Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

Similar documents
LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

2015 ICC Commercial Cooking Systems

2012 ICC Commercial Kitchen Hoods

Kitchen Ventilation Hood Permit Application

REQUIREMENTS FOR HOOD PLANS

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS

IMC Significant Changes Summary Tier I

Comparative Matrix A Comparison of the NFPA 96 and ICC Standards and Codes with regard to Commercial Kitchen Systems

Dear Concessionaire,

Inspection Checklist Mechanical Rough in

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

Notable Changes in the Mechanical Codes

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

MSYS 4490 AC Systems

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

2012 International Mechanical Code Significant Changes. About the Significant Changes

MECHANICAL EXHAUST VENTILATION SYSTEMS FOR RETAIL FOOD FACILITIES. Design, Calculations, and Operational Guidelines

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK

2012 INTERNATIONAL FUEL GAS CODE VENTS

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

MODEL: JRSVH SERIES JEAN S RESTAURANT SUPPLY 426 SOUTH STAPLES CORPUS CHRISTI, TEXAS PH: (361)

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

INSTALLATION INSTRUCTIONS & USE & CARE GUIDE Air-O Ultra Series Range Hoods

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Introduction to the Exhaust Fan Interceptor Commercial Exhaust Fans from a Service Perspective

APPUZO RANGE HOOD INSTALLATION

SECTION AIR HANDLING UNIT

Chapter One Commercial Kitchen Fires

Low Wall Back Shelf Exhaust Canopy

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIFORM MECHANICAL CODE SIGNIFICANT CHANGE COMPARISON STUDY

SECTION AIR DUCT ACCESSORIES

COPPER INSERT INSTALLATION INSTRUCTIONS, USE AND CARE GUIDE

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

CHAPTER 8 CHIMNEYS AND VENTS

COMMERCIAL KITCHEN FIRE SAFETY

Inspection Checklist Mechanical Final

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

CHIMNEYS AND VENTS CHAPTER 8

SECTION COMMERCIAL-KITCHEN HOODS

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

1 Exam Prep Florida Building Code-Mechanical Tabs and Highlights

SECTION DUCTWORK

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS

GASEOUS HYDROGEN SYSTEMS

UNDER CABINET RANGE HOOD

MECHANICAL EXHAUST VENTILATION SYSTEMS Design, Calculations, and Operational Guidelines

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

CHAPTER 8 CHIMNEYS AND VENTS

For the Florida Building Commission And the Fire Code Advisory Council

UNDER CABINET RANGE HOOD. This manual is made with 100 % recycled paper.

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

ICC CODE CORNER 2015 International Fire Code

Winnipeg Fire Department Fire Prevention Branch

101 S. George St 116 E Gas Ave York, PA York, PA (717) (717)

DIVISION 15 MECHANICAL

READ AND SAVE THESE INSTRUCTIONS WARNING! TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK, OR INJURY TO PERSONS OBSERVE THE FOLLOWING:

Commercial Kitchen Exhaust Requirements Kitchen Exhaust for Food Service Operations

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL MECHANICAL CODE 2012 EDITION

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

2015 MECHANICAL CODE REQUIREMENTS

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

UNIFORM MECHANICAL CODE

C. Manufactured double wall chimneys for fuel fired equipment. D. NFPA 54 - National Fuel Gas Code; National Fire Protection Association; 2009.

Code verification sign-off

Effective ventilation is necessary for the comfort

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Mobile Vendors Bulletin

SECTION AIR COILS

NC Mechanical Code. Land Use and Environmental Service Agency (Code Enforcement) Table of Contents

New Construction Fire Inspection Process

DUCT SYSTEMS CHAPTER 6

DUCT SYSTEMS CHAPTER 6

Mechanical Appliance and Equipment Inspection Checklist

MOBILE FOOD VENDING Food Trucks & Trailers

To expedite the plan review and inspection processes, please refer to the information below.

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

Vent Supplement Ultra-80, -105, -155, -230 & -310

GE Monogram. Installation. Instructions. Component Cooktop System. Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y

2012 International Fire Code Significant Changes. IFC Background. Purpose IBC and 2012 NFPA 101 Significant Means of Egress Changes

Food Service Establishment Plan Review Form

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

Owner and Maintenance Guide for M Line Range Hoods with M600/M1200 Blowers

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

Installation Instructions Use and Care Guide Instructions d installation Mode d emploi et d entretien

IVI WARNINGS: Must be followed carefully to avoid personal injury. [VL

Gravity and Pneumatic Waste and Linen Handling Systems NFPA 82 Inspection Form

Analysis of Changes for the 6 th Edition (2017) Florida Codes

University of Delaware

SPECIFIC APPLIANCES, FIREPLACES AND SOLID FUEL-BURNING EQUIPMENT

UMC 2012 ( ): Item # 38

READ AND SAVE THESE INSTRUCTIONS Installer: Leave this manual with homeowner.

