Remote Booster Power Supply Technical Reference Manual

Similar documents
Booster Power Supply Manual

KM300 Carbon Monoxide Detection System Installation Manual

R Series Remote Annunciators and Expander Installation and Operation Guide

RMS/RPX Reader. User Manual

SIGA-CC1 Single Input Signal Module Installation Sheet

TruVision Bullet IR Camera Pocket Guide

Installation Manual. Wiegand Interface Unit Four-State (WIU-4) North America T F Asia T F

TruVision Bullet IR Camera Pocket Guide

MR-2602 Two Zone Fire Alarm Control Panel

Signature Series Auto-Sync Output Module (CC1S)

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

PSN-1000 & PSN 1000(E) Installation Manual

Addressable NAC Output Module D327A

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

4100U City and Relay Cards Installation Instructions

CZ-6A Six Zone Interface Module

Print Specification. Publication. Instructions. Specific requirements. General requirements

SC-6 Six Supervised Control Module

Remote Booster Power Supplies

Installation Guide for models:

FEC403EN Installation Manual

/9308 External Battery Chargers Installation Instructions

Installation Guide for models:

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

30.45 Electric Release PDRP-2001

KFP-CF Series Operation Manual

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

FCPS-24F FIRE ALARM FIELD CHARGER/POWER SUPPLY FOR FIRE PROTECTION/SIGNALING SERVICE FCPS-24F/FCPS-24FE. Field Charger/Power Supply

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

FTP-1000 Touchpad/Display Installation Manual

FIREFORCE 8 NOTIFICATION APPLIANCE CIRCUIT EXPANDER INSTALLATION & OPERATION MANUAL

Remote NAC Power Supply D7038

1X-F Series Installation Manual

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

LDM Series Lamp Driver Modules For Graphic Annunciation and Control

Use this product according to this instruction manual. Please keep this instruction manual for future reference.

Cautions and Warnings. Introduction 4009 NAC POWER EXTENDER

AL800ULADA. NAC Power Extender. Installation Guide

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Series. Access Power Controllers. Installation Guide

MMF Six Zone Interface Module

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

IDP-Zone-6 Six Zone Interface Module

Installation Manual CFP-105. Fire Alarm Control Panel. Version 1.0

Series SPB Audio Boosters Installation, Testing, Operation, and Maintenance Manual

LifeAlarm Fire Alarm Controls

AL1002ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

Notification Appliance Circuit Module

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

AL600ULADA. NAC Power Extender. Installation Guide

R-Series Remote Annunciators and Expanders Installation and Operation Guide

Genesis Low Frequency (520 Hz) Horn-Strobe Installation Sheet

POWERPATH PS-8 (105531) PS-8E (100263) PS-6 (105530) PS-6E (100262)

Field Charger/Power Supply FCPS-24S6 FCPS-24S8. Document # /06/03 Revision: C1 PN: 51977:C1 ECN

1 Watt Supervised Self-Amplified Strobe Speakers Round Flush Grille with 75cd Strobe

PN: 51883:D ECN Field Charger/Power Supply FCPS-24FS6 FCPS-24FS8. Document # /14/05 Revision: D

1. POWERPATH Operation

FCPS-24F/FCPS-24FE. Field Charger/Power Supply D P/N 50079:D ECN Installation, Operation and Application Manual

AL1042ULADA. NAC Power Extender. Installation Guide (See Application Guide for additional information) Rev

Supplement to The PDRP-1001/PDRP-1001A/PDRP-1001E Deluge Preaction Control Panel Manual

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Long Range Radio Alarm Transmitter

* These Remote Mics must be SPRM-GP

SAFEPATH SP40/2 D10 D35 AMP P/N P/N Installation, Testing, TONE SW Operation, and W4 Maintenance D54 SHORT

FA-1000 SERIES. Microprocessor-Based Fire Alarm Control Panel. Installation and Operation Manual

Dimensions of the Optional Mounting Box (BB-400R/W)

ANNUNCIATOR FIXED MODULE

ZP2 Series Operation Manual

Long Range Radio Alarm Transmitter

Data Sheet Fire Safety & Security Products. System Overview. Initiating Circuits SXL-EX FACP 7906

1 INTRODUCTION NOTICE WARNINGS AND CAUTIONS NATIONAL APPROVALS EMC COMPATIBILITY UNPACKING...

Installation, Operating and Maintenance Manual

TrueAlert Notification Appliances

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

PERMACONN PM1030 Includes DI300. Installation Manual

EXTINGUISHING AGENT RELEASE MODULE

ACC-25/50ZST. Zoned System Voice with Telephone Evacuation Control Panel

UNC100 Integra Manual

/5121/5122 TrueAlert Power Supply Installation Instructions

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

FiRe mobile-2 Operation Manual

AL1042ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev X

XP6-C. Six Circuit Supervised Control Module and SYNC-1 Accessory Card

Model 17A00 Expansion Enclosure

SILENT KNIGHT. Model SK-2/E & SK-4/E. Installation and Operations Manual. Fire Alarm Control Panel. Part Number Rev. A ECN /08/05

Pre-March 2016 Design - Click to be redirected to newer SBS-H2 design SBS-H2. Hydrogen Gas Detector Kit

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

ECC-50/100C. Emergency Command Center

IFS Fiber Module Installation & Operation Instructions

INSTALLATION INSTRUCTIONS MODEL PA-250 AND PA-500 BOOSTER AMPLIFIER

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

Independent Zone Control (I.Z.C.)

