Implementation of the Laboratory Air Handling Unit Systems (LAHU)

Similar documents
Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

DIGI-VAV APPLICATIONS

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

The Temperature and Relative Humidity Control in Cushing Library

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Civil Engineering Building

HVAC Controls Upgrades: Requirement Details ( )

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

HVAC Controls Upgrades: Requirement Details ( )

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

Selected Laboratory Energy Efficiency Measures

Do All DOAS Configurations Provide the Same Benefits?

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Adding More Fan Power Can Be a Good Thing

Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems

Mechanical Technical Report 1. ASHRAE Standard 62.1 Ventilation Compliance Evaluation

Auburn University Basketball Arena:

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Achieving Dry Outside Air in an Energy-Efficient Manner

Continuous Commissioning Report

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

7. MECHANICAL SYSTEM DESIGN

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Pharmaceutical Facility Design

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

HVAC Mandatory Provisions Part II, Page 1

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

High-Performance VAV Systems

Dehumidifying with Dedicated Outdoor Air

2009 IECC Commercial Mechanical Requirements

DACC Health Sciences Building Air Handler Assessment/Study

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

REPRODUCTION/DISTRIBUTION IS PROHIBITED. Energy-Savings Strategies for. Rooftop

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

The M & V Guided Recommissioning Process. Energy & Water Conservation Program. September 2015 MOO

Description of All Alternatives Considered-

Digital Precise Air Control - DPAC

UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

Raised Access Floor - (AE Breadth Area)

Displacement Ventilation in Classrooms

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

CHAPTER 4. HVAC DELIVERY SYSTEMS

IAQ: Re-tuning Commercial Buildings

Mold/Moisture Control Case Study

City of Duluth Festival Center 04/25

4. OVERVIEW OF MECHANICAL SYSTEM

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

Physical Plant Complex

Redesign of Bennett Hall HVAC System

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

DOAS UNITS. ReznorHVAC.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR

Active desiccant integration with packaged rooftop HVAC equipment

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Computing Services Center

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

MD and Its Impact on Lab Facilities

Chilled Beams in Labs Eliminating Reheat & Saving Energy on a Budget

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

FORM EG2 (502) FlexSys Configured Packaged Rooftop Air Conditioning Units

Existing Mechanical System Operation

Technical Assignment 3 11/15/04. Executive Summary

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

Designing Energy Efficient Outdoor Air Systems

FLORIDA A&M UNIVERSITY PERFORMANCE CONTRACT SCOPE OF WORK

Benefits Offered by Passive Dehumidification Wheel Speed Control

COMcheck Software Version Review Mechanical Compliance Certificate

BAS Point Trend Data Guidance

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

Indoor Pool Design Considerations Colorado Springs, Colorado

Mechanical Compliance Certificate

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

Challenges and Methods of Estimating a Conceptual HVAC Design

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

Harrington Tower Building

Transcription:

University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Architectural Engineering -- Faculty Publications Architectural Engineering 2003 Implementation of the Laboratory Air Handling Unit Systems (LAHU) Y. Cui University of Nebraska-Lincoln Mingsheng Liu University of Nebraska Lincoln, mliu2@unl.edu K. Conger University of Nebraska-Lincoln Follow this and additional works at: http://digitalcommons.unl.edu/archengfacpub Part of the Architectural Engineering Commons Cui, Y.; Liu, Mingsheng; and Conger, K., "Implementation of the Laboratory Air Handling Unit Systems (LAHU)" (2003). Architectural Engineering -- Faculty Publications. 28. http://digitalcommons.unl.edu/archengfacpub/28 This Article is brought to you for free and open access by the Architectural Engineering at DigitalCommons@University of Nebraska - Lincoln. It has been accepted for inclusion in Architectural Engineering -- Faculty Publications by an authorized administrator of DigitalCommons@University of Nebraska - Lincoln.

