LGCNCOE Study Guide: Fixed Gas Detection

Similar documents
MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN

ANNEX AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS (FSS CODE) CHAPTER 1 GENERAL

STANDARDS FOR VAPOUR EMISSION CONTROL SYSTEMS ( MARPOL reg VI/15 )

Process Control PIP PCEA001 Fixed Gas Detection Guidelines

Monitoring Flammable Vapors and Gases in Industrial Processes

Application Bulletin. LNG / LPG Facilities FLAME AND GAS DETECTION FOR LNG FACILITIES

ENHANCED FIRE PROTECTION ARRANGEMENTS

MSC Guidelines for Foam Fire Suppression Systems

A Bridge to Inspection

RESOLUTION MSC.292(87) (adopted on 21 May 2010) ADOPTION OF AMENDMENTS TO THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

Fixed Fire Extinguishing Equipment and Systems

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

2. Directives Affected. Reference (b). is hereby superseded.

SEMICONDUCTOR FABRICATION FACILITIES

Crosswalk: Weight-Based Rating versus Performance-Based Rating

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 CHAPTER II-2 N(2)

SEMICONDUCTOR FABRICATION FACILITIES

CATALYTIC EMITTER - An old idea in new clothes

SEMICONDUCTOR FABRICATION FACILITIES

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Protecting Ethylene Process Facilities: A Review of Gas Detection Methods

Products and performance

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SEMICONDUCTOR FABRICATION FACILITIES

E-17 Flammable Gas Detection and Alarm System

P R O D U C T S P E C I F I C A T I O N MSA Ultima X Series Sensor/Transmitter Specification

MSC Guidelines for Vital System Automation Procedure Number: E2-01 Revision Date: 11/10/2011

Safe Operation Manual. Honeywell IQ Force Gas Detector

Guide to Explosion Protection and Plant Safety

INTERNATIONAL STANDARD

Ship Name: DORIS T Ship Type: General Dry Cargo Ship. Organization

Fixed Ammonia Gas Detection. Why it's needed and what it can do for you.

CLASSIFICATION NOTES. Type Testing Procedure for. Crankcase Oil Mist Detection and Alarm Equipment

Protecting Ethylene Process Facilities: A Review of Gas Detection Methods

Australian/New Zealand Standard

This policy applies to all Hot Work jobs performed on the Calhoun mill property by AbitibiAbitibiBowater employees.

AS/NZS :2008

ICC CODE CORNER 2015 International Fire Code

SERIES 47K GAS SENSOR

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

Dräger X-am 5600 Personal Monitor Multi-Gas Detection Device

LEARNING SPECIAL HAZARD DETECTION TYPES

Max Fire Box Users Guide

JAMES MOODY IM FLASH LIFE SAFETY AHJ

InstrumentationTools.com

LP GAS LEKAGE ALARM. M. G.. D. D. Wickramasinghe 1*, N. Abhayasinghe 2

MODELS LFP4218/LFP6018 TOP VENT GAS FIREPLACE

WATERFRONT FACILITY COMPLIANCE BOOKLET

MINIMUM TANK GAP. Greater of 3 or one-sixth of sum of adjacent tank diameters. one-half of sum of adjacent tank diameters 20

SPECIFICATION MODEL 5200 GAS MONITOR SYSTEM. User Instructions For The Model 5200 Gas Monitor System

SIMRAD GD10P - IR GAS DETECTOR OPERATING MANUAL

RULES FOR CLASSIFICATION OF MOBILE OFFSHORE UNITS

ACKNOWLEDGEMENT. IIAR expresses its deepest appreciation to these authors for their contributions for the betterment of the industry.

FIXED GAS DETECTORS PDF

Operation and Maintenance Manual

GASEOUS HYDROGEN SYSTEMS

VASTHI ENGINEERS. Vasthi Explosive Meter Sheet No. 1 of 5. Vasthi Monitors for Combustible Gas.

