An Analysis of a New Type Refrigeration Cycle (MICLOSS)

Similar documents
Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Compressor Capacity Control: A New Direction

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

High Efficiency R-134a Compressor for Domestic Refrigerator

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Purdue e-pubs. Purdue University

System Using Exhaust Heat from Residential GHPs

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Autonomic Distributed Coordinative Control "F- VPM" for Multiple Air Conditioners with Concurrent Cooling and Heating Operation

Compressor Capacity Control

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

The Development of the Energy-Saving Technology by the Composition Control of R407C

A Study on Compression Characteristic of Wet Vapor Refrigerant

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Air-Cooled Heat Exchanger Performance for R410A

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

R32 Compressor for Air conditioning and Refrigeration applications in China

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Sub-Critical Operation of the CO2 Expander/ Compressor

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Design of Compressors to Meet the Performance Ranges Required for Residential Air Conditioning

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Efficiency of Non-Azeotropic Refrigerant Cycle

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Diagnosing Troubles in Refrigeration Units with Screw Compressors

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

An Experimental and Theoretical Study on System Performance of Refrigeration Cycle Using Alternative Refrigerants

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Dynamic Simulation of Liquid Chillers

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Low GWP Refrigerants for Air Conditioning Applications

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Study of R161 Refrigerant for Residential Airconditioning

Performance of CO2 Cycles with a Two-Stage Compressor

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Experimental Study of Two-phase Seperators for Vapor Compression Systems in Household Appliances

Characterization of Thermal Processes in Scroll Compressors

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Experimental Study on the Performance of Twisted Capillary Tube

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Two-Step Capacity Modulation of a Single Cylinder Compressor

September 11, 2012 Ministry of Economy, Trade and Industry

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Numerical Simulation of a New Cooling System for Commercial Aircrafts

The Refrigeration Cycle

Two-Phase Evaporation Pressure Drop Experimental Results for Low Refrigerant Mass Flux

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

The Refrigeration Cycle

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Optimization Study of Absorption/Compression Cooling Cycles

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Compressor Durability Tests and System Tests with AB and HFCs

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Transcription:

Purdue University Purdue e-pubs nternational Compressor Engineering Conference School of Mechanical Engineering 1982 An Analysis of a New Type Refrigeration Cycle (MCLOSS) F. Matsuoka Follow this and additional works at: http://docs.lib.purdue.edu/icec Matsuoka, F., An Analysis of a New Type Refrigeration Cycle (MCLOSS) (1982). nternational Compressor Engineering Conference. Paper 395. http://docs.lib.purdue.edu/icec/395 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

AN ANALYSS OF A NEW TYPE REFRGERATON CYCLE (MCLOSS) Fumio Matr;moka Consumer Products Research Laboratory Mitsubishi Electric Corporation Kamakura-shi, JAPAN L ABSTRACT We have developed a nw type refrigeration cycle, which has greatly enhanced the efficiency for refrigeration cold storage equipment, room ACs, refrigerators, display cases, and air conditioning equipment. The development of MCLOSS has aimed at improving the energy efficiency ratio (EER) during standard refrigerting or air conditioning equipment operation along with improving the SEER. Energy losses under compressor starting/ stopping are usually considered to amount to 20 or 25% of the total energy consumption. We conducted quantitative analyses of the operation of refrigeration cycles in connection with the lowering of the efficiency under nonsteady (transient) operating conditions, and as a result the following findings were made: The condition of the refreigerant under pressure - which corresponds to the refrigerating or air conditioning capacity of the compressor- undergoes a change when the compressor is stopped. When the compressor is restarted, there is a time lag before pressure r..eaches the required level for steady (norma1) operation. As a result, during this period of time the compres-. sor capacity is not fully utilized, and the subsequent loss of energy leads to a lowering of the machine efficiency. Subsequently, we moved to remedy this situation by developing a new refrigeration cycle which would reduce the period required for the pressure within the compressor to regain its 'prestop' level to a minimum. This new refrigeration cycle is a conventional cycle plus current cutoff and on/off elements (see Fig.l and Fig.Z). The operating principles are as follows: When the compressor is stopped, the current cutoff element and the on/off element combine to close the refrigerant circuit, thus dividing the refrigerant into high- and low-pressure segments and maintaining both at their 'pre-stop' levels. Concurrently, the current Cl!toff element connects the byp,ass circuit of the compressor to equalize the compressor's discharge (high) pressure with that of its suction (low) pressure. When the compressor is restarted, the discharge pressure builds up, but when it rises above the preset pressure value, the current cutoff again coses the bypass circuit, connecting the com7 pressor's discharge and suction segment, and opens the main refrig.erating circuit. At the same time, the on/off element opens the refrigerant circuit so as to return the compressor to its normal refrigeration cycle. 2. TEST EQUPMENT AND TEST CONDTONS The main merit of the new refrigeration cycle lies in the fact that with operation of the,compressor with repeated s-tart and stop, the pressure, the temperature, and the refrigerant distribution of the compresspr at the time of stop are in about the same as during operation, and accordingly, a valve has been installed to keep the distribution condition of the refrigerant gas and to prevent pressure balan_ce at the time of stop during the refrigeration cycle. n order to grasp and investigate the character +stics at the time of emergency stop, a small air conditioner with a built-in rotary compressor was used as the test equipment. The outline is shown in Fig.3. The symbol Pin Fig.4 shows the pressure measuring point. Testing was executed with the following three conditions for the compressor start and stop time. (a) Operation time: 3 min, stop time; 7 min (operation ratio: 30%) (b) Operation time: 5 min, stop time: 5 min ( (c) Operation time: 7 min, stop time: 3 min (operation ratio: 70%) Temperature measuring -was e'xecuted every 30 sec with copper-constantan thermocouples soldered to the return bends of the evaporator and condenser heat tranfe pipes in the middle in radial direction of the pipes. Fig.4 shows the measuring point for the evaporator. Small semiconductor pressure converters were us.ed for pr,essre measuring, anp recording was executed with a pen recorder via an amplifier. Fig.? shows the measuring p9ints. For the total input.of the air conditioner, a precision integrating 20$

