Menu operation via AKM ADAP-KOOL. Compressor Pack Controller AKC 25H5. Software version 1.3x

Similar documents
Menu operation via AKA 21 ADAP-KOOL. Compressor Pack Controller AKC 25H5. Software version 1.3x

Capacity controller for water chiller AK-CH 650

Menu operation via AKA 21 ADAP-KOOL. Controller for controlling evaporators AKC 114D, 115D and 116D. Software version 1.5x

Function description ADAP-KOOL. Controller for capacity regulation of brine installation AKC 25H7

Controllers for controlling evaporators AKC 114, AKC 115, AKC 116 AKC 114D, AKC 115D, AKC 116D AKC 114A, AKC 115A, AKC 116A. Function description

Capacity controller EKC 331T REFRIGERATION AND AIR CONDITIONING. Manual

Capacity controller EKC 531D1 REFRIGERATION AND AIR CONDITIONING. Manual

Temperature controller for limitation for the discharge gas temperature EKC 319A REFRIGERATION AND AIR CONDITIONING. Manual

Capacity controller AK-PC 651

Controller for controlling one evaporator EKC 414A1 REFRIGERATION AND AIR CONDITIONING. Manual

Instructions AK-PC 520

Liquid level controller EKC 347 REFRIGERATION AND AIR CONDITIONING. Manual

Controller for Condensing unit Optyma Plus Evo 3 REFRIGERATION AND AIR CONDITIONING. Manual

Controller for operation of evaporator on water chiller EKD 316

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual

Capacity Controller AK-PC 351

Controller for evaporator control AK-CC 750

Controller for appliance control AK-CC 550A

Capacity controller for dry cooler AK-PC 420

Optimize your HVAC/R application with the right Danfoss components

Controller for appliance control AK-CC 550B. Manual

Controller for appliance control AK-CC 550. Manual

Controller for temperature control EKC 202D1

Controller for temperature control - EKC 202A,B,C and EKC 302A,B

User Guide. Controller for appliance control AK-CC 450

Controller for temperature control AK-CC 210

Controller for appliance control AK-CC 450. Manual

The full range of Evaporator Controls from ADAP-KOOL

Product Manual SZ1009

INSTALLATION AND OPERATION MANUAL

Basic Plus2 Room Thermostats Floor Heating

MAKING MODERN LIVING POSSIBLE. Technical description DHP-M.

Technical description. Atec.

USER MANUAL S203. Controller for three circuits. - control for 2 heating circuits - 1 domestic hot water control. Saving energy, creating comfort

danfoss Heating Solutions 5

REMOTE CONTROL FOR CHILLER MYCHILLER

Operating instructions

Weather compensated flow temperature control of heating and boiler systems

OPERATING MANUAL Enertronic Control System 2

Product Manual SZ1022/SZ1031/SZ1035/

SLV CONTROLLER 105N46XX SERIES

User manual. User manual. CTS 600 by Nilan. Comfort Comfort Version: 10.00, Software-version: 2.30

/18 (JRK) MTD User Manual OJ Electronics A/S

MicroTech Series-200 Flooded Screw Chiller

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

INSTRUCTIONS AK-CC 250A

OWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference

Type UCG/UDG. English...1 Français...7 Español Up button. OK button. Down button

USER MANUAL. OPTIMA 312 ES960C circuit board

Odyssey. issue 01c. system manual

User manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21

INSTALLATION AND OPERATION MANUAL

User Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015

Owner s Manual. Part Number 33CS250-01

LuxPro Thermostats NEW MULTI-STAGE TOUCHSCREENS. Features & Programming. Mt. Laurel, NJ

Manual for the integration in BMS/GTC

4 Wiring Brochure Wiring and

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

MicroTech Series 200 Centrifugal Chiller

- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions

Planning guide. Atec.

