Modelling impact of collections on indoor climate and energy consumption in libraries and archives

Similar documents
HYGROTHERMAL PERFORMANCE BENEFITS OF THE CELLULOSE FIBRE THERMAL INSULATION STRUCTURES

INTERNATIONAL JOURNAL OF CONSERVATION SCIENCE

Hygrothermal evaluation of a museum storage building based on actual measurements and simulations

PASSIVE HYGROTHERMAL CONTROL OF A MUSEUM STORAGE BUILDING. Jørgen Erik Christensen 1 and Hans Janssen 2

Next Generation Passivhaus Archives

Assessing condensation problems in hydrophobic mineral fiber

The Use Of Attic Space For Cooling and Dehumidification

IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS

Numerical study of heat pipe application in heat recovery systems

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

Victoria & Albert Museum, London Medieval & Renaissance Galleries: A Passive Approach to Humidity Control

K.F. Fong *, C.K. Lee, T.T. Chow

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Can painted glass felt or glass fibre cloth be used as vapour barrier?

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)

Residential Building Walls and Environment in Amman, Jordan

Temperature and Relative Humidity agents of deterioration. 22 September 2015 Mikkel Scharff Sarah Staniforth

Adsorption refrigeration system using waste heat

GROUND COOLING OF VENTILATION AIR FOR ENERGY EFFICIENT HOUSE IN MALAYSIA: A CASE STUDY OF THE COOLTEK HOUSE

Passive Indirect Evaporative Cooler

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

Compression of Fins pipe and simple Heat pipe Using CFD

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

LOW ENERGY CLIMATE CONTROL FOR MUSEUM STORES

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Connect North and South Korean Separated Families Higher Comfort Lower Energy

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Heat transfer and heating rate of food stuffs in commercial shop ovens

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Analysis of Energy Consumption for Biomass Drying Process

International Journal of Food and Biosystem Engineering. May 2015 Vol. 1, No. 1. Optimisation of industrial Food Drying Operation. Henry T.

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Energy efficient climate control in museum stores. Poul Klenz Larsen

DOMESTIC DEHUMIDIFIERS IN COOL CONDITIONS: I PERFORMANCE FACTORS

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

Accepted Manuscript. peer , version 1-18 Jan 2011

Study on Drying Shrinkage Strain and Moisture Transfer in Concrete with Finish Coating Materials

Numerical Stability Analysis of a Natural Circulation Steam Generator with a Non-uniform Heating Profile over the tube length

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Proceedings Design, Fabrication and Optimization of a Silicon MEMS Natural Gas Sensor

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Adelaide Homes Design Guide 4 - Winter warming

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Aim, Challenges and Main Results

Fuzzy Controller for Adjust the Indoor Temperature and Preservation the Buildings

Experimental Investigation of an Indirect Evaporative Cooler Consisting of a Heat Pipe Embedded in Porous Ceramic

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Natural Convection Heat Transfer Augmentation from Heat Sinks using Perforated Fins: A Review

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Considerations in the Design of Smoke Management Systems for Atriums

INFRARED BUILDING HEATING BOARDS

AERECO DEMAND CONTROLLED VENTILATION COMBINING INDOOR AIR QUALITY AND ENERGY SAVINGS

Analysis to speed up of the start-up of steam boiler OP-380

Museum of Bavarian History Regensburg, Germany

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

The Drying Time of Gypsol Screed

Study of air circulation inside the oven by computational fluid dynamics.

EFFECT OF WATER RADIATOR ON AIR HEATING SOLAR COLLECTOR EFFICIENCY

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Available online at ScienceDirect. Energy Procedia 78 (2015 )

COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS

Effect of domestic storage and cooking conditions on the risk distribution in ready to cook meat products

Minimization of Mass Flow in District Heating Network Equipped with One Stage Domestic Hot Water Production Substations

Analysis of Triangle Heating Technique using High Frequency Induction Heating in Forming Process of Steel Plate

Tunnel Fire Dynamics and Evacuation Simulations

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Improving the (museum) indoor climate in a flooded castle

Optimisation of cooling coil performance during operation stage for improved humidity control

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Museum Archive Dehumidification in Hot & Humid Climates