LIEBERT LIQUI-TECT 460 KIT ZONE LEAK-DETECTION SENSOR WITH CABLE

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

Table 1: dba Ratings for AMT Multitone Signal Typical Anechoic dba at 10 Feet per CAN/ULC S525-07

Operation and Installation Guide. Fire Alarm Control Panel

Installation Manual. Wiegand Interface Unit Two-State (WIU-2) North America T F Asia T F

Transcription:

E Security Fire & Life Safety Remote Booster Power Supply Technical Reference Manual P/N 3100485 RE 3.0 ISS 06JUL07

Copyright Copyright 2007 E Security, Inc. ll rights reserved. This document may not be copied in whole or in part or otherwise reproduced without prior written consent from E Security, Inc., except where specifically permitted under U.S. and international copyright law. Document number: 3100485 Revision: 3.0 Disclaimer The information in this document is subject to change without notice. E Security, Inc. ( E Security ) assumes no responsibility for inaccuracies or omissions and specifically disclaims any liabilities, losses, or risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document. For the latest documentation, contact your local supplier or visit us online at www.gesecurity.com. This publication may contain examples of screen captures and reports used in daily operations. Examples may include fictitious names of individuals and companies. ny similarity to names and addresses of actual businesses or persons is entirely coincidental. Trademarks and patents E and the E monogram are registered trademarks of eneral Electric Company. The Remote Booster Power Supply name and logo are registered trademarks of E Security. Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products. Intended use Use this product only for the purpose it was designed for; refer to the data sheet and user documentation for details. For the latest product information, contact your local supplier or visit us online at www.gesecurity.com. FCC compliance This equipment has been tested and found to comply with the limits for a Class digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. You are cautioned that any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment. European Union directives The European directive Waste Electrical and Electronic Equipment (WEEE) aims to minimize the impact of electrical and electronic equipment waste on the environment and human health. For proper treatment, recovery, and recycling, you can return the equipment marked with this symbol to your local supplier upon the purchase of equivalent new equipment, or dispose of it in designated collection points. Further information can be found on the following website: www.recyclethis.info. European representative for manufacture (EMC): E Security B.., Kelvinstraat 7, 6003 DH Weert, The Netherlands.

Content Important information iii Limitation of liability iii Remote Booster Power Supply FCC compliance iii Introduction 4 Models covered 4 Compatibility 4 Installation procedure checklist 5 etting started 6 Description 6 Component descriptions 6 Specifications 7 LED indicators 8 Installing the enclosure 10 Enclosure dimensions 10 Installing option modules in the enclosure 11 Installing the circuit board in the enclosure 13 Setting the jumpers 14 NC Class or Class B (JP1 and JP2) 14 round fault enable (JP3) 14 Battery charging (JP4) 15 Setting the DIP switches 16 Sense 1 and 2 operation (SW1-1 to 3) 16 Synchronization control (SW1-4) 17 NC circuit operation (SW1-5 to 8 and SW2-1 to 4) 18 enesis mode for continuous NCs (SW2-5) 19 C power loss reporting (SW2-6) 19 uxiliary control during C power loss (SW2-7) 20 Class or B NC configuration (SW2-8) 20 Wire routing 21 Connecting the field wiring 22 C power wiring 22 Battery wiring 22 NC Class B (Style Y) wiring 23 NC Class (Style Z) wiring 23 UX power wiring 24 Common trouble relay wiring 25 Sense circuit wiring 25 Tests for grounds, opens, and shorts 26 NC wiring using CC1(S) modules 27 Single CC1(S) using the BPS s 200 m UX Continuous circuit 27 Multiple CC1(S) modules using the BPS s sense inputs 28 Multiple CC1(S) modules using one of the BPS s NC/UX circuits 29 Installing the 3-TMP tamper switch 30 Battery calculation worksheet 31 Notification appliance circuit calculations 33 Introduction 33 What you ll need 33 Worksheet method 35 Equation method 36 Understanding BPS synchronization 39 Connection of booster power supplies 39 Synchronization of visible outputs 40 Synchronization of visible and audible outputs 40 Remote Booster Power Supply Technical Reference Manual i

Important information pplications 42 Key 42 enesis circuit notification 43 Conventional visible and audible circuit notification 44 Conventional visible and audible circuit to enesis notification 45 Conventional audible or visible circuit to enesis notification 45 enesis visible circuit and conventional audible circuit to enesis notification 46 Conventional split mode circuit with fault tolerance notification 47 enesis split mode circuit with fault tolerance notification 48 CDR-3 Coder to enesis notification 48 CDR-3 Coder to conventional notification 49 CDR-3 Coder to enesis visibles and conventional audibles 50 Security 50 ccess control power supply 51 ii Remote Booster Power Supply Technical Reference Manual

Important information Important information Limitation of liability This product has been designed to meet the requirements of NFP 72 National Fire larm Code, UL 864 Standard for Control Units for Fire Protective Signaling Systems, and ULC S527 Standard for Control Units for Fire larm Systems. Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory. E Security shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of E Security products beyond the cost of repair or replacement of any defective products. E Security reserves the right to make product improvements and change product specifications at any time. While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, E Security assumes no responsibility for errors or omissions. Remote Booster Power Supply FCC compliance This equipment can generate and radiate radio frequency energy. If the equipment is not installed in accordance with this manual, it may cause interference to radio communications. This equipment has been tested and found to comply with the limits for Class computing devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules are designed to provide reasonable protection against such interference when this equipment is operated in a commercial environment. Operation of this equipment is likely to cause interference, in which case the user, at his own expense, will be required to take whatever measures may be required to correct the interference. Remote Booster Power Supply Technical Reference Manual iii

Introduction Introduction This installation manual is intended for use by installers and field technicians. It provides the installation procedures, wiring diagrams, DIP switch settings, etc. required to install and set up the Remote Booster Power Supply (BPS). Models covered The following table lists the booster power supply models that are covered in this manual. Catalog number BPS6 BPS6/230 BPS6C BPS6C MIRBPS6 MIRBPS6/230 XLS-BPS6 XLS-BPS6/230 EBPS6 EBPS6/230 BPS10 BPS10/230 BPS10C BPS10C MIRBPS10 MIRBPS10/230 XLS-BPS10 XLS-BPS10/230 EBPS10 EBPS10/230 Description 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 6.5 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply 10 booster power supply Compatibility The input circuits of the booster power supply can be connected to 12 DC or 24 DC systems. For details about device compatibility, refer to the Remote Booster Power Supply ULI and ULC Compatibility List (P/N 3100656). 4 Remote Booster Power Supply Technical Reference Manual

