INSTALLATION INSTRUCTION

Similar documents
SPLIT-SYSTEM EVAPORATOR BLOWER (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: Nothing N4C-0500

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

MODELS K2EU060A, K4EU090A, & K3EU120A

INSTALLATION INSTRUCTION-50 Hz

CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L2EU NOMINAL TONS

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION FEATURES L4EU NOMINAL TONS

Technical Guide DESCRIPTION CHAMPION SPLIT-SYSTEM EVAPORATOR BLOWER L4EU240A 20 NOMINAL TONS (WORLD 50 HZ) FEATURES XTG-A-0307

INSTALLATION MANUAL (AIR COOLED) SPLIT-SYSTEM AIR CONDITIONER MODEL: LA120 NOTES, CAUTIONS AND WARNINGS SAVE THIS MANUAL B-0203

SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K1EU180 5 Thru 15 Nominal Tons DESCRIPTION ACCESSORIES FIELD INSTALLED

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

Technical Guide SUNLINE 2000 DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWER K4EU NOMINAL TONS (WORLD 50 HZ)

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

R-410A. NJ-10 thru -20, 4-Pipe Ton, 60 Hertz TABLE OF CONTENTS LIST OF TABLES LIST OF FIGURES

Technical Guide DESCRIPTION ACCESSORIES FIELD INSTALLED SPLIT-SYSTEM EVAPORATOR BLOWERS. 7-1/2 and 10 NOMINAL TONS LA090 & LA120 SUPPLY AIR PLENUMS

SPLIT-SYSTEM EVAPORATOR BLOWER DESCRIPTION ACCESSORIES - FIELD INSTALLED. K5EU090 and K4EU Hz 7.5 and 10 NOMINAL TONS SUNLINE 2000 (WORLD 50 HZ)

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

SPLIT-SYSTEM HEAT PUMPS 50 AND 60 HZ DESCRIPTION

INSTALLATION INSTRUCTION

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

MODELS B1PA024, 030 AND 036

CHAMPION SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) INSTALLATION INSTRUCTION Supersedes: N4 (778) N4Y (492)

TECHNICAL GUIDE DESCRIPTION EA090/FA090 SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNIT INDOOR UNIT

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

APPLICATION DATA SHEET

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY UIM-C-0214

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: N1Y (497) N1Y (998) MODELS E2FB090 & E1FB120 GENERAL

STELLAR 2000 SINGLE PIECE AIR HANDLERS INSTALLATION INSTRUCTION Supersedes: N2Y (795) N2Y (1195)

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS 15 THROUGH 20 NOMINAL TON HB B-0804

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

INSTALLATION MANUAL SPLIT-SYSTEM CONDENSING UNITS (AIR COOLED) HB Ton HB Ton HB Ton NOTES, CAUTIONS AND WARNINGS

MODELS E1FB180 & E1FB240

CONDENSING UNITS SPLIT-SYSTEM COOLING 6-1/3 TONS INSTALLATION INSTRUCTION MODELS H*DB076 NOMENCLATURE GENERAL LIMITATIONS INSPECTION REFERENCE

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP MODELS: TABLE OF CONTENTS LIST OF FIGURES

INSTALLATION MANUAL G*FD SERIES FULL-CASED A COILS UPFLOW/COUNTERFLOW/HORIZONTAL COOLING/HEAT PUMP

INSTALLATION MANUAL COMMERCIAL SPLIT SYSTEM COOLING UNITS 4 PIPE SYSTEMS. HB 180 & thru 20 Nominal Tons NOTES, CAUTIONS AND WARNINGS

SPLIT-SYSTEM HEAT PUMPS OUTDOOR UNITS. INSTALLATION INSTRUCTION Supersedes: Nothing N1Y (692) MODELS E1FB090 & 120 (50 & 60 HZ) GENERAL

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTION

TECHNICAL GUIDE MODELS: H5CE090, H3CE120 & H1CE /2, 10, & 12-1/2 NOMINAL TONS EER DESCRIPTION

40 RM/RMS Packaged Air-Handling Units

CONDENSING UNITS SPLIT-SYSTEM COOLING 1.5 TO 5 TONS INSTALLATION INSTRUCTION MODELS H*DE018 THRU H*DE060 NOMENCLATURE GENERAL LIMITATIONS INSPECTION

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

INSTALLATION MANUAL LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: SAFETY

MODELS W1LC220, 260 AND 320 STYLE B

DSH Model Air Cooled Self Contained Indoor Packaged Units 2-5 Tons Preliminary Application Data

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

FILTERS MANIFOLD CABINET REFRIGERANT CONNECTION LOCATION

SUBMITTAL DATA SHEET FEATURES. SPLIT-SYSTEM EVAPORATOR BLOWERS 7.5, 10, 15 & 20 TONS MODELS: NH-07 thru -20, 2-PIPE NJ-10 thru -20, 4-PIPE

INSTALLATION MANUAL - 50 Hz

ACCESSORY INSTALLATION INSTRUCTION ELECTRIC HEAT ACCESSORY 10, 16, 26, 36 & 72

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

INSTALLATION MANUAL SINGLE PIECE NON-VARIABLE SPEED AIR HANDLERS MODELS: AHX SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