ACHEIVING COMFORT IN SUBTROPICAL CLIMATES: BUILDING A MICROCLIMATE IN THE GUANGZHOU SCIENCE MUSEUM

Indoor thermal comfort by controlling heat transfer through building envelope

1. COOL ROOFS. What is a Cool Roof

Cooperation of a Steam Condenser with a Low-pressure Part of a Steam Turbine in Off-design Conditions

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Transcription:

Modelling impact of collections on indoor climate and energy consumption in libraries and archives A. Kupczak 1, A. Sadłowska-Sałęga 2, L. Krzemień 1, J. Radoń 2, R. Kozłowski 1 1 Jerzy Haber Institute of Catalysis and Surface Chemistry Polish Academy of Sciences, Krakow, Poland. nckupcza@cyf-kr.edu.pl; nckrzemi@cyf-kr.edu.pl; nckozlow@cyf-kr.edu.pl 2 Radoń Jan Engineering Consulting & Software Development, Krakow, Poland. asadlowska@ar.krakow.pl; jradon@kki.pl Abstract COMSOL Multiphysics was used to model the moisture uptake and release for library and archival collections in response to variations of temperature and relative humidity (RH) in their environment. These results were coupled to the modelling of indoor climate and energy consumption in collection storage spaces with the use of the WUFI Plus software. The study revealed the crucial impact of air-tightness of the building on the indoor climate stability and the humidification and dehumidification loads required to provide selected climate control classes. In the adequately air-tight storage spaces, sizeable paper collections were found to diminish the energy consumption by at least 22%. For the cool storage conditions, optimal for the preservation of library and archival materials, the impact of the collection on the energy consumption was reduced due to high average RH levels which required considerable dehumidification year round. The research was supported by Grant PBS2/A9/24/2013 from the Polish National Centre for Research and Development. Keywords hygrothermal modelling; indoor climate; energy consumption; libraries and archives; moisture buffering 1. INTRODUCTION In recent years, considerable attention has been given to managing indoor environments in museums, libraries and archives in a responsible manner, particularly in terms of reducing energy use and carbon emissions [1,2]. Indoor microclimates are an outcome of many factors, of which construction materials used, air-tightness of the building envelope, its thermal insulation, installed climate control systems of ventilation, heating, humidification or dehumidification, and the collections housed in the building are the most important. A lot of effort has been put into assessing energy consumption in the specific buildings while taking into account different indoor climate control scenarios (the recent publications comprise refs. [3-5]). And yet, all approaches to modelling the indoor climate lack any precise estimations of the buffering effect by hygroscopic heritage objects housed in a building. Only approximations have been used so far to tackle this issue ([6,7] and references quoted therein). In this study, WUFI Plus and COMSOL Multiphysics software codes were used to investigate the buffering effects of paper collections in libraries and archives on the indoor microclimate conditions [8,9]. WUFI Plus allows fully coupled heat and moisture transport problems to be

modelled for different building components, such as exterior or interior walls, ceilings and floors. Additionally, the software takes into account the heat and moisture sources and sinks located inside rooms, including ventilation, heating, cooling, dehumidification and humidification processes. The simulations can be further used to determine energy consumption under selected scenarios of microclimate control, based on recommendations or specifications for managing environmental conditions for heritage asset collections. WUFI Plus however, has limitations in simulating objects other than walls or ceilings, for which heat and moisture transport proceeds through more than one surfaces. In such cases, COMSOL Multiphysics turns out to be useful, as it can precisely simulate heat and moisture transport in objects of complex geometries. In fact museum, library and archival collections comprise objects of complex forms absorbing water vapour from the surrounding environment through many surfaces. 2. METHODOLOGY The general approach to investigating the buffering effect of cultural heritage objects on indoor microclimate in this work is divided into two steps. First, a detailed numerical simulation of water vapour uptake or release by heritage objects of given dimensions, is performed with the use of COMSOL Multiphysics. The results of the simulation constitute an input into the WUFI Plus modelling, as the second step of the procedure. The buffering impact of collections on the indoor climate, and on the energy consumption for cooling, heating, humidification or dehumidification, are investigated in the second step, depending on the selected climate control scenario. 2.1 COLLECTIONS INVESTIGATED AND CLIMATE CONTROL SCENARIOS For the purpose of approximating paper collections in archives or libraries, a statistical book was created basing on the measurements of sizes of 384 books from the storage of the National Library in Warsaw. The average obtained dimensions were 261 186 mm 2. Thickness can take any value, to represent the required number of books placed next to each other on a bookshelf. For such statistically determined book dimensions, a numerical simulation of water vapour sorption was carried out using COMSOL Multiphysics. A relative humidity (RH) step from 30% to 70% was considered. The following material properties of paper were used: density of 690 kg/m 3, water vapour permeability of 9.6E-11 kg/mspa, measured in specimens imitating a book in the direction parallel to the paper sheets, surface emission coefficient of 3E-8 kg/m 2 spa, sorption isotherm measured at 24 o C and described by the Guggenheim-Anderson-de Boer three-parameter sorption equation with the constants v=5.23%, c=15.03, k=0.6 [10]. Sorption of water vapour by a real book in response to the same RH step change was measured gravimetrically and the results agreed very well with the numerical simulation. In computer simulations of books placed next to each other on a bookshelf, only two of six book surfaces are assumed to significantly absorb/desorb water vapour from the surrounding space. Close packing of books on the bookshelves and book covers block the water vapour penetration through two side surfaces, and the book spine and the bookshelf itself isolate the back and bottom surfaces of a

