inch (DN100/10) Model AF/AG Dry Pipe Valves. Gem & inch (DN100/10) Model F02/F021 Dry Pipe Valves. Star & inch (DN100/10) Models A or A-1 Dry Pipe Valves. The control panel for the QRS may be used with one QRS switch for one system riser using the following automatic control valve (deluge valve) used in a double interlock electric/electric preaction system: TFSBP1-1/2thru8inch(DN0thru DN200) Model DV- Deluge Valve. (Ref. Figure 1) utilizes a unique system air pressure monitoring device (UL and C-UL Listed, as well as FM Approved, Model QRS Extinguishing System Attachment) that continuously samples air pressure twice per second. When the air pressure is determined to have a sustained drop exceeding a rate of 0.1 psi (0,00 bar) per second as verified by three consecutive samplings, the QRS signals the Releasing Panel (Model PFC- 10-RC) via its Panel Input initiating zone circuit, which energizes the Solenoid Valve. Page 1 of 1 In the case of a dry pipe valve, the energized Solenoid Valve introduces system air pressure to the intermediate chamber of the dry pipe valve. This pressure neutralizes the differential pressure holding the dry pipe valve closed and permits it to open. In the case of a double interlock electric/electric preaction system, the energized Solenoid Valve releases diaphragm pressure from the automatic control valve (deluge valve) to permit the automatic control valve (deluge valve) to open. automatically adjusts to both small and slow changes in system pressure, but trips when there is a steady drop in pressure (as in the case of sprinkler operation). The QRS Electronic Accelerator features the following: Operation of a dry pipe or preaction MAY, 2009 valve within four seconds independent of various combinations of system initial air pressures, system volumes, or sprinkler K-factors. One release panel can control up to four dry pipe systems or one double interlock preaction system. Built-in low pressure and high pressure alarm supervision. Proven electric release technology as used for electrically operated deluge and preaction systems. Battery back-up in the event of primary power failure. NOTICE described herein must be installed and maintained in compliance with this document and with the applicable standards of the National Fire Protection Association, in addition to the

Page2of1 standards of any authorities having jurisdiction. Failure to do so may impair the performance of this device. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. The QRS uses electronic components to monitor the system air pressure. Keep all radio transmitters or RF sources at least one foot from the QRS. Failure to do so could result in an unintended operation of the dry pipe or preaction system. For additional information please refer to the Potter Electric Signal Company Data Sheet #111 for the QRS Quick Release Switch and/or Manual #0 for the PFC-10-RC Releasing Panel. Technical Data Approvals UL Listed: is UL Listed per UL18 for a maximum system capacity of 190 gallons (9 litters) for a single nominal. K-factor sprinkler and a maximum working water pressure of 1 psi (12,1 bar). FM Approved: is FM Approved based on the sensitivity criteria provided in Graph A and a maximum working water pressure of 20 psi (1,2 bar). Listings and approvals are under the name of Potter Electric Signal Company. NOTICE Quick operation of the Electronic Accelerator does not ensure that the fire protection system will meet the water delivery time requirement of the authority having jurisdiction (following opening of the Inspector s Test Connection). The sprinkler system design must be knowledgeable that water delivery time is primarily determined by the configuration and volume of the piping network, system air pressure at time of Accelerator trip, number and orifice size of open sprinklers, and water supply characteristics. In the case of a double interlock preaction system, water delivery is also based on the electric detection system operating before the first sprinkler activates. Dry Pipe Valve Compatibility is UL Listed and FM Approved for use with the following dry pipe valves: and " (DN 100/10) TFBP DPV-1 (DN80) Central AF and " (DN100/10) Central AF/AG and " (DN100/10) Gem F02/F021 and " (DN100/10) Star Model A and " (DN100/10) Star Model A-1 Preaction System Compatibility is UL Listed and FM Approved for use with the 1-1/2 thru 8 inch (DN0 thru DN200) Model DV- Double Interlock Electric/Electric Preaction System. Refer to Technical Data Sheet TFP1 for additional details. Maximum Working Air Pressure 0 psi (,8 bar) Pressure Decay For Trip Rating 0.1 psi/sec. (0,00 bar/s) High/Low Pressure Settings RefertoTableA. Environmental Specifications TheQRSQuickReleaseSwitchisfor indoor use only (NEMA 1/IP0). Battery Back-Up Battery back-up is provided by two BT-120 (12 AH) Batteries. The nominal battery back-up times are as follows for dry pipe systems: 0 hours in standby with four QRS s. With QRS s connected, 1 in alarm and the solenoid activated continuously, the batteries will provide 12 additional hours of standby. With QRS s connected, 1 in alarm and the solenoid activated continuously, the batteries will provide 1 additional hours of standby. With 2 QRS s connected, 1 in alarm and the solenoid activated continuously, the batteries will provide 1 additional hours of standby. For double interlock preaction systems, battery calculations must be performed by the system designer to determine adequacy of the two BT-120 (12 AH) Batteries to meet the requirements of the authority having jurisdiction. Battery size may be increased as necessary with the use of a separately ordered battery cabinet. Patent U.S.A. No.,91,080