Implementation of the Laboratory Air Handling Unit Systems (LAHU) Y. Cui Graduate Student Energy Systems Laboratory University of Nebraska-Lincoln Omaha, NE, USA M. Liu, Ph.D., P.E. Associate Professor Energy Systems Laboratory University of Nebraska-Lincoln Omaha, NE, USA K. Conger, P.E. Energy Project Engineer Building Systems Maintenance University of Nebraska-Lincoln Omaha, NE, USA ABSTRACT The LAHU system has been designed, installed, and commissioned in a large university research building. This paper provides detailed information about the demonstration project, including the specific LAHU system mechanical design, optimal airflow control schedules, and measured LAHU energy and indoor air quality (IAQ) performance. The measured energy and IAQ performance are also compared with the conventional operation and theoretical predicated values. INTRODUCTION Most laboratory buildings have both office and laboratory spaces. Conventional AHU designs for laboratory buildings use two separate AHUs, one for the office section and another for the laboratory section. The laboratory section AHU uses 100% outside air to satisfy the requirement of the laboratory exhaust airflow rate. The discharge air temperature of the cooling coil is controlled at 55 F (12.8 C) to maintain a suitable humidity level. A significant amount of cooling and heating, especially re-heat, is consumed due to high supply airflow rate required by the fume hood exhaust. At the same time, the office section draws minimal outside air intake to satisfy indoor air quality requirements. The total building outside air intake is higher than necessary, which causes excessive heating and cooling energy consumption. To improve the energy performance of the conventional systems, a number of energy conservation measures have been developed and implemented in laboratory facilities. These measures are the air-to-air heat recovery heat recovery [1-7], the run-around coils [18, 19], the variable air volume (VAV) fume hoods [8-16] and the usage-based control devices (UBC) [17]. These measures have effectively reduced the cooling energy, preheat energy and fan power consumption, and sometime, improved indoor relative humidity control. To maximize AHU energy performance efficiency in laboratory buildings and improve office section indoor air quality (IAQ), the Laboratory Air Handling Unit (LAHU) has been developed [20, 21, 22]. The theoretical investigations have found that the LAHU uses less outside air during summer and winter, improves the indoor air quality (IAQ) of the office section, and saves up to 30% of annual thermal energy when the optimal airflow control schedules are used [23]. This paper presents the implementation of the LAHU in a chemistry engineering education facility, which includes the facility and LAHU design and construction information, optimal airflow control schedules implemented, and measured energy savings and indoor air quality improvements. EXPERIMENT FACILITY The experimental facility is a three-story chemistry engineering research laboratory building located at Lincoln, Nebraska (See Figure 1). The building has a total floor area of 12,077 m 2 (130,000 ft 2 ). Figure 2 presents the typical floor layout. Office spaces are on the perimeter of the building with windows. Some offices and classrooms are located in the interior zone. Laboratory spaces are located in the interior zone as well. Figure 1: Experimental Facility 1

