ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

Similar documents
Designing Energy Efficient Outdoor Air Systems

Adding More Fan Power Can Be a Good Thing

Energy Recovery with Cooling and Heating

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Trane CDQ Desiccant Dehumidification

Heat pump and energy recovery systems

Application Data. Fig. 1 39M Unit with Energy Recovery Section

Heat Recovery Units. Heat Recovery 1

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

Energy Recovery Ventilators

Bill McCullough. Director ERV Products. Dallas, TX

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Dehumidifying with Dedicated Outdoor Air

White Paper. Executive Summary. Overview of Membrane Exchangers CLCH-PRB063A-EN. June 2017

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Heat Recovery Ventilator Model PVe Light Industrial Commercial Institutional

Energy Recovery with Cooling and Heating Model ERCH

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

EU Air Handling Units with SEMCO EXCLU-SIEVE

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

HVAC Mandatory Provisions Part II, Page 1

Two essential attributes of mechanical systems intended to

Benefits Offered by Passive Dehumidification Wheel Speed Control

4. OVERVIEW OF MECHANICAL SYSTEM

Pharmaceutical Facility Design

Agenda and Objectives

Indoor Swimming Pools:

Product Release Summary

HVAC DISTRIBUTION and DELIVERY SYSTEMS

EP SERIES PACKAGED ENERGY RECOVERY SYSTEM ENERGY EFFICIENT AIR COMFORT

EarthWise System Seminar

CHAPTER 4. HVAC DELIVERY SYSTEMS

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

Agenda and Objectives

Mystery of Sustainable Heat Exchange Material Heat Recovery Ventilator(HRV)

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

National Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM

7. MECHANICAL SYSTEM DESIGN

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

RT-OA TM Rooftop Outdoor-Air (DOAS)

Redesign of Bennett Hall HVAC System

Rooftop Ventilator. Models RV and RVE. with Packaged Cooling & Heating

DES CHAMPS PRODUCTS. Specializing in: -- Air-to-Air Energy Recovery -- Conditioning Outdoor Air -- Controlling IAQ -- Indirect Evaporative Cooling

RT-OA TM Rooftop Outdoor-Air (DOAS)

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Air Conditioning Clinic

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Submittal Data Performance Data Electrical Data

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

WORKSHOP VENTILATION- PSYCHROMETRICS-AHU

By MIKE WEST, PHD, PE Advantek Consulting Inc. Melbourne, Fla.

4-Pipe VAV vs. Active Chilled Beams for Labs

Technical Assignment 3 11/15/04. Executive Summary

Energy Recovery Ventilation

BOOK 2 SPECIFICATIONS

Trane Engineers Newsletter Live

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

Munters Heat Exchangers

Your Home. Jacco & Assoc.

Humidity Control Systems for Civil Buildings in Hot Summer and Cold. Winter Zone in China

Why should you opt for ENTHALPY. Wheels for your. AHUs. ERVs. (Energy Recovery Ventilators) (Air Handling Units) from

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

A according to their application as (1) process-to-process, (2)

Civil Engineering Building

DIGI-VAV APPLICATIONS

100% Outdoor Air Dehumidification Methods

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

General unit Specification Version: August 8, 2013 Model JDMA : Make-up / Ventilation Air Page 1 of 13

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

General Unit Specification Version: August 8, 2013 Model JDHA : DX High Outside Air Unit Page 1 of 14

Scholar III Unit Ventilator

TECHNICAL REPORT 3: Mechanical Systems and Existing Conditions. Michael Morder Mechanical Option Advisor: Dr. William Bahnfleth

Existing Mechanical System Operation

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Chapter 6 ALL-AIR HVAC SYSTEMS 6.1 CONTEXT

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Trends in High Efficiency HVAC Packaged Products May 2012

COMcheck Software Version Mechanical Compliance Certificate

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

AHU Air Handling Unit Fundamentals. j.ilangumaran

Liquid desiccant dehumidification systems. Product guide

INSTALLATION INSTRUCTIONS ERVR-A3D-X ERVR-C3D-X RETROFIT ENERGY RECOVERY VENTILATOR

Implementation of the Laboratory Air Handling Unit Systems (LAHU)

DOAS UNITS. ReznorHVAC.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR

Humidity Control & Psychrometrics

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

THE IMPORTANCE OF THE DESICCANT RESULTS OF CROSS-CONTAMINATION TESTING ON DESICCANTS

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation

Enthalpy Wheel and its Application in Air Conditioning

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Transcription:

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.

Learning Objectives Understand how ventilation heat recovery systems work Identify the requirements for ventilation heat recovering as defined by ASHRAE 90.1 Recognize typical situations that lead to cost-effective applications of ventilation heat recovery

Agenda Energy Recovery Types Standard 90.1 Requirements Costs & Benefits Typical Application Schematics & Control Sequences

Energy Recovery Types Rotary (wheel) Sensible Total (Enthalpy) Flat Plate Sensible Total (Enthalpy) Heat Pipe Run-around

Rotary Heat Exchanger

Enthalpy Wheel Desiccants Lithium Chloride Salts dissolve, wash off. Silica Gel Best water transfer characteristics. Molecular Sieves Can be engineered to discriminate between species. Ideal for many process applications.

