CAN/ULC-S109 Flame Resistance of "Argo" Fabric

Similar documents
CAN/ULC-S109 Flame Resistance of "Xanadu" Material

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

Test Method of Specified Requirements of FTTS-FA-015. Flame-Resistant Textiles

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor

BCTC CARPET TECHNICAL CENTRE

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

Analysis Report

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Title: WF Assessment Report No B. Prepared for: CHEMOLLI S.A.S. di Eros Chemolli & C. Via Fitta, Arco (TN), Italy

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

UL 94 Flammability Ratings: Introduction

BS EN ISO : 2010

Public Comment No. 2-NFPA [ Section No ]

We Identify and S.T.O.P. Your Noise Problems

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

SIGMADEK, LTD. FIRE TEST REPORT

NATIONAL TECHNICAL SYSTEMS

BS EN ISO : 2010

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

Department for Communities and Local Government Research Report:

FUNDERMAX GMBH FIRE TEST REPORT

CERTIFICATION BULLETIN

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

Vescom bv Sint-Jozefstraat AV Deurne Nederland

IMO Resolution MSC 61(67): Annex 1: Part 2

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

Review Fire Test Report

Jan07 Rev B

Apr06 Rev A

Heat and Smoke Release of a Ceiling-Installed Speaker

J-PRO TM Cable Support System

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

ASTM E 84 Surface Burning Characteristics of "12 mm Stratificato Panel"

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

Report Test Report


Qualification Test Report LightCrimp* Plus Singlemode and Multimode LC Connector (Field Installable)

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Flammability Test Results

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

BS EN ISO : 2010

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

Report VNLF Test Report

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

Construction Heat CH-02 (up to 400,000 BTU) Record of Training Curriculum Document

NF X : Parts 1, 2, 3, 4 & 5

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

Test Report: ICL/H18/9039 Rev 1

BS EN : 2001 & IEC :2000

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

BS 476: Part 6: 1989+A1:2009

TENDER NO. PGVCL/PROC/SMC BOX FOR CT OPERATED METER & Junction Box/867

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

DEMYSTIFYING FR CLAIMS: AN ERGODYNE WHITE PAPER

Calgary Fire Department Indoor Special Event Requirements. August calgary.ca /fire call

Qualification Test Report 1/Jul/2005 Rev. A

TEMPORARY IMMERSION AND DUST TEST REPORT

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

TABLE OF CONTENTS. 1.0 INTRODUCTION Scope References Test Specimen Description Summary 3

Pressure Equipment Directive PED 2014/68/EU Commission's Working Group "Pressure"

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

BS EN :2004. Test On Electric And Optical Fibre Cables Under Fire Conditions. WF Report Number. Date: 14 th November 2008.

City of Leduc Fire Services Indoor Special Event Requirements

VERIFICATION OF FIRE ALARM SYSTEMS

Technician Tools CAN/ULC-S CAN/ULC-S537-13

Why Buy Certified? Understanding Standards NFPA 2112 and ASTM F1506 and Why Certification Matters When Selecting FR PPE

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

PQS Independent type-testing protocol

Report of Committee on Fire Tests

Test Report No: ICL/H17/7967

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Analysis of Surface resistivity behavior of Conductive Woven fabrics made from Copper Jari & S.S./Polyester yarns for ESD control

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

The Fire Resistance Performance Of Timber Or Mineral Composite Based Insulated Doorsets When Fitted With D & E Architectural Hardware Spring Hinges

16028 September 23, 2016

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

UNDERWRITERS 7 LABORATORIES OF CANADA

Testing coated fabrics

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

Transcription:

CAN/ULC-S109 Flame Resistance of "Argo" Fabric A Report To: Design/Craft Fabric Corporation 2230 Ridge Drive Glenview, IL 60025 USA Phone: Email: (847) 904-7000 x128 mboynton@design-craft.com Submitted By: Warringtonfire North America Report No. 14-002-396(A) 3 pages + appendix Date: July 8, 2014