Figure 2: Typical Floor Plan A total of 28 fume hoods was designed while 23 of them had been installed at the time of the paper was written. The Usage Based Control (UBC) has been installed for each fume hood. The UBC maintains the face velocity at 100 fpm (0.51 m/s) when an operator is present and 60 fpm (0.30 m/s) when the operator is absent. The fume hood airflow is not allowed to be less than 20% of the design airflow regardless of the position of the sash. The current maximum exhaust airflow with existing fume hoods is 29,700 cfm (50,460 m 3 /h). Figure 3 presents the schematic diagram of the LAHU designed and installed in the experimental facility. Four supply air fans (1, 2, 3a and 3b) provide conditioned air to the perimeter, the interior zone other than laboratory spaces, and laboratory spaces, respectively. The fan speeds are modulated by VFDs to maintain the set points of the static pressure in their main supply air ducts. Supply air fan 1 has a design capacity of 46,000 cfm (78,155 m 3 /h). Supply air fan 2 has a design capacity of 25,000 cfm (42,474 m 3 /h). Supply air fans 3a and 3b work parallel and have a total capacity of 60,000 cfm (101,940 m 3 /h). Supply air fan 3a and 3b are installed ahead of the cooling coil 3 (CC3) instead of after the cooling coil because the total supply airflow of the office and classroom sections is expected to be higher than the supply air airflow of the laboratory section. This modification reduces the system cost and simplifies the optimal control. Two return air fans draw return air back from the interior and exterior office and classroom areas and send back to the four supply air fans. The return air distribution to each supply air fan is modulated using two sets of outside air and return air dampers (FAD1 and RAD1, FAD2 and RAD2), two release air dampers (EAD1 and EAD2) and two transfer air dampers (TAD1 and TAD2) based on the optimal airflow distribution control sequence. Seventeen temperature sensors are installed to measure air temperature entering and leaving heat recovery coils, inside the mixed air chambers, leaving preheat coils, leaving cooling coils, and entering return air fans. Eight relative humidity sensors are installed to measure air relative humidity level entering heat recovery coils, leaving cooling coils, and entering return air fans. Three CO 2 sensors are installed to measure zone leaving air CO 2 concentrations. One static pressure sensor is set to monitor the static pressure in the mixed air chamber of laboratory section outside air and return air from return air fan 2 (RF2) relative to the outside airflow before the heat recovery coil 3 (HR3). Three other static pressure sensors are installed 2

Figure 3. Schematic Diagram of Major HVAC Systems in the downstream of each cooling coil. The airflow through each fan is measured using fan inlet airflow station. A constant volume air-to-air heat recovery system is designed to transfer heat between the exhaust air and the outside air. A modern EMCS system is installed to monitor and control the LAHU system and other associated HVAC systems. OPTIMAL AIRFLOW CONTROL SCHEDULES The optimal airflow control schedules have been developed for LAHU systems under general conditions [23] and given supply air temperatures. The optimal airflow control for the experiment facility is presented in Figure 4, which was developed by customizing the general optimal schedules. The control system judges the operation mode based on the monitored air conditions leaving the heat recovery coils and the return air conditions. If the heat recovery discharge air temperature and enthalpy for the perimeter office spaces is lower than the return air temperature and enthalpy respectively, the operation is in economizer mode. Otherwise, the operation is in non-economizer mode. In economizer mode, when the total fresh air intake of the office and classroom sections is higher than the return airflow requirement of the laboratory spaces, economizers are controlled independently for each supply air fan. Otherwise, control the total fresh air of the office and classroom sections at the return air airflow of the laboratory section. This control sequences minimize total thermal energy consumption and maximize the IAQ of the office and classroom sections. The IAQ is also sufficiently maintained at the acceptable level. To implement this optimal control, the control system first tries to maintain the mixed air temperatures of supply air fans 1 and 2 at their set points by modulating the outside air dampers (FAD1 and FAD2), and to maintain the mixed air temperature of supply air fans 3a and 3b by modulating transfer air dampers (TAD1 and TAD2). The mixed air temperature set point is defined as the supply air temperature minus the fan temperature rise. The release air dampers 1 and 2 (EAD1 and EAD2) are reversely interlined with the transfer air dampers 1 and 2 respectively. When the transfer air damper is full open, the release air damper is closed. If the transfer air dampers are full open and the mixed air temperature of supply air fans 3a and 3b is still lower than the set point, the return airflow from the office section is not enough for the laboratory section. Consequently, set the mixed air temperature of 3