Page of 1 THE QRS QUICK RELEASE SWITCH IS TO BE WI TO THE MODEL PFC-10-RC RELEASING PANEL USING SHIELDED CABLE IN METAL CONDUIT (RIGID OR FLEXIBLE). CONNECT DRAIN WIRE OF SHIELD TO EARTH GROUND OF THE PFC-10-RC ONLY. DO NOT CONNECT DRAIN WIRE TO QRS. SHIELDED CABLE: 8 CONDUCTOR, 22 AWG STRANDED, PVC JACKET, OVERALL FOIL SHIELD WITH DRAIN. (ALPHA WIRE TYPE 198C OR EQUIVALENT.) MODEL QRS QUICK RELEASE SWITCH P/N 92-12-1-001 INCH (DN100) MODEL DPV-1 DRY PIPE VALVE WITH TRIM SHOWN 120 VAC MODEL QRS ELECTRONIC ACCELERATOR TRIM P/N 2-12-2-001 MODEL PFC-10-RC RELEASING PANEL, P/N 201, WITH MODEL BT-120 BATTERY BACK-UP, P/N 201 2 VDC VALVE (NORMALLY CLOSED UNTIL ENERGIZED) P/N 2--1-02 FIGURE 1 MODEL QRS ELECTRONIC ACCELERATOR TYPICAL ARRANGEMENT SHOWN ON ONE DRY PIPE VALVE Switch Setting Low Air Threshold PSI (Bar) Nominal Pressure PSI (Bar) High Air Threshold PSI (Bar) 0 (0,8) 10 (0,9) 1 (1,0) 1 (0,8) 1 (1,0) 20 (1,8) 2 1 (1,0) 20 (1,8) 2 (1,2) 1 (1,0) 2 (1,2) 0 (2,0) 20 (1,8) 0 (2,0) (2,1) 2 (1,2) (2,1) 0 (2,) 0 (2,0) 0 (2,) (,10) (2,1) (,10) 0 (,) 8 (,10) (,9) 0 (,1) 9 (,9) (,8) 0 (,8) TABLE A HIGH/LOW PRESSURE SETTINGS FOR THE MODEL QRS QUICK RELEASE SWITCH

Pageof1 00 (1098) 200 (981) K 11.2 200 (908) K=8.0 MAXIMUM SYSTEM CAPACITY, GALLONS (LITRES) 2200 (82) 2000 (0) 1800 (81) 100 (0) 100 (299) K=. K=.2 1200 (2) 1000 (8) 800 (0) 10 20 0 0 0 0 (0,) (1,) (2,1) (2,8) (,) (,1) MINIMUM SYSTEM AIR PRESSURE, PSI (BAR) Note 1. Quick operation of the Electronic Accelerator does not ensure that the fire protection system will meet the water delivery time requirement of the authority having jurisdiction (following opening of the Inspector s Test Connection). The sprinkler system designer has to be aware that water delivery time is primarily determined by the configuration and volume of the piping network, system air pressure at time of Accelerator trip, number and orifice size of open sprinklers, and water supply characteristics. Note 2. The sensitivity criteria for the Model QRS Electronic Accelerator is a function of its pressure decay for trip rating of 0.1 psi (0,00 bar) per second, as well as the system volume, the K-factor of the sprinklers being utilized, and the minimum initial air pressure. The larger the system volume combined with smaller sprinkler K-factor or lower initial air pressure results in a slower air decay rate upon the first sprinkler operation. Conversely, a smaller system volume combined with a larger sprinkler K-factor or higher initial air pressure results in a faster air decay rate. Note. When the sprinkler system has been designed within the criteria provided by Graph A, operation of the Model QRS Electronic Accelerator and subsequent operation of the associated dry pipe or preaction valve can be expected within four seconds. In the case of the double interlock preaction system, operation is based on the electric detection system operating before a first sprinkler operation. Note. The minimum system air pressure must be the greater of that required for the dry pipe/preaction valve as a function of the maximum expected water supply pressure or per Graph A when using the Model QRS Electronic Accelerator. Note. When multiple sprinkler operations are being considered as in the case of using a dry system water delivery design per the 200 edition of NFPA 1, Section.2.., use the 11.2 K-factor and larger curve as referenced in Example. Example 1. Assuming a system volume of 100 gallons (80 liters) and the use of sprinklers having a K-factor of., the minimum system air pressure must be 18. psi (1, bar). Example 2. Assuming a system volume of 2000 gallons (0 liters) and the use of sprinklers having a K-factor of 8.0, the minimum system air pressure must be 1.0 psi (1,1 bar). Example. Assuming the use of a dry system water delivery design per the 200 edition of NFPA 1, Section.2.., wherein the operation of two. K-factor sprinklers might be anticipated (and the effective K-factor is then 11.2), the 11.2 K-factor and larger curve can be utilized. Consequently, assuming a system volume of 200 gallons (908 liters), the minimum system air pressure must be 11. psi (0,8 bar). GRAPH A MODEL QRS ELECTRONIC ACCELERATOR SENSITIVITY CRITERIA BASED ON FM APPROVAL

Page of 1 1/2" NPT ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT 1 9 QUICK RELEASE SWITCH 8 10 P/N 2-12-2-001 NO DESCRIPTION QTY P/N 1 Quick Release Switch, Model QRS........... 1 92-12-1-001 2 Solenoid Valve... 1 2--1-02 1/2" Union... 2 CH 1/2" Tee... 1 CH 1/2" 90 Elbow... 2 CH 1/2" x Close Nipple... 2 CH 8 1/2" x 1-1/2" Nipple... 2 1/2" x -1/2" Nipple... 1 CH CH 9 1/2" x -1/2" Nipple for Inch Valves....... 1 CH 1/2" x " Nipple for Inch Valves....... 1 CH 10 1/2" x 9-1/2" Nipple for Inch Valves....... 1 CH 1/2" x 8-1/2" Nipple for Inch Valves....... 1 CH CH: Common Hardware 2 VALVE INCH (DN100) MODEL DPV-1 DRY PIPE VALVE WITH TRIM 1/2" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE CHAMBER 1/2" NPT ACCELERATOR TRIM CONNECTION TO AIR SUPPLY PORT 1/2" CONDUIT CONNECTION TO RELEASING PANEL 1 QUICK RELEASE SWITCH 8 10 INCH (DN10) MODEL DPV-1 DRY PIPE VALVE WITH TRIM 9 2 VALVE 1/2" CONDUIT CONNECTION TO RELEASING PANEL 1/2" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE CHAMBER FIGURE 2 MODEL QRS ELECTRONIC ACCELERATOR RISER COMPONENTS INSTALLATION DIAGRAM FOR THE AND INCH MODEL DPV-1 DRY PIPE VALVES

