Fire damper ETPR Instructions for Installation, Operation and Maintenance 10/2016

Similar documents
CE-marked ESAD - Smoke Control Duct System Installation instructions 08/2013

VL120. Multi blade smoke evacuation damper 120' C-NT-V24-A 01/2016

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU

Circular Fire Damper Cartridge

Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU

Fire dampers. For diverse applications

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Prodotti > Protezione dal fuoco e dal fumo > Serranda tagliafuoco > Type FK-EU

Fire/Smoke damper EKO-SRBG2

BSK-RPR Fire Damper. Additional operating instructions according to

Bevent Rasch BSKC6. - Fire /06/17

ESAR SMOKE CONTROL DAMPER» TECHNICAL CATALOGUE

Supply air unit VEKA Installation & Maintenance

Smoke Master SMIA Compact pressurisation and smoke exhaust system

BKA-EN Fire Damper. Additional operating instructions according to

Smoke extract fan SMHA HATCH

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

GLEB Kitchen exhaust fan

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

Instructions for the BASIC BCRW Fan, Sizes General

Kezdőlap > Termékek > Tűz és füst elleni védelem > Füstmentesítő csappantyúk > Típus EK-EU. Típus EK-EU

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

DUCTGARD. Duct Mounting Smoke and Fire Control Dampers

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

TEKNISK DOKUMENTATION VENTILATION BG BURCHARTH A/S

ACN SMOKE INSTALLATION AND MAINTENANCE

Part # Page Dampers Supported Directly From Structure 5. Dampers Supported From Ductwork Above 4

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Type EK-EU FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND AS AN ADDITIONAL SUPPLY AIR INLET, ALSO FOR NATURAL SMOKE AND HEAT EXHAUST SYSTEMS

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to

Original instructions. Panther 6-15 kw

SD119 Range of Conventional Smoke and Smoke/Heat Detectors (refer to attached appendix for details and conditions)

Fire damper DESIGN GENERAL FIRE CELL DIVISION DISTRIBUTION OF RESPONSIBILITIES FIRE PROTECTION DOCUMENTATION HAGAB FIRE DAMPER DESIGN

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE

F O C U S D O O R C L O S E R S

AZN ATEX INSTALLATION AND MAINTENANCE


GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

WH45 DECLARATION OF PERFORMANCE (D.O.P.) PRESTATIEVERKLARING GEPATENTEERDE BRANDKLEP RONDE SERIE WH45

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

CE Unit is suitable for material transport. The transported gas may be up to 80 C.

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions

Bevent Rasch RABC-VAV. - Fire /03/2018

TopMaster Air Handling unit. Technical data

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

Guidance Note No 21/1. CE Marking Windows and doorsets to BS EN 16034

Units for suspended ceilings

Installation and operating instructions

Smart Smart IR. Service instruction SALES DATE MANUFACTURED ON (DATE): APPROVAL MARK SOLD. model (check applicable) is recognized as serviceable

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

HEAT RECOVERY AIR HANDLING UNIT

TopMaster Air Handling Unit

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

TopMaster Air Handling unit. Installation instructions

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

SECTION AIR DUCT ACCESSORIES

Topvex SF02-SF12 Air Handling Unit

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

LX-5 FIRE DAMPER. EI 120 (ve ho i o) S EN A1:2010. Damper tightness class: 4 EN 1751:2002. Casing tightness class: C. Fulfils requirements

Declaration of performance ( DoP ) :

Life Safety Dampers Selection and Application Manual

Installation instruction

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

DECLARATION OF PERFORMANCE

Fire protection unit

CE Marking for Fire Resistant doors. The future EN Agustín Garzón Cabrerizo Technical Director Fire Resistance Lab.

