DSA Change Order Submission Program. May 27, 2011

Similar documents
PLAN REVIEW SUBMITTAL GUIDE

Facilities Procedure for Accessibility or Compliance Related Requests:

H BUTCH BROWNING FIRE MARSHAL BUILDING REHABILITATION

Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

New Construction Fire Inspection Process

Garfield Elementary School Feasibility Study for New Library Building Project Number A C

New School Construction: Safe School Opening. OAR and IOR Joint Training February 17, 2005

Commercial Remodel/ Add On Rules and Regulations

Brighton Area Fire Authority

Commercial Rules and Regulations

Number of persons with a disability that live with a disability in your community?

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

YORK COUNTY DEPARTMENT OF FIRE SAFETY BUILDING PLAN REVIEW REQUIREMENTS

Residential Accessibility Checklist - for Unit Types A and B With Connecticut Amendments Type A Units Accessibility Requirements rev.

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

For additional information regarding R-3.1 residential care facilities please contact (951)

SECTION WET-PIPE SPRINKLER SYSTEMS

Abbreviated Accessibility Checklist (Reception, Telephones, and Emergency Procedures) Reception Telephones

S000 SITE REVIEW APPR NO. FIRE CODE COMPLIANCE ITEM

FIRE SPRINKLER SYSTEMS POLICY

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

FIRE AND SAFETY PROJECT REVIEW REPORT

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

FIRE & LIFE SAFTEY STANDARD

FIRE SPRINKLER SYSTEMS POLICY

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

WEST VIRGINIA UNIVERSITY

HIGH-RISE RETROFIT ORDINANCES - NO and NO

TAMARAC FIRE RESCUE DEPARTMENT FIRE PREVENTION BUREAU 6000 North Hiatus Road Tamarac, Florida Telephone: (954) , Fax: (954)

LANDSCAPE AND IRRIGATION PLAN PREPARATION GUIDELINES

Access Aisle (Van) (Flow Test) Water Mains (Location & Sizes) Building Entrances. Building, Facilities, Element. Curb Ramps (Built-up)

MULTI-LEVEL & COVERED BOOTH CONDITIONS

Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region

Bold items are particular to the City of Euless

ADA Checklist Transient Lodging, Hotels, Motels, Inns, Boarding Houses, Dormitories and similar facilities

SECTION : FIRE ALARM & DETECTION SYSTEMS

Port of St Helens SIA Aircraft Hanger Scappoose, OR

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Community Development Department Commercial Permit Application

Thursday, February 28, :15 a.m. - 11:15 a.m. Sacramento Convention Center Room # 306. Workshop #47. DSA Academy Update

NFPA 80 Overview January 21, 2016

Residential-based Care Facility R-4 Guideline

INITIAL FIRE SAFETY ASSESSMENT

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Denver Fire Department Fire Prevention Division

Interior signs are an extension of the exterior sign system and their content and design should take this into consideration.

ALABAMA. Downloaded

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

CITY OF FARMINGTON 800 Municipal Drive Farmington, NM (505) Fax (505)

APPENDIX H (DESIGN SUBMISSION CRITERIA)

Developing a Healthcare Facility Fire Door Inspection Program

El Reno Fire Department Fire Alarm Plan Review Worksheet

CHAPTER 7 ALTERATIONS LEVEL

PUBLIC HEARING May 18, 2010 SUMMARY AND RECOMMENDATION

DESIGN & CONSTRUCTION GUIDELINES

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

Commercial Application/Plan Review Submittal Checklist

INTERIOR FINISH REVIEW

Plot # R019A ± 74' ± 74' ± 65' Plot # R019A LEASE OUTLINE DRAWING GROSS LEASABLE AREA ± 4,631 S.F. DEMISING FRONT WIDTH DEPTH ± 13' ± 32' Lease Line

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

DIVISION 08 OPENINGS HARDWARE AND KEYING PART 1 - GENERAL 1.01 SUMMARY

Construction and Development Guide

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

SPRINKLER PROTECTION OF COMBUSTIBLE CONCEALLED SPACES WITH LESS THAN 6 BETWEEN OPPOSITE FACES IN CAVITY.