Pageof1 NO. DESCRIPTION 1 Releasing Panel, Model PFC-10-RC.... 1 201 2 Battery Back-Up, ModelBT-120... 2 201 00 psi/ 2000 kpa Water Pressure Gauge.. 2 92--1-00 20 psi/ 10 kpa Air Pressure Gauge..... 1 92--1-012 1/" Gauge Test Valve.. 2-00-1-002 Quick Release Switch, Model QRS... 1 92-12-1-001 Model MC-1 Manual Control Station... 1 2-9-2-001 8 Model AD-1 Automatic Drain Valve... 1 2-9-2-00 9 Automatic Shut-Off Valve, ModelASV-1... 1 92--1-021 10 Waterflow Pressure Alarm Switch (PS10-2).. 1 210 11 Solenoid Valve... 1 2--1-02 12 1/" Pressure Relief Valve... 1 92--1-020 1 1/2" Ball Valve... 2-00-1-00 1 1/2" Spring Loaded CheckValve... 1 92-22-1-002 1 1/2" Y-Strainer... 1 2--1-00 29 LOCATION FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL VALVE 2 QTY. 8 9 10 NOTES: 1. Use only the Model CV-1FR Riser Check Valve. 2. All Fittings and Nipples are galvanized (Standard Order).. CH: Common Hardware.. See Figure 2 of TFP10 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel, Item 22. P/N 1 2 2 (GREEN TINT) 9 19 1 2 18 1 0 19 0 1 NO. 1 1/2" Swing Check Valve.1-09-1-00 1/2" Tee... CH 1 1/2" Globe Valve... 1-0-1-00 8 1/2" x 1/" x 1/2" Tee... CH 18 /" Swing Check Valve. 1-09-1-00 9 1/2" x 1/2" x 1/" Tee... 1 CH 19 /" Angle Valve... 2-08-1-00 0 1/2" Cross... 1 CH 20 Drip Funnel Connector.. 1 92-211-1-00 1 /" Tee... 1 CH 21 Drip Funnel Bracket... 1 92-211-1-00 2 /" x 1/2" x /" Tee... 2 CH 22 Drip Funnel... 1 92--1-00 1" x /" x 1/2" Tee... 1 CH 2 /2" Vent Fitting....... 1 92-02-1-002 1/" x Close Nipple... 2 CH 2 1/" x 18" Tubing... 1 CH 1/" x " Nipple... 1 CH 2 1/2" Tubing Connector.. 2 CH 1/2" x Close Nipple... CH 2 1/2" x 12" Tubing... 1 CH 1/2" x 1-1/2" Nipple... 1 CH 2 1/2" x 2" Tubing... 1 CH 8 1/2" x 2" Nipple... 1 CH 1/" Plug... CH 9 1/2" x 2-1/2" Nipple... CH 29 /" Plug... 1 CH 0 1/2" x " Nipple... 1 CH 0 1/2" x 1/" Reducing 1 1/2" x " Nipple... 2 CH Bushing... 1 CH 2 1/2" x " Nipple... 1 CH 1 1/2" Union... CH Select Nipple per Table.. 2 CH 2 /" Union... 1 CH Select Nipple per Table.. 2 CH 1/" 90 Elbow... 1 CH /" x 1-1/2" Nipple... CH 1/2" 90 Elbow... 8 CH /" x 2" Nipple... 1 CH /" 90 Elbow... 1 CH /" x " Nipple... 1 CH /" x 1/2" 90 Elbow... 1 CH 8 1" x 2" Nipple... 1 CH DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. 8 20 21 1 2 9 0 8 1 12 8 22 UNUSED PLUG PORTS 2" (DN0) GROOVE x GROOVE MODEL DV- 1 DELUGE VALVE SHOWN 1 9 RISER CHECK VALVE (NOTE 1) 1 1 1 Nipple Number 1 9 2 Select Appropriate Nipple Sizes per DV- Deluge Valve Size 1-1/2" (DN0) 1/2" x Close 1/2" x " 1, 2 1 2 1 8 2 2 11 2 P/N 2" (DN0) 1/2" x 2" 1/2" x -1/2" 1 8 FIGURE A PART 1 OF 1-1/2 and 2 INCH (DN0 and DN0) MODEL DV- DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION TRIM (2-8-2-1Q) WITH MODEL QRS ELECTRONIC ACCELERATOR EXPLODED VIEW