Flat Plate Heat Exchanger Synthetic matrix embedded with ceramic desiccant capable of water diffusion

Heat Pipe Heat Exchanger

Run-Around Heat Exchanger

Heat Exchanger Cooling Performance 50 90% 80% 70% 60% 50% 40% 30% 50 Leaving Sensible HX, 70% EFF: 82F DB 60 60 70 RA Exhaust air: 78F DB 63F WB OA 25% 15% 100 50 25 HUMIDITY RATIO - GRAINS OF MOISTURE PER POUND OF DRY AIR Outdoor air: 91F DB 73F WB Leaving Enthalpy 75 Wheel, 70% EFF: 82F DB 66F WB 20% 10% RELATIVE HUMIDITY 50 75 100 DRY BULB TEMPERATURE F

Heat Exchanger Ratings ARI 1060 Rotary Flat Plate Heat Pipe Non-ARI Certified language Tested in accordance with ARI 1060 Independently tested in accordance with ASHRAE Standard 84 and ARI standard 1060 Independently certified in accordance to ARI 1060 ARI Certified language ARI 1060 certified and listed in the ARI 1060 Directory of Certified Airto-Air Energy Recovery Ventilation Equipment No seal not certified! ARI 410 Run-around coils

Freezing/Frosting 0.015 60% Humidity Ratio 0.010 0.005 40% Exhaust Air Outside Air Outlet 20% Outside Air Intake Preheated Outside Air 0.000-30 -20-10 -0 10 20 30 T [ C]

Frost Control Function of outdoor temperature and indoor RH Enthalpy wheel has the lowest frost threshold Pre-heat is preferred solution maintains maximum recovery Usually not required in non-humidified buildings

Comparison of HX Types Characteristic Rotary Wheel Fixed Plate Heat Pipe Run-Around Sensible Effectiveness (equal flow) 60%-80% 60%-70% 30%-65% 45%-65% Total Effectiveness (equal flow) 65%-80% 45%-65% Pressure drop (each side) 0.5 to 1.2 in.wg. 0.6 to 1.4 in.wg. 0.2 to 0.8 in.wg. 0.3 to 1.0 in.wg. Susceptibility to frost High (sensible) Highest (sensible) Lowest (total) Low (total) Modest Modest Cross-leakage Modest Slight Slight None Adapted from Trane Heat Recovery Applications Manual

Typical Cost/Performance Ratio $120.00 Cost per MBH of recovered energy $100.00 $80.00 $60.00 $40.00 Heat Pipe Sensible Wheel Run-around Flat Plate Enthalpy Wheel $20.00 $- 2600 6500 15000 20000 Airflow Rate (cfm) from Trane Heat Recovery Applications Manual, 1997

Standard 90.1 Requirements Individual fan systems that have both a design supply air capacity of 5000 cfm or greater and have a minimum outdoor air supply of 70% or greater of the design supply air quantity shall have an energy recovery system with at least 50% recovery effectiveness. Provision shall be made to bypass or control the heat recovery system to permit air economizer operation Note: Addendum to toughen requirements recently out for public review but not likely to be approved as written

Standard 90.1 Exceptions Energy Recovery not required for: a) Laboratory systems meeting 6.5.7.2. b) Systems serving spaces that are not cooled and that are heated to less than 60 F. c) Systems exhausting toxic, flammable, paint, or corrosive fumes or dust. d) Commercial kitchen hoods used for collecting and removing grease vapors and smoke. e) Where more than 60% of the outdoor air heating energy is provided from site-recovered or site solar energy. f) Heating systems in climate zones 1 through 3. g) Cooling systems in climate zones 3c, 4c, 5b, 5c, 6b, 7, and 8. h) Where the largest exhaust source is less than 75% of the design outdoor air flow. i) Systems requiring dehumidification that employ energy recovery in series with the cooling coil.

ASHRAE Climate Zones No Cooling Heat Recovery No Heating Heat Recovery

ASHRAE 90.1 vs. Actual Effectiveness ε ARI = m& m& oa min ( h ( h oae oae h h oal rae ) ) = m& m& oa ea ( h ( h oae oae h h oal rae ) ) ε h h = oae oal > 90.1 h h oae rae 0.5 ASHRAE 90.1 definition basically assumes equal exhaust and outdoor airflow rates

Unbalanced Flow and Effectiveness Effectiveness increases with unbalanced flow, but energy recovered does not! 0.95 0.9 0.85 Effectiveness 0.8 0.75 0.7 0.65 0.6 0.55 0.5 0.5 0.55 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Exhaust/Supply Ratio

Wintertime Sensible Effectiveness 70% Sensible Effectiveness 100% Exhaust Airflow Rate Outdoor Air: DB: 35F WB: 33F h: 12.2 Btu/lb Outdoor Air: DB: 59.5F WB: 46.2F h: 18.4 Btu/lb Exhaust Air: DB: 45.5F WB: 41.7F h: 16.1 Btu/lb ASHRAE Effectiveness: 61% Exhaust Air: DB: 70F WB: 53.4F RH: 30% h: 30.0 Btu/lb