WARNINGS: Must be followed carefully to avoid personal injury. IMPORTANT: Must be followed carefully to avoid damage or incorrect installation.

DUCT SYSTEMS CHAPTER 6

Integrated Ventilation System

Transcription:

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS (630) 620-5750 Fax: (630) 629-2374 www.villageoflombard.org COMMERCIAL HOOD & DUCT SYSTEM PLAN REVIEW REQUIREMENTS International Mechanical Code, 2012 Edition International Fire Code, 2012 Edition Project Name : Project Address : Code Edition: Date : All supporting documentation-showing items listed below are required for review. The checklist is based on the 2012 Editions of the IMC and IFC. General (All submissions shall include the following): A minimum of four copies of shop drawings, and submittal data shall be provided with the permit application permitting evaluation of the system PRIOR TO installation. Name and address of project or tenant where system will be installed. Name, address, and telephone/fax numbers for the designer of the system and a copy of the design professional s qualifications. Drawings are to be uniform in size and drawn to a recognized scale. Every Type I exhaust hood and duct system shall be protected with an approved automatic fire-extinguishing system installed in accordance with the IMC and the IFC IFC 904.2.1 All required fire protection systems shall be supervised and monitored by the Village of Lombard Communications Center (DUCOMM) in accordance with NFPA 72 and Section 901.6.4 of the Village of Lombard Code of Ordinances. 1

Project Plans Checklist Calculated CFM Makeup Air CFM I. IMC 506 - Hood Ventilation System Ducts and Exhaust Equipment Ducts Serving Type I Hoods - IMC 506.3 IMC 506.2 Ducts shall be protected against corrosion. IMC 506.3.1 Grease duct materials: galvanized 16 gage, stainless 18 gage. IMC 506.3.2 - Grease Duct Joints, seams or penetrations continuously welded and brazed. IMC 506.3.2.3 Duct-to-exhaust fan connection: flanged, gasketed and bolted. IMC 506.3.2.4 Vibration isolation: Listed non-combustible packing in metal sleeve joint or listed coated-fabric flexible duct connector, connected only at the duct to fan inlet or outlet connection. IMC 506.3.3 Grease duct bracing and support: non-combustible material securely attached to the structure, bolts, screws, rivets, and other mechanical fasteners shall not penetrate the duct walls. IMC 506.3.4 Velocity: not less than 500 feet per minute. IMC 506.3.6 Grease duct clearances: not less than 18 from combustibles or 3 from gypsum wallboard attached to non-combustible structures. IMC 506.3.7; 506.3.8; 506.3.9 Grease accumulation and cleanout requirements. IMC 506.3.13.1 Termination above roof: not less than 40 above the roof. IMC 506.3.13.2 Termination through exterior wall: does not create a public nuisance, not where protected openings are required, and not within 3 of other exterior openings. IMC 506.3.13.3 Termination location: 10 horizontally from buildings, property lines, air intake openings, and 10 above grade. Exception: Five feet if air discharges away from such locations. Ducts Serving Type II Hoods IMC 506.4 IMC 506.2 Ducts shall be protected against corrosion. IMC 401.4 Opening location: 10 horizontally from buildings and property lines. 2

IMC 506.4.1 Ducts: constructed of rigid metallic materials, construction per IMC chapter 6, positive pressure systems connected and joined in an approved manner. IMC 506.4.2 Exterior exhaust outlets: Shall meet IBC requirements for exterior wall opening. Exhaust Equipment IMC 506.5 IMC 506.5.1 Exhaust fans serving Type I hoods: Constructed as required for a grease duct or per UL 762, fan located outside the air stream. IMC 506.5.2 Exhaust fan discharge: Will not impinge on roof, other equipment, appliances, or parts of structure. Vertical discharge fans to have an approved drain outlet at the lowest point of housing and grease reservoir. IMC 506.5.3 Exhaust fan mounting: Up-blast fans shall be hinged and supplied with a flexible, weatherproof electrical cable to permit inspection and cleaning. Ductwork shall extend 18 above the roof surface. IMC 506.5.4 Clearances: Exhaust equipment to maintain 18 clearance from combustibles. IMC 506.5.5 Termination: Per IMC 506.3.13.3, and 2 between the vertical discharge fan and parapets if fan housing is no taller than the parapet. II. IMC 507 Commercial Kitchen Hoods General IMC 507.1 IMC 507.1 Hoods shall be designed to capture and confine cooking vapors and residues, and shall operate during cooking operations Type I & Type II Hood Requirements IMC 507.2 IMC 507.2.1 Type I hoods shall be installed where cooking appliances produce grease or smoke; such as occurs with griddles, fryers, broilers, ovens, ranges, and wok ranges. IMC 507.2.1.1 Operation: Type I hood systems shall be designed and installed to automatically activate the exhaust fan whenever cooking operations occur. The activation of the exhaust fan shall occur through an interlock with the cooking appliances, by means of heat sensors or other approved methods. IMC 507.2.2 Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion, and do not produce grease or smoke; such as steamers, kettles, pasta cookers, and dishwashing machines (some exceptions apply). 3