Page of 1 NO. DESCRIPTION 1 Releasing Panel, Model PFC-10-RC.... 1 201 2 Battery Back-Up, ModelBT-120... 2 201 00 psi/ 2000 kpa Water Pressure Gauge.. 2 92--1-00 20 psi/ 10 kpa Air Pressure Gauge..... 1 92--1-012 1/" Gauge Test Valve.. 2-00-1-002 Quick Release Switch, Model QRS... 1 92-12-1-001 Model MC-1 Manual Control Station... 1 2-9-2-001 8 Model AD-1 Automatic Drain Valve... 1 2-9-2-00 9 Automatic Shut-Off Valve, ModelASV-1... 1 92--1-021 10 Waterflow Pressure Alarm Switch (PS10-2).. 1 210 11 Solenoid Valve... 1 2--1-02 12 1/" Pressure Relief Valve... 1 92--1-020 1 1/2" Ball Valve... 2-00-1-00 1 1/2" Spring Loaded CheckValve... 1 92-22-1-002 1 1/2" Y-Strainer... 1 2--1-00 1 1/2" Swing Check Valve.1-09-1-00 29 LOCATION FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL VALVE 2 QTY. 9 8 NOTES: 1. Use only the Model CV-1FR Riser Check Valve. 2. All Fittings and Nipples are galvanized (Standard Order).. CH: Common Hardware.. See Figure 2 of TFP10 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel, Item 22. P/N 1 2 2 18 1 19 1 1/2" Globe Valve... 1-0-1-00 8 1/2" Tee... CH 18 /" Swing Check Valve. 1-09-1-00 9 1/2" x 1/" x 1/2" Tee... CH 19 1-1/" Angle Valve... 2-08-1-00 0 1/2" x 1/2" x 1/" Tee... 1 CH 20 Drip Funnel Connector.. 1 92-211-1-00 1 /" Tee... 1 CH 21 Drip Funnel Bracket... 1 92-211-1-00 2 /" x 1/2" x /" Tee... 2 CH 22 Drip Funnel... 1 92--1-00 1-1/" x 1-1/" x 1/2" Tee. 1 CH 2 /2" Vent Fitting....... 1 92-02-1-002 1/" x Close Nipple... 2 CH 2 1/" x 18" Tubing... 1 CH 1/" x " Nipple... 1 CH 2 1/2" Tubing Connector.. 2 CH 1/2" x Close Nipple... 2 CH 2 1/2" x 18" Tubing... 1 CH 1/2" x 1-1/2" Nipple... 20 CH 2 1/2" x 2" Tubing... 1 CH 8 1/2" x 2-1/2" Nipple... 1 CH 1/" Plug... CH 9 1/2" x -1/2" Nipple... 1 CH 29 /" Plug... 1 CH 0 1/2" x " Nipple... 1 CH 0 1/2" x 1/" Reducing Bushing... 1 CH 1 2 1/2" x -1/2" Nipple... 1 1/2" x " Nipple... 1 CH CH 1 1/2" Union... CH 1/2" x -1/2" Nipple... 1 CH 2 /" Union... 1 CH 1/2" x " Nipple... 2 CH 1/" 90 Elbow... 1 CH /" x 1-1/2" Nipple... CH 1/2" 90 Elbow... 8 CH /" x 2" Nipple... 1 CH /" x 1/2" 90 Elbow... 1 CH 1-1/" x 2" Nipple... 2 CH 1-1/" 90 Elbow... 1 CH 8 1-1/"x"Nipple... 1 CH 1/2" Cross... 1 CH 9 1-1/"x"Nipple... 1 CH 9 0 1 1 1 10 0 2 8 8 (GREEN TINT) 2 20 22 21 19 NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. 2 1 8 9 1 12 PLUG UNUSED PORTS " (DN80) GROOVE x GROOVE MODEL DV- DELUGE VALVE SHOWN RISER CHECK VALVE (NOTE 1) 1 0 1 1 1 2 9 2 1 8 1 9 2 1, 2 8 11 2 P/N 1 9 FIGURE A PART 2 OF INCH (DN80) MODEL DV- DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION TRIM (2-8-2-12Q) WITH MODEL QRS ELECTRONIC ACCELERATOR EXPLODED VIEW

Page8of1 NO. DESCRIPTION 1 Releasing Panel, 19 2" Angle Valve... 2-08-1-009 Model PFC-10-RC.... 1 201 20 Drip Funnel Connector.. 1 92-211-1-00 2 Battery Back-Up, 21 Drip Funnel Bracket... 1 92-211-1-00 ModelBT-120... 2 201 22 Drip Funnel... 1 92--1-00 00 psi/ 2000 kpa 2 /2" Vent Fitting....1 92-02-1-002 Water Pressure Gauge.. 2 92--1-00 2 1/" x 2" Tubing... 1 CH 20 psi/ 10 kpa 2 1/2" Tubing Connector.. 2 CH AirPressureGauge... 1 92--1-012 2 1/2" x 2" Tubing... 2 CH 1/" Gauge Test Valve.. 2-00-1-002 2 1/" Plug... CH Quick Release Switch, /" Plug... 1 CH Model QRS... 1 92-12-1-001 29 1/2" x 1/" Reducing Model MC-1 Manual Bushing... 1 CH Control Station... 1 2-9-2-001 0 1/2" Union... CH 8 Model AD-1 Automatic 1 1" Union... 1 CH Drain Valve... 1 2-9-2-00 2 1/" 90 Elbow... 1 CH 9 Automatic Shut-Off Valve, 1/2" 90 Elbow... 8 CH ModelASV-1... 1 92--1-021 1/2" Tee... CH 10 Waterflow Pressure 1/2" x 1/" x 1/2" Tee... CH Alarm Switch (PS10-2).. 1 210 1/2" x 1/2" x 1/" Tee... 1 CH 11 Solenoid Valve... 1 2--1-02 1/2" Cross... 1 CH 12 1/" Pressure Relief 8 /" x 1/2" x /" Tee... 2 CH Valve... 1 92--1-020 9 1" x 1/2" 90 Elbow... 1 CH 1 1/2" Ball Valve... 2-00-1-00 0 1" x /" x 1" Tee... 1 CH 1 1/2" Spring Loaded 1 2" 90 Elbow... 1 CH CheckValve... 1 92-22-1-002 2 2" x 2" x 1/2" Tee... 1 CH 1 1/2" Y-Strainer... 1 2--1-00 1/" x Close Nipple... 2 CH 1 1/2" Swing Check Valve.1-09-1-00 1 1/2" Globe Valve... 1-0-1-00 12 18 /" Swing Check Valve. 1-09-1-00 1 1 0 8 9 8 QTY. LOCATION FOR OPTIONAL ELECTRICALLY SUPERVISED N.O. ALARM CONTROL VALVE 2 10 P/N 2 (GREEN TINT) 19 NOTES: 1. Use only the Model CV-1FR Riser Check Valve. 2. All Fittings and Nipples are galvanized (Standard Order).. CH: Common Hardware.. See Figure 2 of TFP10 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel, Item 22. 1 8 0 1 2 2 2 18 2 19 NO. 0 DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. 8 29 0 1 9 0 0 1 0 9 2 2 2 PLUG UNUSED PORTS 8 20 21 " (DN100) FLANGE x GROOVE MODEL DV- DELUGE VALVE SHOWN 8 22 RISER CHECK VALVE (NOTE 1) 0 1 1 1/" x " Nipple... 1 CH 1/2" x Close Nipple... 2 CH 1/2" x 1-1/2" Nipple... 1 CH 1/2" x 2-1/2" Nipple... 2 CH 8 1/2" x " Nipple... 1 CH 9 1/2" x " Nipple... 2 CH 0 1/2" x " Nipple... 1 CH 1 1/2" x " Nipple... 2 CH 2 Select Nipple per Table.. 2 CH Select Nipple per Table.. 2 CH Select Nipple per Table.. 2 CH /" x 1-1/2" Nipple... 1 CH /" x 2" Nipple... 1 CH Select Nipple per Table.. 2 CH 8 1" x Close Nipple... 2 CH 9 1" x " Nipple... 1 CH 0 2" x " Nipple... CH Nipple No. 2 0 1 (DN100) 1/2" x 2-1/2" 1/2" x 2" 1/2" x -1/2" /" x 2-1/2" 2 0 9 Select Appropriate Nipple Sizes per DV- Deluge Valve Size " " 8" 2 0 9 (DN10) 1/2" x -1/2" 1/2" x " 1/2" x -1/2" /" x -1/2" 1, 2 1 2 11 2 P/N (DN200) 1/2" x 8-1/2" 1/2" x -1/2" 1/2" x 9" /" x -1/2" 0 FIGURE A PART OF,, and 8 INCH (DN100, DN10, and DN200) MODEL DV- DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION TRIM (2-8-2-122Q) WITH MODEL QRS ELECTRONIC ACCELERATOR EXPLODED VIEW