Set T c,1, T c,2, T c,3 Get T hr,1, T oa, Rh oa Get T r,1, Rh r,1 Y (Economizer) Economizer N (Outside Econ.) Modulate FAD1and FAD2 to Make T m,1=t set,m1, T m,2=t set,m2 Modulate FAD1and FAD2 to Make T m,1=t set,m1, T m,2=t set,m2 Modulate TAD1or TAD2 to Make T m,3=t c,3 Keep TAD1and TAD2 Full Open SET EAD1and EAD2 Keep EAD1and EAD2 Closed N TAD1 or TAD2 Y AHU3 get 100% Y N RESET T set,m1 or T set,m2 To a Lower Value RESET T set,m1 or T set,m2 Figure 4: Control Procedures of the Optimal Airflow Distribution Schedules the office section at lower value to force more outside air intake to the office section. In non-economizer mode, the total fresh air intake of the office section should be controlled at the airflow of supply air fans 3a and 3b provided the total airflow of the office section is higher than the airflow of the laboratory section. Otherwise, the office section should use 100% outside air. To implement this principal of optimal airflow control, the control system sets the transfer air dampers at full open and relief air dampers closed since the laboratory section airflow is always higher than the minimum airflow required than the office section. If the static pressure in the mixed air chamber of outside airflow and return air flow from fan RF2 is less than the set point of +0.05 inh 2 O (adjustable, slightly higher than 0.0 inh 2 O), close return air dampers 1 and 2 (RAD1 and RAD2) more to force more outside air flow to supply air fans 1 and 2 (SF1 and SF2). If the static pressure is higher than the set point, open the return air dampers 1 and 2 more to reduce outside air intake to supply air fans 1 and 2. In this case, the laboratory section uses 100% return air. When both return air dampers 1 and 2 are closed and the static pressure of the mixed air 4

chamber is still less than the set point, outside air is drawn automatically into the mixed air chamber for supply air fans 3a and 3b. In this case, the office and classroom sections receive 100% outside air. The total outside air intake of the building equals the summation of the exhaust air of the laboratory section, and the common exhaust and the air ex-filtration of the office and classroom sections. The release airflow of the two sections is zero. Therefore, the LAHU uses less fresh air than the conventional design. The optimal control sequences are developed based on the given heat recovery system operation sequences. Heat recovery system is kicked on when the outside air temperature is higher than 83 F (28.3 C) or lower than 55 F (12.8 C) and shut off otherwise. Each heat recovery control valve is modulated to control its discharge air temperature at the set point of mixed air temperature for each supply air fan. The interactions of the heat recovery control sequence and the outside airflow intake control is not considered in this case. RESULTS Two sets of control sequences are developed and implemented in the EMCS system. One set of the control sequences is the optimal control sequence described in the last section. This is called the LAHU case. The other set of the control sequences is the optimal control sequences with the following constraints: (1) return fan 1 serves supply air fan 1 only; (2) return air fan 2 serves the supply air fan 2 only; (3) supply air fan 3a and 3b receive 100% outside air. This is called the base case, where the system is operated as a conventional system for laboratory buildings. In both the LAHU and the base cases, the supply air temperature set points for supply fans 1 and 2 are the same. In the LAHU case, the supply air temperature set point of supply air fans 3a and 3b is 60F. In the base case, it is set at 55F for room relative humidity control. In both the LAHU and the base cases, the heat recovery system is controlled under the same schedule. Test Results for Economizer Operation The LAHU system hourly economizer operation was tested and recorded between 9:00 a.m. on April 7, 2003, and 10:00 a.m. on April 9, 2003, when the cold deck was set to 55 F (12.8 C) for all three units. The recorded airflow rate during this period was around 30,000 CFM, 20,000 CFM and 26,000 CFM respectively for AHU1, AHU2 and AHU3. The test shows that these three units all maintained the mixed air temperature at each set point. Therefore, AHU3 consumed no preheat. The preheat energy savings of the LAHU operation over the outside air temperature, compared with the normal operation where AHU1 and AHU2 use economizer and AHU3 takes 100% outside air, is then calculated and presented in Figure 5 for this operation period. Since exhaust fumehoods have not been fully equipped as design so far, the AHU3 total supply airflow rate is not high and subsequent supply air temperature is not high. However, the supply air temperature will be higher than the current set after all the fumehoods are installed due to high ventilation requirement. Therefore, the test also shows the preheat energy savings when AHU3 cold deck set point is 60 F (15.6 C) in Figure 5. The preheat savings agrees exactly with the predicted optimal energy savings since the optimal schedules are obtained in the operation with the measurement bias. This test demonstrates that the energy savings of the LAHU operation will be about 420 MMBtu (443.0E6 KJ) and 820 MMBtu (865.0E6 KJ) with cold deck set point 55 F (12.8 C) and 60 F (15.6 C) separately over the outside air temperature between 20 F (-6.7 C) and 40 F (4.4 C) which account for 2,800 hours of yearly 8,760 hours [24]. In fact, as AHU3 supply air flow rate increases with the installation of more fumehoods, the savings will be higher. Preheat Savings (MMBtu/hr) 0.45 0.4 0.35 0.3 Tc,3 =60F 0.25 0.2 0.15 0.1 Tc,3 =55F 0.05 0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 Figure 5: Outside Air Temperature (F) Preheat Energy Savings for LAHU Economizer Operation The discharge air pressure for the three AHUs during the LAHU operations is illustrated as Figure 6. The set points are 1.6 and 2.0 for 5