High Profile Evaporator

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

INSTALLATION INSTRUCTIONS

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

INSTALLATION INSTRUCTIONS FMB/FMC SERIES MULTI-POSITION AIR HANDLER

DRY CHARGE UNITS. 1.5 to 5 Tons AIR CONDITIONERS LCS13DC PRODUCT SPECIFICATIONS L C S 13 DC MODEL NUMBER IDENTIFICATION

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

COMMERCIAL AIR HANDLER

Installation Instructions

INSTALLATION INSTRUCTION

SUNLINE SERIES SINGLE PACKAGE AIR CONDITIONERS. INSTALLATION INSTRUCTION Supersedes: Nothing N3Y (394) MODELS D*SC360 & 480 INSPECTION

VariCool VAV Engineering Guide

Installation, Start-Up and Service Instructions

INSTALLATION MANUAL SINGLE PIECE STANDARD ECM AIR HANDLERS MODELS: AHX61 SERIES LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES SECTION I: GENERAL

Advance Release September 2009

Installation, Start-Up and Service Instructions

Installation, Operation and Service Instructions

INSTALLATION INSTRUCTIONS

SSL / SBS Sales Guide BLOWER-COILS REDUCED-FOOTPRINT, VERTICAL

Installation Instructions

INSTALLATION INSTRUCTION

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM HEAT PUMPS 60 HZ MODELS: EF-10 & FF-10

VertiCool Aurora Engineering Guide

INSTALLATION MANUAL WARNING WARNING FULL-CASED UPFLOW/COUNTERFLOW FOR COOLING/HEAT PUMPS FULL-CASED MULTI-POSITION FOR COOLING/HEAT PUMPS MODELS: CF

MIN. CCT. QTY RLA LRA HP FLA AMPACITY /1/ /3/

SECTION AIR HANDLING UNIT

INSTALLATION INSTRUCTIONS

Installation, Operation, and Maintenance Information

Condensing Unit Installation and Operating Instructions

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL WARNING WARNING MODULAR NON-VARIABLE SPEED AIR HANDLERS MODELS: MA LIST OF SECTIONS LIST OF FIGURES LIST OF TABLES

INSTALLATION INSTRUCTION

C13-Series Engineering Guide

Installation Instructions

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

INSTALLATION AND COMMISSIONING MANUAL. Neos 100S Integra 20X, 30S, 35X, 40X, 50X

INSTALLATION INSTRUCTIONS TXV Coils EBU, EBA

INSTALLATION INSTRUCTIONS TXV Coils EBD, EBA

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

R-410A MODELS: YD360 Thru Ton 60 Hertz

Transcription:

INSTALLATION INSTRUCTION SPLIT-SYSTEM EVAPORATOR BLOWER ( COOLED) CONTENTS NOMENCLATURE... 3 GENERAL... 3 NOTES CAUTIONS AND WARININGS... 3 PARTS... 3 INSPECTION... 3 LIMITATIONS... 3 INSTALLATION... 3 MAINTENANCE... 14 FOR A COMPLET TABLE OF CONTENTS SEE FOLLOW- ING PAGE. MODEL L*EU360 L*EU480 CAUTION: READ ALL SAFETY GUIDES BEFORE YOU START TO INSTALL YOUR UNIT. SAVE THIS MANUAL 035-16617-001REV A (799) Form

TABLE OF CONTENTS NOMENCLATURE...2 GENERAL...3 NOTES CAUTIONS AND WARININGS...3 PARTS...3 INSPECTION...3 LIMITATIONS...3 INSTALLATION...3 LOCATION... 3 RIGGING... 3 CLEARANCES... 3 FOUNDATIONS... 4 DUCT CONNECTIONS... 4 INSULATION......................................4 SUPPLY DUCTS................................ 4 RETURN DUCT ANGLES......................... 4 DISCHARGE CONVERSION... 4 CAPACITY REDUCTION... 5 DRAIN CONNECTIONS... 8 BLOWER MOTOR MOUNTING LOCATIONS... 10 MOTOR ARRANGEMENTS... 10 FOR LOCATION A................................. 10 FOR ALL OTHER LOCATIONS....................... 10 REFRIGERANT MAINS... 10 INSTALLING REFRIGERANT MAINS.................. 10 EVAPORATOR SECTION PIPING... 12 EXPANSION VALVE BULB... 12 SYSTEM ADJUSTMENT... 12 TWIN BELT DRIVE ADJUSTMENT.................... 12 ELECTRICAL CONNECTIONS... 13 MAINTENANCE...14 3 PLENUM BASE ACCESSORY................... 5 4 VERTICAL ARRANGEMENTS.................... 7 5 HORIZONTAL ARRANGEMENTS................ 7 6 UNIT MOUNTING............................. 8 7 RECOMMENDED DRAIN PIPING................. 9 8 LIQUID LINE SOLENOID VALVES............... 10 9 SHIPPING LOC OF MOTOR MNT ASSEMBLY..... 10 10 MOTOR MOUNTING ASSEMBLY AND MOTOR.... 10 11 MOTOR ARRANGEMENT LOCATIONS........... 11 12 DOUBLE GROOVE PULLEY................... 13 13 UNIT DIMENSIONS........................... 16 14 BLOWER CURVE..................... 18 15 BLOWER CURVE..................... 20 LIST OF TABLES 1 PHYSICAL DATA............................. 6 2 UNIT MOUNTING DIMENSIONS................. 8 3 OPERATING WEIGHT DISTRIBUTION (LBS.)....... 9 4 ACCESSORY OPERATING WEIGHT DIST. (LBS.)... 9 5 ELECTRICAL DATA - SUPPLY MOTOR....... 13 6 ACCESSORY STATIC RESISTANCE, IWG........ 14 7 BLOWER MOTOR DATA...................... 14 8 BLOWER DRIVE DATA........................ 15 9 UNIT DIMENSIONS........................... 16 10 l*eu360 SUPPLY BLOWER PERFORMANCE.. 17 11 L*EU480 SUPPLY BLOWER PERFORMANCE.. 18 LIST OF FIGURES 1 CONNECTING SUPPLY DUCTWORK......... 5 2 MOUNTING HARDWARE....................... 5 NOMENCLATURE - 7! $ ) 2 4, 7 + 6 + ) 6 - / 4 ; 5 F EJ 5 O I J A - L = F H = J H * M A H. ) + 6 4 ; 1 5 6 ) -, 0 - ) 6 ) + E C O H H H H 2 4, 7 + 6 / - - 4 ) 6 1 1 ) + 1 / I J / A A = J E + ) 2 ) + 1 6 ; 2 4, 7 + 6 1, - 6 1. 1-4! $! 6 I " & " 6 I - 7 - L = F = J * M A 7 EJ 2 Unitary Products Group

