Lifeline 5 Cable-pull Safety Switch

Similar documents
Magnetically Coded Non-contact Switch (MC2)

SensaGuard TM Integrated Latch Installation Instructions

CENTERLINE 2100 Motor Control Center (MCC) Doors and Units with Vertical Operating Handles

IEC Lighting Contactor Specifications

Safety Function: Single-beam Area Access Control (AAC)

Compact I/O End Caps/Terminators

Bulletin 440N-Z 440N-S 440K 440G. Sipha Magnetically Coded Non Contact Switches

GuardShield PAC Type 4 (Perimeter Access Control) Safety Light Curtain User Manual

Solid-State Contactor Specifications

RFID Non-contact switches are designed to monitor hinged, sliding or removable guard doors. RFID technology provides increased tamper resistance.

Operating Guide Safe Torque Off

/ / 2018

Operating Guide Safe Torque Off

panasonic.net/id/pidsx/global Lights up when conditions are normal (and at incipient liquid leak detection) Use as a warning Sensor

Original operating instructions Photoelectric safety sensors (safety light curtain / safety light grid) Protected area width (range) 0...

Bulletin 1608N MiniDySC Dynamic Sag Corrector

Series Description. Features. Available Models. Specifications. Specifications for All Models. Specifications for Standard Models

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating Manual MS220DA

INSTALLATION GUIDE. AXIS A1001 Network Door Controller

General terms and conditions... F-7 General precautions... P panasonic.net/id/pidsx/global. Use as a warning. Sensor. Emergency stop.

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Overload relays. General descriptions. Configuration of the front

ISIS SAFETY SYSTEM Installation guide

Fisher LCP100 Local Control Panel

pre-wired E3FA-TP11-F2 2M E3FB-TP11-F2 2M

F3SJ Overview. Three Versions available to meet your exact safety needs. Safety Light Curtains NEW! Introducing the F3SJ Series

SAFETY INTERFACES SAFETY INTERFACES AND RELAYS

Multifunctional Gate Box MGB. More than safety.

MICRO SWITCH Cable-Pull Safety Switches CPS Series Issue 3. Datasheet FEATURES DESCRIPTION POTENTIAL INDUSTRIAL APPLICATIONS

ORIGA-SENSOFLEX Displacement Measuring System for Cylinder Series OSP-P

Datasheet - MZM 100 ST-SD2PREM-A

panasonic.net/id/pidsx/global Gentle start-up switches in accordance with ergonomics Reduces load on hands and fingers

Original instructions Sense7-series Non-contact coded safety switch

Safety. Detection. Control. SAFETY INTERFACES. Safety Interfaces and Relays. Product catalogue. Issue 1

Datasheet - MZM 100 B ST2-SD2PREM-A

Safety Light Curtains Area Access Control

Datasheet - MZM 100 ST2-1P2PWREM-A

Color Mark Sensor. Sensing gdsa distance Spot diameter e. Possible to switch between vertical or horizontal connection using the M12 rotary connector.

MACHINERY SAFEBOOK 5. Safety related control systems for machinery. Principles, standards and implementation. (Revision 5 of the Safebook series)

FLEX I/O Digital Input and Output Modules

XM-441 Expansion Relay Module

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

REA 105 Arc Protection Module. Operator s Manual

4 & 8-POINT ANNUNCIATORS Instruction Manual

BES M30EP-PFC12F-S04G-D12 BES Q40ZU-PFC15B-S04G-D12 BES Q40ZU-PFC20F-S04G-D12 Inductive Safety Sensors User's Manual

Emotron M10 Shaft Power Monitor. Instruction manual English

PD154 & PD158 VIGILANTE II ANNUNCIATORS Instruction Manual

E3M-V. Mark Sensor. Applications

POINT I/O Field Potential Distributor Modules

Multi-Gas-Controller MGC2

Annunciator Unit SACO 16 D1. Product Guide

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

DDS-SSENSOR - INSTALLATION MANUAL. Installation Manual DDS-S SENSOR

Operating Manual MS220KA and MSR220KA

GuardShield Safe 2 and Safe 2 PAC Safety Light Curtains User Manual

XM-360 Process Module, XM-361 Temperature Module, and XM-362 Isolated Temperature Module

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

Original operating instructions Safety switch with guard locking AC901S AC902S

SAFEMASTER PRO. The configurable safety system versatile and extendable. Our experience. Your safety.