CAN/ULC-S109 Flame Resistance of "Argo" Fabric Page 2 of 3 ACCREDITATION To ISO/IEC 17025 for a defined Scope of Testing by the International Accreditation Service SPECIFICATIONS OF ORDER Determine flame resistance in accordance with the CAN/ULC-S109-03 Small and Large Flame Tests, as per your PO No. SA90007 dated June 24, 2014. IDENTIFICATION Material identified as color S70, 72" wide, 100% polyester: "Argo." ( sample identification number 14-002-S0396-1) TEST RESULTS Tested "as-received" CAN/ULC-S109-03 Small-Flame Test Fabric Weight: 192 g/m² Damaged Afterflame Flaming Length (mm) Time (s) Dripping (s) Machine Direction #1: 108 7.5 0.0 #2: 117 0.0 1.0 #3: 134 0.0 0.0 #4: 133 0.0 0.0 #5: 134 0.0 0.0 Cross Direction #6: 124 6.3 2.0 #7: 129 0.0 0.0 #8: 131 0.0 1.0 #9: 108 6.4 0.0 #10: 122 4.0 2.0 Average: 124 - - Maxima Specified by ULC-S109 Small Flame Test: 165 - - (average) 190-2.0 (individual)

CAN/ULC-S109 Flame Resistance of "Argo" Fabric Page 3 of 3 TEST RESULTS (continued) CAN/ULC-S109-03 Large Flame Test Tested "as-received" and in single sheet configuration. Damaged Afterflame Flaming Length (mm) Time (s) Dripping (s) Machine Direction #1: 12 0.0 0.0 #2: 9 0.0 0.0 #3: 17 0.0 0.0 #4: 14 0.0 0.0 #5: 13 0.0 0.0 Cross Direction #6: 15 0.0 2.0 #7: 22 0.0 0.0 #8: 25 0.0 1.0 #9: 27 0.0 0.0 #10: 19 0.0 0.0 Average: 17 - - Maxima Specified by ULC-S109 Large Flame Test: - - - (average) 250-2.0 (individual) (Above tip of test flame) CONCLUSIONS When tested "as-received", the material identified in this report meets the flame resistance requirements of both the Small-Flame and Large-Flame Tests of CAN/ULC-S109-03. Note: This is an electronic copy of the report. Signatures are on file with the original report. Victor Tarcenco, Technologist Ian Smith, Technical Manager Note: This report and service are covered under Canada Inc. Standard Terms and Conditions of Contract which may be found on the website (www.exova.com), or by calling 1-866-263-9268.

CAN/ULC-S109 Flame Resistance of "Argo" Fabric APPENDIX (1 Page) Summary of Test Procedure

CAN/ULC-S109-03 Small-Flame Test Ten specimens are cut, each 70 x 250 mm, with five in the warp direction and five in the weft direction, where applicable. The specimens are conditioned for 30 minutes at 105 C, or if they melt or distort at thes e temperatures, 18-22 C at 50% R.H. for at least 1 2 hours or by drying in an oven for 1 hour at 60 C. Each specimen is removed from the conditioning chamber individually, clamped in a U-shaped metal holder and suspended in a specified cabinet. The free edge of the specimen is positioned 20 mm above the tip of a gas burner which has been adjusted to yield a flame height of 40 mm. Flame exposure time is 12 seconds. Char length and afterflame time are measured. Flame Resistance Requirements: Maximum Average Length of Maximum Length of Char or Char or Destroyed Material for Destroyed Material for any Ten Specimens Specimens 165 mm 190 mm The specified maximum flaming time for residue on the floor of the tester from any specimen is 2.0 seconds. Large-Flame Test For conducting flame tests of fabrics in single sheets, the procedure specifies ten specimens, 125 mm by 750 mm to 2100 mm long. The specimens are conditioned at 105 ±2 C for 30 minutes or, if distortion or mel ting occurs at these temperatures, 20 ± 2 C at 25-50% relative humidity for at least 12 hours or by drying in an oven for 1 hour at 60 C. Each specimen is removed from the conditioning chamber and cooled in a desiccator prior to being suspended in a steel stack 310 mm square and 2130 mm high, the said stack being open both top and bottom and supported 300 mm above the floor. The lower edge of the specimen is positioned 100 mm above the tip of a gas burner which is inclined at 25 to the vertic al. The burner, which has been adjusted to yield a flame 280 mm in height is ignited and inserted directly beneath the specimen for 2 minutes. Char length is measured from the tip of the flame, upwards. For conducting flame tests of fabrics hung in folds, at least four specimens 625 mm by 750 mm to 2100 mm are required. Each specimen is folded longitudinally to form four folds. Flame Resistance Requirements - Specified Maxima: Specimen Char Length or Damaged Flaming Residue on Configuration Material Length (mm) Floor of Tester (s) Single sheets 250 2.0 Folded 635 2.0 Note: As stated in the standard, "fabrics shall comply with both the Small-Flame and the Large-Flame Test".