GENERAL These LEU evaporator blowers are designed for use with condensing units. Each unit consists of a coil section and a blower section which are factory assembled and shipped as shown per Arrangement 1 of Figure 4. These sections may be rearranged in the field for other air discharge patterns. See Arrangements 2 through 6 of Figure 4 and 7 through 12 of Figure 5. The LEU units have 115 volt solenoid valves to match the 115 volt control circuits of the HCA300, 360 and 480 condensing units. LIMITATIONS This unit must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform with the appropriate national code. The unit is designed to meet National Safety Code Standards. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense. See Table 1 for unit application data. INSTALLATION LOCATION The evaporator blowers are not designed for outdoor installation. They must be located within the building structure, either inside or outside the conditioned space. REFER TO FORM 550.13-N3Y AND 550.12-N4Y FOR INFORMATION ON THE 360 AND 480 EVAPORATORS RESPECTIVELY NOTES CAUTIONS AND WARININGS Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and/or equipment damage may result if installation procedure is not handled properly. PARTS Renewal Parts: Refer to Parts Manual for complete listing of replacement parts on this equipment. The above forms and all other forms referenced in this instruction may be ordered from: UPG Publications Center FAX (877) 379-7920 Refer to Parts Manual for complete listing of replacement parts on this equipment. INSPECTION As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing. The unit should be located as close to the condensing unit as practical and positioned to minimize bends in the refrigerant piping. Units being installed vertically or horizontally can be set directly on a floor or platform, or they can be supported by metal or wooded beams. Units being installed horizontally can be suspended from above as shown in Figure 6. Refer to Form 550.13-N7.1Y for more information on the installation of the suspension accessory and for the individual load on each hanger rod. RIGGING Care must be taken when moving the unit. Do not remove any packaging until the unit is near the place of installation. SPREADER BARS SHOULD BE USED BETWEEN THE SLINGS TO PREVENT CRUSHING THE UNIT FRAME OR PANELS. When preparing to move the unit, always determine the center of gravity of the unit in order to equally distribute the weight. Rig unit by attaching chain or cable slings around the bottom skid. A lift truck may be used to raise a unit to a suspended location. Refer to Table 2 for the total unit operating weight. CLEARANCES A 25" clearance is required on the end with the piping connections and the supply air blower motor to properly service and maintain the unit and to replace the filters. Some clearance will also be required for the duct and power wire connections. Unitary Products Group 3

A clearance equal to the unit width will be required on one end of the unit if the blower shaft or the evaporator coil will have to be replaced without moving the unit. FOUNDATIONS All units may be set directly on a floor, pedestal, platform shelf or mounted on the suspension accessory used as a base. The evaporator blower may be suspended from joists with isolation-type hangers or hooks. Refer to Figures 2 and 6 and Tables 3 and 4. TABLE 1: UNIT APPLICATION DATA POWER SUPPLY VOLTAGE VARIATION SUPPLY RANGE CFM ENTERING TEMPERATURE, F COOLING - DB/WB HEATING - DB MIN. MAX. MIN. MAX. MIN. MAX. MIN. MAX. 1 208/230-3-60 187 253 10,000 14,000 460-3-60 414 506 12,800 19,200 65/57 95/72-150 2 1. 2. Both hot water and steam coils. (DO NOT use steam in hot water coils) Maximum inlet steam pressure. DUCT CONNECTIONS Ductwork should always be suspended with hangers or supported by legs. It should never be fastened directly to the building structure. Allow clearance around ducts for safety in the handling of heated air and for insulation when required. INSULATION Ductwork insulation should: 1. Be used when ducts pass through an unconditioned space during the cooling season or through an unheated space during the heating season. 2. Include a vapor barrier around the outside to prevent the absorption of moisture. 3. Be no less than 2 inches thick with weather proof coating when applied to ducts exposed to outdoor conditions. SUPPLY DUCTS See Figure 1 for suggested method of connecting supply air ductwork. Non-flammable material collars should be used to minimize the transmission of noise and/or vibration. RETURN DUCT ANGLES Return air duct angles are shipped turned in. They are intended to be unscrewed and turned for connection of duct work. The return air grille accessory attaches in the same manner as the panels. The supply air plenums and bases that are shown in Figure 3 are shipped knocked-down. Separate assembly instructions are packed with these accessories. DISCHARGE CONVERSION Units are shipped for upflow operation, but may be converted for any of the illustrated air discharge patterns shown in Figure 4 and 5. Convert a follows: 1. Remove the panels from the blower section. 2. Remove Phillips machine screws located inside casing corner angles which hold coil and blower sections together. 3. Rotate blower section for the air discharge pattern desired. NOTE:Before proceeding to Step 4, see the section on Blower Motor Mounting Locations and mount the blower motor in the desired position. 4. If accessory heating coils are used, mount heating coil between coil and blower sections. Screw fastening locations are the same for all sections and heating accessories. 4 Unitary Products Group