Supply Air Static Pressure (Inch) 2.5 2 1.5 1 0.5 0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 Outisde Air Temperature (F) AHU1 AHU2 AHU3 Figure 6: Static Pressure for LAHU Economizer Operation AHU2 and AHU3. The set point for AHU1 is linearly reset between 0.5 and 2.0 when outside air temperature is 30F and 100F. Figure 6 clear shows that the integrated LAHU system can maintain stable static pressure set point. AQ for AHU1 and AHU2 kept the same as the normal operation since the economizer is used in both the normal and LAHU operation under the airflow rate at that time. Test Results for Non-Economizer Operation The LAHU optimal airflow control programs are being tested for the Noneconomizer operations. The primary results have proved the feasibility of the optimal LAHU operation and shown the potential thermal energy savings and the improved IAQ predicted by the theoretical optimal schedules. The test shown below was conducted between 5:00p.m. and 8:30p.m. on July 1, 2003. The LAHU operation data were recorded on 6:20p.m. The normal operation data were recorded on 8:30 when the system kept stable after it was switched back to the normal operation from the LAHU operation. The data are listed on Table 1, where AHU3 supply air temperature is 55 F (12.8 C). Table 1 Comparison of Normal and LAHU Operation for the Outside Economizer Operation Condition AHU1 AHU2 AHU3 Fresh Air Temp ( F) / Normal 86.8/80.2 83.5/80.2 85.7/80.8 HR Disch. Air Temp( F) LAHU 90.8/82.1 89.5/83.3 90.4/80.1 Return Air Temp ( F) Normal 74.7 72.3 75.7 LAHU 74.7 72.3 75.7 Mixed Air Temp ( F) Normal 77.6 76.2 80.2 LAHU 79.6 83.9 73.8 Outside Air Damper Normal 5%/ 2% 4%/ 2% 100%/ Position/transfer damper LAHU 18%/ 98% 87%/ 99% 100%/ Cooling Coil Valve Normal 30.8% 27.5% 31.5% Position LAHU 37.8% 33.2% 19.7% Supply Airflow Rate Normal 34,132 20817 29,869 (CFM) LAHU 37,869 20,377 28,327 Fresh Air CO 2 (ppm) Normal 418/371 418/377 / /Return Air CO 2 (ppm) LAHU 428/375 428/381 / 6