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

Safety Control Modules for Emergency Stop Circuits FF-SRS5988 FF-SRS5935 FF-SRS5925 FF-SRS5934 FF-SRS5924 TYPICAL APPLICATIONS APPROVALS DIMENSIONS

Freeze Protection Thermostat TRACON MODEL GPT 3 Installation and Operation Manual

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

SPACEMOTION SERIES SMM 01

LZR -I100/ -I110. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

UNC100 Integra Manual

Improved productivity Two-stage detection

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

Lights up when conditions are normal (and at incipient liquid leak detection) Use as a warning. Sensor. Ensure productivity. Emergency stop.

FACTORY AUTOMATION. Instruction Manual NBB20-L2-E2B-C-V1 NBN40-L2-E2B-C-V1 Inductive Sensor

CarSense 303 O P E R A T I N G I N S T R U C T I O N S M A G N E T O R E S I T I V E V E H I C L E D E T E C T O R

XGUARD-10/-5. LASER SCANNERS for industrial doors. User s Guide for product version 0600 and more

VAMP 120 & 121. Arc flash detection units. Product picture

Pump Logic User Manual CB-1000 P/N ILK-CB1000-1

POINT I/O Field Potential Distributor Module

BSF4-AH80. Flameproof Type Light Curtain Type 4. Globally-compliant flameproof structure. Ample protective height 1,595 mm 62.

Advanced Diagnostic Gateway with Ethernet and FF-H1 Interface and I/O. Assembly

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

LZR -I30. max. detection range of 30 ft x 30 ft LASER SCANNERS FOR INDUSTRIAL DOORS LZR-I Page 1 of 12

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

XM-440 Master Relay Module

Annunciator unit. Application

Ex SOLENOID / ALARM DRIVER. PRepower 5203B. Table of contents. Applications Safety instructions Technical characteristics...

Analog Annunciator Unit SACO 16 A3. Product Guide

PTE0705 Electric Fence Monitor

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

ME 3011C / Alarm Indication / Quick Reference Guide

XUM0APSAM8 photo-electric sensor - XUM - multi - Sn 0..10m VDC - M8

Series PHOTOSWITCH Photoelectric Sensors. Standard and Timing. Description. Supplied Accessories

Index Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:

RE-PR3-E-27 3-Phase Panel Mount 27kW

Non-Contact Safety Switches FF6 Series Issue 4. Sensing and Internet of Things. Datasheet FEATURES DESCRIPTION DIFFERENTIATION

MD12-1 Vehicle Loop Detector

Transcription:

Installation Instructions Original Instructions Lifeline 5 Cable-pull Safety Switch Catalog Numbers 440E-LL5SS8, 440E-LL5SS5, 440E-LL5SE8, 440E-LL5SE5, 440E-LL5SN8, 440E-LL5SN5 Topic Additional Resources 1 Introduction 1 Technical Specifications 2 Mounting 2 Dimensions 3 Wiring Diagram 3 OSSD Test Pulses 4 Diagnostic 4 Function Overview 4 Indicators 5 Installation of Rope/Cable 6 Cable Considerations/Thermal Expansion 6 Timing Diagram 7 Series Circuit 8 Application Wiring Examples 9 List of Recommended Safety Control Interfaces 15 Maintenance 15 Declaration of Conformity 15 Summary of Changes Page This publication contains new and updated information as indicated in the following table. Topic Added (Included) to Tension Spring descriptions 2 Added NFPA 79 to Standards in Technical Specifications table 2 Page Additional Resources You can view or download publications (including translations) at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Introduction ATTENTION: Read this document and the documents that are listed in the Additional Resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wire instructions and requirements of all applicable codes, laws, and standards. Suitably trained personnel are required to install, adjust, put into service, use, assemble, disassemble, and maintain this equipment in accordance with the applicable code of practice. If this equipment is used in a manner that is not specified by the manufacturer, the protection that is provided by the equipment can be impaired. Resource Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http:// www.rockwellautomation.com/products/certification Description Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. ATTENTION: Do not attempt to install this device unless the installation instructions have been studied and understood. This document acts as a guide for a typical installation and is available in some languages at www.rockwellautomation.com/literature. Select the publication language and type 440E in the search field. A full user manual is also available.