NON-FLAMMABLE COLLAR DUCT TRANSITION DUCT NOTE: The following illustration shows how the channels should be secured to the unit using the hardware provided with the suspension accessory. (2) 9/16 HOLES FOR 1/2 HANGER RODS SUSPENSION CHANNEL 24" 5/16 NUT, FLATWASHER 3 5/16 NUT, LOCKWASHER, FLATWASHER OUTLET 3/8 NUT (USED AS SPACER) UNIT PANEL 5/16 BOLT, FLAT-WASHER BLOWER GASKETS (BY INSTALLER) FLANGED DUCT CONNECTION (FIELD FABRICATED) SIDE PANEL FIGURE 2 : MOUNTING HARDWARE UNIT ANGLE FIGURE 1 : SUGGESTED METHOD FOR CON- NECTING SUPPLY DUCTWORK If heating coils are not used, fasten coil section to blower section with machine screws removed in Step 2. 5. Before replacing panels, see Duct Connections and Drain Connections. 6. Replace panels. DECORATIVE BASE CAPACITY REDUCTION The evaporator coils for these blower units are split for face control and are equipped with liquid line solenoid valves for both capacity control and pumpdown. As the external controller (thermostat) becomes satisfied, the control circuit of the condensing unit will unload its compressor and will de-energize (close) the solenoid valve for capacity reduction. When the external controller is fully satisfied, the control circuit of the condensing unit will de-energize the solenoid valve for pumpdown, but the compressor will continue to operate until the low side of the system is pumped out and the system is shut down by its low pressure control. FOR ARRANGEMENTS 1 THRU 6 When outside air is required, hole can be cut in panel for connecting ductwork. FIGURE 3 : PLENUM BASE ACCESSORY Unitary Products Group 5

TABLE 2: PHYSICAL DATA DESCRIPTION MODEL LEU600 Rows Deep X Rows High 4 x 32 4 x 40 4 x 50 EVAPORATOR COIL Finned Length, inches 93 96 96 Face Area, feet 2 26.0 33.4 41.7 Tube (copper) OD, inches 1/2 1/2 1/2 Fins (Aluminum) per 1 inch 12 12 12 CENTRIFUGAL BLOWERS (2 PER UNIT) Diameter X Width, inches (Forward Curved) 18 x 18 18 x 18 20 x 18 FILTERS (THROWAWAY) Size and Quantity Per Model, inches 16 x 25 x 1 - - 6 20 x 20 x 1-12 - 20 x 22-1/4 x 1-3 - 20 x 25 x 1 10-3 25 x 25 x 1 - - 6 Total Face Area / feet 2 34.7 42.6 53.1 OPERATING CHARGE LBS (REFRIGERANT - 22) System 1 18 12 14 System 2-12 19 Tube (copper) OD, inches 1/2 1/2 1/2 DRAINABLE HOT WATER COIL ACCESSORY Rows Deep 2 2 2 Fins (Aluminum) per 1 inch 12 12 8 Face Area, feet 2 21.2 27.2 27.2 Connections (Supply & Return), inches 13/8 OD (copper) 1-5/8 OD (copper) Tube (copper) OD, inches 1 (Outside) 5/8 (in.) NON-FREEZE, STEAM DISTRIBUTING COIL ACCESSORY Rows Deep 1 Fins (Aluminum) per 1 inch 8 Face Area, feet 2 18.2 N/A Connection, (Brass) Inches (NPTE) Inlet 2 Outlet 1-1/2 Basic Unit (Less Motor & Drive) 690 1170 1500 Shipping Weight (lbs) 990 1170 Operating Weight (lbs) 1115 1310 Hot Water Coil 150 190 190 COMPONENT WEIGHT Accessories Blower Motor (1750 RPM) Steam Coil 160 - - Supply Air Plenum 125 - - Return Air Grille 25 - - 120 (5HP) - - 150 (7.5HP) 150 (7.5HP) 150 (7.5HP) 180 (10HP) 180 (10HP) 180 (10HP) 6 Unitary Products Group

1 BLOWER VERTICAL ARRANGEMENTS 2 3 ) 1 4 EVAPORATOR COIL 4 5 6 * IF REQUIRED, SOME CAN BE BROUGHT THROUGH THE BOTTOM OF THE EVAPORATOR SECTION. FIGURE 4 : VERTICAL ARRANGEMENTS HORIZONTAL ARRANGEMENTS 7 8 9 10 11 12 FIGURE 5 : HORIZONTAL ARRANGEMENTS Unitary Products Group 7

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fter these bottom channels are cup per Note 1 of Figure 6, a new hole will have to be drilled at the cut. DRAIN CONNECTIONS All drain lines MUST be trapped and located so they will not be exposed to freezing temperatures. The evaporator blower has 7/8" OD steel condensate stub at each end of a singe drain pan. Both ends are closed with plastic caps. A plastic ell with clamps is provided. Attach the ell to the desired end and run a full size 7/8" drain line to the nearest drain facility. Seal the cap at the unused end with suitable mastic. NOTE: has 1-1/8" OD steal condensate stub at each end. The 3 inch dimension must equal or exceed the negative static pressure developed by the supply air blowers. If it does not, the condensate will not drain properly and may overflow the drain pan. The trap must be at least 2 inches deep to maintain a water seal under all operating conditions, especially when the blowers are starting up. 8 Unitary Products Group