Page 9 of 1 NOTES: 1. Use only the 2" Model CV-1FR Riser Check Valve with 1-1/2" and 2" DV- Valves. Use corresponding sized Model CV-1FR Riser Check Valves for "-8" Model DV- Valves. 2. Nipples 1- vary in length relative to the Model DV- size used. Select per the table. All other nipples packed unassembled shall be installed per the appropriate trim exploded view, Figure A Part 1, 2, or.. Install subassemblies in alphabetical order.. See Figure 2 of TFP10 for Deluge Valve Port identification.. Route all Tubing to Drip Funnel. / INCH NPT CONNECTION FOR WATER MOTOR ALARM WATERFLOW PRESSURE ALARM SWITCH NIPPLE 1 NIPPLE MAIN DRAIN VALVE (NORMALLY CLOSED) SYSTEM WATER SUPPLY PRESSURE GAUGE ALARM TEST VALVE (NORMALLY CLOSED) B SYSTEM MAIN DRAIN CONNECTION (SIZED PER TABLE) SYSTEM MAIN DRAIN VALVE (NORMALLY CLOSED) VENT FITTING (GREEN TINT) C AUTOMATIC DRAIN VALVE E Nipple Select Appropriate Nipple Sizes per DV- Deluge Valve Size Number 1 2 1-1/2" (DN0) 1/2" x Close 1/2" x Close 2" (DN0) 1/2" x 2" 1/2" x Close " (DN80) 1/2" x 1-1/2" 1/2" x 1-1/2" " (DN100) 1/2" x 2-1/2" 1/2" x 2" " (DN10) 1/2" x -1/2" 1/2" x " 8" (DN200) 1/2" x 8-1/2" 1/2" x -1/2" 1/2" x " 1/2" x -1/2" 1/2" x " 1/2" x -1/2" 1/2" x -1/2" 1/2" x 9" /" x 1-1/2" /" x 1-1/2" /" x 1-1/2" /" x 2-1/2" /" x -1/2" /" x -1/2" System Main Drain /" NPT /" NPT 1-1/" NPT 2" NPT 2" NPT 2" NPT Size Main Drain Size SYSTEM AIR SUPPLY CONTROL VALVE (NORMALLY OPEN) DRIP FUNNEL WITH 1-1/ INCH NPT CONNECTION TO DRAIN PLUG UNUSED PORTS A MAIN DRAIN CONNECTION (SIZED PER TABLE) /" NPT /" NPT 1-1/" NPT 2" NPT 2" NPT F " (DN100) FLANGE x GROOVE MODEL DV- DELUGE VALVE SHOWN QUICK RELEASE SWITCH 1/2 INCH NPT CONNECTION FOR SYSTEM AIR SUPPLY SYSTEM AIR SUPPLY PRESSURE GAUGE RISER CHECK VALVE (NOTE 1) AUTOMATIC SHUT-OFF VALVE (NORMALLY OPEN) NIPPLE 2 D RELEASING PANEL WITH BATTERY BACK-UP VALVE (NORMALLY CLOSED) DIAPHRAGM CHAMBER SUPPLY CONTROL VALVE (NORMALLY 1/2 INCH NPT OPEN) CONNECTION FROM WATER SUPPLY 2" NPT 1/2 INCH CONDUIT CONNECTION FOR "ELECTRIC DETECTION" NIPPLE DIAPHRAGM CHAMBER PRESSURE GAUGE MANUAL CONTROL STATION FIGURE B 1-1/2 thru 8 INCH (DN0 thru DN200) MODEL DV- DELUGE VALVES DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION TRIM WITHMODEL QRS ELECTRONIC ACCELERATOR OPERATIONAL COMPONENTS