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Use a minimum loading pad 6' curb length of a hard surface to connecting curb and sidewalk.

1-300 Fire and/or Smoke Dampers to Inspect $ Fire and/or Smoke Dampers to Inspect $34.30

Fire Rated Door Assemblies: Compliant Designs

Edward Jenner Elementary Academy of the Arts

Richard Henry Lee Elementary School

INITIAL FIRE SAFETY ASSESSMENT

Aging-In-Place Remodeling Checklist

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

PALO ALTO HIGH SCHOOL. Palo Alto Unified School District SCHEMATIC DESIGN TO DESIGN DEVELOPMENT TRANSITION MEETING. 21 January 2010, 12:30pm-2:00pm

Unit # 1038 ± 900 SF Width ± 15' Depth ± 60'

LOS ANGELES UNIFIED SCHOOL DISTRICT OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY PROCEDURE

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

To provide the requirements needed for Care Facilities Having 6 or Fewer Clients. This occupancy is classified as an R-3.1.

PARKLET PROPOSAL PACKAGE & PROCESS

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

Chapter 2: Definitions

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

Residential Based Care Facility Guidelines

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

MONTECITO FIRE PROTECTION DISTRICT

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

2.11 Submittal Guidelines for Emergency Evacuation Signs (2016)

CITY OF PASADENA FIRE DEPARTMENT

BCBC 2012 CHANGES TO PART 3

Transcription:

DSA Change Order Submission Program May 27, 2011

Improving the Quality of DSA Change Order Submissions Introduction Overview LAUSD Steven Hooper, PE Access Compliance David Stuber, CASp Fire & Life Safety Structural Safety Administrative Glenn Janes Dr. Hassan Sassi, PE, SECB Steven Hooper, PE Ryan Guerrero

Shared Knowledge Leverage the CCT QA Experience Improve Overall Quality of DSA Submissions Enable DSA Plan Check Efficiency

Shared Knowledge Think Like a Plan Checker Access Compliance, Fire and Life Safety, and Structural Safety Common CO Deficiencies DSA CO Submission Requirements Reference Documents

Summary of CO Review Items by Category 5,200 Total Change Orders

Summary of CO Review Items by Category 3,500 Modernization Change Orders

Summary of CO Review Items by Category 1,700 New Construction Change Orders

DSA Approval Rating Full CCT QA Process

Shared Knowledge

Shared Knowledge Reference Documents are posted to the HUB...

Shared Knowledge Reference Documents: DSA Stickers Owen Group Typical Comments DSA Access Resources List LAUSD QA/QC s Most Frequently Recurring Comments LAUSD Checklist DSA IR A-6 Question Addenda

Think Like a Plan Checker 1. Provide enough information to answer all required questions. 2. Don t make the Plan Checker guess. 3. Provide information to exclude reviews that are not necessary (watch for trigger words). 4. Provide a complete explanation/narrative. 5. Include sketches, as necessary. 6. Provide approved plans for reference.

Shared Knowledge Common Change Order Deficiencies Access Compliance Fire & Life Safety Structural Safety Administrative

Change Order Category Access Compliance ( ACS ) David Stuber, CASp

Access Compliance Top 10 Topics 1. Path of Travel ( POT ) 2. Parking Layout 3. Ramps/Stairs and Railings 4. Restroom-related Work 5. Counters and Casework 6. Drinking Fountains 7. Grading and Re-grading 8. Doors/Gates/Hardware 9. Furnishings and Equipment 10.Signage

1.1 Path of Travel Q. What is DSA looking for? A. DSA ACS Checklist 3 - Item 3.3 Fullydefined Path of Travel ( POT ). POT from Accessible Parking to Campus Main Entrance POT from Main Entrance to Fully-accessible Compliant Toilet Facilities POT throughout Entire Campus to Classrooms, Laboratories, Shops, Athletic Facilities, and Food Services POT from public right-of-way to campus main entry

