EHPA Testing Regulation

Similar documents
EHPA Testing Regulation

DIN EN , DIN EN , DIN EN , DIN EN

Technical Note. EHPA Quality Label Model Range Definition Version

AIR CONDITIONERS MINIMUM ENERGY PERFORMANCE, LABELLING AND TESTING REQUIREMENTS FOR LOW CAPACITY WINDOW TYPE AND SINGLE-SPLIT

Test Report No.: Page 2 of 14

A Notification under Article 12 of Regulation (EU) No 1025/2012 1

PHRIE / PHIE InvERTER monoblock air To water HEaT PumP medium TEmPERaTuRE

Draft COMMUNICATION FROM THE COMMISSION

0.4 In the preparation of this standard, assistance has been derived from the following standards:

The products covered by the Regulation can be classified as follows:

EXHAUST AIR HEAT PUMPS EVALUATED FOR NORDIC CIRCUMSTANCES

ETSI Standard Environment Engineering (EE); Thermal Management requirements for outdoor enclosures

Technical data. Danfoss DHP-L

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE

ANNEXES. to the. COMMISSION REGULATION (EU) No /..

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

nemo 5,4 30,5 kw 6,4 37,4 kw R410A PLATE water cooled chillers / heat pumps and motoevaporating units COOLING HEATING

In accordance with the Radio Waves Act Chapter 58 Article 8(3), the document below is a

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

Technical Data. Danfoss DHP-C. Provides heating, cooling and hot water TWS technology provides hot water quickly with low operating

Performance Rating of Heat Pump Pool Heaters

COMMISSION DELEGATED REGULATION (EU) /... of

Modular Air-cooled Chillers

CEN standardization work on refrigerating systems, especially standard EN 378

DHP-H Varius Pro+/DHP-L Varius Pro+

COMMISSION REGULATION (EU) No /.. of

Technical data LA 60TUR+

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

ENVIRONMENT-FRIENDLY HEATING WITH R290 HEAT PUMPS. Dr. Joachim Maul - Brussels, 15th of October 2013

(Non-legislative acts) REGULATIONS

Energy Efficiency Requirements for Air Conditioners, Chillers and Close Control Units

Water chillers water/water type SIGMA Technical information manual

PAC BT LOW TEMPERATURE HEAT PUMP WITH DHW TANK INCLUDED

DYNACIAT LGN. Description. Split system Water chillers. High energy efficiency Compact and quiet Scroll compressors Brazed-plate heat exchangers

ENTE CERTIFICAZIONE MACCHINE

BRL-K21030/02 5 August Certification of Alarm Communication. Certification Alarm Transmission Systems (ATS) Alarm Transmission Systems

ebrochure the information contained within this pdf document has been downloaded from the official Dimplex website

Smart Rules - Smart Application. Introduction to Ecodesign & Energy Labelling

Technical Data Sheet. Brine/Water Heat Pumps 8 12kW - single phase 230V. Heliotherm Basic Comfort. Basic Comfort Advantages

Working Document on a possible COMMISSION DELEGATED REGULATION

APPLICATION BROCHURE Chillers and Heat Pumps Hydraulics Manual. Suggestions for the hydraulic integration of chillers and heat pumps

Performance Rating of Unit Ventilators

CONTENTS AUTOMATIC TRANSFER SWITCHES

DRAFT ECODESIGN REGULATION FOR ENER LOT21 PRODUCTS

kw COOLING kw HEATING

HazLoc Essential Guides:

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

OJ L 239, , p. 1. OJ L 239, , p. 83, OJ L 239, , p. 136.

Refrigerating Appliance ErP Test Report

Delegated Regulation (EU) 1059/2010 of 28 September 2010 supplementing Directive 2010/30/EU with regard to energy labelling of household dishwashers

COMMISSION IMPLEMENTING REGULATION (EU) /... of XXX

(Non-legislative acts) REGULATIONS

AHRI Standard 870 (I-P) Standard for Performance Rating of Direct Geoexchange Heat Pumps

User manual. Explosion-safe window air conditioning system Type series AR-054. II 3 G Ex ic nac h IIC T3 Gc

Hydrocarbons as refrigerants

USER-MANUAL Tamson Cool Cube Immersion Cooler

Criteria of the German Ecolabel ("Blue Angel") for Stationary Air Conditioners

RSES Technical Institute Training Manual 3 72 hours, 72 NATE CEHs, 7.2 CEUs

Official Journal of the European Union. (Non-legislative acts) REGULATIONS

Lawnmowers, pedestrian controlled (combustion engine powered)