Page 10 of 1 CAUTION: THE QRS QUICK RELEASE SWITCH IS TO BE WI TO THE MODEL PFC-10-RC RELEASING PANEL USING SHIELDED CABLE IN METAL CONDUIT (RIGID OR FLEXIBLE). CONNECT DRAIN WIRE OF SHIELD TO EARTH GROUND OF THE PFC-10-RC ONLY. DO NOT CONNECT DRAIN WIRE TO QRS. SHIELDED CABLE: 8 CONDUCTOR, 22 AWG STRANDED, PVC JACKET, OVERALL FOIL SHIELD WITH DRAIN. (ALPHA WIRE TYPE 198C OR EQUIVALENT.) JUMPER JUMPER TAMPER ALARM HIGH/ 2VDC LOW EOLR AIR 1 2 8 9 LAST QRS SWITCH JUMPER JUMPER TAMPER ALARM HIGH/ 2VDC LOW EOLR AIR 1 2 8 9 GREEN VIOLET BLUE BROWN ORANGE YELLOW TYPICAL WIRING FOR QRS 1, 2 OR (ALL BUT LAST) FIRST, SECOND OR THIRD QRS SWITCH GREEN VIOLET BLUE WIRING FOR LAST QRS ONLY BROWN EOLR.1 K EOLR LOCATE AT LAST QRS ORANGE YELLOW NOT USED ON LAST QRS DO NOT CONNECT SHIELD ALPHA WIRE TYPE 198C OR EQUIVALENT DO NOT CONNECT SHIELD ALPHA WIRE TYPE 198C OR EQUIVALENT SYSTEM 1 SYSTEM 2 SYSTEM SYSTEM SHIELD SHIELD SHIELD SHIELD GREEN VIOLET ORANGE YELLOW BLUE BROWN GREEN VIOLET ORANGE YELLOW BLUE BROWN GREEN VIOLET ORANGE YELLOW BLUE BROWN GREEN VIOLET ORANGE YELLOW BLUE BROWN NOT USED ON LAST QRS 2VNR DC AUX. POWER 2VR DC SUP + SUP - ABORT SUPERVISORY ZONE 1 ZONE 2 ZONE ZONE GND. OUTPUT 1 OUTPUT 2 OUTPUT OUTPUT PFC-10-RC PANEL REFERENCE WIRING DIAGRAM PROGRAM #1.1K S SYSTEM 1 RELEASING END OF LINE DIODE ASS'Y PART #00012 INSTALL AT LOCATION FIGURE WIRING DIAGRAM FOR MODEL QRS ELECTRONIC ACCELERATOR FOR DRY PIPE VALVE(S).1K S SYSTEM 2 RELEASING END OF LINE DIODE ASS'Y PART #00012 INSTALL AT LOCATION.1K S SYSTEM RELEASING END OF LINE DIODE ASS'Y PART #00012 INSTALL AT LOCATION.1K S SYSTEM RELEASING END OF LINE DIODE ASS'Y PART #00012 INSTALL AT LOCATION

Page 11 of 1 CAUTION: THE QRS QUICK RELEASE SWITCH IS TO BE WI TO THE MODEL PFC-10-RC RELEASING PANEL USING SHIELDED CABLE IN METAL CONDUIT (RIGID OR FLEXIBLE). CONNECT DRAIN WIRE OF SHIELD TO EARTH GROUND OF THE PFC-10-RC ONLY. DO NOT CONNECT DRAIN WIRE TO QRS. SHIELDED CABLE: 8 CONDUCTOR, 22 AWG STRANDED, PVC JACKET, OVERALL FOIL SHIELD WITH DRAIN. (ALPHA WIRE TYPE 198C OR EQUIVALENT.) JUMPER JUMPER TAMPER ALARM HIGH/ 2VDC LOW EOLR AIR 1 2 8 9 QRS SWITCH GREEN VIOLET BLUE BROWN EOLR.1 K EOLR LOCATE AT QRS ORANGE YELLOW NOT USED DO NOT CONNECT SHIELD ALPHA WIRE TYPE 198C OR EQUIVALENT SYSTEM DETECTION SEE POTTER MANUAL #0 SHIELD GREEN VIOLET ORANGE YELLOW BLUE BROWN NOT USED SEE POTTER MANUAL #0 2VNR DC AUX. POWER 2VR DC SUP + SUP - ABORT SUPERVISORY ZONE 1 ZONE 2 ZONE ZONE GND. OUTPUT 1 OUTPUT 2 OUTPUT OUTPUT PFC-10-RC PANEL REFERENCE WIRING DIAGRAM PROGRAM #1 SEE POTTER MANUAL #0 FIGURE WIRING DIAGRAM FOR MODEL QRS ELECTRONIC ACCELERATOR FOR DOUBLE INTERLOCK ELECTRIC/ELECTRIC PREACTION SYSTEMS.1K S SYSTEM RELEASING END OF LINE DIODE ASS'Y PART #00012 INSTALL AT LOCATION SEE POTTER MANUAL #0