TABLE 4: OPERATING WEIGHT DISTRIBUTION (LBS.) SUPPORT POINT DESIGNATION MODEL BLOWER MOTOR HORIZONTAL INSTALLATION VERTICAL INSTALLATION W1 W2 W3 W4 W5 W6 1 W1 W2 W3 W4 W5 W6 1 5 HP 195 175 165 205 190 180 205 185 165 205 185 165 7.5 HP 200 180 165 210 195 180 215 190 165 215 190 165 10HP 205 185 165 215 200 180 225 195 165 225 195 165 7.5HP 230 210 195 245 225 215 245 220 195 245 220 195 10HP 235 215 195 255 235 215 255 225 195 255 225 195 1. Blower Motor End of Unit TABLE 5: ACCESSORY OPERATING WEIGHT DIST. (LBS.) 1 ACCESSORY BASE 2 25 30 115 VOLT LIQUID LINE SOLENOID VALVE FOR CAPACITY CONTROL HOT WATER COIL 35 45 STEAM COIL 1 ROW 30 - B 2ND STAGE = 15 TONS TX VALVES 1. These weights should be added to each point load (W1 through W6) in Table 4. 2. This accessory can only be applied on units installed in the vertical position 1ST STAGE = 15 TONS A 115 VOLT LIQUID LINE SOLENOID VALVE FOR PUMPDOWN EVAPORATOR COIL PLASTIC ELL 3" STEEL STUB CONNECTION DRAIN PAN EVAPORATOR COIL 20 TONS 3RD STAGE C TX VALVES 115 VOLT LIQUID LINE SOLENOID VALVE FOR PUMPDOWN 115 VOLT LIQUID LINE SOLENOID VALVE FOR CAPACITY CONTROL 2" HOSE CLAMPS EVAPORATOR COIL FIGURE 7 : RECOMMENDED DRAIN PIPING 10 TONS 2ND STAGE B 10 TONS 1ST STAGE A 115 VOLT LIQUID LINE SOLENOID VALVE FOR PUMPDOWN FIGURE 8 : LIQUID LINE SOLENOID VALVES Unitary Products Group 9

BLOWER MOTOR MOUNTING LOCATIONS The blower units are always shipped from the factory less motor and drive. The motor mounting assembly, however, is always factory-installed as shown in Figure 9. Figure 10 shows a more detailed view of the motor mounting assembly (the mounting plate and the channels) with a motor. NOTE:The 10HP 200/208 volt motors are not inherently protected. For proper operation these motors require separate starters with overload heater elements, a 24 volt coil or a manual reset button. NOTE:The comes with a motor mounting adapter plate that is used for the 7.5 and 10 HP motors. If a 5 HP motor is used, remove the adapter plate. MOTOR MOUNTING CHANNELS AND MOUNTING PLATE ARE ALWAYS SHIPPED IN THIS LOCATION & 480 FIGURE 9 : SHIPPING LOCATION OF MOTOR MOUNTING ASSEMBLY MOTOR ARRANGEMENTS The recommended motor location for each blower arrangement is as follows. Refer to Figure 10. FOR ALL OTHER LOCATIONS 1. Move the entire motor mounting assembly (both the mounting plate and the channels) so that the mounting plate will be in the correct location. NOTE:The blower section must be lifted off the evaporator section to gain access to the mounting channel fasteners. Since these sections have to be repositioned for arrangements 2,3,5,6,7,9,10 and 12 of Figures 4 and 5, the motor mounting assembly should be relocated before the two sections are rejoined. 2. Rotate the motor mounting plate 180 degrees on the mounting channels.(for locations B, and D only! Do not rotate the plate for location C or E.) 3. Install the motor and drive package. REFRIGERANT MAINS A majority of service troubles are caused by lack of adequate precautions to provide an internally clean and dry system. It is extremely important that all field-supplied materials conform with established standards. Hard drawn copper tubing should be used where no appreciable amount of bending around pipes or other obstructions is necessary. Use long radius ells wherever possible. If soft copper is used, care should be taken to avoid sharp bends which may cause a restriction. Where refrigerant lines pass through a wall, pack fiber glass insulation and a sealing material such as permagum around the refrigerant lines to reduce vibration and to retain some flexibility in the lines. 6 4 7 6 1 / 2 ) 6-6 4 6 4 7 6 1 / + 0 ) - 5 The refrigerant lines should be supported by suitable hangers, brackets or clamps. Braze all copper to copper joints with Silfos-5 or equivalent brazing material. Do not use soft solder. Never braze or solder the liquid and suction lines together. The complete suction line should be insulated with no less than 1/2" ARMAFLEX or equivalent. FIGURE 10 : MOTOR MOUNTING ASSEMBLY AND MOTOR FOR LOCATION A Install the motor and drive package. The motor mounting assembly is already in the correct position. If it is desirable to tape or wire the liquid and suction lines together for support purposes, they must be completely insulated from each other. INSTALLING REFRIGERANT MAINS The units are shipped with a holding charge of Refrigerant- 22. The connections are terminated with a copper disc brazed over the ends. Before starting installation of the mains, be sure the unit has not developed a leak in transit by connecting a pressure 10 Unitary Products Group