ECOS Position Paper: Further recommendations

HT V2 HT Split

Chain saws (electric mains powered and battery powered)

Data sheet SI 24TE. Brine-to-water heat pump with two performance levels

ENERGY ANALYSIS OF HEAT PUMP WITH SUBCOOLER

The Solar O&M Best Practices Mark

Energy Efficiency Schemes Brief Introduction

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

Technical data. Danfoss DHP-A

Do you want a versatile solution

Multiple split-system air-conditioners and air-to-air heat pumps Testing and rating for performance

Operator s Manual. IP-100 Immersion Probe Cooler

flexotherm exclusive Installation and maintenance instructions Installation and maintenance instructions For the competent person

F261 Series Fluid Flow Switches

WZS 82(H)(K)3M 20 I B0W I I I (263) (288) 7.0

ILNAS-EN 50304:2001. Electric ovens for household use - Methods for measuring the energy consumption

ASHRAE Standard

Performance Rating of Heat Pump Pool Heaters

A REVIEW ON GREEN TECHNOLOGY IN HVAC

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

Title 24, Part 6 Certification of Economizer Fault Detection and Diagnostics (FDD)

O L R E RGA ST RA N AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL

This document is a preview generated by EVS

PDF Created with deskpdf PDF Writer - Trial ::

Lawn trimmers and lawn edge trimmers (hand held electric mains powered)

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

COMcheck Software Version Review Mechanical Compliance Certificate

FINAL REPORT ON THE 4 TH JOINT CROSS-BORDER EMC MARKET SURVEILLANCE CAMPAIGN (2011) LED LIGHTING PRODUCTS

SA Series Startup Form

The test items passed the test specification(s).

IT COOLING CLOSE CONTROL AIR CONDITIONERS PRECISION AIR CONDITIONERS WITH INVERTER TECHNOLOGY FOR STABLE ROOM CONDITIONS

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

AIR TREATMENT. ReCOOLER HP» INTEGRATED COOLING/HEATING FUNCTION WITH REVERSIBLE HEAT PUMP IN THE eq AIR HANDLING UNIT

RULEBOOK ON ELECTROMAGNETIC COMPATIBILITY

Heat Pumps. Compact. Device Information. Operating manual supplement. LWC Series

Blue Box Epsilon Echos +

CO 2. ECO Water Heaters. Energy efficient and environmentally friendly water and space heating. SANYO Air Conditioners. The natural choice.

Neosys Product catalogue

Heat pump systems and Chillers

Transcription:

EHPA Testing Regulation Testing of Water/Water and Brine/Water Heat Pumps Terms, Test Conditions and Test Method based on EN 14511-1 to 14511-4 and EN 12102 Additional requirements for granting the international quality label for heat pumps Version 1.5 Release 01.09.2012 European Heat Pump Association Rue d Arlon 63-67 B-1040 Brussels www.ehpa.org phone +32 24 00 10 17 fax +32 24 00 10 18 info@ehpa.org contact: Michèle Mondot michele.mondot@cetiat.fr Page 1 / 10

Contents 1 INTRODUCTION... 3 2 SCOPE OF REGULATION... 3 3 REFERENCE DOCUMENTS... 3 4 TERMS AND DEFINITIONS... 3 5 OPERATING RANGE... 3 6 TESTS TO BE PERFORMED... 4 6.1 Performance tests... 4 6.1.1 Test conditions... 4 6.1.2 Test method... 6 6.2 Sound power level measurement... 7 6.3 Testing the operating range... 7 6.3.1 Test conditions... 7 6.3.2 Test sequence... 8 6.4 Safety tests... 8 7 TEST REPORT LEVEL 1 (DISCLOSURE STATUS: PRIVATE )... 9 7.1 General Information on the testing institute... 9 7.2 Technical datasheet... 9 7.3 Performance tests... 9 7.4 Sound power level measurement... 9 7.5 Operating range and safety tests... 9 8 MARKING... 9 EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 2 / 10