Figure 7: Supply Air Static Pressure of AHU1, AHU2 and AHU3 in LAHU Operation (Unit: Inch WCI) It needs attention that the return air temperature sensor is located in the inlet of the return air fans of the AHU1 and AHU2. The transfer air temperature dampers are full open for LAHU operation, and the outside air dampers of AHU1 and AHU2 were partially open at different positions. AHU3 s mixed air temperature indicates that AHU3 used 100% return air. The cooling energy savings is calculated to be over 20%. Accordingly, AHU3 reheat energy can then be saved 0.16MMBtu/hr (46.88KW) when supply air temperature increase to 60 F from 55 F (12.8 C) and 0.32MMBtu/hr (93.76KW) when supply air temperature increase to 65 F from 55 F (12.8 C). With the test AHU3 supply air flow rate 29,869 cfm (50,747m 3 /h), the annual reheat savings will be 340 MMBtu (358.6E6 KJ) situation and 680MMBtu (712.7E6 KJ) with supply air temperature 60 F (12.8 C) and 65 F (15.6 C) separately when outside air temperature is higher than 72 F (22.2 C) which account for 2,100 hours of yearly 8,760 hours [24]. As laboratory has higher exhaust, the reheat and cooling savings will be higher. The IAQ improvement is not obvious because of low occupancy in the building during the test. The data also show that the room IAQ of the office sections is better in the LAHU operation relative to the simultaneous outside air CO2 (the reason the outside air CO2 concentration is higher than the return air is due to different sensor accuracy). The value of AHU1 s and AHU2 s return air CO2 concentration was a little lower in normal operation due to low occupancy and lower outside air intake. Discharge air static pressure stability was demonstrated as Figure 7 after LAHU operation was stable, where the discharge air pressure set point was 1.7, 1.6 and 2.0 for AHU1, AHU2 and AHU3 separately. The three records in Figure 6 are the discharge air pressure AHU3, AHU1 and AHU2 from the top to the bottom. It shows that stable pressure can be maintained for LAHU operations. To test the room humidity level results from high cold deck set point, AHU3 cold deck set point was adjusted to 55 F (12.8 C), 60 F (15.6 C) and 65 F (18.3 C). The AHU3 room air relative humidity was recorded as 55%, 58%, and 59%. This test proves that high cold deck set point 65 F (18.3 C) will increase room relative humidity by around 4% compared with the cold deck set point 55 F (12.8 C), which indicates that high cold deck set point will not cause humidity problem for AHU3 lab section. More tests are being conducted on the chilled water and reheat energy savings hourly measurement and IAQ improvement. CONCLUSIONS The implementation of the LAHU system in the research facility shows that the optimal LAHU system works not only theoretically but also in practice in modern laboratory building automation systems. The implementation principal used for this facility is applicable to any laboratory building with specific control details considering the local weather and mechanical system characters. The implementations of LAHU system in this typical size laboratory building can save significant preheat in economizer operation as well as reheat and cooling in non-economizer 7