Owner s Manual. Part Number 33CS250-FS and 33CS220-FS

OPERATING INSTRUCTIONS. G214 Software - Version 4

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

Installer Manual KNX Touchscreen Thermostat

Installation Guide. ECL Comfort 210, application A Table of Contents

ER65 - Mini Rack Controller Electronic Refrigeration Line

MAKING MODERN LIVING POSSIBLE. FP975 7-Day Electronic Programmer. User Guide. Danfoss Heating

Revolutionary ETS Colibri valves Engineered to give you maximum flexibility and dependability

OWNER S MANUAL. Part Number P

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

Owner s Manual. Part Number 33CS250-RC

REACH-IN SAFETEMP (-AAC)

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION

103E7. User Guide. 7-Day Electronic Timeswitch for Controlling Hot Water and Heating (Including Factory Replacement Units FRU) Danfoss Heating

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Danfoss Gas Sensor DGS MODBUS

USER MANUAL Comfort System4 TM

OPERATING MANUAL Enertronic Control System 2

1 DOCUMENT REVISION CONTROL ELEMENTS... 9

Control of the system, MLP RO pump station

- Data Brochure tekmarnet 4 Thermostat 542e

MAKING MODERN LIVING POSSIBLE. User Guide. ECtemp 550. Electronic Intelligent Thermostat.

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

NA G µair CONNECT 2

THERMOMAX COLTREC RCX 100 MICROPROCESSOR REFRIGERATION CONTROL SYSTEM ENGLISH.

CTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11

food-retail.danfoss.com Overview Brochure ADAP-KOOL Evaporator Controllers Achieve best-in-class energy efficiency and food safety

for for Industrial Refrigeration

ComfortSense 7500 Thermostat. User Guide

ECL Comfort 210 / 296 / 310

TE809-Ats Instructions Manual

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Capacity regulators, type CPCE and LG REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

MAKING MODERN LIVING POSSIBLE. Performer VSD. For Residential Applications - R410A. Quick reference

Open Protocol Data Communications

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Refrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301

Transcription:

Menu operation via AKM ADAP-KOOL Compressor Pack Controller AKC 25H5 Software version 1.3x RC.1J.33.02 RC1J.35.02 06-2000

Menu list This menu function can be used together with system software type AKM. The description is divided up into function groups that can be displayed on the PC screen. Within each group it is now possible to show the measured values, or settings. Regarding the use of AKM, reference is made to the AKM Manual. Application This menu operation (dated May 2000), applies to controller type AKC 25H5, code number 084B2020 and 084B2021 with programme version 1.3x. Function groups The operation is divided up into several function groups. When a selection has been made, push OK, and you may continue to the next display. By way of example, Compressor capacity Ctrl. has been selected here. From the measure line the different values can be read. The values are constantly updated. In the list of settings the set values can be seen. If a setting has to be changed, select the parameter and proceed via OK. Measurements The various measurements can be read directly. If a graphic display of the measurements is required, up to eight of them can be shown. Select the required measurements and push Trend. Settings There are four kinds of settings, ON/OFF settings, settings with a variable value, time settings and reset alarms. Set the required value and push OK Enter the new value or move the sliding scale up or down. The new value will apply, when OK is pushed. 2 Menu operation RC.1J.35.02 Danfoss 06/2000 AKC 25H5 Version 1.3x