1.2 Path of Travel Show POT from Public Right-of- Way to Campus Main Entrance Indicate POT with Heavy Dashed Line POT from Accessible Parking to Campus Entry

1.3 Path of Travel Show POT from Entrance to Accessible Restrooms POT throughout Campus: 1. Classrooms and Athletic Facilities 2. Safe Dispersal Area 3. Food Services

2.1 Parking Layout Q. What is DSA looking for? A. Layout Access Compliant Spaces: Total Number of Parking Spaces Required Number of Accessible Spaces Number of Van Accessible Spaces Compliant Signage Slopes Not-to-Exceed 2% in Any Direction Loading Areas/Access Aisles Curb Ramps/Flush Transitions

2.2 Parking Layout Show Provide and Reference Details Fully Dimension Accessible Parking Space Label Maximum Slope Not-to- Exceed 2% in Any Direction Label Pavement Markings Accessible Signage Wheel Stops or Curb

3.1 Ramps/Stairs and Railings Q. What is required to be shown? A. Ramps/stairs and railings. Ramps Fully-dimensioned and annotated drawings. Indicate spot elevations. Correctly calculate slope. Compliant handrails. Stairs Fully-dimensioned and annotated drawings. Indicate spot elevations. Correctly calculate rise and run. Compliant handrails. Railings Guards, handrails, extensions, diameter, clearances, heights.

3.2 Ramps/Stairs and Railings Case Study #1 Provide missing dimension for mid-landing (long dimension). Lower Ramp Section: provide correct length or height differential. As shown, slope significantly exceeds 1:12.

3.3 Ramps/Stairs and Railings Case Study #1 For pedestrian ramp, coordinate changes in level/rise on crosssection. Provide spot elevations top, intermediate and bottom landings. Provide missing dimension for length of ramps and all landings. Ramp sections: provide correct length or height differential not exceeding 1:12 slope.

3.4 Ramps/Stairs and Railings Case Study #1 Dimension indicates 1'-0 (12 ) typical for each handrail extension. Extension not provided at inside handrail. Each leg of pedestrian ramp shall have the minimum required handrail extension before turning.

3.5 Ramps/Stairs and Railings Case Study #1 Provide and reference As Approved sketches to indicate access compliant details. Provide handrail dimensions and notes including: diameter, wall clearance, smooth welds, mounting heights and extensions. If any changes, then provide and reference Revised sketches to show access compliance. Show Handrails as required on both sides of stairs. Provide all necessary dimensions.

3.6 Ramps/Stairs and Railings Case Study #1 Correctly calculate changes between levels. Correctly calculate Rise and Run. Construction tolerances for riser differential shall not exceed 3/8. Indicate radius for each nosing shall be maximum of 1/2. At sections, dimension handrail mounting height. Show required warning stripe at top approach and each tread: maximum 1" from nosing; 2" to 4" wide of contrasting color.

4.1 Restroom Related Work Q. What is DSA looking for? A. Layout Access Compliant Restrooms: Access Compliant Plumbing Fixtures Access Compliant Accessories Fully-Dimensioned and Annotated Drawings Dimension Required Clearances

4.2 Restroom Related Work Show Fully Dimension Restroom Dimension Required Clearances Dimension Grab Bars Clear Space at Lavatories and Change Tables Dimension All Mounting Heights Clear Opening Requirements

5.1 Counters and Casework Q. What is required to be shown? A. Counters and casework. Counters Fully Dimensioned Plans, Sections & Details. Correctly Indicate Clearances & Mounting Heights Casework Fully Dimensioned Plans, Sections & Details. Correctly Indicate Hardware, Reach Dims and Accessible Features

5.2 Counters and Casework Case Study #1 Clarify all countertop support clearances. Dimension 30" minimum clear width required. Dimension countertop at 2'-10 (34 ) maximum AFF. Dimension knee clearance shall be 2'-3 (27") minimum AFF. Clarify use of countertop: if used for printers, non-computer /computer workstations, or other, show minimum 5.0% or minimum 1 of each type shall be accessible. Show 36 x48" clear floor space on plan.

