PANTHER. Condensate removal pump Installation and operating guide

Similar documents
SUBMERSIBLE WATER PUMPS

PUDDLE PUMP PUDDLE PUMP. MODEL No: PSP125 OPERATION & MAINTENANCE INSTRUCTIONS. Part No:

NON-SUBMERSIBLE WATER PUMP

3 In 1 AIR CONDITIONER with REMOTE CONTROL MODEL NO: CA9000 PART No: OPERATION & MAINTENANCE INSTRUCTIONS

LEC L6014W/S User Manual

Hozelock Ltd. Midpoint Park, Birmingham B76 1AB. England Tel: +44 (0)

Mobile Air Conditioner Instruction Manual Model TC-N9KM

CLEAN WATER PUMP. MODEL No: Hippo4A OPERATION & MAINTENANCE INSTRUCTIONS. Part No:

VADA - Rain2Main Automatic Rainwater Controller

Electrisaver User and Installation Instructions

Dual-Hose Portable Air Conditioner User Manual

Glass Chimney Hood. Installation & User Instructions Please keep for future reference

Your Blast Vac Pro. Your Blast Vac Pro

DEHUMIDIFIER MODELS: SD-30E / SD-40E / SD-65E INSTRUCTION MANUAL

SH3020 USER INSTRUCTIONS

Safety Warnings & Advice 3 Your Blast Vac Pro 4 Care & Cleaning 13 Using Your Vacuum 8 Troubleshooting 14 Guarantee 14 Technical Information 15

INDUSTRIAL VACUUM CLEANER WITH AUTO START/STOP

INSTALLATION AND OPERATION INSTRUCTIONS FOR WALL-MOUNT AND BUILT-IN UNITS

INSTRUCTION MANUAL Model: SU3022

Gallery Electric Fireplaces

Installation & Operating Instructions

EH0533 Indoor Climate Control

Gobi II. English. Condensate Pump Instruction manual Gobi II

Portable Ventilation Fans

INFRARED PARAFfIN / KEROSENE / model No: ir20.v2 1. SAFETY INSTRUCTIONS RECOMMENDED FUSE RATING: 5AMP

ISIS SAFETY SYSTEM Installation guide

INSTANTANEOUS ELECTRIC SHOWER

IDL/ De Longhi Appliances via Seitz, Treviso Italia

PRESSURE WASHER MODEL NO: JETSTAR 1750 OPERATION & MAINTENANCE INSTRUCTIONS. WARNING Read the instructions before using the machine PART NO:

Refresh & Clean Carpet Washer

4L Instant Water Boiler Instructions for Use

MODEL:DCB09(2.6kW Cooling / 2.4kW Heating) DCB14(4.1kW Cooling / 3.6kW Heating) DCB05C(1.6kW Cooling) DCBB07C(2.2kW Cooling) IMPORTANT

INSTALLATION AND OPERATION INSTRUCTIONS FOR BI-DEEP UNITS

CENTRIFUGAL PUMPS OPERATING INSTRUCTIONS

Installation, Operation and Maintenance Manual

Flomate Mains Boost Pump Installation & Maintenance Instructions

Instruction Manual Model: IM03A

Trouble Shooting and Help Guide TT / TTB 1840

General Care and Safety Guide

Installation & User Instructions: Model: e600s e600gf e700s e1000s e1000gf e1030gf/2/3 e1500gf/2/3

SUBMERSIBLE WATER PUMP. Model Nos. CSE1 - CSE1A - CSE2 - CSE2A CSD3- -CSD3A CSV1A - CSV2 - CSV2A - CSW1A OPERATING & MAINTENANCE INSTRUCTIONS

MODEL: DCB07(2.2kW Cooling / 2.05kW Heating) DCB09(2.6kW Cooling / 2.4kW Heating) DCB14(4.1kW Cooling / 3.6kW Heating) DCB05C(1.

V80-H Multistage Pump Instruction Manual

MULTI-FUNCTION HAND VACUUM INSTRUCTION MANUAL. For Authentic Monster Replacement Parts Call Model #: H056

EVAPORATIVE COOLER PUMPS

Paper Shredder. Installation & User Instructions Please keep for future reference 913/0153

WET & DRY VACUUM CLEANER

GRUNDFOS INSTRUCTIONS. Sololift2 C-3. Installation and operating instructions

INSTALLATION AND OPERATION INSTRUCTIONS FOR SAFETY INFORMATION WARNING

model No: ir20.v2 FUSE

Imperial Electric Fires

A4 Laminator. Installation & User Instructions Please keep for future reference 908/6197

LIMITED LIFETIME WARRANTY

Operating instructions HOT WATER BOILER HEETWATERAPPARAAT HWA 20

PARAFFIN/DIESEL HEATER

Operating and assembly manual: Electric instantaneous flow heater Admiral

IMPORTANT SAFEGUARDS Ensure that your mains supply voltage is the same as that marked on the underside of your kettle.