Page 12 of 1 Installation The Tyco Model QRS Electronic Accelerator must be installed in accordance with the following instructions: Step 1. The QRS Electronic Accelerator Riser Components (P/N 2-12-2-001) must be installed per Figure 2 or as applicable; the Model DV- Double Interlock Preaction Trim with Electric/Electric Actuation and Model QRS Electronic Accelerator must be installed per Figure ; the solenoid valve must be installed with its flow direction arrow as indicated; and, pipe thread sealant is to be applied sparingly to male threads only. Step 2. The Releasing Panel is to be located in a dry and protected area; however, it should be located in close proximity to the valve riser(s). (In the case of one panel being used for multiple dry pipe valve risers, it is recommended that a single panel only be used when the multiple risers are adjacent to each other. Otherwise, difficulty may be encountered when performing the resetting procedure.) Step. The QRS Quick Release Switch, Solenoid Valve, and Releasing Panel must be wired per Figure or as applicable. All electrical connections are to meet the requirements of NFPA 2. NOTICE Figure, provides the wiring connections for dry pipe systems using the PFC-10-RC Standard Program #1. Figure provides the wiring connections for a double interlock electric/electric preaction system using the PFC-10-RC Standard Program #1. In the case of Figure, the EOLR for the supervisory circuit is located in the last QRS Quick Release Switch. In the case of Figure, the EOLR for the supervisory zone is located at the QRS and the Orange and Yellow wires are not used. Any tamper switches for system shut off valves required for double interlock preaction systems should be connected to Zone of the PFC-10-RC releasing panel which is programmed as a Tamper Zone. Refer to PFC-10-RC Manual #0. The QRS Quick Release Switch is only to be wired to the Model PFC-10-RC Releasing panel using shielded cable in metal conduit (rigid or flexible). Connect drain wire of the shield to earth ground of the PFC-10-RC only. Do not connect drain wire to the QRS. Shielded cable: 8 conductor, 22 AWG stranded, PVC jacket, overall foil shield and drain. (Alpha wire type 198C or equivalent. Color coding provided in the wiring diagrams is applicable to Alpha wire type 198C.) All QRS wiring must be terminated (landed) while the PFC-10-RC is de-energized. Failure to do so may result in unseen damage to the QRS, rendering it inoperable. To de-energize the PFC-10-RC, disconnect the stand-by batteries then disconnect the A/C input. Reverse this process to re-energize the panel. For additional PFC-10-RC Releasing Panel information (e.g. power and battery connections, programming, basic operation, etc.,) refer to the Potter Electric Signal Company Manual #00. For additional QRS Quick Release Switch information refer to the Potter Electric Signal Company Data Sheet #111. Step. As a function of the nominal air pressure to be maintained in the sprinkler system, set the 10 position, high/low level, rotary switch setting of the QRS Quick Release Switch using the information provided in Table A on Page 12, as well as inside the cover of the QRS Quick Release Switch. Step. To complete the installation, the cover of the QRS Quick Release Switch must be securely fastened to the base to ensure metal to metal connect, and the PFC-10-RC Releasing panel must be programmed using Standard Program #1 or #1, as applicable. Programming instructions are provided in Potter Electric Signal Company Manual #00. Setting Procedure (Dry Pipe Valve) The Dry Pipe System and the Tyco Model QRS Electronic Accelerator must be reset and restored to service as soon as possible after an operation. NOTICE The system must be completely drained before proceeding. In the case of one panel serving multiple risers, whenever the Program Switch is moved to the right (Steps and ), the QRS Electronic Accelerators is taken out of service for all connected system risers. Therefore, the proper authorities and all personnel who may be affected must be notified. In the event of a fire and where a QRS Electronic Accelerator has been taken out of service, an increased time in water delivery can be expected. Step 1. If desired and until the system is to be set for service, the internal audible alarm may be silenced by momentarily depressing the Buzzer Silence button (Figure ). Step 2. Locate of all of the system s low point drain valves to help facilitate resetting of the system. Step. Follow the resetting procedure for the dry pipe valve using the instructions provided in the technical data sheet for the dry pipe valve. When the procedure calls for the system piping to be pressurized with air, proceed with Step. Step. Momentarily press the System Reset button (Figure D) and then move the Program Switch to the right. The display will read OK to charge system. Begin applying air pressure to the system. At this point the solenoid valve will be de-energized and allowed to close to enable pressurization of the system piping, and a 0 minute countdown to repressurize the system will be displayed. NOTICE If within 0 minutes, the Program Switch is not returned to the left position during the upcoming Step, the releasing panel will automatically revert to a normal condition. If at least 8 psi has not been reached, the solenoid valve will be energized and open. If at least the low air pressure threshold of Table A has not been reached, a supervisory condition will occur. If more than 0 minutes is required, the counter can be restarted before the 0 minutes has elapsed. In order to reset the counter, the system must be pressurized to at least 8 psi, at which time the Program Switch can can be moved to the left and then quickly back to the right. A 0 minute countdown will then be restarted. Step. When the system reaches an air pressure of approximately 10 psi and while the system is in process of reaching its intended pressure, blowdown each drain valve one at a time (including the low body drain (or priming level valve) at the dry pipe valve and the Inspector s Test Connection) by opening each drain valve until water ceases to drain and then closing the drain valve. The blow-down procedure that will assure complete draining

Page 1 of 1 OUTPUT LED STEADY: ABORT ZONE 1 OUTPUT 1 ZONE 2 OUTPUT 2 ZONE OUTPUT ZONE OUTPUT PROGRAM MODE RUN MODE RUN PROGRAM AC POWER POWER TBL SYSTEM TBL SUP TBL GROUND FAULT SUP 1/ABORT SUPERVISORY 2 COMMON ALARM ALARM SILENCE STEADY: DISCHARGED FLASHING: PRE- DISCHARGE SET SCROLL-UP BUZZER SILENCE } LAMP TEST SCROLL-DOWN BUZZER SILENCE SELECT SIGNAL SILENCE FUNCTION SYSTEM RESET VIEWING ANGLE FIGURE OPERATING INTERFACE FOR THE MODEL PFC-10-RC RELEASING PANEL of the system will be more easily accomplished with 10 psi air pressure in the system. Step. When the system reaches the intended pressure and the pressure is stabilized, return the Program Switch (Figure)totheleft. Step. After waiting at least 0 seconds, open the Inspector s Test Connection, wait seconds, and then close the Inspector s Test Connection. Verify that the time to Accelerator trip is essentially the same as in previous tests. A momentary burst of air from a dry pipe valve s Automatic Drain Valve indicates that the QRS has tripped. In addition the Display on the Operating Interface of the Release Panel will notify operation. This procedure will also allow any scale and debris to be cleared from the pipe and nipples that are connected solenoid valve. Momentarily press the System Reset button and then move the Program Switch to the right. The display will read OK to charge system. At this point, once again, the solenoid valve will be de-energized and allowed to close to enable pressurization of the system piping. Allow the system to automatically return to its intended pressure via its automatic air supply, and, after waiting for the pressure to stabilize, return the Program Switch to the left, Step 8. Partially open the Main Control Valve. Slowly close the system s Main Drain Valve as soon as water discharges from the drain connection. Depress the plunger on the dry pipe valve s Automatic Drain Valve to make sure that it is open and that no water discharges. The absence of water discharge from the Automatic Drain Valve is an indication of a properly set water seat within the dry pipe valve. If water is discharging, refer to the Care and Maintenance section within the technical data sheet for the dry pipe valve to determine/correct the cause of the leakage problem. If there are no leaks, the system s Main Control Valve must be fully opened. The system is now set for service. NOTICE After setting a fire protection system, notify the proper authorities and advise those responsible for monitoring proprietary and/or central station alarms. Setting Procedure (Preaction System) The Tyco Model DV- Double Interlock Electric/Electric Preaction System and the Tyco Model QRS Electronic Accelerator must be reset and restored to service as soon as possible after an operation. Refer to Technical Data Sheet TFP1 for details.