Go through the individual functions one by one and make the required settings. When settings have been made for one controller, the set values may be used as basis in the other controllers of the same type and with the same software version. Copy the settings by using the copy settings function in the AKM programme, and adjust subsequently any settings where there are deviations. NB! If a list is required for noting down the individual settings, a printout can be made of it with a function in the AKM programme. Read the next section, Documentation. Documentation Documentation of the settings of the individual controllers can be made with the print function in the AKM programme. Select the controller for which documentation of the settings is required and select the Print Settings function (cf. also the AKM Manual). Functions Shown below are function groups with corresponding measurements and settings. A printout of the given settings can be made using the AKM function Print Settings (see above). Alarms See page 11. Main Function Rfg.Type R Reading of set refrigerant type Settings Main Switch Function switch: 1: Regulation Rfg. Type Refrigerant selection: 0: No refrigerant selection 12: R142b 1: R12 13: User defined 2: R22 14: R32 3: R134a 15: R227 4: R502 16: R401A 5: R717 (ammonia) 17: R507 6: R13 18: R402A 7: R13b1 19: R404A 8: R23 20: R407C 9: R500 21: R407A 10: R503 22: R407B 11: R114 23: R410A AKC 25H5 Version 1.3x Menu operation RC.1J.35.02 Danfoss 06/2000 3

Language Mains freq. Selection of language. Three languages have been entered in the controller. Either: Or: 0: English 0: English 1: German 3: Danish 2: Franch 4: Spanish NB! If this setting is changed, another Upload must be made of the controller's data for the AKM programme. You do it this way: - Select one of the available languages. - Close the menu - Proceed to menu Configuration - Advanced Configuration - Delete description file - Push file type Default - Select controller's code number and software version - Push OK - Proceed to menu Configuration - Upload - Complete the fields Network, Net configuration and AKC description - Push OK Texts will now be obtained from the controller in the required language. Set the network frequency to 50 or 60 Hz Compressor Capacity Ctrl. P0 Ref. C Suction pressure reference (incl. external reference signal, if any) Req.Cap.% Reference for compressor capacity (deviations may be due to time delays) Sd C Discharge gas temperature measured with the temperature sensor on the Sd input SH K Night s.b. Measured superheat (Ss - P0). Ss = Temperature signal. P0 = Pressure signal. Status of night setback function ON: An increase of the evaporating pressure is permitted OFF: Normal situation Settings Main Switch Function switch: 1: Regulation P0 SP C Setting of required suction pressure in C Man.Cap. Forced control function OFF: No forced control ON: There may be forced control of the compressor capacity Man.Cap.% Forced control function Manual setting of compressor capacity The value is in % of total capacity controlled by the controller ++Zone s Time delay between step cut-ins in the regulation band over the "+Zone band" Set in seconds +Zone s Time delay between step cut-ins in the regulation band over the neutral zone Set in seconds +Zone K Regulation band over the neutral zone NZ K Neutral zone for suction pressure -Zone K Regulation band under the neutral zone -Zone s Time delay between step cut-outs in the regulation band under the neutral zone Set in seconds --Zone s Time delay between step cut-outs in the regulation band under the "-Zone band" Set in seconds Step mode Cut-in and cut-out sequence for compressors 1: Sequential (first in, last out) 2: Cyclic (equalisation of run time) k1 Gain K Displacement to be produced by max. reference signal (10 V) (value is only set, if "Ext.Ref" inputs is used) NightRef K Displacement value for suction pressure in connection with an active night setback signal (set in Kelvin) ForcedNght Forced control for night operation Evaporator reference changed by setting in "NightRef K" 4 Menu operation RC.1J.35.02 Danfoss 06/2000 AKC 25H5 Version 1.3x

Compressor Status 1 Cap. % Actual cut-in capacity on this compressor 1 Run Time Compressor's aggregate run time in hours (Zero-setting of the value can be performed under "Output Configuration" 1 Cut/24 h Number of compressor starts during the past 24 hours 2 As above for compressor no. 2 to 9 Settings Main Switch Function switch: 1: Regulation Condenser Capacity Ctrl. Req. Cap.% Reference for condenser capacity Pc Ref. C Discharge pressure reference in C S7 C Temperature measured by S7 sensor S8 C Temperature measured by S8 sensor Settings Main Switch Function switchs: 1: Regulation Pc SP C Setting of required discharge pressure in C Man.Cap. Forced control function OFF: No forced control ON: There may be forced control of the condenser capacity Man.Cap.% Forced control function Manual setting of condenser capacity The value is in % of total capacity ++Zone s Time delay between step cut-ins in the regulation band over the "+Zone band" +Zone s Time delay between step cut-ins in the regulation band over the neutral zone +Zone K Regulation band over the neutral zone NZ K Neutral zone for discharge pressure in K -Zone K Regulation band under the neutral zone -Zone s Time delay between step cut-outs in the regulation band under the neutral zone --Zone s Time delay between step cut-outs in the regulation band under the "-Zone band" AKC 25H5 Version 1.3x Menu operation RC.1J.35.02 Danfoss 06/2000 5