wattmeter was used to measure the integrated value for the specified time. Fig. l Current cutoff element Fig. 2 On/off element Pressure gauge. Condenser- Ev-aporator Accumulator..,.., /f-+- 1. -J.-------------- -., On/ off element Return bend measuring position Fig. 3 Test equipment Fig. 4 Evaporator temperature measuring point 209

3. TEST RESULTS The measuring results for the time characteristic of temperature, pressure, and input at the time of compressor start and stop with use of the test equipment shown in Fig.3 for the conventional refrigeration cycle and the MCLOSS refrigeration cycle are shown in the following. The test air conditions were set to a constant temperature of 35 C for the condenser side and 27 C for the evaporator and a relative humidity of SO%, independent of compressor start and stop. (1) The values shown in the following were obtained for capacity, input, and EER at the time of compressor start and stop, and the EER of the MCLOSS refrigeration cycle has been improved by about 20%. (The values 1 shown in_ the table are relative values. Refrigeration Refrigeration nput EER cycle capacity Conventional 100 100 100 MCLOSS 111.7 92.7 120.4 (2) The time until steady state is reached is about 1 min with the MCLOSS cy.cle, while this is not reached by the conventional cycle even at the time 5 min before compressor stop (refer to Fig.5 and Fig.6). (3) The evaporator temperature distribution becomes constant for about 80 to 90% from the time of start for the MCLOSS refrigeration cycle, and it was found that the evaporator is used effectively (refer to Fig.5 and Fig.6). (4) n regard to the pressure characteristic, the conventional refrigeration cycle shows a pressure peak which can be taken as liquid compression on the high-pressure side and drawing in on the low-pressure.side, while this does not occur with the MCLOSS refrigeration cycle, which soon reaches a stable state (refer to Fig. 7 and Fig.8). 30.... Q) s 20....<...< 10., :>.,.. Q jl. nlet: 5 10 Directly before operation,( 15 20 1 Time Hat transfer pipe No. outlet Fig. 5 Temperature characteristic during compressor.. c.:>. E rl rl :> Fig. 6 2.0 30 20 operation (conventional refrigeration cycle, Directly before operation 10 r 0 1 nlet 5 Heat transfer pipe No. -out:l.et ltime Temperature characteristic during compressor operation (MCLOSS refrigeration cycle, operaion ratio: 50%} Pl 1..5 nput - ------ ; XlO 10. g 0.5 '\ P6 Time (min)_ Fig. 7 Pressure-input characteristic 10 (conventional refrigeration cycle, 0 210