book. Since WUFI Plus cannot model any two-dimensional (2D) sorption process, the statistical book was represented by another cuboid, with the same volume and only one side open to water vapour transport. The surface of this new side is the sum of two surfaces of the initial statistical book. The obtained dimensions of the new equivalent book are 447 109 mm 2. This change has led to the shortening of time needed for the material to reach the new equilibrium moisture content, in response to a step change of RH. To correct this effect, the original diffusion coefficient was systematically decreased. A perfect agreement between the true 2D water vapour diffusion and sorption in the books, and their 1D approximation was achieved when the diffusion coefficient was divided by 1.5 that is to say was taken to be 6.4E-11 kg/mspa. Such 1D model of a statistical book with the modified diffusion coefficient was implemented in the WUFI Plus simulations. Four climate control scenarios based on the ASHRAE specifications for classes of climate quality in museums, libraries and archives were analysed [11]. First, the ASHRAE highest class of climate control AA was considered reflecting the conventional ideal option, and a single value RH target of 50% with conservative tolerance of variations of ± 5% was selected. The ASHRAE B class of control was selected as the second case, in which RH was allowed to vary between 40-60%. This class of control is a moderate-cost strategy in historic buildings also in use by museums of limited potential for tighter climate control. At the same time, class B constitutes little risk to most paintings or artefacts and no risk to most books. International Institute of Conservation IIC and ICOM Conservation Committee recommended the 40 60% RH range as acceptable for loaning objects containing hygroscopic material (such as canvas paintings, textiles, ethnographic objects or animal glue) to international exhibitions [12]. The ASHRAE class of control C, in which RH was assumed only to stay within the 25-75% RH range all year round, was selected as an option in which just high risk extremes are prevented. In all three climate control scenarios described, the temperature was maintained at a constant level of 21 o C all year round to ensure human comfort. The ASHRAE cool storage recommendations optimal for the preservation of library and archival material, were the last climate control scenario. The RH range between 30 and 50% and natural yearly temperature cycle, but not dropping below 10 o C, was assumed. 2.2 MODELLING OF INDOOR CLIMATE A typical storage space of 14 15 2.5 m 3 (volume of 525 m 3 ) in a historic building housing a library or an archive was considered. The building envelope was modelled with the following materials (interior to exterior): walls cement plaster (0.015 m), ceramic brick (0.51 m), sandstone (0.1 m); floor stone (0.05 m), cement base (0.05 m), reinforced concrete (0.3 m); celling cement plaster (0.015 m), reinforced concrete (0.15 m), mineral wool (0.05 m), cement finish plaster (0.05 m), asphalt roofing felt (0.005 m). The water and heat transport properties for these materials were taken from the WUFI Plus database. Basing on a typical capacity of storage spaces for paper collections, it was assumed that the storage room housed shelves of the total length of 1780 m. Books of statistical dimensions of 447