Safety Functions Settings Main Switch Function switches: 1: Regulation Sd Max C Max. value of discharge gas temperature (If the value is exceeded, the entire compressor capacity will be cut out) Pc Max C Max. value of discharge pressure in C (If the value is exceeded, the entire compressor capacity will be cut out) (At 3 K under Pc Max. the entire condenser capacity is cut in) P0 Min C Min value of suction pressure in C (If the value becomes less, the entire compressor capacity will be cut out) Restart m SH Max K SH Min K SH Delay m Time delay before restart (Applies to the three earlier functions: "Sd Max", "Pc Max" and "P0 Min") Alarm limit for max. superheat Alarm limit for min. superheat Time delay before alarm for "SH max" and "SH min" Special Functions Settings Main Switch Function switchs: 1: Regulation Mo day h Time table for displacement of evaporating pressure on Mondays. End of night setback (normal suction pressure) At setting = 0 there is no displacement this day Mo night h Time table continued: Start (of night setback) when the suction pressure is changed with setting "Night Ref K". At setting =0 there is no displacement this day. If day and night settings are identical, or if night comres before day, there will be a different function. See functional description. Tu day h As above, Tuesdays Tu night h As above, Tuesdays We day h As above, Wednesdays We night h As above, Wednesdays Th day h As above, Thursdays Th night h As above, Thursdays Fr day h As above, Fridays Fr night h As above, Fridays Sa day h As above, Saturdays Sa night h As above, Saturdays Su day h As above, Sundays Su night h P0 Ref. md. As above, Sundays Displacement of suction pressure as a function of external signals 1: Reference = set reference + voltage signal on EXT.REF (0-10 V), if any 2: Reference = set reference + RH% signal on EXT.REF (0-10 V), if any + signal on S6, if any. 6 Menu operation RC.1J.35.02 Danfoss 06/2000 AKC 25H5 Version 1.3x