Standard Switch Stainless Steel Switch It is required that installation is in accordance with these instructions and implemented by qualified personnel. This device is intended to be part of the safety-related control system of a machine. Before installation, a risk assessment must be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics of the application. See the Specifications for certification information and ratings. Use appropriate screws, bolts, or nuts that are fitted by tools to mount the switch to avoid the risk of tampering. Do not over torque the mounting hardware. Technical Specifications Safety Ratings Attribute Standards Safety Classification Functional Safety Data Certifications Tension Spring (Included) Tension Indicator Status Indicator Aluminum Housing with E-stop Tension Indicator E-stop Aluminum Housing without E-stop Status Indicator Tension Spring (Included) Stainless Steel Housing PLe Cat 4 according to EN ISO 13849-1, SIL CL3 per IEC 62061 and IEC 61508, NFPA 79 The intent of the operational functionality that is required by EN ISO 13850 and IEC 60947-5-5 is achieved by using electronic technology. PLe Cat 4 according to ISO 13849-1 For functional safety data, see http://literature.rockwellautomation.com/idc/groups/literature/ documents/sr/safety-sr001_-en-e.pdf CE Marked for all applicable directives, c-ul-us (UL 508), and TÜV. http://www.rockwellautomation.com/certification/overview.page Attribute Operating Characteristics Cable Span Tension Force to Run Position Tension Force to Lockout Operating Voltage Response Time (Off) Switches Connected in Series Utilization Category According to Ue le Mounting 100 m (328 ft) 135 N (30.35 lbs) 195 N (43.84 lb) V DC 10%/-15% Class 2 SELV or PELV power supply 60 ms Response time-off is 5 ms for each additional switch DC-12 and DC-13 V 200 ma Frequency of Operating Cycle 0.25 Hz Off-state Output Current < 0.5 ma Outputs Safe State De-energized (2 x PNP, 0V), AUX energized (1 x PNP, V) Run State Energized (2 x PNP, V), AUX de-energized (1 x PNP, 0V) Tension Energized (1 x PNP, V) No-load Supply Current < 50 ma Load Current 200 ma maximum Voltage Drop < 2V Mechanical Housing Material Aluminum Stainless Steel 304 Environmental Operating Temperature -20 +75 C (-4 167 F) Operating Humidity 5 95% relative Washdown Rating IP66 IP66 IP66, IP69K Shock and Vibration IEC 60068-2-27: 30 g (1.05 oz), 11 ms IEC 60068-2-6: 10 500 Hz Pollution Degree IEC 60947-1: 3 Attribute Electro-magnetic Compatibility (EMC) Electrostatic Discharge ESD Radiated EMF immunity Electrical Fast Transient/Burst Immunity Conducted Immunity Rated Impulse Withstand Voltage Protection Aluminum Housing with E-stop It s recommended that you use M5 or 10-32 bolts to mount the sensor to the frame of the machine. 440E IEC 61000-4-2: air discharge Per IEC 61326-1 (functional): 8 kv Per IEC 61000-6-7 (fail-safe): 8 kv IEC 61000-4-2: contact discharge Per IEC 61326-1 (functional): 4 kv Per IEC 61000-6-7 (fail-safe): 6 kv IEC 61000-4-3 Per IEC 61326-1 (functional): 10V/m Per IEC 61000-6-7 (fail-safe): 20V/m IEC 61000-4-4 Per IEC 61326-1 (functional): 2 kv/5 khz Per IEC 61000-6-7 (fail-safe): 2 kv/5 khz IEC 61000-4-6 Per IEC 61326-1 (functional): 10V Per IEC 61000-6-7 (fail-safe): 20V Aluminum Housing without E-stop Stainless Steel Housing IEC 60947-1: 1 kv Short circuit, overload, reverse polarity, overvoltage, loss of ground 2 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