Page 1 of 1 Care and Maintenance The following procedures and inspections should be performed as indicated, in addition to any specific requirements of the NFPA, and any impairment must be immediately corrected. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 2), in addition to the standards of any authority having jurisdiction. The installing contractor or product manufacturer should be contacted relative to any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service. must be maintained and serviced in accordance with the following instructions: NOTICE The QRS uses electronic components to monitor the system air pressure. Keep all radio transmitters or RF sources at least one foot from the QRS. Failure to do so could result in an unintended operation of the dry pipe or preaction system. If an Accelerator is to be temporarily taken out of service, the proper authorities and all personnel who may be affected must be notified. Before performing an alarm test, notify the proper authorities and all personnel who may be affected. Before closing a fire protection system main control valve for inspection or maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Model QRS Electronic Accelerator Testing Procedure It is recommended that the following Accelerator test procedure be performed quarterly. Step 1. When operation of the dry pipe/preaction valve is not intended during the Accelerator trip test, close the system s Main Control Valve and open the system s Main Drain Valve to relieve the supply pressure to the dry pipe/preaction valve. Otherwise proceed as follows. Step 2. For a dry pipe system, open the Inspector s Test Connection. Verify that the time to Accelerator trip is essentially the same as in previous tests. A momentary burst of air from a dry pipe valve s Automatic Drain Valve indicates that the Accelerator has tripped. In addition the Display on the Operating Interface of the Release Panel will notify operation. For a double interlock electric/electric preaction system, first operate the detection system and then open the Inspector s Test Connection. Verify that the time to Accelerator trip is essentiallythesameasinprevioustests. Release of the DV- diaphragm pressure though the open solenoid valve indicates that the Accelerator has tripped. In addition, the Display on the Operating Interface of the Release Panel will notify operation. Step. Reset the Model QRS Electronic Accelerator in accordance with the appropriate Setting Procedure Section. Release Panel and Batteries Inspect, test, and maintain per the instructions provided for the Model PFC-10-RC Releasing Panel. Limited Warranty Products manufactured by Tyco Fire Suppression & Building Products (TFSBP) are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFSBP. No warranty is given for products or components manufactured by companies not affiliated by ownership with TFSBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFSBP to be defective shall be either repaired or replaced, at TFSBP s sole option. TFSBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. TFSBP shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer s representatives. In no event shall TFSBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential damages, including but not limited to labor charges, regardless of whether TFSBP was informed about the possibility of such damages, and in no event shall TFSBP s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, express or implied, including warranties of merchantability and fitness for a particular purpose. This limited warranty sets forth the exclusive remedy for claims based on failure of or defect in products, materials or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full extent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder.

Page 1 of 1 NOTES: 1. Installation notes are typical of all Dry Pipe Valve models shown. 2. Some items provided with the Model QRS Trim (P/N 2-12-2-001) are not used and may be discarded. Field fabrication of additional materials will be required to facilitate connection to the existing system riser accelerator connection. NO DESCRIPTION QTY P/N 1 Quick Release Switch, Model QRS........... 1 92-12-1-001 2 Solenoid Valve... 1 2--1-02 1/2" Union... 2 CH 1/2" Tee... 1 CH 1/2" x Close Nipple... 2 CH CH: Common Hardware 1 1 1 FLOW FIELD FABRICATE TO SUIT FROM 1/2" NPS PIPE AND FITTINGS FLOW 1/2" NPT SYSTEM RISER ACCELERATOR CONNECTION 2 FLOW RIGHT SIDE VIEW Refer to Data Sheets: Central Inch Model AF, 10-.2 (-9), and & Inch Model AF/AG, 10-.0 (-9) or 10-.0 (-9), Star Model A-1 2-2.1.1 (2-00) Inch 2-2.1.1 (2-00) Inch 2 RIGHT SIDE VIEW Refer to Data Sheets: Star Model A 2-2.1.0 (-9) Inch 2-2.1.0 (-9) Inch 2 1/2" NPT ACCELERATOR TRIM CONNECTION TO INTERMEDIATE CHAMBER LEFT SIDE VIEW Refer to Data Sheet: Gem & Inch Model F02/F021 TD10 (11-9) FIGURE MODEL QRS ELECTRONIC ACCELERATOR RISER COMPONENTS INSTALLATION DIAGRAM WITH DRY PIPE VALVES MANUFACTU BY TFSBP OTHER THAN THE MODEL DPV-1 DRY PIPE VALVE

Page 1 of 1 Ordering Procedure DryPipeValve Electronic Accelerator Package (Required components for one dry pipe valve riser or one double interlock electric/electric preaction system riser): Specify: Model QRS Electronic Accelerator Package, P/N 2-12-2-102. Package includes the following: Model QRS Electronic Accelerator Riser Components (Qty. 1), P/N 2-12-2-001. Model PFC-10-RC Releasing Panel, (Qty. 1) P/N 201. Model BT-120 12.0 AH Battery (Qty. of 2 provided and required), P/N 201. DryPipeValve Electronic Accelerator Riser Components (One each required for each additional dry pipe riser up to three additional dry pipe risers): Specify: Model QRS Electronic Accelerator Riser Components, P/N 2-12-2-001. Model DV- Double Interlock Preaction Trim with Elecrtric/Electric Actuation and Model QRS Elctronic Accelerator (Refer to Technical Data Sheet TFP1 for additional details): Specify: (specify size), Galvanized, Semi-Preassembled Double Interlock Preaction System with Electric/Electric Actuation Trim and Model QRS Electronic Accelerator for Model DV- Deluge Valves, P/N (specify). 1-1/2 & 2 Inch Galvanized............P/N 2-8-2-1Q Inch Galvanized............P/N 2-8-2-12Q, & 8 Inch Galvanized............P/N 2-8-2-122Q Replacement Parts: (Specify description) for use with Model QRS Electronic Accelerator, P/N (see Figure 1). 2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, 1 North Cannon Avenue, Lansdale, Pennsylvania 19