EDD61 & EDD91 Extractors

Ceiling diffusers. Type DLQL

Technical information. Remeha P200. Pressurized boiler. Heat output: kw

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

Intumescent Fire Dampers

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

Cooper Lighting & Safety Limited Wheatley Hall Road, Doncaster, DN2 4NB, United Kingdom

DECLARATION OF PERFORMANCE

HULME MARTIN HEAT SEALERS

Installation instruction

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

FSD-TD Series. Fire and Smoke Dampers B RITAI N. LPCB certificated fire dampers (LPS 1162)

3480/RCH SERIES INSTALLATION INSTRUCTIONS

Able to respond to smoke alarms for the protection of escape routes and areas with sleeping risk (ADB)

Smoke Master SMPA Installation, operation and maintenance

iq Star LYRA II chilled beam cassette

breeze easytm model # F100-1W

Original instructions AR

CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE

Cooling Strip Model SPB

FIREPRO SoftSeal System

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL

EUROPEAN TECHNICAL ASSESSMENT

Smoke Master SMPA Compact pressurisation system

Transcription:

Instructions for Installation, Operation and aintenance 10/2016 Installation Fire damper ETPR must be installed according to this installation manual, see pages 2-5. Operation and function testing According to CE marking, a fire damper must always be equipped with a tripping mechanism based on temperature. Fire dampers can be delivered equipped with either a fuse mechanism or an actuator. ETPR motorized fire dampers may additionally be linked to a smoke detection based tripping mechanism. A tripping system based on smoke detection is easy to install using FläktWoods FICO control and monitoring system. The FICO system can also be used for automatic function tests of fire dampers. The function testing for the motorized damper can be performed by cutting off the power supply by using the switch of the thermal trip connected to the motor. The spring will then close the damper. The function testing can also be done by means of the control and monitoring system FICO, either manually or automatically. The recommended automatic function testing interval for the motorized damper is 48 hours. The operation of the fuse mechanism is tested by pushing the red test button the spring will close the blade. Beware of the reset handle as it will rotate rapidly during test operation. To reset the mechanism, turn the handle until the mechanism clicks. aintenance The function testing interval is always determined separately for each building, but testing must be carried out at least twice a year according to product standard EN 15650:2010 (see example of check list beside). WARNING! Never put your hands inside the damper while it is closing. Clean the fire damper by means of a vacuum cleaner. Avoid chemical cleaning agents. Spare parts Actuator: see type specification on the actuator. Fuse part ETFF-99-01 Fuse part replacement, see page 7. aintenance Check List: Fire damper reference Date of inspection Check actuator wiring for damage (where applicable) Check end-switch wiring for damage (where applicable) Check fire damper cleanliness and clean where necessary Check the condition of blades and seals, rectify and report where necessary Confirm the safety closure operation of the fire damper according to the manufacturer s instructions Confirm operation of damper to OPEN and CLOSE by use of the control system and physical observation of the fire damper, rectify and report where necessary Confirm operation of OPEN and CLOSED end-switches, rectify and report where necessary Confirm that the fire damper fullfills its function as a part of the control system (where applicable) Confirm that the fire damper is left in its normal working position NOTE! A fire damper is usually part of a system. As this is the case, the whole system should be checked as governed by the operation and maintenance requirements for the system.

Installation into building elements with fire classification EI 60 (Ø100 - Ø630) S ØD ØD 100 mm Figure 1 Figure 2 116 mm S 120 mm/ 140 mm (Ø100-400/ Ø500-630) 200 mm Figure 3 Figure 4 Fläkt Woods 9938 EN 2016.10 2 All rights reserved.