5.3 Counters and Casework Case Study #1 Opening hardware on cabinet doors; indicate type and specific mounting height AFF. HW shall not require twisting of wrist, tight grasping or tight pinching. HW shall be within reach ranges. Indicate what occurs inside tall cabinets. If coat hook and/or rod, they shall be within reach ranges. Indicate depth of vertical cabinet.

5.4 Counters and Casework Case Study #1 FEC shall be accessible to disabled persons. FEC shown in new location. Provide 30" clear width in front of FEC. HW on entry door to limit opening to maximum 90 degrees. Indicate what occurs inside tall cabinets. If coat hook and/or rod, they shall be within reach ranges.

6.1 Drinking Fountains Q. What is DSA looking for? A. Access compliant drinking fountains. Dual or Single Height D.F. Location in Alcove or Non-Alcove Protected Mounting Height and Projection Height of Bubbler and Control Valve Knee Clearances Wing/Alcove Clearance Clear Floor Space

6.2 Drinking Fountains Case Study #1 Show Mounting Location and Protection Dimension Required Clearances Dimension Mounting Heights Clear Floor Space 30 X42 Section View w/ Heights & Clearances

7.1 Grading and Re-Grading Q. What is DSA looking for? A. Access compliant grading. Spot Elevations and Contours/Critical Points Locations of Walls, Curbs, Barriers and Railings Curb Protection at Abrupt Grade Changes Grade Slopes at Plant Areas and Along POT Grating Details and Opening Dims at POT Preventing Obstructions or Abrupt Changes of Elevation >1/4

7.2 Grading and Re-Grading Provide spot elevations and horizontal control (dimensions). For walks, slopes shall not 5.0% (1:20). For ramps, slopes shall not exceed 8.3% (1:12). Cross-slopes shall not exceed 2.0% (1:50); NOT 1/4" per foot, which is (1:48). Slopes at changes in direction and large paved areas, which have many possible directions for POT, shall not slope more than 2.0% in any direction.

7.3 Grading & Re-Grading Show Spot Elevations at Critical Points Top and Bottom of Landings Barriers, Walls or Railings at Changes in Elevation >4 Complying Slopes along POT Cross Slopes

8.1 Doors/Gates/Hardware Q. What is DSA looking for? A. Access compliant doors/gates/hdw. Door/Gate Swing and Direction Door/Gate Dimensions Dimension Strike Side Clearances Door/Gate Signage Hardware Type, Latches, Closers, Heights Threshold Maximum Rise

8.2 Doors/Gates/Hardware Case Study #1 Show Door/Gate Landing Dimensions and Slopes (2% Maximum in any direct) Door/Gate Minimum Clearance Threshold Maximum Rise Hardware Type, Latch, Closers, Mounting Heights Strike Side Clear Dimensions Landing Dimensions and Maximum Slopes

9.1 Furnishings and Equipment Q. What is DSA looking for? A. Accessible furnishings and equipment. Clear Aisle Dimensions Between Furnishings Clear Access to Accessible Work Space Required Clearances at Work Spaces Accessible Equipment Reach Dimensions to Controls and Accessories Clearances for Front or Side Approach

9.2 Furnishings and Equipment Case Study #1 Show Access to Work Areas Floor Clear Space 30 x48 Work Surface Height and Knee Clearance Reach Limitations for Side and Front Approach Equipment Controls within Reach Limits

10.1 Signage Q. What is DSA looking for? A. Access compliant signage. Parking Signage including Tow Away Info Mounting Height and Details Room Identification Signage with Braille Face Text and Braille Dimensions and Text Height Signs Requiring Symbols (Toilet Rooms) Directional Signs for Exit/Entrance Path Requirements for Raised Characters

10.2 Signage Show Dimensions and Area of Signage Details of Signage Text and Font of Tactile Signs Mounting Height of Each Sign Type Contrasting Colors of Background vs. Text and Images