Aluminum Dust Management in a Metallizing Facility

Product Selection Guide Fixed Gas Detection Systems for Personnel & Equipment Safety

HYDROGEN DETECTION INSTRUMENTATION FOR THE SIAC HYDROGEN RECOMBINERS. Summary

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

GUIDE TO APPROVAL OF RETROFIT BALLAST WATER MANAGEMENT SYSTEM INSTALLATIONS

Craig Wolfe Toxalert International, Inc. Mound, MN

SECURITY BLANKET Foam Fire Protection Products

IEC TC31 (Explosive Atmospheres) Gas Detection as Method of Protection Jon Miller

Fire is No Accident Fire is No Accident It can be prevented.

INFRARED RADIANT GAS SYSTEMS FOR THERMAL TREATMENTS

ULTIMA XL/XT Series Gas Monitors. [ Ultimate Features Extreme Design ]

NJSP HMRU. Module 5 B HM Operations 1

4-20mA CYBER Cyber Transmitter for flammable, toxic and IR gas detection Cyber Head Increased security in ATEX certified head

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

Gas Detection. - Disposable - Serviceable. Single Gas Detectors

3years. Detection of explosive gases, toxic gases and oxygen. Infrared XP IR version. SIL 2 high reliability IP 66.

SIMRAD GD10PE IR GAS DETECTOR

Zareba Metro Gas Detector

Fire Prevention Plan Program

Operate the Mutli-Gas Monitor PID

CERTIFICATE OF FIRE APPROVAL

Gas detectors for Industrial Refrigeration: Safety, efficiency and peace of mind

Ammonia Detection System Codes and Design Specifications

Instruction Manual Model GX-86 Portable Four Gas Monitor

MSC Guidelines for Automatic Sprinkler Systems

Detection of explosive gases, toxic gases or oxygen. Infrared XP version. SIL 2 high reliability IP 66. Certifications. The Fixed Gas Detection People

Water Spray Systems: NFPA 15

F&G detection system for LNG plants

Gas detection for your safety

RK / RK Methane Detector Operator s Manual

RESOLUTION MSC.98(73) (adopted on 5 December 2000) ADOPTION OF THE INTERNATIONAL CODE FOR FIRE SAFETY SYSTEMS

Choosing the best detection technologies for measuring combustible gas and VOC vapors

Presentation to. IOSH Food and Drink Group. Danny McDougall Richard Perkin

Refrigeration Technology in Building Services Engineering

MSC Guidelines for General Emergency Alarm & Public Address Systems

SIMRAD GD10 IR GAS DETECTOR

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

OLC(T) 100 FIXED GAS DETECTOR

ALTAIR 5X Multigas Detector Product Specification

The regulatory section first discusses codes and standards and then Federal and State legislative and local requirements.

Transcription:

LGCNCOE Study Guide: Fixed Gas Detection References Regulatory International Gas Carrier Code (IGC) regulation 13.6 Gas Carrier Code (GC) regulation 13.6 Existing Gas Carrier Code regulation 13.6 46 CFR 154.1345 & 154.1350 Other Industry Manufacturer s Fixed Gas Detection Manual Ship s Cargo Operations Manual FGCE PQS (*this is a placeholder reference to PQS revisions currently in draft form) Task # 17 Examine fixed gas detection system 17.1 Witness a satisfactory calibration of the fixed gas detection system 17.2 Verify that sampling points are installed in the required spaces 17.3 Verify the location of sampling points relative to authorized cargo types 17.4 Verify the integrity of gas detection sampling pipe system LGCNCOE Study Guide 1 Fixed Gas Detection