Installation of fire damper into rigid building elements (walls and intermediate floors) with fire classification EI 60 and into floors with fire classification EI 90 (Fig. 1 and Fig. 4) 1. Installation opening in the rigid wall or intermediate floor must comply with the dimensions given in the table below. Size ØD (mm) 100 125 150 160 200 250 300 315 400 500 630 Installation opening Ø (mm) 175 195 175 195 200 220 210 230 250 270 300 320 350 370 365 385 450 470 550 570 680 700 2. The fire damper blade must be closed during installation. 3. Place the circular duct centrally in the opening. 4. Place the fire damper in the duct so, that the damper flange rests against the building element. Use screws of sufficient length (e.g. 6 x 40 mm), which are suited for rigid construction, to fasten the damper to the building element through the bendable brackets on the flange. The damper must be fastened at 4 brackets at the minimum. The blade shaft can be placed in any position. 5. Completely fill the gap between the duct and the building element using incombustible, rock based, fine-grained gypsum or concrete cast. Protect the damper whilst infilling. 6. Check the functioning of the fire damper and proper movement of the blade. Clean the damper, if necessary. Place plastic covers on the openings and keep them covered, until ducts are connected to the damper. 7. To reset the fuse mechanism: Turn the handle towards the OPEN position until the mechanism clicks and the blade locks into position. 8. anual function testing of the motorized fire damper can be performed with the tool delivered with the actuator. When connected to a power supply, function testing is done by using the switch of the thermal trip. NOTE! If you open the damper blade manually with the tool, be sure to release the damper back to the closed position before switching on power. 9. Connect ducts to the damper according to the instructions provided by the designer and the manufacturer. Use rivets of sufficient length (e.g. DIN Installation of fire damper into flexible building elements (gypsum board walls or similar) with fire classification EI 60 (Fig. 2 and Fig. 3) 1. Installation opening in the flexible wall must comply with the dimensions given in the table below. Size ØD (mm) 100 125 150 160 200 250 300 315 400 500 630 Installation opening Ø (mm) 135 137 135 137 160 162 170 172 210 212 260 262 310 312 325 327 410 412 510 512 640 642 2. The fire damper blade must be closed during installation. 3. Place the circular duct in the opening. 4. Fill the gap S between duct and wall opening on both sides by using fire-resistant mass. 5. Place the fire damper in the circular duct so, that the damper flange rests against building element. Use screws or anchors suited for gypsum board walls to fasten the damper to the building element through the bendable brackets on the flange. The damper must be fastened at 4 brackets at the minimum. The blade shaft can be placed in any position. 7337 4x10 or shorter) to lock fire damper to the duct. Note! Always check that damper blade can rotate freely and rivets/screws are out of the way. Access panel should be placed next to the fire damper to enable necessary cleaning and inspection. Suspend the ducts according to instructions from the manufacturer and ensure that the ductwork does not cause any load on the damper installation. 10. If the fire damper is used as an air transfer or air terminal device, it must be equipped with a protective grille. The distance between the grille and the damper blade in the open position must be at least 30 mm. In case of large fire dampers, an extension piece must be installed between the grille and the damper blade. A circular duct of suitable length can be used as an extension piece. 11. When dampers are to be mounted next to one another, the distance between the dampers should be 200 mm (Figure 4). Fläkt Woods 9938 EN 2016.10 3 All rights reserved.

Installation outside building elements with fire classification EI 60 (Ø100 - Ø630) 2 1 100 mm ØD Figure 5 S 1 2 Figure 7 116 mm ØD Figure 6 Fläkt Woods 9938 EN 2016.10 4 All rights reserved.

Installation of fire damper outside building elements with fire classification EI 60 (Fig. 5-7) 1. Install the duct in the usual manner so that it penetrates the building element, and seal the openings ( or S) using an approved method. 2. Connect damper to duct according to the instructions provided by the designer or manufacturer. Use rivets of sufficient length (e.g. DIN 7337 4x10 or shorter) to lock fire damper to the duct. Note! Always check that damper blade can rotate freely and rivets/screws are out of the way. Access panel should be installed next to the damper to enable necessary cleaning and inspection. 3. Support the duct installation so that there is no extra load on the fire damper. In horizontal installation use hangers (1) and in vertical use shaft hangers (2) or other approved methods to stabilize the damper (Figures 5-7). 4. Insulate the duct between wall and fire damper flange as shown in figures 5-7, so that the fire classification EI 60 is met. 5. Check the functioning of the fire damper and proper moving of the blade. Clean the damper, if necessary. Place plastic covers on the openings and keep them covered, until ducts are connected to the damper. 6. To reset the fuse mechanism: Turn the handle towards the OPEN position until the mechanism clicks and the blade locks into position. 7. anual function testing of the motorized fire damper can be performed with the tool delivered with the actuator. When connected to a power supply, function testing is done by using the switch of the thermal trip. NOTE! If you open the damper blade manually with the tool, be sure to release the damper back to the closed position before switching on power. 8. The fixings used to secure the fire damper and ventilation duct must have a fire resisting capacity that is at least as high as the fire classification of the penetrated building element (the fire resistance rating of a class EI 60 element is R 60, etc.). 9. If the fire damper is used as an air transfer or air terminal device, it must be equipped with a protective grille. The distance between the grille and the damper blade in the open position must be at least 30 mm. In case of large fire dampers, an extension piece must be installed between the grille and the damper blade. Fläkt Woods 9938 EN 2016.10 5 All rights reserved.