Change Order Category Fire & Life Safety ( FLS ) Glenn Janes

Fire and Life Safety Issues Top 8 Topics 1. Fire Sprinkler Systems 2. Fire Alarm Systems 3. Substitution of Approved Devices 4. Fire-rated Corridors and Barriers 5. Penetrations in Fire-rated Barrier 6. Egress, Exit Path, Exit Devices and Safe Dispersal 7. Type of Construction 8. Occupancy Group

Fire and Life Safety Overview What drives DSA FLS? Fire Safety Clearly Defined Type of Construction, Occupancy, Fire Alarms, Sprinklers and Setbacks Occupant Safety Fire Ratings, Occupant Loads, Exit Path, Exit Devices and Hardware and Safe Dispersal Area Property Safety Approved Fire Authority Access, Fire Hydrant Placement, Exterior Wall and Opening Protection, Structure Placement

Fire and Life Safety Overview Q. What is DSA looking for? A. Code Analysis, Fire Life Safety Systems, FD Access and Fire Flow requirements. Code Analysis Occupancy Classification, Construction Type and Rating, Use of Each Area, Total Square Footage of Each Floor, Area Increases Fire Life Safety Systems AFSS, Automatic Fire Alarm, Occupant Loads, Exit Path to Public Way, Exit Devices and Hardware and Safe Dispersal Area FD Access and Fire Flow Requirements Approved LFA Access (gates, fire lane), Fire Flow and Hydrant Locations residual and flow

1.1 Fire Sprinklers Q. What is DSA looking for? A. The following: Fire Flow Provide a Current Fire Flow Test to obtain Water and Fire Flow Availability and Design Requirements Fire Underground Identify Fire UG Piping, Fire Hydrant Locations, Determine Fire Riser Size and Locations, Determine if a Fire Pump is Required Fire Sprinkler Piping Plan Piping Distribution and Water Delivery, Structural Support of Piping System, Types of Sprinkler Heads

1.2 Fire Sprinklers Case Study #1 Wet Pipe System Fire Sprinkler Calculations based on Hazard Classification Fire Service to Building including Fire Department Connection and Post Indicator Valve Design, Details and Size of Fire Riser This is actually a preaction system Piping Plan, Pipe Sizing, Main Lines and Branch Lines Details of Pipe Support Systems and Seismic Bracing

2.1 Fire Alarm Systems Q. What is Required to be provided? A. Fire Alarm Devices: Smoke and Heat Detectors, Strobes Provide Design and Layout of Smoke Detection Devices, Heat Detectors and Strobe Lights with Mounting Details Fire Alarm Control Panel Provide Design Layout with Fire Alarm Control Panel and Annunciator Locations Device Schedules, Calculations & Cut Sheets Provide Device Schedules, Battery Voltage Drop Calculations and Manufacture Cut Sheets of all Devices

2.2 Fire Alarm Systems Case Study #1 Provide: Automatic Detection Coverage Strobe and Horn Coverage Smoke Detector Adjacent to FA Annunciator Wall-Mounted Details for Horn, Strobe and Pull Station Devices for Heights -added HD but need to know why in narrative Device Manufacturer Cut Sheets with Current State Fire Marshall Listing Automatic Shutdown Lighting and PA System Overrides and Monitoring

3.1 Substitution of Approved Devices Q. What is DSA looking for? A. Details of Substitution Requirements FA Devices and Panels: Design and Layout of Detection Devices with Mounting Details Design Layout with Fire Alarm Control Panel, Remote Power Supply and Annunciator Locations Device Schedules, Calculations and Cut Sheets Riser Diagrams, Device Schedules, Battery Voltage Drop Calculations and Manufacture Cut Sheets of all Devices Exception:* Full Compliance with IR A-28