109 mm 2, placed next to each other on the shelves, took up 16% of the room space. Half of that space occupancy, 8%, was also considered in the simulation. Natural ventilation of the storage space, typical of most historical buildings, was assumed. Two aspects controlling the natural ventilation - the air tightness of a building and its pattern of use are reflected in the air changes per hour (ACH). Five libraries studied in the UK showed a range of ACHs between 0.28 and 0.93 h -1 [13]. Two extreme values of 0.3 and 0.9 h -1 were considered for the climate control scenarios in which temperature was maintained at the human comfort level of 21 o C, therefore, in which the conditions are suitable for people visiting the storage rooms or working in them. In contrast, low ACH of 0.04 h -1 was assumed for the cool storage conditions as they can be established at low running costs if the storage space is kept tight and the human traffic and work is kept to a minimum. Such ACH level was estimated in a storage facility at Vejle, Denmark, in which the concept of passive climate control through air tightness of the building supported by the auxiliary dehumidification was implemented [14]. A statistical climatic data for Krakow were taken as outside weather conditions. The energy required to remove or add 1 kg of water by dehumidification (desiccant wheel) or humidification was assumed to be 1.3 and 0.6 kwh, respectively. The moisture content in the building shell or paper was assumed to correspond to 60% RH at the start of the simulation. To avoid the effect of this initial condition on the results, two yearly cycles were considered in the simulations, whereas the results analysed come only from the second year. 3. RESULTS 3.1 BUFFERING EFFECT OF THE COLLECTIONS Figs. 1 and 2 show the indoor RH in an empty room and in the same room when paper collections of increasing volumes were introduced, for two different ACH values and the constant temperature of 21 o C. The stationery heating regime bringing the indoor temperature to a human comfort level caused low RH indoors in cold periods as the cold air outside is drawn in and heated. As a result, the ASHRAE lowest class of climate control D (RH below 75% all year round) was attained in the empty room. The buffering effect of the paper objects begins to be meaningful only when ACH is lower than 0.3 h -1 in which case the minimum RH in winter is brought within the boundaries of ASHRAE class of climate control C when the amount of paper stored is sufficient. Increasing ACH to a level of 0.9 h -1 rises the rate of outdoor air ingress into the building, which decreases the impact of the paper collections. For the building with ACH=0.04 h -1 and the cool storage climate conditions, the indoor average RH levels are around 60% RH. Therefore, dehumidification needs to be continually operated to ensure the required RH range between 30 and 50% RH. The buffering effect of the paper collection only minutely reduces the maximum RH level in the summer (Fig. 3) and therefore plays an insignificant role in bringing climate to the optimal conservation conditions selected.

Figure 1. Buffering of indoor climate by paper collections for ACH=0.3 h -1 and temperature of 21 o C. Figure 2. Buffering of indoor climate by paper collections for ACH=0.9 h -1 and temperature of 21 o C. Figure 3. Buffering of indoor climate by paper collections for ACH=0.04 h -1 and the natural yearly temperature cycle between 10 and 21 o C.

3.2 ENERGY CONSUMPTION UNDER VARIOUS CLIMATE CONTROL SCENARIOS The energy demands for dehumidification and humidification calculated for various climate control scenarios and ACHs are collected in Tables 1 and 2. Table 1. Energy consumption for humidification (Hu) and dehumidification (De) of a 210 m 2 storage space with varying volume of paper collections, for different climate control scenarios and ACH levels. Percentage of storage space occupied by paper ASHRAE AA (45-55% RH) ASHRAE B (40-60% RH) ASHRAE C (25-75% RH) Hu [kwh] De [kwh] Hu [kwh] De [kwh] Hu [kwh] De [kwh] ACH=0.3 h -1 0 1981 530 1446 236 227 0 8% 1796 417 1306 142 175 0 16% 1625 335 1168 76 127 0 ACH=0.9 h -1 0 6063 1831 4499 975 932 33 8% 5499 1523 4082 757 779 1 16% 4974 1274 3690 585 658 0 Table 2. Energy consumption for humidification and dehumidification for the cool storage climate control scenario (210 m 2 of storage space). Percentage of storage space occupied by paper Cool storage (30-50% RH), ACH=0.04 h -1, Humidification [kwh] Dehumidification [kwh] 0 0 469 8% 0 429 16% 0 394 The data in Table 1 confirms entirely the expectation that maintaining the ASHRAE rigorous climate control scenario AA is the most demanding energetically whilst the ASHRAE most relaxed climate control class C practically does not require energy input when the storage space contains paper collections of sufficient volume. The data reveal the crucial impact of air-tightness of the building, reflected in the ACH values, on the humidification and dehumidification loads required to provide selected climate control classes. The total energy consumption is reduced by a sizeable paper collection by at least 21% when compared with the empty space (the worst case of the climate control class AA combined with high ACH of 0.9). Lower reduction of 16% in the energy consumption is caused by the collection in the case of the cool storage conditions as the moisture buffering by paper has merely a smoothing effect on the yearly variations of the indoor RH around high average level of approximately 60% (Fig. 3). Therefore, a considerable dehumidification all year round is required to maintain the desired 30-50% RH range.