IMC 507.2.3 Domestic cooking appliances used for commercial purposes shall be provided with Type I or Type II hoods as required for the type of appliances and processes proposed. IMC 507.2.4 Type I hoods over extra-heavy duty appliances used for commercial shall discharge to an exhaust system that is independent of other exhaust systems. IMC 507.3 Where vented fuel-burning appliances are located in the same room or space as the hood, provisions shall be made to prevent the hood system from interfering with the appliance s operation. IMC 507.4 Type I hood materials: Steel 18 gage, stainless 20 gage in thickness. IMC 507.5 Type II hood materials: Steel 22 gage, stainless 24 gage, copper 24 oz/sq. ft. IMC 507.6 Supports: Type I hoods shall be secured by non-combustible supports. IMC 507.7.1 Type I hoods: External hood joints, seams, and penetrations shall be made with a continuous external liquid, tight weld, or braze. IMC 507.7.2 Type II hoods: Joints, seams, and penetrations shall be as set forth in IMC Chapter 6, shall be sealed on the interior of the hood, and shall provide a smooth surface that is readily cleanable and watertight. IMC 507.8 A hood shall be designed to provide for a thorough cleaning of the entire hood. Grease gutters shall drain to an approved collection receptacle that allows access for cleaning. IMC 507.9 Type I hood clearances: Not less than 18 from combustibles. Clearance from gypsum wallboard attached to non-combustible structures is not required if a smooth, cleanable, non-absorbent, and non-combustible material extends 18 beyond the hood. IMC 507.12 The hood shall extend a minimum of 6 inches past the edge of the appliances, and shall be no more than four feet above the surface of the appliances. The front edge of the hood may be flush with the appliances when the rear wall of the appliance space is constructed of non-combustible materials. IMC 507.13 Capacity of hoods: Commercial food service hoods shall exhaust a minimum net quantity of air as determined by the multipliers below based on the length of the hood. The heaviest duty appliance covered by the hood shall be used for the entire hood. IMC 507.13.5 Dishwashing appliances: Minimum net airflow for a Type II hood shall be 100 CFM per linear foot. IMC 507.15 Exhaust outlets shall not serve more than a 12-foot hood. 4

Extra Heavy-Duty Cooking Appliance Type I Hood Double Island Canopy (per side) 550 Single Island Canopy 700 Wall-mounted Canopy 550 Heavy-Duty Cooking Appliance Type I Hood Backshelf/Pass-over 400 Double Canopy (per side) 400 Single Island Canopy 600 Wall-mounted Canopy 400 Medium-Duty Cooking Appliance Type I Hood Backshelf/Pass-over 300 Double Canopy (per side) 300 Eyebrow 250 Single Island Canopy 500 Wall-mounted Canopy 300 Light-Duty Cooking Appliance Type I & Type II Hood Backshelf/Pass-over 250 Double Canopy (per side) 250 Eyebrow 250 Single Island Canopy 400 Wall-mounted Canopy 200 III. Commercial Kitchen Makeup Air IMC 508 IMC 508.1 Makeup air shall be supplied during operation of commercial kitchen exhaust systems that are provided for commercial cooking appliances. The amount of makeup air supplied shall be approximately equal to the amount of exhaust air. For mechanical makeup air systems, the exhaust and makeup air systems shall be electrically interlocked. IMC 508.1.1 Makeup air temperature differential between makeup air and air in the conditioned space shall not exceed 10 F. IMC 508.2 Manufacturers of compensating hoods shall provide a label indicating minimum exhaust flow and/or maximum makeup airflow that provides capture and containment of the exhaust effluent. 5

IV. System Testing IMC 506.3.2.5; 507.16; 507.16.1 IMC 506.3.2.5 Grease duct test: Prior to the use of any portion of a grease duct system, a leakage test shall be performed in the presence of the code official. The permit holder will be responsible to provide the necessary equipment and perform the test (bare bulb light test). IMC 507.16 A performance test shall be conducted upon completion and before final approval of the installation of the commercial kitchen hood ventilation and exhaust system. The test shall verify the rate of exhaust and makeup airflow. The permit holder will be responsible to provide the necessary equipment and perform the test. Test shall be performed in the presence of a code official. IMC 507.16.1 Capture and containment test: The permit holder shall verify capture and containment performance of the exhaust system. The field test shall be conducted with all the appliances under the hood at operating temperatures, with all sources of ventilation and exhaust air functioning, and containment visually observed with smoke or steam produced by actual or simulated cooking. Test shall be performed in the presence of the code official. 6