What type of system is represented in this photograph? Pictured above is the inside view of a LGC s fixed gas detection systems control cabinet. Gas carriers are fitted with fixed gas detection systems to monitor the spaces (required in IGC 13.6/ GC 13.6.7) for the presence of gas vapors. As part of a liquefied gas carrier s certificate of compliance examination, Foreign Gas Carrier Examiners (FGCEs) should conduct examinations of the vessel s fixed gas detection system. These systems are required in accordance with regulation 13.6 of the IGC & GC codes. The regulations require that the gas detection system be capable of gas sampling and analyzing at each required sampling head location, sequentially at intervals not exceeding 30 minutes, with the exception of gas detection found in the ventilation hoods and engine room gas supply pipelines (LNG ships only) where sampling must be continuous. A visual and audible alarm is required to actuate if the gas concentration levels reach 30% of the lower explosive limit (LEL). Alarms should be observed while onboard, IAW the manufacturer s fixed gas detection manual. Continuous gas detection for LNG ships must be provided to indicate leaks and to shut down the gas fuel supply to the machinery space if gas concentration levels have reached 60% LEL. Sampling points must be provided in the following areas (IAW IGC 13.6.7/GC 13.6.7): Cargo compressor rooms Electric motor rooms Cargo control rooms unless classified as gas safe Enclosed spaces such as hold spaces and inter barrier spaces Air locks Ventilation hoods and engine room gas supply pipelines (LNG ships only) There are two types of gas detection systems used to meet the regulations: 1. Gas Sampling: The first is a system that consists of one gas detection cabinet, usually located in the cargo control room with a vacuum pump, one gas analyzer, solenoid valves, and individual piping. This system draws a sample of air from a particular location and then transports it back to the analyzing unit, within the gas detection cabinet. Sampling and analyzing from each detector is done sequentially and is automatically controlled by the solenoid selection valves. This process is repeated at intervals not to exceed 30 minutes for all detector locations. 2. Gas Detection Sensor/Transmitter: The second system has individual gas detection analyzers inside the required areas which monitor the atmosphere continuously and will detect the presence of any gas should it accumulate. These analyzers then convert the presence of gas into an electrical signal and send it back to the gas detection panel. There are two types of gas detectors (analyzers) used in the gas detection systems above: 1. Catalytic: Catalytic detectors are based upon the principle that when gas oxidizes it produces heat, and a sensor converts the temperature change via a standard Wheatstone Bridge-type circuit to a sensor signal that is proportional to the gas concentration. The sensor components consist of a pair of heating coils (reference and active). The catalytic sensor reacts exothermically to LGCNCOE Study Guide 2 Fixed Gas Detection

the present combustible gases, resulting in a change of resistance. This analyzer is used to monitor flammable gases within the following spaces: Accommodation Spaces Engine Room Cargo Machinery Room 2. Infrared: The Infrared (IR) detection method is based upon the absorption of infrared radiation at specific wavelengths as it passes through a volume of gas. Typically, two infrared light sources and an infrared light detector measures the intensity of two different wavelengths, one at the absorption wavelength and one outside the absorption wavelength. If a gas intervenes between the source and the detector, the level of radiation falling on the detector is reduced. Gas concentration is determined by comparing the relative values between the two wavelengths. Infrared sensors can only detect hydrocarbons, thus making them ineffective on an LPG ships carrying chemical gases such as Vinyl Chloride and Anhydrous Ammonia. These analyzers will be located in the following locations: Cargo Holds and Inter Barrier Spaces Vent Masts Double Bottom and Under Deck Pipe Passages Note: The infrared system is used in locations that may be oxygen deficient and the catalytic sensors require at least 10% oxygen to oxidize the gas. Before evaluating these systems, what is the first thing you should witness? As part of the fixed gas detection system examination, examiners should always witness a calibration of the system. This is usually performed by the Chief Officer or the Gas Engineer, and demonstrates the system s ability to function properly, as well as, the ability of the ship s crew to properly calibrate and operate the equipment. The calibration should always be done in accordance with the manufacturer s fixed gas detection manual. Suitable equipment and span gas are required to be onboard for the calibration and usually located in the gas detection cabinet. Note: A ship s gas detection system will be calibrated using span gas IAW manufacturer s fixed gas detection manual and then the calibration setting will be adjusted using a calibration curve depending upon the cargo being carried. How do you ensure that the sampling points of this system are located in the required spaces? An integral part of this examination is to ensure the sampling points are located in the required spaces. Each FGCE should review the ship s cargo operations manual prior to performing the cargo portion of the exam in order to familiarize themselves with the specifics of the onboard cargo system. Each cargo operations manual will have a section that identifies the locations of the gas sampling points onboard. FGCE s should use the cargo operations manual to cross reference the locations of the installed gas sampling points with the locations that are required to have gas detection in accordance with regulations 13.6.7 & 13.6.11 of the IGC & GC codes. LGCNCOE Study Guide 3 Fixed Gas Detection