k2 Gain RH Ref. % ta Ref C P0RefMax K P0RefMin K LoadShed % Inj.Diff K Sens. P0 Pc Ref.md. min tm K dim tm K PcRefMax K PcRefMin K Heat SP C HeatDiff K Sens. Pc Amplification factor for temperature displacement (set only, if "P0 Ref.md" is with setting = 2) Reference for relative humidity. Is used, when a signal on the relative humidity at input "EXT.REF" is added. (Set only if "P0 Ref.md" is with setting = 2) Reference for temperature in connection with temperature displacement. (Set only if "P0 Ref.md" is with setting = 2) Max. permissible increase of suction pressure reference with external signal Max. permissible reduction of suction pressure reference with external signal Max. permissible compressor capacity when input "LOAD SHED" is short-circuited Temperature setting for "Liquid injection in suction line" function. Set the value where the liquid injection starts (SH max - Inj. Diff) Amplification factor for the compressor regulation's PI controller. The setting should not be changed Displacement of the condensing pressure as a function of external signals 1: Reference = set reference "Pc SP" 2: Reference is changed as a function of the S7 signal and possibly the Tc signal Mean temperature differential across the condenser at the lowest actual compressor capacity (tm differential at min. load) (It is the temperature differential between air- and condensing temperature) Mean temperature differential across the condenser at max. load (tm differential at max. load) (It is the temperature differential between air- and condensing temperature) Max. permissible increase of condensing pressure reference with external singal Max. permissible reduction of condensing pressure reference with external singal Thermostat value at heat recovery (S8 measurement and AKV output) (Cut-invalue) Temperature differential for the heat recovery thermostat (cut-out value = cut-in value + differential) Amplification factor for the condenser regulation's PI controller. The setting should not be changed. INPUT Configuration Settings Settings can only be made when the MAIN SWITCH input is cut out. Main Switch Function switchs: 1: Regulation There are three settings for each input. Define first what the input is to register. Next, the information that is to belong to the input. And finally, a time delay. DI1 Type Alarm input DI 1 0: Input not used 1: Input registers the compressors' safety circuit Compressors no. is selected in the next menu 2: Input registers the condensers' safety circuit Condensers no. i selected in the next menu 3: Other alarm monitoring. (Alarm text is selected in next menu) DI1 Dev.No Type = 1: (see above): Select the compressor no. Type = 2: (see above): Select the condenser no. Type = 3: (see above): Select the alarm text 0: Factory setting. Correct setting to one of the following values: 1: Low liquid level 2: Refrigerant leak 3: Current fault 4: Phase fault 5: Liquid flow switch 6: Air flow switch 7: Speed controller fault 8: Condensate pump fault 9: High condensate level DI1 Del.m Time delay from the alarm is registered until executed DI As above for DI 2 to DI 9 AKC 25H5 Version 1.3x Menu operation RC.1J.35.02 Danfoss 06/2000 7

OUTPUT Configuration Settings Settings can only be made when the MAIN SWITCH input is cut out. Main Switch Function switches: 1: Regulation DO1 Type Relay outputs are used for: 0: Not used 1: Compressor / compressor steps 2: Condenser / condenser steps DO1 Dev.No Type = 1: (see above): Select the compressor no. Type = 2: (see above): Select the condenser no. DO1 Cap. % Output capacity in relation to the whole system's capacity DO1 Recy m Minimum period of time between two successive starts (If the output controls an unloader or a condenser step, the setting will have no effect). DO1 ON m Minimum duration of ON period (If the output controls an unloader or a condenser step, the setting will have no effect). DO1 Time h Reading and adjustment, if applicable, of hourmeter DO As above for DO 2 to DO 9 Recommendation Use DO1 and up. If you skip DO1 or another DO, a subsequent DI-alarm will not be displayed satisfactorily. Speed regulation, if required, must however be installed on DO9. This text is only relevant if Speed Ctrl is set in pos. ON. If the output is used for controlling the speed regulation of a compressor, the setting must represent the max. capacity the compressor is able to produce. I.e., the nominal capacity times the max. speed which is then converted into a percentage value of the whole system s capacity. Example: Three compressors of 5, 5 and 10 kw, respectively, where the 10 kw unit is speed-regulated at between 0.8 and 1.3 times the nominal speed. The capacity here will be 1.3 times 10 = 13 kw. This will give a setting of 56% (13/(5+5+13) = 0.56). (Remember to set the two values 0.8 and 1.3 in the speed regulation). Speed Ctrl MinCap DO9 AKV appl. Switch for speed regulation ON: AO output is active. DO9 starts and stops the speed regulation OFF: DO9 functions as normal ON/OFF output Setting of the step s min. capacity in relation to the step s max. capacity: Value = min. speed/max. speed (e.g. 0.8/1.3 = 0.62). The output is used for: 1: Liquid injection with an AKV valve in the suction line 2: Liquid injection with a thermostatic expansion valve and a solenoid valve in the suction line 3: Solenoid valve for heat recovery (S8 measurement) 4: Conventional thermostat function (S8 measurement) 8 Menu operation RC.1J.35.02 Danfoss 06/2000 AKC 25H5 Version 1.3x