Installation procedure checklist Installation procedure checklist Follow these steps to install and set up the booster power supply (BPS). Unpack the equipment Review the etting started section Review the applications: Review the applications to determine how you want to use the BPS. See the pplications section. Prepare the site: Make sure the installation location is free from construction dust and debris and extreme temperature ranges and humidity. Install the enclosure: See Installing the enclosure for enclosure dimensions. Install option modules if required: See Installing option modules in the enclosure. Set the jumpers: See Setting the jumpers. Set the DIP switch options: See Setting the DIP switches. Review wire routing: See Wire routing. Connect the field wiring: See Connecting the field wiring. Install the 3-TMP tamper switch (if one is used): See Installing the 3-TMP tamper switch. Test for proper operation WRNIN: Make sure that the C power circuit breaker is off before connecting wires to the terminal block. Caution: Turn on C power before connecting the batteries. Remote Booster Power Supply Technical Reference Manual 5

etting started etting started Description The 6.5 amp and 10 amp booster power supplies are designed to extend the signaling capacity of a fire alarm, security, or access control system. The BPSs can be connected to existing Class or Class B notification appliance circuits (NCs) or activated via option modules. The BPSs can either pass or generate synchronization signals for enesis sync strobes. The BPSs have four independent NC/UX circuits that are supervised when configured for NC, plus a trouble relay. Component descriptions 1 2 3 4 5 6 7 12 10 9 8 11 Component Description 1 Enclosure: Houses the electronics and two standby batteries 2 Heat sink: Distributes heat away from the circuit board 3 Circuit board: Provides connections for all circuits 4 Tamper switch standoffs: 3-TMP mounting standoffs 5 Jumper JP3: round fault enable or disable option 6 C LED: C power on 6 Remote Booster Power Supply Technical Reference Manual

etting started Component Description 7 Mounting brackets: Option module mounting brackets 8 Jumpers JP1 and JP2: Class or Class B NC option 9 DIP switches: Two eight-position DIP switches used for configuration 10 Circuit LEDs: NC, battery, and ground fault trouble LEDs 11 Batteries: Up to two 10 h batteries fit in the enclosure. For larger batteries, use an external battery cabinet (BC-1 or BC-2). 12 Jumper JP4: Battery charging jumper Specifications The following specifications apply to all BPS models. C line voltage 6.5 amp BPS 10 amp BPS Sense voltage (input) 120 C / 230 C (50/60 Hz) 390 watts 120 C / 230 C (50/60 Hz) 580 watts 6 to 45 DC 11 to 33 RMS (FWR and unfiltered DC) Sense current (input) 6 m @ 24 DC, 3 m @ 12 DC, 12 m @ 45 DC NC output voltage (special application circuit) Refer to the Remote Booster Power Supply ULI and ULC Compatibility List P/N 3100656 for the maximum number of devices that can be used on a NC circuit. UX output voltage (special application circuit) NC/UX output current NC/UX capacitive loading NC/UX class Wire size NC EOL 17.93 to 26.40 DC Note: ll NCs are supervised. 19.0 to 26.48 DC 3.0 max. per circuit with 0.35 power factor (6.5 or 10 max. total for all NCs) (6.5 or 8 max. total for all UXs) 10,000 µf max. for continuous NC circuits 2,200 µf max. for stroking rate NC circuits 2,200 µf max. for UX circuits Class B (Style Y) or Class (Style Z) 18 to 12 W (0.75 to 2.5 sq mm) UL: 15 kω (P/N EOL-15) ULC: Use P/N EOL-P1 and select the 15 kω resistor Remote Booster Power Supply Technical Reference Manual 7

etting started uxiliary output (continuous) 1 dedicated 200 m auxiliary output, not supervised by BPS, included in total current oltage range: 19.49 to 26.85 Common trouble relay Battery requirements [1] Form C, 1, 30 DC (resistive) 6.5 to 24 h for fire and security applications (10 h max. in enclosure) -Under 10 h, cut JP4-10 h or above, do not cut JP4 Battery charger current limit 1.2 when the battery jumper wire is cut 2.1 when the battery jumper wire is not cut Operating environment Operating temperature Operating humidity round fault impedance Intended installation environment 32 to 120 F (0 to 49 C) 0 to 93% RH, noncondensing at 90 F (32 C) 10 kω Indoor-dry [1] The maximum battery size the panel can charge is 24 h (Portalac PE12-23 or equivalent) for fire and security applications. LED indicators The BPS has seven LED indicators. See Component descriptions for the location of the LEDs. LED Color Description C reen C power on NC1 Yellow NC1/UX1 trouble [1] NC2 Yellow NC2/UX2 trouble [1] NC3 Yellow NC3/UX3 trouble [1] NC4 Yellow NC4/UX4 trouble [1] BT Yellow Battery trouble. Indicates that the battery level has fallen below acceptable levels. ND Yellow round fault. Indicates that a ground fault has been detected on the field wiring. [1] The NC LEDs indicate a trouble with the load or external wiring on the NC/UX circuit. For circuits configured as NCs, this could be an open circuit trouble, short circuit trouble, or an overload trouble. For short circuit troubles, the NC does not activate until the short circuit condition is removed. For overload troubles, an active NC is shutdown. fter shutdown, if there is no short circuit condition, the NC reactivates after 30 seconds and checks to see if the overload condition still exists. For UX circuits, the trouble indicates an overload condition. The UX circuit is shutdown for 30 seconds and then is reactivated to see if the overload condition still exists. 8 Remote Booster Power Supply Technical Reference Manual

etting started Trouble indicating and reporting When the BPS trouble relay is not dedicated to C power loss reporting (DIP switch SW2-6 OFF), the trouble conditions listed in the table above are reported through the trouble relay. Other internal troubles that do not have an associated LED are also reported via the BPS trouble relay. Other internal troubles include: DIP switch read trouble, RM failure, code checksum failure, to D failure, and battery charger failure. ll troubles are also reported through both sense circuit trouble relays. Remote Booster Power Supply Technical Reference Manual 9

Installing the enclosure Installing the enclosure When installing this system, be sure to follow all applicable national and local fire alarm codes and standards. The enclosure can be surface mounted or semiflush mounted. See Enclosure dimensions below for details. To surface mount the enclosure: 1. Position the enclosure on the finished wall surface. 2. Fasten the enclosure to the wall surface where indicated. 3. Install all conduit and pull all wiring into the enclosure before proceeding. To semiflush mount the enclosure: 1. Frame the interior wall as required to support the full weight of the enclosure and standby batteries. 2. Fasten the enclosure to the framing studs where indicated. 3. Install all conduit and pull all wiring into the enclosure before proceeding. Enclosure dimensions D5 Top iew D2 D3 D4 D1 Side iew Front iew D6 ll knockouts for 3/4 in conduit (1.9 cm) Side iew D1 D2 D3 D4 D5 D6 17.0 in (43.2 cm) 3.5 in (8.9 cm) 13.0 in (33.0 cm) 6.5 in (16.5 cm) 3.375 in (8.6 cm) 12.0 in (30.4 cm) 10 Remote Booster Power Supply Technical Reference Manual