1 Introduction This regulation specifies the terms and definitions, the test conditions, the performance tests and other requirements for granting the EHPA Quality Label for water-to-water and brine-to-water heat pumps for space heating. The test conditions and testing methods described in this regulation are based on the European standard EN 12102:2008 and EN 14511, Parts 1 to 4, version 2011 and on additional specifications referenced herein. Anything not defined in this test regulation shall be proceeded regarding EN 14511. A heat pump can be awarded with the International Heat Pump Quality Label once it is successfully tested in accordance with this regulation. The process is described in the EHPA regulations for granting the international quality label for electrically driven heat pumps. This regulation has been adopted by the EHPA Quality Label Committee. Any changes to them must be approved by the Committee. 2 Scope of regulation This regulation applies to the testing of factory-made electrically driven water-to-water and brine-towater heat pumps for space heating under the testing conditions given in Chapter 6. In order to qualify for the EHPA Quality Label, the heat pump submitted for testing must be from series production. 3 Reference documents EN 14511:2011 Parts 1 to 4 Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 1: Terms and definitions Part 2: Test conditions Part 3: Test method Part 4: Requirements EN 12102:2008 Air conditioners, heat pumps and dehumidifiers with electrically driven compressors Measurement of airborne noise Determination of the sound power level 4 Terms and definitions The terms and definitions given in EN 14511-1 and EN 12102 apply. 5 Operating range The operating range defined by a maximum of 6 boundary conditions shall be declared by the manufacturer. Figure 1 provides an example of an operating range declared by the manufacturer. EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 3 / 10

Operating range 60 Supply 50 40 30 20-15 -10-5 0 5 10 15 20 25 Source [ C] Figure 1: Example of operating range defined by the manufacturer 6 Tests to be performed To be granted the heat pump shall perform the following tests: a) Performance tests (see chapter 5.1), b) Acoustic test (see chapter 5.2) c) Testing the operating range (see chapter 5.3) d) Safety tests (see chapter 5.4), 6.1 Performance tests Performance tests shall be made in accordance with EN 14511 for the determination of the heating capacity and COP at the test conditions given in Tables 1 to 3, when included in the operating range declared by the manufacturer. 6.1.1 Test conditions Environmental conditions are as defined in EN 14511-2. Test condition Table 1 Test conditions for low applications Type Heat source Heat sink Water-to-water heat pumps W10/W35 reference 10 7 30 35 W15/W35 1 15 * * 35 Brine-to-water heat pumps B0/W35 Reference 0-3 30 35 B5/W35 1 5 * * 35 B-5/W35 2-5 * * 35 (*) with the flow rate measured during the corresponding reference test condition EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 4 / 10

EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 5 / 10

Test condition Table 2 Test conditions for medium applications Type Heat source Heat sink Water-to-water heat pumps W10/W45 reference 10 7 40 45 W15/W45 1 15 * * 45 Brine-to-water heat pumps B0/W45 Reference 0-3 40 45 B5/W45 1 5 * * 45 B-5/W45 2 (**) -5 * * 45 (*) with the flow rate measured during the corresponding reference test condition (**) to be performed if test conditions in Table 3 are not in the operating range of the unit Test condition Table 3 Test conditions for high applications Type Heat source Heat sink Water-to-water heat pumps W10/W55 reference 10 7 47 55 W15/W55 1 15 * * 55 Brine-to-water heat pumps B0/W55 reference 0-3 47 55 B5/W55 1 5 * * 55 B-5/W55 2-5 * * 55 (*) with the flow rate measured during the corresponding reference test condition 6.1.2 Test method The testing shall be made according to EN 14511-3 with the additional following requirements: 6.1.2.1 Refrigerant charge Units that are prefilled from factory can be delivered as produced, if no additional refrigerant charge is required for testing installation. This is valid only if the factory has a control procedure for the refrigerant charging. If the heat pump is delivered filled with nitrogen and shall be charged with refrigerant by the test laboratory, then the refrigerant type and charge shall be as specified in the technical data (nameplate or technical documentation) provided by the manufacturer. 6.1.2.2 Brine When testing brine/water heat pumps, a brine concentration of 30 % by volume of ethylene glycol, with a freezing point of -15 C shall be used. Note: The concentration shall be checked by the test laboratory against density, freezing point or other properties. EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 6 / 10