ARRANGEMENT 1, 4, 8 OR 11 ARRANGEMENT 2, 6 OR 7 SEE NOTES A B C D SEE NOTES ARRANGEMENT 3, 5 OR 10 ARRANGEMENT 9 OR 12 SEE NOTES SEE NOTES C E NOTE: Since the motor mounting assembly cannot be secured to the panel with the blower openings, the motor cannot be installed in either of the normally recommended bottom positions. NOTES: 1. Shipping Location for the motor mounting plate on the mounting channels. 2. The motor cannot be mounted on the other side of the blower section because: A. The blower shaft does not extend far enough beyond the bearing on the opposite end to accommodate a pulley. B. The blowers on the are not centered and there is not enough space on the other side of the blower section to install a motor. If the motor must be located on the opposite end of the unit, the blower section should be rotated on the evaporator coil section. 3. The motor mounting plate cannot be moved to the opposite end of the mounting channel because: A. The channels do not have mounting slots on their opposite end. B. The contactor for the supply air blower motor is mounted between the channels on the end opposite the motor mounting plate. FIGURE 11 : MOTOR ARRANGEMENT LOCATIONS gauge to the service access port. If pressure still exits, the circuit may be considered leak free. If pressure does not exist, the unit must be evacuated along with the field installed refrigerant piping. NOTE:To minimize the possibility of system failure due to dirt and moisture, a filter-drier must be installed in each liquid line as close to the evaporator as possible. Filter-driers are not supplied with the evaporator blowers. They are supplied with the matching condensing units. Unitary Products Group 11

The temperature required to make or break a brazed joint is sufficiently high to cause oxidation of the copper unless an inert atmosphere is provided. DRY NITROGEN SHOULD FLOW THROUGH THE SYSTEM AT ALL TIMES WHEN HEAT IS BEING APPLIED AND UNTIL THE JOINT HAS COOLED. The liquid, suction and drain connections inside the unit must be piped to the outside. Refer to Figure 13 for unit dimensions or the locations and the dimensions of the access openings in the unit panel. Copper liquid and suction line elbows and plastic drain elbow with hose clamps are shipped with the unit for field installation. The refrigerant piping and the condensate drain can be connected from either end of unit. AFTER RECOVERING THE R-22 HOLDING CHARGE, USE A SMALL DRILL BIT TO PUNC- TURE SEALING CAPS AND DISCS BEFORE UNBRAZING TO PREVENT THE PRESSURE IN THE LINE FROM BLOWING THEM OFF. Begin the refrigerant mains by installing the liquid line from the condensing unit liquid stop valve to the evaporator liquid connection, maintaining a flow of nitrogen during all brazing operations. The filter-drier and sight glass must be located in this line, close to the evaporator. Make the suction line connection at the evaporator and run the line to the condensing unit. After puncturing the sealing caps with a small drill bit, unbraze the condensing unit suction disc and connect the line. Maintain a flow of nitrogen from the liquid valve access connection through the liquid line to the evaporator, through the evaporator, back to the condensing unit and out the suction valve access connection. The evaporator coil section is shipped with the side panels suitable for right hand piping connections when viewed from the return air end of the section. If left hand piping connections are required, the large and the small panels on the right side of the coil section can be interchanged with the single panel on the left side. The small panel has the holes for the refrigerant lines and the condensate drain line, and it is interchangeable for left hand or right hand piping connections. When left hand piping connections are installed, the suction line must be insulated to prevent moisture from condensing on it and being carried into the blower section. Grommets are supplied by the factory for field mounting in the holes provided in the narrow panel. These grommets are packed in the same carton with the other piping connections, and the carton is shipped in the unit's evaporator coil section. Remove the evaporator holding charge and any caps or discs on the liquid and suction connections that will not permit a free flow of nitrogen. EVAPORATOR SECTION PIPING Connect a supply of dry nitrogen through a reducing regulator to an access valve or charging tail. Choose a procedure that will allow nitrogen to flow continuously through the system and reach all joints to be brazed. THE LIQUID LINE SOLENOID VALVES ARE SHIPPED IN THE MANUALLY OPEN POSITION. AFTER BRAZING IS COMPRETED, CLOSE THE VALVES BY TURNING THE STEM CLOCKWISE. NOTE:Size the suction line outside the evaporator casing per the line sizing information provided in condensing unit instruction Form 550.13-N6Y. EXPANSION VALVE BULB The bulb for the first stage TX valve on each of these blower units is not factory-installed in its final location; it's only temporarily taped for shipment. It must be fastened in a 4 o'clock position to the common suction line out of the evaporator coil after piping connections are made. Use the bulb clamps from the bag tape to the suction connection inside the blower unit. SYSTEM ADJUSTMENT Refer to Table 8 and 9 to adjust air system. TWIN BELT DRIVE ADJUSTMENT Check to see if both belts drive at the same speed. Do this by making a mark across both belts. Turn the drive several revo- 12 Unitary Products Group