Dimensions Figure 1 - Standard Housing [mm (in.)] 91 (3.58) 59 66 (2.32) (2.6) Description M12 8-pin cordset Temperature Rating [C (F)] -20 +105 (-4 +221 ) Jacket Material PVC Coupling Nut Epoxy-coated Zinc Stainless Steel Cat. No. 889D-F8AB-2 889DS-F8AB-2 Replace the 2 with 5 (5 m [16.4 ft]) or 10 (10 m [32.8 ft]) for standard cable lengths. Table 2-5-pin Connection 101 (3.98) Scale 0.75 5 2 Figure 2 - Stainless Steel Housing [mm (in.)] Wiring Diagram Table 1-8-pin Connection 3 8 1 (4.88) 48 78 (1.88) (3.07) 59 62 (2.32) (2.44) 4 7 5 6 Pin Number Wire Color Signal 1 Auxiliary Output 2 V DC 3 Green Tension Output 4 Safety OSSD 2 Input 5 Safety OSSD 1 Output 6 Safety OSSD 2 Output 7 0V 8 Safety OSSD 1 Input 2 1 Description M12 5-pin cordset M12 4-pin cordset 1 3 4 Pin Number Color Signal 1 2 Safety OSSD 1 Output 3 0V 4 Black Safety OSSD 2 Output 5 Auxiliary Output Temperature Rating [C (F)] -20 +105 (-4 +221 ) -50 +105 (-58 +221 ) Jacket Material PVC Coupling Nut Epoxy-coated Zinc Stainless Steel Cat. No. 889D-F5AC-2 889DS-F5AC-2 TPE Stainless Steel 889DS-F4HJ-2 Replace the 2 with 5 (5 m [16.4 ft]) or 10 (10 m [32.8 ft]) for standard cable lengths. IMPORTANT If you do not require the auxiliary signal, a 4-pin cordset (889D-F4AC-2) can be used. For low temperature applications, use a 4-pin cordset (889DS-F4HJ-2). The recommended patchcord for use with ArmorBlock Guard Safety I/O is 2 m (6.5 ft) - 889D-F4ACDM-2. Replace the 2 with 0M3 (0.3 m [0.98 ft]), 1 (1 m [3.28 ft]), 5 (5 m [16.4 ft]), or 10 (10 m [32.8 ft]) for standard cable lengths. IMPORTANT Do not use a 5-pin patchcord with the ArmorBlock Guard Safety I/O. Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 3

OSSD Test Pulses Test pulses appear on each OSSD output. These pulses are approximately every 60 ms. The times that are shown are approximate and depend on the processing of the safety-related status. Figure 3 - Individual Pulses Periodicity Wire Wire Diagnostic Table 3 - Unit Indicators 0 200 Time (µs) 0 30 60 Time (ms) Function Safety The table describes the demand on the safety switch that results in a stop function and how to reset that function. Table 4 - Safety Function Function Result Restore to Normal Operation Actuation of Rope/Cable E-stop Pressed Safety OSSD Inputs Off and not Floating Safety OSSD Input Wires Floating Integrated Emergency Stop Push Button The Lifeline 5 safety cable pull switch is offered with a twist release emergency stop push button that can be pressed in emergency situations to stop the machine. After E-stop actuation, the safety outputs remain in the off state and can only be reset manually by rotating the emergency stop push button clockwise. Figure 4 - Integrated E-stop Safety Outputs OFF State Press the Button Rotating the E-stop Button Clockwise Turn OSSD Inputs On Connect Input Wires Status/Diagnostic Indicator Function Overview State Status Troubleshooting Off Not powered OSSD not active Green OSSD active Green flash flash Power up test or OSSD inputs not valid 1 Hz flash OSSD fault Check V DC or OSSD inputs (yellow or red wire) OSSD fault check OSSD outputs are not shorted to GND, V DC or each other. 4 Hz flash internal fault Cycle power. A Lifeline 5 cable pull system consists of the Lifeline 5 safety cable pull switch, red colored rope/cable, and supports (eye-bolts and pulleys). The Lifeline 5 meets the intent of the international requirements according to IEC 60947-5-5 and EN ISO 13850. Indication of Rope Tension During installation/adjustment of the rope/cable assembly, the correct tension of the rope can be checked by observing the tension indicator. During setup, the tension indicator flashes at 1 Hz and the tension output will pulse at the same rate. This output can be wired to an indicator light to help with initial setup and diagnostics. As the tension is increased on the rope/cable, the tension indicator flash rate increases. When the tension indicator turns off, the sensor is properly tensioned. Margin Indication the Rope Tension If the status indicator is green and the tension indicator flashes amber, the rope/cable requires maintenance/adjustment before the machine shuts down. This output can be used as an indication signal or be connected directly to an indicator light. 4 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