Contents. Specifications. Description SV HP 55 SV HP 90. Specifications Warnings Introduction Overview... 4

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

TH100 Three in One Instant Hot Water Tap

M770 ph Controller Owner s Manual

USERS INFORMATION MANUAL

Mini Tower Fan NSMTF-18

DIRTY WATER SUBMERSIBLE PUMP

Safety and Instruction Manual

s l it l on for Infrared Heaters

Compact Cyclonic Bagless Upright Vacuum Cleaner

INSTRUCTIONS MANUAL. 1.8L Electric Kettle with Multi-Temp Feature SK-1800R (Red) SK-1800SS (Stainless Steel)

MODEL: DC10RCDH / DC12RCDH

10L Dehumidifier. Model Number: LDH V AC 50/60Hz 290W

WET/DRY VACUUM. QUEST for Continuous Improvement Windsor s Quality Management System is Certified ISO MODEL: T1. Operating Instructions (ENG)

INSTRUCTION MANUAL FOR ELECTRIC RADIANT INFRARED HEATERS

OPERATOR'S MANUAL. IMPORTANT: READ OPERATOR'S MANUAL CAREFULLY Please fill out & return your warranty card! DP80405

DIRTY WATER SUBMERSIBLE PUMP KIT

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

Flo~mate Mains Boost Pump Installation & Maintenance Instructions

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

INSTALLATION AND OPERATION INSTRUCTIONS FOR

CENTRIFUGAL PUMPS OPERATING INSTRUCTIONS

INSTALLATION AND OPERATION INSTRUCTIONS FOR WALL-MOUNT AND BUILT-IN UNITS

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Greenleaf 600 Macerator Toilet Waste Pump

Argos Value Tabletop Fridge

Installation, Operation & Maintenance Instructions

SUSHI SHOWCASE BMCSS05

CPE RANGE PUMPS CPE RANGE PUMPS. MODEL Nos: CPE15A1 15A3 20A1 20A3 30A1 30A3 PART Nos:

NXM2G Installation and Operating Manual

Power Supply Display Module PSDM. Installation and Operation Manual

BOILING UNIT REDITAP. Installation and User Guide. IMPORTANT: This booklet should be left with the user after installation and demonstration

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Note: before using the system read this manual carefully, store it and, in case, transfer it to a new user. prima

90cm Chimney Extractor

DIESEL/PARAFFIN HEATERS

Antari Z-300 ORDERCODE 60661

Instruction Manual WARNINGS

Saturn Booster PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USE AND KEEP THEM FOR FUTURE REFERENCE

User Manual 120/240/300 Outdoor Motion Detector

LOW TEMPERATURE DEHUMIDIFIER DES 80 OWNER S MANUAL

Induction Fryer. Instruction manual. Model Modèle Modell Modello Modelo Malli: CP793

Sanitary Water Tank INSTALLATION & SVC MANUAL

Transcription:

PANTHER Condensate removal pump Installation and operating guide The PANTHER is a self-contained condensate removal system for use directly inside trunking and highwall-mount air conditioners.the small remote sensor can be fitted inside the air handler whilst the pump unit can be positioned elsewhere. Specifications Power supply: /4Vac, 5/6Hz Auto sensing Power consumption: 6W max.,.5w when idle Alarm relay: 5A, Vdc, 5Vac Break on fault Capacity: litres/hour max. (.7 US gal/h) Maximum head: Vertical >m (65 ft), Horizontal > m (8 ft) Suction m max. (.8 ft) Ambient temp: - 4 C Water temp: 5 C max. Material: Flame retardant ABS UL94 5VA Discharge tube: 6mm (/4 ) ID Dimensions: Pump: 5 x 46 x mm (5. x.8 x.6 ) : 45 x 6mm dia. (.8 x.4 dia.) IP: Flow rate (US gal/h)) (l/h) 9 8 7 6 5 4 Capacity 4 5 6 7 8 9 4 5 6 7 8 9 (m) 4 5 6 Vertical lift m Horiz 5m Horiz m Horiz (ft)

SAFETY INSTRUCTIONS AND WARNING Under normal use this equipment requires no user intervention. Installation, both fixing and electrical, and maintenance work shall be carried out only by the manufacturer or by its service center or in any case by a person having similar skills, so as to prevent any risk. Electrical installation of equipment shall be in compliance with these installation instructions and with all National and Local Regulations for Electrical Safety. To reduce the risk of fire, electrical shock and injury to persons, the following safety instructions shall be used: This pump is intended for indoor use with water only (max 5 C). This pump is NOT SUBMERSIBLE. Disconnect ALL power supplies before starting installation, connection or maintenance work. This pump is provided with a grounding conductor. To reduce the risk of electric shock, be certain that it is connected only to a properly grounded, grounding type receptacle. All interconnecting tubes and cables should be confined within the air conditioning unit, or enclosed in any way During electrical installation, make sure this condensate pump is connected to a circuit having switch with contact separation in all poles that provide full disconnection from the power supply under over-voltage categories III During electrical installation, a fuse non-time delay (rated 5V A), shall be fitted into the line, supply side, see electrical installation section. The power cord is not replaceable. If the power cord is damaged then the entire pump must be replaced. Children should be supervised to ensure that they are not left unattended in the area where the pump is in use. Children or persons with reduced physical, sensory or mental capabilities which limits their ability to use the appliance should have a responsible person to instruct them in its use. Do not allow any chemicals to come into contact with this pump. Remove the pump from the system before using cleaning fluid or any other chemicals. Flush the system with clean water before re-connecting the pump. All fittings on this pump are designed to be finger-tight. The use of tools to attach pipework may result in damage to the pump. In any installations where property damage and/or personal injury might result from an inoperative or leaking pump, it is strongly recommended that the alarm relay should be used to operate an alarm and/or switch off the air conditioning unit.