lutions by hand. If mark hasn't separated, the belts are traveling at the same speed. Twin groove blower motor pulleys should be installed with the shaft set screw (A) towards the motor (see Figure 12). B B If necessary to align pulleys, the housing of the twin groove motor pulley may extend 25% of its length beyond end of motor shaft. A E Always align twin groove pulleys using the stationary web. The blower motor pulleys are adjustable by half turns. Select required RPM from Table 8 and adjust pulley. Check belt tension. Drive packages are supplied with Fiberglass belts which must be properly tensioned at installation because they do not stretch. The belt should deflect 3/16" per foot of belt span with a 2 or 3-pound force. Alignment of the resilient motor mount can be corrected by adjustment at the slots on the end opposite the pulleys. D C C STATIONARY WEB FIGURE 12 : DOUBLE GROOVE PULLEY TABLE 6: ELECTRICAL DATA - SUPPLY MOTOR NOMINAL HP RATING POWER SUPPLY NAME PLATE AMPS LOCKED ROTOR AMPS MIN. WIRE SIZE 1, AWG MAX. WIRE LG. 2 MAX. FUSE SIZE AMPS AVAILABLE ON MODELS 208-3-60 13.6 86.0 12 135 25 5 230-3-60 13.4 85.0 12 150 25 Yes Yes 460-3-60 6.7 42.5 14 385 12 208-3-60 21.0 115.0 10 135 35 7.5 230-3-60 21.0 125.0 10 150 35 Yes Yes 460-3-60 10.5 62.5 14 245 20 208-3-60 25.0 145.0 8 175 40 10 230-3-60 25.0 157.0 8 195 40 Yes Yes 460-3-60 12.5 78.5 12 320 20 1. 2. Based on three 60 C, insulated copper conductors in steel conduit Based on a 80% power factor and a 3% voltage drop. ELECTRICAL CONNECTIONS Refer to matching condensing section wiring diagrams. Install a power supply to meet the requirements listed in Table 6. Install interconnecting control wiring between condensing section, evaporator blower and room thermostat. NOTE:For the 10 HP 200/208 volt motors, install the power wiring to the supply air blower through the starter. Provide a disconnect switch and fusing as required. Unitary Products Group 13

TABLE 7: ACCESSORY STATIC RESISTANCE, IWG 1 MAINTENANCE MODEL CFM NON-FREEZE 1-ROW STEAM COIL HOT WATER COIL 10000.05.08 11000.06.09 12000.07.10 13000.08.12 14000.10.14 13000.08.11 14500.09.13 16000.11.15 17500.13.17 19000.15.20 Filters must be cleaned or replaced as often as necessary to assure good air flow and filtering action. 1. To remove filters through the sides of the unit, remove either the solid side panel on the piping end, or the larger side panel on the end opposite the piping. 2. To remove filters from the front of the unit, loosen 2 screws and raise the top filter retainer. The upper filters can be lifted over the center filter lip. Three wing nuts are provided under the center filer retainer. Remove these and a part of the center filter support, giving access to the bottom filters. Drain pan(s) should be inspected regularly to assure proper drainage. The evaporator blower bearings and blower motor bearings are permanently lubricated. 1. Air cannot be returned through the base section accessory. TABLE 8: BLOWER MOTOR DATA UNIT MODEL MODEL NUMBER BLOWER RPM RANGE ADJUSTABLE MOTOR PULLEY PITCH DIA. (IN.) BORE (IN.) FIXED BLOWER PULLEY PITCH DIA. (IN.) BORE (IN.) QTY. BELTS PITCH LENGHT (IN.) DESIGNATION 1LD0415 636-795 4.0-5.0 11.0 1-3/16 11.0 2 63.3 A62 1LD0407 668-827 4.2-5.2 11.0 1-3/16 11.0 2 63.3 A62 1LD0408 827-986 5.2-6.2 11.0 1-3/16 11.0 2 59.7 A59 1LD0409 607-776 4.3-5.5 12.4 1-3/16 12.4 2 85.1 B84 1LD0410 776-917 5.5-6.5 12.4 1-3/16 12.4 2 86.8 B85 14 Unitary Products Group

TABLE 9: BLOWER DRIVE DATA MODEL MODEL # HP MODEL # FRAME SIZE VOLTAGE (3PH-60HZ) 1LD0415 5 2LR04605023 2LR04605032 184 208 230/460 1LD0407 7.5 2LR04607523 2LR04607532 213 208 230/460 1LD0408 10 2LP04610033 2LR04610032 215 208 230/460 1LD0409 7.5 1LD0410 10 2LR04607523 2LR04607532 2LP04610033 2LR04610032 213 215 208 230/460 208 230/460 Unitary Products Group 15

- 7! $ ), - 7 " & ) 1 4 7 6 ) 1 4 7 6 # & # & + ) 1 4 1 * 9-4 5 - + 6 1 0 /., + 7 6. 4 % &, 1 3 7 1, 2 1 2 1 / - - 5 5 * 6 6 2 ) -, # $ - 8 ) 2 4 ) 6 4 + 1 5 - + 6 1 ) 1 4 1 + 7 6. 4,, 4 ) 1 2 1 2 1 / + 7 6. 4 2, 5 7 + 6 1 2 1 2 1 / # & 2 ) - 6 0 - - 7 " & 0 ) 5 6 9 1 3 7 1, ), 6 9 5 7 + 6 1 + - + 6 1 5 ) *, # & * 6 6 # & + 7 6 2 ) -. 4 % &, 13 7 1, 2 12 1 / " & " "! " %! " 5 ) 5 1, - 2 ) -. 4-7 " & % & $ " # & + 7 6. 4 # &, 5 7 + 6 1 2 1 2 1 / # & + 7 6. 4 &,, 4 ) 1 2 12 1 / FIGURE 13 : UNIT DIMENSIONS TABLE 10: UNIT DIMENSIONS MODEL A B C D E F G H J K M N P 100-1/8 95-5/8 33-1/4 36-5/8 73-1/4 2-1/2 18-7/8 16-1/2 15-13/16 21-7/8 22-9/16 1 2-1/8 103-1/8 98-5/8 40-5/8 44 88 2-1/2 18-7/8 23-7/8 20-11/16 21-7/8 20-11/16 1-1/8 1-5/8 16 Unitary Products Group