Indicators Table 5-8-pin Connector Functions Function Switch Outputs Status Indicators Safety Auxiliary Tension Status Tension E-stop Pressed Off On Off Off Sensor not Tensioned/Cable Cut Off On On Amber Flash Low Tension Indication On Off On Green Amber Flash Sensor Tensioned Properly On Off Off Green Off High Tension Indication On Off On Green Amber Flash Cable Pulled/Tripped Off On Off Off Safety OSSD Inputs not Connected Off On Off Off Table 6-5-pin Connector Functions 5-pin Connector Version Switch Outputs Status Indicators Function Safety Auxiliary Status Tension E-stop Pressed Off On Off Sensor not Tensioned/Cable Cut Off On Amber Flash Low Tension Indication On Off Green Amber Flash Sensor Tensioned Properly On Off Green Off High Tension Indication On Off Green Amber Flash Cable Pulled/Tripped Off On Off Safety OSSD Inputs not Connected Off On Off Status indicator flashes red, see Diagnostic on page 4. Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 5

Installation of Rope/Cable Attach the tension spring to the eye hook to the front of the switch, as shown. Tension Spring ATTENTION: The sensor must NOT be used without this spring attached. Setting/Adjusting the Cable Tension Power up the Switch (Application Wiring Examples on page 9) The status indicator becomes solid red and the tension indicator begins to blink amber/1 Hz rate. Slowly increase the tension on the cable. The tension indicator blink rate increases as the tension is increased. When the tension indicator turns off, the sensor is properly set. Press the reset button. The status indicator turns green (the reset button must be pressed between 125 msec and 3 seconds for the sensor to be reset). The tension is set. Verifying the System When the installation is complete, you have performed a thorough functional test. This test includes checking all types and directions of pull over the length of the cable. IMPORTANT The first eye bolt must be located 300 mm (11.8 in.) from the switch eyelet. This distance provides for a straight and efficient pulling action on the sensor. Additional eye bolts are spaced 2 3 m (6 9 ft) apart to help keep the perpendicular pull force within IEC 60947-5-5 specifications of 200 N (45 lbs) and 400 mm (15.75 in.). EN ISO 13850 standard requires that the full length of cable be within view when the reset is pressed. Or the machine must be inspected over the whole length of the cable, before and after resetting. Install inside and outside pulley so cable can go around corners or whenever direction is changed, even slightly. Figure 5 - Typical Mounting Example with One Switch Lifeline 5 = 100 m 300 mm 2-3 m The choice between two switches or one switch is a matter of a risk assessment while considering the probability of a trapped rope along the span. Figure 6 - Typical Mounting Example with Two Switches Lifeline 5 = 100 m 300 mm 2 3 m IMPORTANT Cable Considerations/Thermal Expansion The cable is the actual interface with the user. It is typically red plastic coated and less than 4 mm (0.16 in.) in diameter. The cable is installed between the switch at one end and a support at the opposite end. It is important that the support for the cable is sturdy enough to handle the force that is required to operate the switch. Temperature effects on the cable are important to note when configuring a system. Example: A cable that runs along a conveyor is 20 meters. After the tension is adjusted properly, the Lifeline 5 safety cable pull switch can accommodate a temperature variance from -32 +48 C (-26 +118 F) without readjustment required (see graph). Another consideration of the cable is that when it is pulled with great force, the cable can initially expand or stretch and affect system setup. It is recommended that the cable is forcefully pulled before tuning the cable tension with the turnbuckle. This step exposes areas in the system that initially stretch or expand. Adjustments can then be made to take up the added slack. Figure 7 - Thermal Expansion Chart Temperature Variation ( C) EN ISO 13850 requires the full length of cable to be within view when the reset is pressed. If it is not, the machine must be inspected over the whole length of the cable, both before and after resetting. 60 50 40 30 20 10 Ambient Temperature when Setting the Sensor Tension 0-10 -20-30 -40 0 20 40 60 80 100 120 Cable Span (m) 6 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

Timing Diagram DC S11 S12 S52 A1 13 23 33 41 Lifeline 5 Unit 1 Lifeline 5 Unit 2 Lifeline 5 Unit 3 MSR127TP 440R-N23132 S21 S22 A2 S34 14 34 42 Response Time: Safety Outputs Turn OFF Initial Conditions: All Lifeline 5 and tensioned properly. Unit 1 sensor is tripped. Unit 1 OSSD outputs (gray and pink) turn OFF. Sensor 1 indicator turns solid red. Unit 2 OSSD outputs (gray and pink) turn OFF. Sensor 2 indicator flashes green. Unit 3 OSSD outputs (gray and pink) turn OFF. Sensor 3 indicator flashes green. 0 ms 60 ms 65 ms 70 ms Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 7