Electrical wiring for motorized fire damper Only a trained electrician is allowed to perform the electrical wiring according to separate drawings and wiring diagrams. Wiring diagram for fire damper actuator is shown below. Power supply AC 230 V AC 24 V DC 24 V ~ T Status data of limit switches 1 2 S1 S2 S3 S4 S5 S6 < 5 < 80 Thermal trip Tf1 Tf2 Tf3 LED icroswitch wiring for fuse mechanism operated fire damper The microswitch does not affect fire damper triggering, it just indicates the position of the fire damper blade. The fire damper closes when the thermal trip activates. Status data from the microswitch can be provided from two microswitches (open/close). Proper functioning of the microswitch must be checked and proper indication verified. Electric specification: Operating temperature -25 C... +70 C I max = 0,1 A U max = 30 V (AC/DC) 5 Wiring diagram for microswitch Wiring digram shows the situation where damper blade is in closed position and microswitch (0 ) is activated. 1 2 3 4 5 6 0 90 1 2 3 4 5 6 2 1 4 1 Test button 2 Cover 3 Cable clamp 4 icroswitches (under cover) 5 Handle 2 3 Figure 8. Figure 9. Fläkt Woods 9938 EN 2016.10 6 All rights reserved.

Replacing fuse part ETFF-99-01 1. Release the mechanism with the test button (1) close the fire damper. Figure 10. 2. Remove the fuse part mounting screw (6). Figure 11. 3. Holding the test button, pull out the complete fuse part (7). Figure 12. 4. Correctly install the new fuse part and fasten it with the screw (6). 5. Test the function of the product and reset the fire damper. Turn the handle towards the OPEN position until the mechanism clicks and the blade locks into OPEN position. To test the operation of the fuse mechanism, push the red test button (1) the spring should close the blade. Beware of the turning reset handle! 6 1 Figure 10. 6 Figure 11. 7 6 Figure 12. Fläkt Woods 9938 EN 2016.10 7 All rights reserved.

DECLARATION OF PERFORANCE No. 013CPR2013-07-01 1. Product: Fire Damper ETPR 2. Intended use: Fire damper to be used in conjunction with fire separating elements to maintain fire compartmentation 3. anufacturer: Fläkt Woods Oy, Kalevantie 39, FI-20520 Turku, Finland Tel. +358204423000, Email: info.fi@flaktwoods.com 4. System of AVCP: System 1 5. Harmonized standard: SFS-EN 15650:2010 6. Notified Body: SP Technical Research Institute of Sweden, Nr. 0402 Performed determination the product type on the basis of type testing; initial inspection of the manufacturing plant and of factory production control; continuous surveillance, assessment and evaluation of the factory production control (FPC) under system 1 and issued: Certificate of constancy of performance - 0402-CPR-SC0423-16. 7. Declared performance: Essential characteristics Nominal activation conditions/sensitivity: sensing element load bearing capacity sensing element response temperature Response delay (response time): closure time Operational reliability: cycling Fire resistance (300 Pa): Pass Pass Pass (50 cycles) Installation in flexible wall Installation in rigid wall Performance Installation in rigid floor Installation remote of wall/floor integrity E 90 E 120 E 120 E 60 insulation EI 60 EI 60 EI 60, EI 90 EI 60 smoke leakage EI 60 S, E 90 S EI 60 S, E 120 S EI 60 S, EI 90 S, EI 60 S E 120 S mechanical stability (under E) Pass Pass Pass Pass maintenance of the cross section (under E) Pass Pass Pass Pass Durability of response delay: sensing element response to temperature and load bearing capacity Pass Durability of operational reliability: Actuator 10 200 cycles Pass open and closing cycle tests The performance of the product identified above is in conformity with the set of declared performance. This declaration of performance is issued, in accordance with Regulation (EU) No 305/2011, under the sole responsibility of the manufacturer identified above. Signed for and on behalf of the manufacturer by: Jari Hokkanen, R&D anager Turku 12.9.2016... Fläkt Woods Oy Kalevantie 39 FI-20520 Turku Tel. +358 20 442 3000 Fax +358 20 442 3010 ETPR Installation 9938 GB 2016.10