TABLE 11: L*EU360 SUPPLY BLOWER PERFORMANCE 1 CFM RPM SP 2 BHP 3 KW SP 2 BHP 3 KW SP 2 BHP 3 KW SP 2 BHP 3 KW SP 2 BHP 3 KW 10,000 11,000 12,000 13,000 14,000 600 0.48 2.8 2.4 0.35 3.3 2.9 0.20 3.9 3.4 0.03 4.5 3.9 635 4 0.62 3.1 2.7 0.49 3.7 3.2 0.35 4.3 3.7 0.19 4.9 4.2 0.03 5.5 4.7 700 5 0.87 3.8 3.3 0.76 4.4 3.8 0.63 5.0 4.3 0.49 5.6 4.8 0.34 6.3 5.4 775 6 1.21 4.7 4.1 1.11 5.3 4.6 0.99 5.9 5.1 0.86 6.5 5.6 0.72 7.2 6.2 800 7 1.30 4.9 4.2 1.20 5.5 4.8 1.08 6.2 5.4 0.95 6.9 6.0 0.81 7.6 6.6 875 8 1.64 5.9 5.1 1.54 6.5 5.6 1.43 7.1 6.1 1.32 7.8 6.7 1.20 8.6 7.4 900 1.75 6.2 5.4 1.66 6.8 5.9 1.55 7.4 6.4 1.44 8.1 7.0 1.33 8.9 7.7 970 9 2.10 7.2 6.2 2.00 7.8 6.7 1.90 8.5 7.3 1.81 9.2 7.9 1.71 10.0 8.6 1000 2.25 7.6 6.6 2.15 8.2 7.1 2.06 8.8 7.6 1.97 9.5 8.2 1.88 10.4 9.0 1. Unit resistance is based on a wet evaporator coil and clean filters. 2. Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information. 3. Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heating device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP rating of the motor. 4. Min. speed for drive accessory 1LD0415. 5. Min. speed for drive accessory 1LD0414 6. Min. speed for drive accessory 1LD0408 7. Max. speed for drive accessory 1LD0415 8. Max. speed for drive accessory 1LD0414 9. Max. speed for drive accessory 1LD0406 Unitary Products Group 17

3.2 3.0 2.8 1000 RPM 2.6 900 RPM 10 BHP 2.4 TOTAL STATIC PRESSURE, IWG 2.2 2.0 1.8 1.6 1.4 1.2 1.0 800 RPM 700 RPM 600 RPM 2 BHP 3 BHP 5 BHP 4 BHP 6 BHP 8 BHP 0.8 0.6 500 RPM 0.4 0.2 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 CFM (X 100) Available external static pressure for unit accessories and the duct system. Internal unit resistance based on a wet cooling coil plus 1" throwaway filters. FIGURE 14 : BLOWER CURVE 18 Unitary Products Group

TABLE 12: L*EU480 SUPPLY BLOWER PERFORMANCE CFM RPM SP 1 BHP 2 KW SP 1 BHP 2 KW SP 1 BHP 2 KW SP 1 BHP 2 KW SP 1 BHP 2 KW 12,800 14,400 16,000 17,600 19,200 600 0.31 4.3 3.7 0.13 5.1 4.4 640 3 0.49 4.8 4.1 0.31 5.6 4.8 0.15 6.3 5.4 700 0.76 5.5 4.7 0.59 6.4 5.5 0.42 7.2 6.2 0.24 8.1 7.0 0.03 9.2 7.9 775 4 5 1.10 6.5 5.6 0.96 7.4 6.4 0.80 8.4 7.2 0.63 9.4 8.1 0.42 10.4 9.0 800 1.22 6.8 5.9 1.08 7.8 6.7 0.93 8.8 7.6 0.76 9.8 8.4 0.55 10.8 9.3 900 1.76 8.1 7.0 1.64 9.3 8.0 1.50 10.5 9.0 915 6 1.84 8.3 7.2 1.72 9.5 8.2 1.58 10.7 9.2 1. 2. 3. 4. 5. 6. Unit resistance is based on a wet evaporator coil and clean filters. Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information. Min. speed for drive accessory 1LD0409. Min. speed for drive accessory 1LD0410. Max. speed for drive accessory 1LD0409. Max. speed for drive accessory 1LD0410. Unitary Products Group 19

3.2 15 BHP 3.0 1000 RPM 2.8 2.6 12-1/2 BHP 2.4 TOTAL STATIC PRESSURE, IWG 2.2 2.0 1.8 1.6 1.4 1.2 1.0 900 RPM 800 RPM 700 RPM 600 RPM 5 BHP 6 BHP 8 BHP 10 BHP 0.8 0.6 500 RPM 0.4 0.2 0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 CFM (X 100) Available external static pressure for unit accessories and the duct system. Internal unit resistance based on a wet cooling coil plus 1" throwaway filters. FIGURE 15 : BLOWER CURVE Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group 1999. All rights reserved. Supersedes: (494) (199) Unitary 5005 Norman Product York OK Group Drive 73069