Series Circuit Consideration must be given to the protection of the wiring. For example, by using wire duct, conduit, shielded cable, separation, or other means to help prevent faults or to confirm detection of faults (see ISO 13849-2, Table D.4). Power DC Supply 1606-XL120D Power Supply Lifeline 5 Unit 1 Lifeline 5 Unit 2 Lifeline 5 Unit 3 Lifeline 5 Unit 4 Lifeline 5 Unit 5 Unit 1 is functioning properly. OSSDs are energized to V. Green indicator is on. Unit 2 is functioning properly. OSSDs are energized to V. Green indicator is on. Unit 3 has a fault. See Diagnostic table red indicator flashes. Unit 4 is functioning properly. OSSD inputs are 0V. OSSDs are de-energized to 0V. Green indicator flashes to indicate that OSSD inputs are not V. Safety Rating Note: Series circuits that contain only devices having OSSD outputs can be used in safety functions, which require up to PLe per ISO 13849-1. DC Unit 5 is functioning properly. OSSD inputs are 0V. OSSDs are de-energized to 0V. Green indicator flashes to indicate that OSSD inputs are not V. OSSDs are off. Lifeline 5 Unit 1 Lifeline 5 Unit 2 Lifeline 5 Unit 3 Lifeline 5 Unit 4 Unit 1 is functioning properly. OSSDs are energized to V. Green indicator is on. Unit 2 is functioning properly. OSSDs are energized to V. Green indicator is on. Safety device with voltage free contacts, is open. Unit 3 is functioning properly. OSSD inputs are 0V. OSSDs are de-energized to 0V. Green indicator is flashes to indicate that OSSD inputs are not V. Unit 4 is functioning properly. OSSD inputs are 0V. OSSDs are de-energized to 0V. Green indicator is flashes to indicate that OSSD inputs are not V. Safety Rating Note: A maximum safety function rating of PLd is achievable depending on the installation details when wiring the series circuits that contains voltage from contacts. OSSDs are off. 8 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

Application Wiring Examples Wiring to MSR127 Safety Relay (M12 8-pin Version) Lifeline 5 Lifeline 5 S11 S12 S52 A1 13 23 33 41 S11 S12 S52 A1 13 23 33 41 MSR127RP 440R-N231xx S22 S21 A2 S34 14 34 42 MSR127TP 440R-N231xx S22 S21 A2 S34 14 34 42 VGround VGround MSR127RP with 1 Sensor, Monitored Manual, Driving 100S, or 700S Safety Relays. MSR127RP with 1 Sensor, Automatic, Driving 100S, or 700S Safety Relays. Lifeline 5 Lifeline 5 Lifeline 5 Lifeline 5 440L GuardShield Receiver Transmitter 2 1 6 5 7 Green 3 3 S11 S12 S52 A1 13 23 33 41 S11 S12 S52 A1 13 23 33 41 MSR127RP 440R-N231xx S22 S21 A2 S34 14 34 42 MSR127RP 440R-N231xx S22 S21 A2 S34 14 34 42 VGround MSR127RP with one Sensor, Monitored Manual, Driving 100S or 700S Safety Relays. MSR127RP with two Sensors and one 440L Light Curtain in Series, Monitored Manual, Driving 100S or 700S Safety Relays. IMPORTANT The light curtain must be last (the furthest from MSR127). Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 9

Guardmaster SI or DI Safety Relay Wiring (M12 5-pin Version) DC 889D-F5AC-5 1 Black 889D-F5AC-5 1 Black S32 S42 S22 S12 A1 13 23 S34 Logic DI 8 7 440R-D22R2 6 0 1 2 3 4 5 S11 S21 L11 L12 A2 14 Y32 DC 889D-F5AC-5 1 Black S11 S21 S22 S12 A1 13 23 S34 0 AM SI 440R-S12R2 L11 MM A2 14 Y32 1 For low temperature applications, use 889DS-F4HJ-2 instead of 889D-F5AC-5. 10 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

Guardmaster SI or DI Safety Relay Wiring (M12 8-pin Versions) DC 889D-F8AB-* 889D-F8AB-* Green N.C. Green S12 S22 S32 S42 A1 13 23 S34 Logic 0 1 2 DI 8 3 7 4 6 5 440R-D22R2 S11 S21 L11 L12 A2 14 Y32 DC 889D-F8AB-* Green N.C. S11 S21 S22 S12 A1 13 23 S34 AM SI 440R-S12R2 L11 0 MM A2 14 Y32 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 11