If liquid heat transfer media other than water are used, the specific thermal capacity and density of the heat transfer medium must be determined and taken into account during the calculations. 6.1.2.3 Fixed capacity units For fixed capacity units, the thermostat shall be set at the highest value to force the unit to operate continuously with no On/Off cycling of the compressor. 6.1.2.4 Variable and staged capacity units For variable and staged capacity units, a part load test can be performed in the reference test conditions of either Table 1 or 2 or 3, according to manufacturerʼs specifications. 6.2 Sound power level measurement Measurement of the sound power level of the heat pump shall be performed according to the European standard EN 12102, using Class A method, at the reference condition of the highest application for which the unit shall be granted. According to the type of heat pump, the following sound power levels shall be measured: 1. Package unit, outdoors a. LWo : sound power level radiated by the outdoor side casing 2. Package unit, indoors a. LWi : sound power level radiated by the indoor side casing 3. Split unit a. LWo : sound power level radiated by the outdoor side casing b. LWi: sound power level radiated by the indoor side casing, only if the compressor is a part of the indoor unit. If a unit is declared to operate either with brine or water as heat source, only one sound power level measurement is required and performed with brine as heat source. 6.3 Testing the operating range The tests at the boundary limits are intended to show whether the heat pump is fully functional and operable in the warranted operating range stated by the manufacturer. 6.3.1 Test conditions For checking the operating range, four boundary test conditions are defined, including the test conditions specified in EN 14511-4 clause 4.2.1, as specified in Table 4: Test condition n Table 4 Boundary test conditions for testing the operating range water (brine) at the outdoor heat exchanger water at the indoor heat exchanger (*) Water(brine) flow rate at the outdoor heat exchanger Water flow rate at the indoor heat exchanger 1 Upper limit Upper limit Max. Max. 2 Lower limit Lower limit Min. Min. 3 Lower limit Upper limit Min Max. 4 Upper limit Lower limit Max Min. EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 7 / 10

(*) limited by the given air inlet upper or lower limit. Test shall be conducted at nominal voltage and with the minimum and maximum water(brine) flow rates as declared by the manufacturer. Supply 60 50 40 30 20 3 2 Operating range -15-10 -5 0 5 10 15 20 25 Source [ C] 4 1 Figure 2: Example of the four boundary limits to be tested for a given operating range 6.3.2 Test sequence For the boundary test conditions n 2 and 4, the heat pump shall start and remain in operation for at least 30 minutes without external interference and without being shut off by a safety device. For the boundary test conditions n 1 and 3, the heat pump shall start and remain in operation for at least 60 minutes without external interference and without being shut off by a safety device. During the tests, the permissible deviations as stated in EN 14511-4 clause 4.2.1 apply. There shall be no damage to the heat pump throughout the entire test. 6.4 Safety tests The safety tests check if the safety devices respond correctly to operational malfunctions and protect the heat pump from damage. The safety devices are tested by simulating operational malfunctions during normal heat pump operation, as follows: 1 Shutting off the heat transfer medium flows (see EN 14511-4 clause 4.4) 2 Complete power supply failure (see EN 14511-4 clause 4.5). Reference test conditions for low applications, as specified in Table 1, shall be used for the safety tests. Safety tests shall be performed in accordance with EN 14511-4 procedures given in Clause 4.4 and 4.5. EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 8 / 10

7 Test report Level 1 (disclosure status: private) Production of this test report by the heat pump test centre is part of the overall test procedure. The report is sent only to the manufacturer or the customer who has ordered the tests. The heat pump test centre is allowed to publish the test results only if the applicant has approved such publication with an authorized signature. This test report level 1 shall contain all test documents and shall fulfil the requirements in EN 14511-3 and EN 12102. 7.1 General Information on the testing institute - Date - Name of the testing institute - Test location - Test supervisor - Test number - References for properties of fluids - Test methods and reference to EN standards - References to the EHPA regulation and version 7.2 Technical datasheet - Name of the customer (usually the manufacturer) - Machine type, designation - Serial number (if not available, compressor serial number) - Brief description of the design - Information on the components, such as compressor type, heat exchanger type, expansion valve type, etc. - Year of production - Photos of the machine - Dimensions and weight of the heat pump - Type and charge of refrigerant: - GWP value of the refrigerant (as required by the EU Ecolabel, 2007/742/EC) 7.3 Performance tests The report shall include a description of the heat pump tested including all settings, such as thermostat, fan and pump speeds and capacity control settings where applicable. It shall include all data recorded as specified in EN 14511-3 Table 6 for the different test conditions given in Tables 1 to 3, where applicable. 7.4 Sound power level measurement - Specific requirements for installation of the tested model(s), where applicable - acoustic test method - measured sound power level(s) 7.5 Operating range and safety tests - Operating range tests passed or failed - Safety tests passed or failed 8 Marking EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 9 / 10

Each heat pump shall have a durable, permanently fixed marking that is easily readable when the unit is in position for use, bearing at least the information required by the safety standards. The nameplate shall include the following information: - Manufacturer or supplier - Model designation and serial number - Type and filling weight of the refrigerant As heating capacities and COPs are dependant of the test conditions and of the different possible matching of the two parts of a split unit, these performances shall be indicated in the technical documentation of the manufacturer. EHPA TestReg BW-WW-HP V1.5 september 2012.doc Version 1.5 Page 10 / 10