Service Mode P0 Bar Suction pressure (measured with P0 pressure transmitter) Pc Bar Discharge pressure (measured with Pc pressure transmitter) Ss C Suction gas temperature (measured with Ss temperature sensor) Sd C Discharge gas temperature (measured with Sd temperature sensor) S6 C Temperature measurement (performed with S6 temperature sensor) A display less than -150 C means that the input is short circuited S7 C Temperature measurement (performed witht S7 temperature sensor) S8 C Temperature measurement (performed witht S8 temperature sensor) Ext.Ref. V Voltage signal on "Ext.Ref." input Disp. Sel. Status of "Disp Sel" input (parameters Nos. 1 to 9 are displayed) DI 1 Status of input DI 1. In pos. "ON" the signal is OK, and the controller can regulate DI As above for DI 2 to DI 9 Load Shed. Status of "Load Sheding" input. 0: No capacity limitation 1: Max. capacity limitation is activated Tc Signal Status of "Tc" input (AKC 14-116 signal). In pos. "OFF" the voltage on the input is 230 V Ext.Main Status of "Main Switch" input. In pos. "OFF" the regulation is stopped by force AO Volt Status of "AO" output (analog signal 0-10 V d.c.) AKV % AKV output opening degree in % DO1 Relay Status of relay output DO 1. In pos. "ON" the relay is operated DO As above for DO 2 to DO 9 AKC ON Status of relay output "AKC ON" OFF: Forced closing of all AKV valves ON: Normal operation of AKC controllers Alarm Relay Status of alarm output. In pos. "ON" the relay is operated, and there is no alarm Settings Main Switch Function switches: 1: Regulation Man. Ctrl. ON: Manual control permitted PLEASE NOTE! No monitoring When manual setting has been concluded, the setting must be changed to OFF AO Volt AKV % Manual control of analog output "AO" Manual control of AKV output 0%: Valve is closed 100%: Valve is completely open DO 1 Relay Manual operation of relay output DO 1 ON: Relay activated OFF: Relay not activated DO As above for DO 2 to DO 9 AKC ON Alarm Relay Manual operation of relay output "AKC ON" OFF: Forced closing of all AKV valves ON: (Activated) Normal operation Manual operation of alarm relay ON: Relay activated (no alarm) OFF: Relay not activated AKC 25H5 Version 1.3x Menu operation RC.1J.35.02 Danfoss 06/2000 9

Alarm destinations Settings Main Switch Function switches: 1: Regulation Network ON: When alarms are registrated via PC or Gateway printer OFF: When alarm are registrated via AKA 21, only Set the priority for the following alarm texts (choose between 1, 2, 3 or 0. They have the following meaning:) 1: Alarm at relay output + DANBUSS message 2: DANBUSS message only 3: Alarm at relay output + DANBUSS message, but the DO2 output on a master gateway will not be activated 0: No alarm and no DANBUSS message The individual alarms are explained in more detail on page 11 StandbyMod (Regulation has stopped) RfgType (Changed refrigerant) Man. Ctrl. (Peak load limitation) Load Shed (Regulation is overridden) No. DI Def. (DI-input not defined) P0 Min C (Min. value of suction pressure in C) Pc Max C (Max. value of discharge pressure in C) Sd Max C (Max. value of discharge gas temperature) SH max/min (Alarm limit for max/min. superheat) DI1 AlDest (Cut-out in safety circuit DI 1) DI2 AlDest (Cut-out in safety circuit DI 2) DI3 AlDest (Cut-out in safety circuit DI 3) DI4 AlDest (Cut-out in safety circuit DI 4) DI5 AlDest (Cut-out in safety circuit DI 5) DI6 AlDest (Cut-out in safety circuit DI 6) DI7 AlDest (Cut-out in safety circuit DI 7) DI8 AlDest (Cut-out in safety circuit DI 8) DI9 AlDest (Cut-out in safety circuit DI 9) P0 error (Faulty P0 pressure transmitter) Pc error (Faulty Pc pressure transmitter) Ss error (Faulty Ss sensor) Sd error (Faulty Sd sensor) S6 error (Faulty S6 sensor) S7 error (Faulty S7 sensor) S8 error (Faulty S8 sensor) AKM menu "For DANFOSS only" This menu contains data and setting values for special internal controller functions. Do not chage the stated values. 10 Menu operation RC.1J.35.02 Danfoss 06/2000 AKC 25H5 Version 1.3x