4. CONCLUSIONS Although a lot of effort has been put into assessing energy consumption to maintain stable indoor microclimate in the memory institutions preserving cultural heritage collections, so far heat and moisture buffering by the stored collections has not been integrated into the simulations. This study analysed quantitatively the impact of paper collections on indoor climate and energy consumption in libraries and archives by implementing a model of a paper wall equivalent to the library collection in the simulations. The results indicated that the collections can have a visible although not significant effect on stabilising the relative humidity, by absorbing and releasing moisture, only when air exchange rates are low. However, the impact of collections on the humidification and dehumidification loads and the related energy consumption crucially depends on the climate control scenarios and need to be assessed individually for each specific case. 5. REFERENCES [1] S. Staniforth, Environmental conditions for the safeguarding of collections: Future trends. Studies in Conservations, vol. 59, pp. 213-217, 2014. [2] S. H. Hong, M. Strlic, I. Ridley, K. Ntanos, N. Bell, M. Cassar, Climate change mitigation strategies for mechanically controlled repositories: The case of The National Archives, Kew. Atmospheric Environment, vol. 49, pp. 163-170, 2012. [3] J. Ferdyn-Grygierek, A. Baranowski, Internal environment in the museum building Assessment and improvement of air exchange and its impact on energy demand for heating. Energy and Buildings, vol. 92, pp. 45-54, 2015. [4] M. Napp, T. Kalamees, Energy use and indoor climate of conservation heating, dehumidification and adaptive ventilation for the climate control of a mediaeval church in a cold climate. Energy and Buildings, vol. 108, pp. 61-71, 2015. [5] M. Qin, J. Yang, Evaluation of different thermal models in EnergyPlus for calculating moisture effects on building energy consumption in different climate conditions. Building Simulation, vol. 9, pp. 15-25, 2016. [6] M. Steeman, M. De Paepe, A. Janssens, Impact of whole-building hygrothermal modelling on the assessment of indoor climate in a library building. Building and Environment, vol. 45, pp. 1641-1652, 2010. [7] H. Janssen, J. E. Christensen, Hygrothermal optimisation of museum storage space. Energy and Buildings, vol. 56, pp. 169-178, 2013. [8] K. Lengsfeld, A. Holm, Entwicklung und Validierung einer hygrothermischen Raumklima-Simulationssoftware WUFI -Plus. Bauphysik, vol. 29, pp. 178-186, 2007. [9] Comsol Multiphysics, ver. 4.3a, 2012. [10] Ł. Bratasz, A. Kozłowska, R. Kozłowski, Analysis of water adsorption by wood using the Guggenheim-Anderson-de Boer equation. European Journal of Wood and Wood Products, vol. 70, pp. 445-451, 2012. [11] ASHRAE Handbook: Heating, Ventilating, and Air-conditioning Applications. Atlanta: ASHRAE, 2003, chap. 21 Museums, libraries and archives. [12] Joint IIC ICOM CC Declaration of Environmental Guidelines. Internet: www.iiconservation.org/sites/default/files/news/attachments/5681-2014_declaration_on_environmental guidelines.pdf [Feb. 19, 2016]. [13] D. Thickett, S. Rhee, S. Lambarth. Libraries and archives in historic buildings. Proceedings of Museum Microclimates, 2007, pp. 145-155. [14] M. H. Rasmussen, Evaluation of the climate in a new shared storage facility using passive climate control. Proceedings of Museum Microclimates, 2007, pp. 207-212.