Installing option modules in the enclosure Installing option modules in the enclosure Up to three option modules can be installed on the mounting brackets inside the enclosure. Depending on the model, the device must be either screw-mounted or snapped to the bracket. To snap-mount modules to a bracket: 1. Snap the module into a mounting bracket. 2. Connect all wiring. Refer to the module s installation sheet for wiring information or the Signature Series Component Installation Manual P/N 270497. Note: The first module you install must be installed in the top mounting bracket. The second module must be installed in the middle mounting bracket and the third module in the bottom bracket. Note: Route the wiring around the perimeter of the enclosure, not across the circuit board. Mounting brackets Option module To screw-mount Signature Series modules to a bracket: 1. Remove the module s plastic cover. 2. Remove the circuit board from the plastic backing. 3. Screw the plastic backing to the mounting bracket using two #6, 1/4-inch, flat head sheet metal screws. Remote Booster Power Supply Technical Reference Manual 11

Installing option modules in the enclosure 4. Insert the circuit board into the plastic backing. 5. Snap the module s plastic cover into place. 6. Connect all wiring. Refer to the module s installation sheet for wiring information or the Signature Series Component Installation Manual P/N 270497. Note: Route the wiring around the perimeter of the enclosure, not across the circuit board. 12 Remote Booster Power Supply Technical Reference Manual

Installing the circuit board in the enclosure Installing the circuit board in the enclosure You may have to remove the circuit board to install the enclosure. Reinstalling the circuit board in the enclosure must be done with accuracy to avoid causing ground faults or shorts. The screws and standoffs must be installed correctly and in the right positions. Use the diagrams below to install the circuit board. Complete circuit board installation Enclosure Circuit board Long screws Note: See Barrel spacer installation diagram below Cover Short screws Spacers Enclosure standoffs Barrel spacer installation Note: The barrel spacers must be positioned correctly so that the long screw can pass through the spacer and into the enclosure standoff. Barrel spacers Long screws Remote Booster Power Supply Technical Reference Manual 13

Setting the jumpers Setting the jumpers There are four jumpers on the BPS. See Component descriptions for the location of the jumpers. NC Class or Class B (JP1 and JP2) JP1 and JP2 are used to select a Class, Style Z or Class B, Style Y NC wiring configuration for all NCs. The default is Class B. Note: JP1 and JP2 must be positioned to match the SW2-8 DIP switch selection (Class or Class B). 1 1 Class 2 2 Class B 3 3 JP1 JP2 Class Class B round fault enable (JP3) JP3 is used to set the NC/UX circuits for ground fault enabled or disabled operation. The sense inputs are always isolated from local power. Enabled: llows the BPS to perform its own ground fault checking. This is the default position. Disabled: Disable the BPS s ground fault detection if the host panel is detecting system ground faults. Disabling ground fault detection removes the ability of the BPS to detect ground faults and isolates the BPS from earth ground. This is what allows the control panel to do the system s ground fault checking. If you do not disable ground fault detection when connecting powered devices as shown in the diagram below, you may get excessive ground faults on your system or ground faults on your system may fail to be reported. Note: NC circuit ground fault detection is required for all fire and security applications. It is recommended that systems, which are set with ground fault disabled, be tested after installation. Control panel [1] Powered device Powered device BPS [2] Powered device To next device or end 14 Remote Booster Power Supply Technical Reference Manual

Setting the jumpers [1] The control panel is responsible for ground fault detection when your system is wired in this fashion [2] Disable the BPS s ground fault jumper (JP3) JP3 1 2 F disable: Do not install jumper F enable: Install jumper Battery charging (JP4) The battery charging jumper is a small wire that controls how the batteries are charged. Battery size determines whether you must cut the jumper wire or leave it intact. JP4 Cut the jumper wire when using batteries under 10 h. Do not cut the jumper wire when using batteries 10 h or over. Remote Booster Power Supply Technical Reference Manual 15

Setting the DIP switches Setting the DIP switches NOTICE TO USERS, INSTLLERS, UTHORITIES HIN JURISDICTION, ND OTHER INOLED PRTIES This product incorporates field-programmable options. In order for the product to comply with the requirements in the Standard for Control Units and ccessories for Fire larm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below. Programmable feature or option Permitted in UL 864? (Y/N) Possible settings Settings permitted in UL 864 Four second NC audible synchronization delay [1] N On (4 second delay) Off (1 second delay) Off [1] This option is controlled by switch SW1-4. See Synchronization control (SW1-4) on page 17. Two eight-position DIP switches are used to configure the BPS. The following sections show the DIP switch settings for the various input and output configurations. Note: From the factory, all switches are in the OFF position. ON 12345 6 7 8 SW1 12345 6 7 8 SW2 Sense 1 and 2 operation (SW1-1 to 3) The BPS has three operating modes, as shown in the following table. Switches SW1-1, -2, and -3 determine which mode is used. Switch setting Operating mode [1] SW1-1 SW1-2 SW1-3 Correlate mode OFF enesis Master mode ON OFF ON Nondelayed mode ON ON [1] See the descriptions below for operation details These switches also determine how Sense 1 and 2 correlate to the NC circuits. Details for each mode are described below. Correlate mode In correlate mode, switches SW1-2 and SW1-3 control which NCs activate when the sense circuits activate. The correlations do not affect output circuits that are operating as UX circuits. The following table details which NCs activate when the sense circuits activate. 16 Remote Booster Power Supply Technical Reference Manual

Setting the DIP switches Sense circuit to NC correlations Switch settings Class B Class SW1-2 SW1-3 Sense 1 Sense 2 Sense 1 Sense 2 OFF OFF 1, 2, 3, 4 1, 2, 3, 4 1/2, 3/4 1/2, 3/4 OFF ON 1 2, 3, 4 1/2 3/4 ON OFF 1, 2 3, 4 ON ON 1, 2, 3 4 enesis Master mode In enesis Master mode, Sense 1 is connected to a visible zone and Sense 2 is connected to an audible zone. ll NCs are activated when Sense 1 activates. Continuous NCs generate enesis audible on/off signals based on the Sense 2 input circuit. Nondelayed mode Nondelayed mode is intended to support coders. In this mode, there is no delay between activation of the sense input and activation of the NC. In nondelayed mode, switch SW1-3 controls which NCs activate when the sense circuits activate. The correlations do not affect output circuits that are operating as UX circuits. The following table details which NCs activate when the sense circuits activate. Sense circuit to NC correlations SW1-3 setting Class B Class SW1-3 Sense 1 Sense 2 Sense 1 Sense 2 OFF 1, 2, 3, 4 1, 2, 3, 4 1/2, 3/4 1/2, 3/4 ON 1, 2 3, 4 1/2 3/4 In nondelayed mode, SW2-5 can be used to generate sync pulses for NCs configured in continuous mode. This supports applications that include enesis strobes and conventional audibles. For this operation, the NCs for the audible signals must be configured in sense follow mode. There is no delay for either the visibles or the audibles. Synchronization control (SW1-4) Switch SW1-4 controls the synchronization of signals with either one- or four-second delay times. See the topic Understanding BPS synchronization for more information. Note: When using nondelayed mode, this switch is inactive. Remote Booster Power Supply Technical Reference Manual 17