Alarms The menu display for alarms shows the active alarms. Dots will appear at the top of the menu for as long as data is being obtained. Alarms may be acknowledged one by one by selecting one, and then pushing "OK". An Alarm message will now appear, e.g.: Push "OK" to acknowledge. The following alarm messages may occur: Alarm message Meaning Action/cause P0 Error Faulty P0 pressure transmitter Check connection Pc Error Faulty Pc pressure transmitter Check connection Ss Error Faulty Ss sensor Check sensor connection / sensor resistance Sd Error Faulty Sd sensor Check sensor connection / sensor resistance S6 Error Faulty S6 sensor Check sensor connection / sensor resistance S7 Error Faulty S7 sensor Check sensor connection / sensor resistance S8 Error Faulty S8 sensor Check sensor connection / sensor resistance RFG.Type change after power up Changed refrigerant Check the selected refrigerant. Regulation with changed refrigerant may not be done until the controller has been de-energised Discharge temp. too high Too high discharge Sd higher than max. Sd setting. Wait for temperature to gas temperature drop Condensing temp. too high Too high condensing Pc higher than max. Pc setting. Wait for temperature to temperature drop Suction temp. too low Too low suction P0 lower than min. P0 setting pressure temperature Suction gas SH too high Too high superheat (Ss-P0) SH higher than max. SH setting Suction gas SH too low Too low superheat SH SH lower than min. SH setting (Ss-P0) Compr. no ( ) safety cut-out Signal on terminal DI ( ) Check compressor safety circuit interrupted Compr. no ( ) not in auto Wrong setting of switch Put switch in pos. "AUT." on AKC 22H AKC 25H5 Version 1.3x Menu operation RC.1J.35.02 Danfoss 06/2000 11

Compr. no ( ) disch temp. cut-out Alarm from AKC 22H Check compressor safety circuit Compr. no ( ) motor prot. cut-out Alarm from AKC 22H Check compressor safety circuit Compr. no ( ) current cut-out Alarm from AKC 22H Check compressor safety circuit Compr. no ( ) oil press. cut-out Alarm from AKC 22H Check compressor safety circuit Compr. no ( ) disch press cut-out Alarm from AKC 22H Check compressor safety circuit Cond no ( ) safety cut-out Signal on terminal DI ( ) Check condensator safety circuit interrupted Low liquid level Low level of refrigerant Check refrigerant quantity Refrigerant leak Refrigerant leaking Check the unit that monitors refrigerant leaks Current fault Wrong supply voltage Check earth leakage circuit breaker Phase fault Wrong supply voltage Check supply voltage Liquid flow switch Error message from Check the flow switch liquid flow switch Air flow switch Error message from Check the flow switch air flow switch Speed controller fault Speed controller Check speed controller/frequency converter has stopped Condensate pump fault Faulty drip tray pump Check the pump High condensate level High drip tray level Check the drip tray RFG.type not selected No selection of refrigerant Select refrigerant Stand by mode Regulation has stopped The function switch (Main Switch) is either set in the position "Controller stopped" or "Service function". Man. Compr. Cap. Regulation is overridden The forced control function for the compressor capacity or ctrl set ON the condenser capacity is active. Load shedding Peak load limitation There is a signal from other control system No DI defined for compressor A "DI-input" for a Define the input under "Configuration of inputs" or set compressor is not defined alarm destination at "0". Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. AC-RDT 12 Menu operation RC.1J.35.02 Danfoss 06/2000 AKC 25H5 Version 1.3x