3.2 Substitution of Approved Devices Case Study #1 Exchange of Total System (Existing or New Building) Provide All Documents for Full DSA Project Submittal For Partial Exchange (Existing Building Only) Comply with all IR A-28 Requirements Basic Submittal Provide Assurance in Letter: 1. Certify all Portions Compatible 2. New / Added Components ADA Compatible 3. Final Design does not Require Expansion to all areas in Buildings on Campus 4. DSA Submittal Package is Required for Changes

4.1 Fire Rated Corridors & Barriers Q. What is DSA looking for? A. All rated assemblies. Legend with Fire Ratings Plan with Symbols/Callouts of Fire Rating Details and Wall Types of Rated Assemblies with Listing References Details of Assembly Connections at Walls and Ceilings Schedule of Openings and Fire Rating of Approved Assembly Protection

4.2 Fire Rated Corridors & Barriers Case Study #1 Provide: Coordinate Revisions with Door Schedule Assembly Rating to be Shown on Schedule

4.3 Fire Rated Corridors & Barriers Case Study #1 Provide: Symbols of all Fire Rated Wall Assemblies Reference to Wall Assembly Details

5.1 Penetrations in Fire Rated Barrier Q. What is DSA looking for? A. The following: Legend with Fire Ratings Details with Penetrating Material Called Out Details of Fire Safe Sealing with F.R. Listing References Details of Escutcheons where used

5.2 Penetrations in Fire Rated Barrier Case Study #1 Provide: Locations of Fire Rated Assemblies Label Penetration and Protection [i.e. Combination Smoke and Fire Damper (CSFD)]

5.3 Penetrations in Fire Rated Barrier Case Study #2 Provide: Show Wall Rating and Maximum Penetration Opening Label Material Label Fire Stop Assembly Material, Listing and Rating

6.1 Exit Analysis (Load/Path/Widths) Q. What is DSA Looking for? A. Provide Exit Analysis Location of All Exits and Exit Hardware Requirements Number of Occupants and Exit Path Calculate Required Door Opening based on Number of Occupants Actual and Maximum Distance to Exit from Furthest Point Location of Safe Dispersal Area

6.2 Exit Analysis (Load/Path/Widths) Case Study #1 Provide: Exit Travel Distances Actual and Maximum i.e. Classroom-to Public Way Locations of Safe Dispersal Areas Show on Site Plan with Area

6.3 Exit Analysis (Load/Path/Widths) Case Study #2 Provide: Exit Path Through Building including Exiting from Upper Levels Number of Occupants Exiting each Area

7.1 Type of Construction Q. What is DSA looking for? A. Basic Building Construction Type Five Basic Classifications Pick One Schedule with Type of Construction If Building is Fully Sprinklered Allowable Building Height and Areas Allowable Area Increases for Fully Sprinklered and/or Separations from Lot Lines Total Area per Floor and Building Total

7.2 Type of Construction Case Study #1 Schedule Listing the Code Defined Type of Construction Table 503 Tabular Values Show Allowable Heights, Area, Increases and Actual Total Areas

8.1 Occupancy Group Q. What is DSA looking for? A. Occupancy Classification Based on Type of Use Use correct Occupancy Load Factor Occupant Loads Based on Code Minimums Number of Occupants per Space Maximum Number of Occupants in Classrooms and Assembly Areas Occupant Load greater than 50?

8.2 Occupancy Group Case Study #1 Include in Code Analysis Schedule Listing the Code Defined Occupancy Groups Show Allowable Actual Areas & Max No. of People per Use

* INTERMISSION * (Please Return in 15 Minutes) After the Break: - Structural Safety - Administrative

Change Order Category Structural Safety Section ( SSS ) Hassan Sassi, PE, SECB

Structural Safety Overview Q. What is DSA Looking for in Structural Safety? A. DSA considers the following: Changes that may impact the Foundation Changes that may impact the gravity system Changes that may impact the lateral (Seismic) system Anchorage of Non-Structural Components

Structural Safety Top 10 Issues 1. Changes to Structural without SEOR Approval/Knowledge 2. Calculations or SEOR Stamp and Signature 3. Foundation Changes 4. Anchorage Changes 5. Post/Column Changes 6. Beam Changes 7. Connection Changes 8. Mechanical Units 9. Soffits 10.Mounting of Non-Structural Components

1.1 Changes to Structural without SEOR Approval Q. Why is the SEOR Approval important to DSA? A. For the following reasons: SEOR s knowledge and experience. When there is a structural change, DSA is looking for an SEOR stamp and signature. Modifying a standard detail will still require an SEOR stamp and signature. Second pair of eyes for review.