Setting the DIP switches Switch setting ON OFF Operation description NCs turn on 4 seconds after the sense input is activated (e.g. enesis NCs sync with the second round of the temporal signal) NCs turn on 1 second after the sense input is activated (e.g. the enesis NCs sync with the second flash of the enesis strobes) NC circuit operation (SW1-5 to 8 and SW2-1 to 4) Switch SW1-5 to 8 and SW2-1 to 4 control NC operation. NC1 NC2 NC3 NC4 Operating mode SW1-5 SW1-6 SW1-7 SW1-8 SW2-1 SW2-2 SW2-3 SW2-4 Sense Follow [1] OFF OFF OFF OFF OFF OFF OFF OFF Continuous [1] OFF ON OFF ON OFF ON OFF ON Temporal or California [1] [2] ON OFF ON OFF ON OFF ON OFF uxiliary [1] ON ON ON ON ON ON ON ON [1] See the descriptions below for operation details [2] BPS models BPS6C and BPS10C use California operation in place of temporal. For temporal operation, set the BPS to sense follow mode and use an external temporal source to activate the BPS sense circuit to generate the temporal pattern. Sense follow mode In sense follow mode, NCs are activated following the sense circuits that are defined to turn on the NCs. The NCs turn on with a one- or four-second (does not comply with UL864 9th edition) delay to allow enesis strobes to synchronize on the NC side and sense side. In this mode, a continuous input, 120 ppm, temporal, or coded input can be used. Note: Sense follow must be used when the sense circuit is connected to a SI-CC1S, enesis 1M-RM, FireShield panel, or a BPS generating enesis sync pulses. Continuous mode In continuous mode, NCs are activated following the sense circuits in continuous mode. They activate one or four (does not comply with UL864 9th edition) seconds after the sense input activates and restore seven seconds after the sense input restores. Temporal mode In temporal mode, NCs are activated following the sense circuits in temporal mode. They activate one or four (does not comply with UL864 9th edition) seconds after the sense input activates and 18 Remote Booster Power Supply Technical Reference Manual

Setting the DIP switches restore seven seconds after the sense input restores. NCs generate temporal output as defined by NFP. California mode In California mode, NCs generate the California output: 10 seconds of 120 ppm followed by five seconds off. uxiliary In auxiliary mode, NCs turn on during power up. Sync pulses are not generated. ux circuits can be configured to stay active during a power fail or load shed on a power fail (after a 30 second delay). ux circuits are load shed when the system reaches low battery to prevent deep discharge of the batteries. enesis mode for continuous NCs (SW2-5) Switch SW2-5 controls NC operation for enesis synchronization in continuous mode. Switch setting ON OFF Operation description Continuous NCs are enesis strobe or horn/strobe circuits. Continuous NCs generate a enesis sync pulse. In enesis Master mode, continuous NCs generate enesis audible on/off signals based on the Sense 2 input circuit. Continuous NCs do not generate enesis signaling pulses C power loss reporting (SW2-6) Switch SW2-6 controls when a report is sent to the system for an C power loss. Switch setting ON Operation description The BPS trouble relay is dedicated to C power loss reporting. The trouble relay switches within 20 seconds when C fails or restores. The sense circuits immediately signal a fault condition for any non-c power loss faults. If C power fails, the sense circuits signal a fault condition after three hours of power loss. OFF The trouble relay operates for any trouble on the BPS. The sense circuits signal a fault for any troubles. Remote Booster Power Supply Technical Reference Manual 19

Setting the DIP switches uxiliary control during C power loss (SW2-7) Switch SW2-7 controls auxiliary outputs during C loss. Note: The 200 m continuous UX circuit is not affected by C power loss. Switch setting ON OFF Operation description uxiliary outputs turn off 30 seconds after power fail uxiliary outputs stay on after C power fail until the battery is less than 18.4 DC Class or B NC configuration (SW2-8) Switch SW2-8 controls NC Class or B operation for all NCs. Note: Jumpers JP1 and JP2 must be set to match the operation of this switch. Switch setting ON OFF Operation description Class NCs Class B NCs 20 Remote Booster Power Supply Technical Reference Manual

Wire routing Wire routing To avoid noise, separate high current input or output wiring from low current wiring. Separate power-limited from nonpower-limited wiring. Wiring within the enclosure should be routed around the perimeter of the enclosure, not across the circuit board. Power-limited wiring area Route C supply through these knockouts only (Nonpower-limited and supervised) Battery wiring (nonpowerlimited and supervised) Battery Battery Notes 1. Maintain 1/4-inch (6 mm) spacing between power-limited and nonpower-limited wiring or use type FPL, FPLR, or FPLP cable per NEC 2. NC circuits are power-limited and supervised for opens, shorts, and overcurrents. When configured as auxiliary power circuits, they are power-limited and supervised for shorts and overcurrents. 3. Source must be power-limited. Source determines supervision. 4. Position the battery terminals towards the door Remote Booster Power Supply Technical Reference Manual 21

Connecting the field wiring Connecting the field wiring C power wiring TB3 TB4 Caution: Break the wire run at each terminal connection to provide proper connection supervision. Do not loop wires under the terminals. L N - To 120 ac 50/60 Hz branch circuit or 230 ac 50/60 Hz branch circuit Battery wiring Two backup batteries are required with the BPS. The largest batteries that fit in the BPS enclosure are 10 h. Batteries larger than 10 h must be installed in a BC-1 or BC-2 battery cabinet. Notes Batteries should be replaced every five years Refer to local and national codes for battery maintenance requirements TB3 TB4 Caution: For proper battery charging, the battery charging jumper wire (JP4) must be set according to the battery size you are using. Refer to Setting the jumpers for details about jumper JP4. L N - 22 Remote Booster Power Supply Technical Reference Manual