CR30 Software Configurable Relay Wiring (M12 5-pin Versions) DC 889D-F8AB-5 Green N.C. Safety 889D-F5AB-5 Black 00 01 02 03 04 05 06 07 08 09 10 11 CR30 440C-CR30-22BBB A1 A2 12 13 14 15 16 17 18 19 20 21 100S or 700S or 700HPS Contactors and Relays Lifeline 5 Lifeline 5 12 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

1734 POINT Guard I/O Wiring (M12 5-pin Versions) DC 889D-F8AB-5 Green N.C. Safety 889D-F5AB-5 Black EtherNet/IP 0 1 I0 I1 I4 I5 O0 O1 O4 O5 2 3 I2 I3 I6 I7 O2 O3 O6 O7 4 5 COM COM COM COM COM COM COM COM 6 7 T0 T1 T2 T3M COM COM COM COM 1734-AENT 1734-IB8S 1734-OB8S 100S or 700S or 700HPS Contactors and Relays Set On->Off Input Delay Time to 6 ms to ignore the OSSD output test pulses. Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 13

1732DS/ES ArmorBlock Guard Safety I/O Wiring (M12 5-pin Versions) 871A-TS5-DM1 5-pin Field Attachable Connector 1732ES-IB12XOB4 Ethernet 2 1 2 1 3 5 4 3 5 4 X100 X10 X1 The screen shots show the input and output configuration for the 1732ES. 889D-F8AB-5 Cordset 889D-F5UCDM-5 Patchcord Green 871A-TS5-DM1 N.C. N.C. Safety DC 1 T1 2 I1 3 C 4 I0 5 T0 Power 1 T1 OSSD 2 I1 Ground 3 C OSSD 4 I0 Aux. 5 T0 1 T1 2 I1 3 C 4 I0 5 T0 1 T1 2 I1 3 C 4 I0 5 T0 4 3 1 2 A B C D Power E F G H 1 4 2 3 1 T1 2 I1 3 C 4 I0 5 T0 1 T1 2 I1 3 C 4 I0 5 T0 1+ 2 O1 3 C 4 O0 5 C 1+ 2 O1 3 C 4 O0 5 C 871A-TS5-DM1 100S or 700S or 700HPS Contactors and Relays 14 Rockwell Automation Publication 440E-IN008B-EN-P - June 2017

List of Recommended Safety Control Interfaces GSR DI, GSR DIS, GSR SI, CR30, MSR126, MSR127, MSR131, MSR138, SmartGuard controller, 1791DS/ES CompactBlock Guard I/O, 1732DS/ES ArmorBlock Guard Safety I/O. Relay must have OSSD (light curtain) inputs. Maintenance Every Month Check the correct operation of the switching circuit. Also check for signs of abuse or interference. Inspect the switch casing for damage. Every Five Years Check the correct operation of the switching circuit. Also check for signs of abuse or interference. Inspect the switch casing for damage. The switch must be disconnected and readjusted. Repair If there is any malfunction or damage, no attempts at repair can be made. The unit can be replaced before machine operation is allowed. Declaration of Conformity This declaration is to declare that the products that are shown in this document conform with the Essential Health and Safety Requirement (EHSRs) of the European Machinery Directive 2006/42/EC. These products also conform to EN 60947-5-3, EN ISO 12100, EN 60204-1 and have third-party approval. Visit http://www.rockwellautomation.com/certification/overview.page Rockwell Automation Publication 440E-IN008B-EN-P - June 2017 15

Rockwell Automation Support Use the following resources to access support information. Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates. https://rockwellautomation.custhelp.com/ Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page Direct Dial Codes Literature Library Product Compatibility and Download Center (PCDC) Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer. Installation Instructions, Manuals, Brochures, and Technical Data. Get help determining how products interact, check features and capabilities, and find associated firmware. http://www.rockwellautomation.com/global/support/direct-dial.page http://www.rockwellautomation.com/global/literature-library/overview.page http://www.rockwellautomation.com/global/support/pcdc.page Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, ArmorBlock Guard Safety I/O, CompactBlock, Guardmaster, Lifeline, Rockwell Automation, Rockwell Software, and SmartGuard controllers are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 Publication 440E-IN008B-EN-P - June 2017 Supersedes Publication 440E-IN008A-EN-P - March 2017 Copyright 2017 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.