Wintertime Sensible Effectiveness 82% Sensible Effectiveness 70% Exhaust Airflow Rate Outdoor Air: DB: 35F WB: 33F h: 12.2 Btu/lb Outdoor Air: DB: 59.5F WB: 46.2F h: 18.4 Btu/lb Exhaust Air: DB: 45.5F WB: 41.7F h: 16.1 Btu/lb ASHRAE Effectiveness: 50% Exhaust Air: DB: 70F WB: 53.4F RH: 30% h: 30.0 Btu/lb

Summertime Sensible Effectiveness 80% Sensible Effectiveness 100% Exhaust Airflow Rate Outdoor Air: DB: 95F WB: 78F h: 41.9 Btu/lb Outdoor Air: DB: 79F WB: 73.6F h: 37.6 Btu/lb Exhaust Air: DB: 91F WB: 68.5F h: 33.0 Btu/lb ASHRAE Effectiveness: 33% Exhaust Air: DB: 75F WB: 63F RH: 51% h: 28.8 Btu/lb

Conclusion Where 90.1 requires heat recovery for cooling: Enthalpy heat exchanger required Where 90.1 requires heat recovery for heating: If humidified (RH>~30%): Enthalpy heat exchanger required If not humidified : Any style will work

Enthalpy Wheels Advantages Somewhat self-cleaning and easy to clean Low frost temperature limits May eliminate preheat coil in non-humidified buildings Increases heat recovered in cold weather Compact Highest effectiveness, sensible & total Lowest cost per unit of recovered energy Free winter humidification (recovers latent load) Disadvantages Moving parts affect maintenance costs Leakage and carryover between airstreams Airstreams must be side-by-side (vs. run-around)

First Costs/Benefits Costs Heat recovery device Routing exhaust ducts (or run-around pipes) to intakes Added fans (where applicable) Increased fan motor HP of existing supply air and exhaust air fans Benefits Downsizing heating/cooling systems

Operating Costs/Benefits Costs Increased maintenance (filters, coil/core cleaning, motor, bearings) Benefits Reduced cycling due to smaller AC unit size for improved temperature and humidity control No real humidity benefits from moisture transfer it is the cooling system that removes the moisture Reduced cooling and heating loads Offset partly by added fan energy Net savings varies by application, design, and climate

Net Energy Savings (School in Madison, WI. No summer classes) No Heat Recovery Enthalpy Wheel

Net Energy Savings (Big Box Department Store, Iowa)

Most Cost Effective Applications High outdoor air rate Densely occupied spaces Excess return air that would have to be exhausted anyway to prevent over-pressurizing building Allows HR to be used without extra ductwork and without extra fan if there already is a relief fan

Typical Constant Volume AHU without Energy Recovery Economizer Outdoor Air Supply Air Return Air Relief Air

Constant Volume AHU with Energy Recovery Economizer Outdoor Air Supply Air Enthalpy Wheel Return Air Exhaust Air Bypass Damper for Capacity Control

Variable Volume AHU with Energy Recovery & Economizer Economizer Outdoor Air Supply Air Enthalpy Wheel VFD Return Air Exhaust Air VFD Bypass Damper for Capacity Control & Fan Energy Savings

Control Logic Return Air Damper (high limit not shown) Exhaust HX Bypass Damper (high limit not shown) Economizer Outdoor Air Damper (high limit not shown) 0 % Full Open 100 HW Valve CHW Valve 0% Supply Air Temperature Control Loop 100% HX Wheel On when Economizer Outdoor Air Damper is closed. Bypass & Economizer Outdoor air damper closed, Return air damper open when outdoor air enthalpy > return air enthalpy

Wheel Operation Madison, WI, 8am-8pm, 8pm, 70% min OA 500 450 400 350 Hours 300 250 200 150 100 50 0-15 -10-5 0 Wheel On Minimum OA HW Valve Modulated 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 Wheel On Minimum OA Bypass Modulated Wheel Off Economizer Dampers & CHW Modulated Wheel On Minimum OA CHW Valve Modulated 100 More

100% OA Variable Volume AHU with Energy Recovery Bypass Damper for Fan Energy Savings Outdoor Air Supply Air Enthalpy Wheel VFD Return Air Exhaust Air VFD Bypass Damper for Capacity Control & Fan Energy Savings

Summary & Tips Usually the optimum Energy Recovery type is: Enthalpy Wheel in humid climates & cold climates with humidification Flat Plat or Run-around for hot dry climates and no humidification No heat recovery in mild climates Use ARI Certified products only Ensures fair playing field, realistic load reduction estimates Keep pressure drops low to minimize fan energy losses Only apply to minimum outdoor air Bypass HX for economizer outdoor air Take credit for reduced loads in heating/cooling equipment sizing Necessary for cost effectiveness and control benefits Determine savings using annual energy program of actual system application Manufacturer s programs are often over-simplified and favor recovery

Questions? Steven Taylor Taylor Engineering 510.263.1540 staylor@taylor-engineering.com http://www.taylor-engineering.com