Connecting the field wiring NC Class B (Style Y) wiring Connect a single NC circuit to one NC output. Terminate the circuit with a 15 kω EOL resistor. NC1 NC2 NC3 NC4 200 m UX Continuous TB5 TB1 IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC TB2 Notification appliance circuit (NC) UL listed EOL 15 kω Notification appliance circuit (NC) UL listed EOL 15 kω EOL [3] NC Class (Style Z) wiring Input or signaling circuit To next signaling device, booster, or NC end-of-line resistor NC C power fail monitoring Connect one NC circuit to one NC output, either NC1 or NC3. Terminate the circuit at the NC2 or NC4 terminal screw, respectively. NC1 NC2 NC3 NC4 200 m UX Continuous IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC TB2 TB5 TB1 EOL [3] Input or signaling circuit To next signaling device, booster, or NC returning to existing control panel Notification appliance circuit (NC) Notification appliance circuit (NC) NC C power fail monitoring NC wiring notes 1. trouble on the booster power supply is sensed on the existing control panel s NC circuit causing a NC trouble on that panel. This removes the need to separately monitor the trouble contact except for C power failure (see [3] below). In an alarm condition, the booster power supply allows NC current to move downstream to devices connected to the existing control panel s NC circuit. 2. Refer to the connected control panel s documentation for more details on NC wiring [3] The C power failure panel connection annunciates at the panel but does not report off premises for a predetermined time period in U.S. fire applications Remote Booster Power Supply Technical Reference Manual 23

Connecting the field wiring UX power wiring Dedicated UX power TB5 UX power 200 m continuous NC configured as UX power Each NC can be configured through a DIP switch for use as UX power. DIP switch also controls UX operation during C power loss. See Setting the DIP switches for details. This auxiliary configuration is compatible with fire alarm, security, and access control applications, which can be combined in a single system, if all of the devices are listed. Note: When a NC is configured as an UX power circuit, a UL listed EOL relay (PM1, 6254-003, or 73402) is recommended for supervision of the circuit. Trouble relay wiring with four UX circuits When all four NC/UX circuits are configured as UX circuits and DIP switch SW2-6 is ON, a SI-CT2 module must be used to monitor the sense 1 trouble contacts and the trouble relay. TB1 NC1/ UX1 To auxiliary device [3] NC2/ UX2 To auxiliary device [3] NC3/ UX3 To auxiliary device [3] NC4/ UX4 To auxiliary device [3] 200 m UX Continuous IN Sense 1 COM OUT IN Sense 2 COM OUT NO CT2 [1] [2] Trouble COM NC EOL 47 kω TB2 Data in from Data out to previous device or next device Signature controller Notes TB5 [1] Modules must be wired and programmed on the Signature controller for proper operation [2] C power loss causes circuit 2 on the CT2 to report a trouble to the control panel (see panel programming). ll other BPS 24 Remote Booster Power Supply Technical Reference Manual

Connecting the field wiring troubles cause circuit 1 on the CT2 to report a trouble to the panel. [3] The NC/UX circuit must be configured for UX operation using the DIP switches. See Setting the DIP switches for details. Common trouble relay wiring The BPS has a Form C common trouble relay that provides a normally open and normally closed contact. The trouble relay switches under any trouble condition when DIP switch SW2-6 is off. When the switch is on, the BPS trouble relay is dedicated to C power loss reporting. The trouble relay switches within 20 seconds when C fails or restores. The sense circuits immediately signal a fault condition for any non-c power loss faults. When C power fails, the sense circuits signal a fault condition after three hours of power loss. TB2 NC COM NO OUT CO TROUBLE SEN To booster trouble monitoring device Sense circuit wiring The BPS has two sense circuits Class B, Style (Sense 1 and Sense 2). Sense circuit operation is controlled by the BPS s DIP switches. Sense activation of existing NC circuits reports a trouble condition to the control panel using these circuits. Note: ny BPS trouble opens the sense circuit, which sends a trouble event message to the control panel, indicating that a trouble exists on that circuit. 200 m UX Continuous IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC TB2 TB5 EOL [1] NC circuit To next signaling device, booster, or NC end-of-line resistor Control panel or other device NC C power fail monitoring Remote Booster Power Supply Technical Reference Manual 25

Connecting the field wiring [1] The C power failure panel connection annunciates at the panel but does not report off premises for a predetermined time period in U.S. fire applications Tests for grounds, opens, and shorts The following are testing procedures for ground fault, open circuit, and short circuit indications. round fault test: Directly short one leg of the circuit to chassis ground. The ground fault and trouble fault LEDs must light. NC open circuit test: Remove the EOL resistor from the last device on the circuit. The trouble LED must light. NC short circuit test: Place a short across each NC output individually. The individual NC LED must light. UX power short circuit test: This test applies to NC outputs configured as UX outputs. It does not apply to the 200 m UX Continuous output. Place a short across each NC/UX output individually. The corresponding individual NC/UX LED must light. 26 Remote Booster Power Supply Technical Reference Manual

NC wiring using CC1(S) modules NC wiring using CC1(S) modules The following wiring diagrams show Signature Series CC1(S) module connections. However, other Signature Series signal modules can be used. Single CC1(S) using the BPS s 200 m UX Continuous circuit TB1 NC1/ UX1 NC2/ UX2 NC3/ UX3 NC4/ UX4 200 m UX Continuous IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC TB2 TB5 Notification appliance circuit (NC) Notification appliance circuit (NC) EOL 47 kω CT1 module [4] Data in from previous device or Signature controller UL listed EOL 15 kω 10 9 8 7 6 5 4 3 2 1 UL listed EOL 15 kω CC1(S) module [1][3] Data out to next device Data in from previous device or Signature controller Notes Data out to next device [1] Modules must be wired and programmed on the Signature controller for proper operation 2. ny BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel when DIP switch SW2-6 is on. C power failure is delayed for three hours. [3] CC1(S) wiring must be within three feet of the BPS enclosure and in conduit or mounted within the BPS s enclosure. If CC1(S) wiring is more than three feet from a BPS enclosure, then a separate listed EOL relay (PM1, 6254-003, or 73402) or equivalent must be used to supervise the 200 m UX circuit wiring. [4] When configured for C power loss reporting using the trouble relay (DIP switch SW2-6 ON), the CT1 module supervises and reports the C power loss to the control panel. When DIP switch SW2-6 is OFF, the CT1 module is not required. Remote Booster Power Supply Technical Reference Manual 27