operation under the optimal airflow control as projected by theoretical analysis. IAQ of office section can be improved. The LAHU system can maintain stable supply air pressure control and room comfort requirement. The implementation proves that the LAHU system is an applicable energy and IAQ efficient system for laboratory buildings. NOMENCLATURE T = Air temperature ( F or C) h = Enthalpy (Btu/lb or KJ/Kg ) P = Static Pressure (Inch Water or Pa) Subscripts oa = Outside air c = Cold deck hr = Heat recovery discharge air m = Mixed air r = Return air set = Set point,1 = Exterior Office Section, 2 = Interior office and classroom section,3 = Laboratory section ACKNOWLEDGMENT The authors would like to express the appreciation to Ms. Derrick for her editing assistant. REFERENCES [1] Sauer, H. J., and Howell, R. H., 1981, Promise and Potential of Air-to-Air Recovery Systems, ASHRAE Transactions, Vol. 87, Part 1, pp. 167-182. [2] Barker, P. L., 1994, Biomedical Laboratory Uses VAV Fume Hoods and Heat Recovery to Save Fuel Costs, ASHRAE J., 36(3), pp. 41-43. [3] Bard, E. M., 1994, Energy Efficient HVAC System Features Thermal Storage and Heat Recovery, ASHRAE J., 36(3), pp. 38-40. [4] Lacey, D. Randall and Smith, Darin C., 1997, Innovative Ventilation System for Animal Anatomy Laboratory, ASHRAE Journal, 39(4), pp. 65-67. [5] Carnes, L., 1988, Air-to-Air Heat Recovery Systems for Research Laboratories, ASHRAE Transactions, Vol. 90, part 2A, pp. 327-340. [6] Moyer, R. C., 1978, Energy Recovery Performance in the Research Laboratory, ASHRAE Transactions, Vol. 84, Part 1, pp. 538-546. [7] Streets, R. A., and Setty, B. S. V., 1983. Energy Conservation in Institutional Laboratory and Fume Hood Systems, ASHRAE Transactions, Vol. 89, pp. 542-551. [18] Hill, J. M., and Jeter, S. M., 1994, The Use of Heat Pipe Heat Exchangers for Enhanced Dehumidification, ASHRAE Transactions, Vol. 100, Part 1, pp. 91-102. [19] Scofield, C. Mike., 1993, Low Temperature Air with High IAQ for Tropical Climate, ASHRAE J., 35(3), pp. 52-59. [8] Boldt, Jeffrey G., 1993, Separate HVAC systems maximize energy efficiency, ASHRAE Journal, 35(4), pp. 16-19. [9] Bard, E. M., 1995, Laboratory Integrates VAV Fume Hood Controls with Central Building Automation System, ASHRAE Journal, 37(3), pp. 40-42. [10] Murry, H. J., 1983, The effect of load diversity on HVAC costs, ASHRAE Transactions, Vol. 89, Part 1B, pp. 150-154. [11] Davis, S. J., and Benjamin, R., 1987, VAV with Fume Hood Exhaust System, Heating/Piping/Air Conditioning, 59(8), pp. 75-78. [12] Moyer, R. C., and Dungan, J. O., 1987, Tuning Fume Hood Diversity into Energy Savings, ASHRAE Transactions, Vol. 93, Part 2, pp. 1822-1832. [13] Lentz, M. S., and Seth, A. K., 1989, A Procedure for Modeling Diversity in Laboratory VAV Systems, ASHRAE Transactions, Vol. 95, Part 1, pp. 113-120. [14] Parker, J. A., Ahmed, O., and Barker, K. A., 1993, Application of Building Automation System (BAS) in Evaluating Diversity and Other Characteristics of a VAV Laboratory, ASHRAE Transactions, Vol. 99, pp. 1081-1089. [15] Rabiah, T. M., and Welkenbach, J. W., 1993, Determining Fume Hood Diversity Factors, ASHRAE Transactions, Vol. 99, Part 2, pp. 1090-1096. [16] Bard, E. M., 1995, Laboratory Integrates VAV Fume Hood Controls with Central Building Automation System, ASHRAE J., 37(3), pp. 40-42. [17] Phonenix Controls Corporation, Laboratory Source Book. [20] Cui, Y., and Liu, M., 2001, Laboratory Air handling Unit System, Proceedings of International Conference for Enhanced Building Operation, Austin, TX, pp. 17-24. [21] Cui, Y., and Liu, M., 2002, Optimal Airflow Control for Laboratory Air Handling (LAHU) Systems, Thirteenth symposium on Improving Building Systems in hot and Humid Climates, Houston, TX. [22] Boldt, Jeffrey G., 1993, Separate HVAC systems maximize energy efficiency, ASHRAE Journal, 35(4), pp. 16-19. [23] Cui, Y., and Liu, M., 2003, Optimal Airflow Control of Laboratory Air Handling Unit 8

(LAHU) Systems, Journal of Solar Energy, in review. [24] Degelman, L., 1986, Bin Data Weather, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., Atlanta. 9