4. ANALYSS MODEL AND RESULTS The time changes for the local heat flux ai: the local flow quality Xk: the local refrigerant distribution amount Gk: the local density k: and the_local void fraction fgk: were analyzed from the measuring results for the above evaporator pipe wall temperatures and the inlet and outlet pressures. 4.1 Local heat flux ai Friction resistance coefficient A A 0.316 Re- 0 25 Re: Reynold's number Re u (do- 2) /v v : Kinematic viscosity wg/y 1-1 vmlo- x) +vg x vt : Liquid viscosity ).lg : Vapor viscosity Correction item 1.0 + 1.0//X + 1.0/x x Cvt/).lg) 0 1 Cpsg/pst) 0 5 [(1.0- x)/x) 0 9 psg: Vapor density ps2: Liquid density Pipe outside: Pipe wall Pipe inside : Qk Aok ao (To- Tek) Qk Aok A (Tek- Teik)/p Qk Aik aik (Teik- Terr) Aok x do tk Aik (do-2d) tk ao Outer surface heat flux aik Local heat flux in the pipe Correction coefficient This correction coefficient is the correction coefficient includes the various pressure losses from bends in the piping, oil influence, refrigerant flow pattern, etc. 4.2 Local flow guality xk Circulation flow G G hi: nlet enthalphy ho: Outlet enthalpy Local enthalpy hk hk Qk/G +hk- 1 Xk (hk-hst)/(hsg-hst) from hsg f(pr, Terr) and hst f(pr, Terr) Here, Terr is the saturation of Pr. hsg: Saturated gas enthalpy hst: Saturated liquid enthalpy 4.3 Local density yk 4.4 4.5 yk 1/(Xk Vsg + (1 - Xk) Vst) from the specific volume Vsg of the saturated gas at Pk, the specific volume Vst of the saturated liquid, and Xk. Local void fraction fgk fgk (1.0 + (1.0/Xk - 1.0) S yg/yt) with s (yt/yg)l/3 Local refrigerant volume Gk Gk x d 2 tk/4 [fgk/vsg + (1.0- fgk) /Vst] -1 2.0 1.5 2 H :;1.!:: 1.0 10 XlO g o.s ) P6 Fig. 8 0 0 5 10 Time (min) Pressure-input characteristic (MCLOSS refrigeration cycle, 5 :;1 4.6 Local pressure drop Fk The local pressure drop is obtained from the following formula. Fk [1.0/(do- 2p) A' u 2 /(2 0 g v) l0-4 ] (; 2k Fk Local pressure drop A' Corrected friction resistance coefficient u g v Flow speed Newton's constant Specific volume Correction coefficient. 1-----------------------1 1--> 0 00 @ 0 Fig. 9 Evaporator temperature measurement point model Corrected friction resistance coefficient A 1 A' A Vst (1.0- x/ 75 q,2; [Vsg x + (1.0- x) Vst] A Friction resistance coefficient X Correction item Flow quality Fig. 10 Heat exchanger model 211

Analysis results The time characteristics for the local heat echange and heat transfer rates for the conventional refrigeration cycle and the MCLOSS refrigeration cycle are shown in Fig.ll to Fig.l4. The plot numbers in the figures indicate the data at intervals of 30 sec. and increasing numbers indicate a longer elapsed time from the start time. The plot number 1 indicates an elapsed time of 17 sec from the time of start. As shown in Fig.ll and Fig.l2, the characteristic for the local heat echange differs considerably, where the heat exchange amount of latter half of the evaporator decreases considerably for the conventional refrigeration cycle, while the entire evaporator executes uniform heat echange with the MCLOSS refrigeration cycle, and the volume also is larger. n regard to the local heat transfer characteristic, the operation of the evaporator with the MCLOSS refrigeration cycle is large and with good efficiency for nearly the entire operation. With the conventional refrigeration cycle, it is already small and the dry point is reached at the halfway point. The flow quality of this point is estimated to be about 0.7 to 0.8. The local void fraction is about 0.8 near the evaporator inlet (flow quality 0.25) when the local slip ratio derived-theoretically from Zivi is used. The analysis results for the local refrigerant amounts show that the total refrigerant amount directly before stop of the compressor is increased by about 10% at the time of the MCLOSS refrigeration cycle. 5. CONCLUSON n regard to the MCLOSS refrigeration cycle with improved efficiency for the not steady state of the refrigeration cycle, the characteristics of a small air conditioner with a built-in rotary compressor have been introduced in comparison with the conventional refrigeration cycle, and it has been reported, that the efficiency and the characteristics have been improved, and it is believed that increased efficiency also can be reached for other refrigeration and air conditioning equipment. REFERENCE LTERATURE (1) F.J. Moody: Trans. ASME (1965-2) (2) G.L. Wedekind and B.T. Beck: nt. Heat Transfer cont 5[4] (1974) (3) Saito: Refrigeration 47 [542] (4) Zivi: ASME Journal of Heat Transfer. 247 (1964-5), Fig. 11 90 60 ;;..-<.,.., 30 1 5 10 1 5 ;w Evaporator pip., No. Local heat echange time characteristic (conventional refrigeration cycle, 1 5 10 15 20 Evaporator pip., No. Fig. 12 Local heat exchange time characteristic g..-< 20 10 '-' XlO (MCLOSS refrigeration cycle, operation ratio: 50%) 0 1 5 10 15 20 Evaporator. pipe No. Fig. 13 Local heat ttansfer rate time characteristic _..., 2- :;1..-<.,... Q) 20 10 XlO l. (conventional re-frigeration cycle, operation ratio: 50%) Fig. 0 14 1 Evapol'ator '['pe No Local heat transfer rate time characteristic (MCLOSS refrigeration cycle, operation ratio: 50%) 212