NC wiring using CC1(S) modules Multiple CC1(S) modules using the BPS s sense inputs NC1/ UX1 NC2/ UX2 NC3/ UX3 NC4/ UX4 200 m UX Continuous TB5 TB1 IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC TB2 Notification appliance circuit (NC) Notification appliance circuit (NC) EOL 47 kω EOL 47 kω 10 9 CC1(S) module [1] UL listed EOL 15 kω UL listed EOL 15 kω 10 9 CC1(S) module [1] 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 Data in from previous device or Signature controller Notes CT1 module [4] Data out to next device [3] [1] Modules must be wired and programmed on the Signature controller for proper operation 2. ny BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel when DIP switch SW2-6 is on. C power failure is delayed for three hours. [3] CC1(S) wiring must be within three feet of the BPS enclosure and in conduit or mounted within the BPS s enclosure. If CC1(S) wiring is more than three feet from a BPS enclosure, then a separate listed EOL relay (PM1, 6254-003, or 73402) or equivalent must be used to supervise the 200 m UX circuit wiring. [4] When configured for C power loss reporting using the trouble relay (DIP switch SW2-6 ON), the CT1 module supervises and reports the C power loss to the control panel. When DIP switch SW2-6 is OFF, the CT1 module is not required. 28 Remote Booster Power Supply Technical Reference Manual

NC wiring using CC1(S) modules Multiple CC1(S) modules using one of the BPS s NC/UX circuits NC1/ UX1 NC2/ UX2 NC3/ UX3 NC4/ UX4 200 m UX Continuous TB5 TB1 IN Sense 1 COM OUT IN Sense 2 COM OUT NO Trouble COM NC TB2 Notification appliance circuit (NC) Notification appliance circuit (NC) From existing fire alarm panel notification circuit or CC1(S) module Out to EOL or next device 10 9 8 7 6 5 4 3 2 1 NC circuit CC1(S) module UL listed EOL 15 kω UL listed EOL 15 kω UL listed EOL 47 kω Notes [1] When a booster power supply output is programmed as an UX output, a listed EOL relay (PM1, 6254-003, or 73402) or equivalent must be used to supervise the UX output [2] When a booster power supply output is programmed as an NC output, a 15 k8 EOL resistor must be used for supervision Data out to next device Data in from previous device or Signature controller NC circuit UL listed EOL 47 kω 10 9 CC1(S) module 8 7 6 5 4 3 2 1 [1] EOL 47 kω [2] EOL 15 kω UL listed EOL relay Data out to next device Data in from previous device or Signature controller [1] CT1 module 6 5 RM1 module Data in from control panel Data out to next device Data in from control panel Data out to next device Remote Booster Power Supply Technical Reference Manual 29

Installing the 3-TMP tamper switch Installing the 3-TMP tamper switch The 3-TMP tamper switch is used to detect an open enclosure door for security purposes. Note: The 3-TMP tamper switch must be used for security applications and connected to a SI-SEC2 module mounted in the enclosure. To install the tamper switch: 1. Install an EOL resistor on the 3-TMP. Refer to the 3-TMP Installation Sheet (P/N 387422) for more information. 2. Position the tamper switch over the mounting standoffs. See the diagram below. 3. Use the two locking nuts provided to secure the tamper switch. See the diagram below. 4. Connect all wiring to the tamper switch. Refer to the 3-TMP Installation Sheet (P/N 387422) for details on wiring the tamper switch. 3-TMP tamper switch Mounting standoffs Locking nuts 30 Remote Booster Power Supply Technical Reference Manual

Battery calculation worksheet Battery calculation worksheet Supervisory (UX1, UX2, UX3, UX4) Note: Only add auxiliary current if SW2-7 is OFF. uxiliary output stays on after C power failure. Device type Quantity Current (m) Total/device Total UX current (0 if switch SW2-7 is off, maximum of 8 ): m () Number of circuits set to UX 35 m (per UX circuit) m (B) 200 m UX Device type Quantity Current (m) Total/device Total 200 m UX current: m (C) Rated base BPS supervisory current: Total supervisory current ( B C D): Hours of supervisory: Supervisory mh required (E x F): 70 m (D) m (E) Hrs (F) mh () larm (NC1, NC2, NC3, NC4) Device type Quantity DC current (m, RMS) Total/device Total NC current: m (H) Rated base BPS alarm current: Total alarm current (E H J): Minutes of alarm: Hours of alarm (L/60): larm mh required (K x M): 270 m (J) m (K) Min (L) Hr (M) mh (N) Total battery mh required (N ): Total battery h required (O/1000): Supervisory battery current (E/1000): mh (O) h (P) (Q) Remote Booster Power Supply Technical Reference Manual 31

Battery calculation worksheet To use the load current table below: First, select the column where the load is greater than or equal to (Q). Second, select the row from that column where the capacity is greater than or equal to (P). Third, select the corresponding battery size. Battery size Load current (amps) 0.2 0.4 0.6 0.8 1 2 3 4 5 6 7 8 9 10 6.5 hr 5.4 5.3 5.2 5.0 4.8 4.3 3.9 3.6 3.3 3.0 2.8 2.6 2.5 2.3 10 hr 8.3 8.3 8.1 7.9 7.7 7.1 6.6 6.2 5.8 5.5 5.2 5.0 4.7 4.5 17 hr 14.1 14.1 14.1 14.1 13.5 12.8 12.3 11.8 11.3 10.9 10.5 10.1 9.8 9.5 24 hr 20.0 20.0 20.0 20.0 20.0 18.7 18.1 17.5 17.0 16.5 16.0 15.6 15.2 14.8 40 hr [1] 33.0 33.0 33.0 33.0 33.0 33.0 32.0 31.0 30.0 29.0 28.5 28.0 27.5 27.0 50 hr [1] 42.0 42.0 42.0 42.0 42.0 42.0 41.0 40.0 39.0 38.0 37.0 36.5 36.0 35.5 55 hr [1] 46.0 46.0 46.0 46.0 46.0 46.0 45.0 44.0 43.0 42.0 41.0 40.5 40.0 39.5 65 hr [1] 54.0 54.0 54.0 54.0 54.0 54.0 54.0 53.0 52.0 51.0 50.0 49.0 48.5 48.0 [1] Batteries larger than 24 hr are not intended for use on fire and security applications. 32 Remote Booster Power Supply Technical Reference Manual