When this is complete, the FGCE can spot check those locations while conducting the cargo exam. Would you find the sampling points located at the top or at the bottom of a particular space? The location of the fixed gas detection sampling points within a space depends on the products the ship is authorized to carry and their relative density. Relative density is the ratio of the density of one substance to another. For gases, the relative density is the ratio of the density of the gas to that of air. For gas cargoes that have a relative density of less than 1.0, the gas will rise if a leak occurs. For gases that have a relative density of more than 1.0, the gas will fall. IGC & GC regulation 13.6.2 requires that the relative density of the cargoes be taken into account when locating the gas detection sampling points within a space. On some LPG ships, sampling points are located at both the top and bottom of a space, dependent upon the density of the cargoes authorized to be carried aboard the vessel. To determine where the gas sampling points are required to be located on a particular ship prior to attending the ship, compare the list of authorized cargoes on the Subchapter O Endorsement to cargo information contained in Material Safety Data Sheets (MSDS) or the International Chamber of Shipping Tanker Safety Guide (Liquefied Gas). How do you ensure that the sampling pipe system is in satisfactory condition? In each space that is required to have gas detection installed, the sampling points are connected to the analyzing unit with a small steel piping system. If the integrity of the piping system is breached, then the atmosphere inside of a particular space will not be able to be analyzed. The procedure for testing the integrity of the piping system should be completed in accordance with the manufacture s fixed gas detection manual. Note: FGCE s are to witness and observe the testing of the system and not become an active participant. Two common methods for testing are: 1. Low flow alarm: Select a sampling point and have the Chief Mate or Gas Engineer ensure the analyzing unit is switched on manual and selected to the desired sampling point. A crewmember and if possible the other CG examiner will proceed to the selected location, and the crewmember will block the sampling point. If the piping system is in good condition, a low flow alarm will be activated. If there is a breach in the sampling piping system, air will be drawn in from the location of the breach, resulting in the failure of alarm activation. 2. Span gas: Integrity of the piping system can be verified by supplying span gas to the sample point. The % LEL displayed on the gas detection cabinet should be equal to what is stated on the span gas bottle +/- 5%. Span gas being utilized should be IAW manufacture s fixed gas detection manual. Note: The farther the sampling point is located from the analyzing unit, the longer it will take for the reading or low flow alarm to activate. When in doubt as to the effectiveness of any test on a specific system, refer to the manufacture s fixed gas detection manual. In summary: the steps for testing of the fixed gas detection system: LGCNCOE Study Guide 4 Fixed Gas Detection

1. Witness a satisfactory calibration. 2. Verify sampling points are installed in the required spaces. 3. Verify location within a space of the sampling points relative to the cargoes authorized (i.e., top or bottom). 4. Verify the integrity of the sampling pipe system. Please keep in mind that the gas detection system is a vital piece of equipment that ensures the safety of the ship s personnel, environment, and to the ship itself. An inoperative gas detection system may be grounds for denial of entry to port, expulsion from port or detention in accordance with Navigation and Vessel Inspection Circular (NVIC) 06-03, CH-2. The specific course of action will be at the discretion of the local OCMI. LGCNCOE Study Guide 5 Fixed Gas Detection