Operation GB The PANTHER sensor will automatically start the pump when condensate is detected and stop the pump when the condensate has been removed. The PANTHER sensor is also fitted with a high water level alarm that will operate the alarm relay if the water level rises to abnormal levels. The pump will continue to run until the minimum water level is reached and then the alarm will reset. Pump inlet (from sensor) socket Breather tube Inlet connector Pump outlet Breather support Pump Fig.. plug outlet inlet installation The PANTHER sensor can be installed at any angle between horizontal and vertical so long as the breather tube inlet is above the condensate inlet (Fig. ). The PANTHER sensor can also be tilted sideways up to from horizontal (Fig. ). 9 Fig.. Fig.. The PANTHER sensor can be positioned in any suitable location within the equipment below the level of the collection tray. The top of the breather tube should be positioned above the highest level that the condensate may reach. Three typical installations are shown below. (Fig.4) Horizontal mounting, typical of high wall mounted fan units. (Fig.5) Angled, typical of direct mounting to collection tray. (Fig.6) Vertical, typical of cassette unit mounting. Fig.4. Fig.5. Fig.6.

Pump installation The PANTHER pump can be installed in any convenient space inside the equipment, trunking or voids up to metre above the sensor. Typical installations are shown below. (Fig.7) Inside the air handler. (Fig.8) In a false ceiling above the air handler. (Fig.9) Inside trunking or false wall. Where possible the pump should be placed on or wrapped in foam insulation and cables and tubes should be secured to reduce vibration and noise. Fig.7. Fig.8. Fig.9. Wiring Connections Connect the ground, live and neutral wire from the supply cable of the PANTHER pump to the supply terminals (see Fig.6) This product must be connected using a switch with contact separation in all poles that provide full disconnection from the power supply under over-voltage categories III. A fuse non time delay (rated 5V A), shall be fitted into the line, supply side (see Fig.). Cable Connections Wire Colour Connect Symbol GREEN/ YELLOW EARTH E BLACK LIVE L WHITE NEUTRAL N 4 VIOLET Alarm contact 5 VIOLET Alarm contact POWER SUPPLY Alarm Contacts Volt Free Break On Fault connection is rated 5 amps 5VA. It may be necessary to use a contactor if the air handler supply is to be switched. E L N A FUSE CONTROL CIRCUIT 4 5 4 Fig..

Testing Before testing, ensure that the collection tray and drain hose is free of dirt and debris. Pour clean tap water into the collection tray until the pump starts. Pump operation may be noisy initially until any air has been purged from the system. Continue to add water and the pump should switch to full power and the alarm contacts should open. Do not continue to add water if it becomes visible in the breather tube. Allow the PANTHER to clear the water. The pump should switch off and the alarm relay should reset. GB Trouble Shooting Pump does not run: Check fuse and electrical supply connections. Check that water is reaching the pump sensor in sufficient quantities to start the pump. Check the sensor connector is plugged into the pump. Pump is noisy: Check that the PANTHER, mains cable and outlet tube are not vibrating against the sides of the equipment. Pump is pumping air: Check that the sensor is in the correct orientation. Check the tube between sensor and pump. Check that the pump outlet tube is not syphoning. Check sensor for dirt or mould. Pump continues to run with no water: The water sensor can become over sensitive if contaminated by dirt or certain cleaning chemicals. If this occurs the pump may continue to run with no water. Disconnect the PANTHER sensor from the pump and flush the sensor by pouring clean tap water into the inlet for around seconds (Fig. ). If the problem persists, flush with methylated spirit and then rinse with water. In dirty environments an in-line filter is recommended to avoid pump and sensor damage. Fig.. WARRANTY This product is guaranteed for two years to be free from manufacturing defects or faulty materials. If it should fail for either of these reasons within two years from the date of manufacture it will be repaired or replaced free of charge, at the option of EDC International Limited. EDC International Limited can accept no liability whatsoever for any loss or damage arising from the use of this product, however caused. Before using this product the user should satisfy himself that it is suitable for use in the intended application and for the manner in which it is intended that it be used. This product is subject to continuous development and improvement and EDC International Limited reserves the right to alter the specification or design without prior notice. 5