Notification appliance circuit calculations Notification appliance circuit calculations Introduction This topic shows you how to determine the maximum cable length of a notification appliance circuit (NC) for a given number of appliances. Two methods are presented: worksheet and equation. The worksheet method is simpler, but your installation must meet the criteria listed on the worksheet. If your installation does not meet these criteria, you need to use the equation method. The methods given here determine cable lengths that work under all operating conditions. The calculations ensure that the required operating voltage and current will be supplied to all notification appliances. To do this, we assume these two worst-case conditions: The voltage at the NC terminals is the minimum provided by the power supply The notification appliances are clustered at the end of the NC cable Other, more detailed methods that distribute the appliance load along the NC cable may indicate that longer cable runs are possible. What you ll need ppliance and cable values Whether you use the worksheet method or the equation method, you ll need to know: The minimum operating voltage required for the appliances The maximum operating current drawn by each appliance The resistance per unit length of the wire used (Ω/ft) This information can be found on the appliance installation sheets and on the cable specification sheet. Power supply values For either method, you ll need some fixed or calculated operating values for your specific power supply. The fixed values are: Maximum voltage = 26.3 Source voltage = 19.7 Load factor = 0.59 / Power type = DC Remote Booster Power Supply Technical Reference Manual 33

Notification appliance circuit calculations The maximum voltage is the highest voltage measured at the NC terminals. This value is not used in the calculations, but is given so you can ensure appliance compatibility. The source voltage is the theoretical operating minimum for the power supply, and is calculated as 85% of 24 volts minus the diode drop. The load factor is a measure of how the power supply voltage reacts when a load is applied. The load factor measures the voltage drop per ampere of current drawn by the load. The power type reflects the type of power supplied to the NC terminals at minimum voltage. The current draw of notification appliances can vary substantially with the type of power supplied: full-wave rectified (FWR) or direct current (DC). It is important to know the power type at minimum terminal voltage. You ll need to calculate the following values relating to your power supply and to the NC circuit current. These are: Minimum voltage oltage drop The minimum voltage is the lowest voltage measured at the NC terminals when the power supply is under the maximum load for that circuit (i.e. for the appliances that constitute the NC.) The voltage drop is the difference between the minimum voltage and 16. This value is for use with the worksheet only. 34 Remote Booster Power Supply Technical Reference Manual

Notification appliance circuit calculations Worksheet method Use this worksheet to determine the maximum cable length of a notification appliance circuit for a given number of appliances. Use this worksheet only if all the appliances are regulated. That is, they must have a minimum operating voltage of 16. For other appliances, use the Equation method. Worksheet 1: NC cable length NC1 NC2 NC3 NC4 Total operating current [1] Load factor 0.59 0.59 0.59 0.59 / Load voltage drop = Source voltage 19.7 19.7 19.7 19.7 Load voltage drop Minimum voltage = Regulated appliance voltage 16.0 16.0 16.0 16.0 oltage drop [2] = Total operating current Maximum resistance = Ω Wire resistance (Ω/ft) [3] Maximum wire length = ft 2 2 2 2 Maximum cable length = ft [1] Total of the maximum operating currents for all appliances as specified for DC power. See the appliance installation sheets for operating currents. [2] This voltage drop is valid for regulated notification appliances only. For special application appliances, see Equation method, later in this topic. [3] Use the manufacturer s published wire resistance expressed in ohms per foot. For typical values, see Table 1 on page 36. Remote Booster Power Supply Technical Reference Manual 35

Notification appliance circuit calculations Equation method ppliance operating voltage and current Regulated notification appliances have an operating range from 16 to 33. Use 16 as the minimum appliance voltage when using regulated notification appliances. When using special application appliances, refer to the installation sheets to determine the minimum appliance voltage required. What if there are different types of appliances in the NC, and each type has a different minimum operating voltage? In this case, use the highest minimum voltage required by any appliance. The total current requirement for the appliances will be the sum of the individual maximum currents drawn by each appliance when using DC power. Use the maximum current for the appliance over the 16 to 33 range. If all appliances draw the same maximum current, the total current is the maximum current multiplied by the number of appliances. If different appliance types have different maximum currents, the total current is the sum of the maximum current for each appliance type multiplied by the number of appliances of that type. Wire resistance Typical wire resistances are shown in the following table. Table 1: Typical wire resistances Wire gauge (W) Resistance 1-strand uncoated copper Resistance 7-strand uncoated copper Ω per foot Ω per meter Ω per foot Ω per meter 12 0.00193 0.00633 0.00198 0.00649 14 0.00307 0.01007 0.00314 0.01030 16 0.00489 0.01604 0.00499 0.01637 18 0.00777 0.02549 0.00795 0.02608 When performing these calculations, always refer to the actual cable supplier documentation and use the actual Ω/ft (or Ω/m) for the cable being used. Calculating cable length To calculate the maximum NC cable length: 1. Calculate the total current (Itot) as the sum of the maximum operating currents for all the appliances. 36 Remote Booster Power Supply Technical Reference Manual

Notification appliance circuit calculations Itot = ΣIa Where: Ia = appliance maximum current See the appliance installation sheets for Ia. Remember to use the maximum operating current specified for DC power. 2. Calculate the minimum voltage (m). m = s (Itot K) Where: s = source voltage Itot = total current (from above) K = load factor For the power supply, s is 19.7 and K is 0.59 /. 3. Calculate the allowable voltage drop (d) between the power supply and the appliances. d = m a Where: m = minimum voltage (from above) a = appliance minimum voltage For regulated notification appliances, a is 16. For special application appliances, a is the lowest operating voltage specified on the appliance installation sheet. 4. Calculate the maximum resistance (Rmax) for the wire. Rmax = d / Itot Where: d = voltage drop Itot = total current 5. Calculate the maximum length of the cable (Lc), based on the maximum resistance allowed, the resistance of the wire, and the number of wires in the cable (two). Lc = (Rmax / Rw) / 2 Where: Rmax = maximum resistance Rw = wire resistance factor Example: You re using regulated notification appliances. ssume that the maximum operating current for each appliance is 100 m for DC power, and that 20 appliances will be placed on the NC. The cable is 12 W wire, and the manufacturer specifies a wire resistance factor of 0.002 Ω/ft. Remote Booster Power Supply Technical Reference Manual 37