1.2 Changes to Structural without SEOR Approval Missing Typical Information Without SEOR Stamp and Signature, Calculations are Required

2.1 Calculations or SEOR Stamp & Signature Basic Changes: Provide the SEOR stamp and signature. Or include calculations to justify change. Complex Changes: Require stamp, signature and calculations.

2.2 Calculations Example Case Study #1 Verify by calculations that ¾ Hilti KWIK Bolt 3 with 4 ½ embedment has the same capacity as the approved detail of ¾ A307 Headed anchorage with 6 embedment.

3.1 Foundation Changes Q. What are the most common foundation issues? A. Typical foundation issues are: Score Board Pole Foundation Light Pole Foundation Flag Poles Foundations (taller than 35 ) Stair Landing too Close to Existing Footing Canopy Pole Foundation Need to be Moved due to Interference Utility Lines or Pipes too Close to Footing

3.2 Foundation Changes Case Study #1 Piping/Conduit through Footings COs should include: Section Detail Quantity of Conduits Detailed Locations

3.3 Foundation Changes Case Study #2 Show how metal stud furring wall is connected to concrete wall (how 18 ga. angle connected to metal stud). Clarify and show how new curb is connected to slab on grade. Detail said that Anchor bolt embedment is 4" minimum into curb, but curb is 6" minimum.

4.1 Anchorage Changes Q. What are typical issues related to anchorage? A. The following are typical issues: Edge distances Embedment ICC Report Compliance with ICC Report

4.2 Anchorage Changes Case Study #1 As per IR 19-1, shallow epoxy type anchors are not allowed for overhead applications.

5.1 Post/Column Q. When a Post changes what is important? A. The following is important: SEOR is involved. Material Steel, Concrete, Masonry, Wood. Location changes may impact span lengths and loading. Size for adequacy for loading, torsion and deflection. Connection is still adequate or has changed as well. Calculations as required for any complicated change.

5.2 Post/Column Case Study #1 CO Allows Nine (9) Penetration is Load Bear Post Shear Wall

5.3 Post/Column Case Study #1 Calculations Required Spacing Between Holes Hole Sizes (7/S1.50) Loading on the Member

5.4 Post/Column Case Study #1 Detail 7/S1.50 Hole Size is 0.4d D=6 Hole = 2.4 Why is this important?

5.5 Post/Column Case Study #1 3 1.2 1.8 At the narrowest section, the wood is 1.8 thick. 8d Common nail is approximately 2.5. Penetrating the hole and whatever is inside.

6.1 Beams Q. When a beam changes what is important? A. The following is important: SEOR is involved. Material Steel, Concrete, Masonry, Wood. Location changes may impact span lengths and loading. Size for adequacy for loading, torsion and deflection. Connection is still adequate or has changed as well. Calculations as required for any complicated change.

6.2 Beams Case Study #1 Justify the removal of the W8x beam would not jeopardize the structural integrity of the opening.

6.3 Beams Case Study #2 Provide details on how the studs are attached to the metal deck and/or the steel beam.

6.4 Beams Case Study #3 Verify the location of the perpendicular beam serving as a brace is directly aligned with the Guard Rails Support. If not, SEOR should provide an acceptable tolerance/range where the beam acts as a brace. Include this dimension in the revised note.

7.1 Connections Q. When a connection changes, what is important? A. The following is important: SEOR is involved. Detailing all the components and dimensions. Material to Material Type is identified. Location(s) if the change is not applicable in all locations. ICC Reports for adequacy and proper use. Calculations as required for any complicated change.

7.2 Connections Case Study #1 Provide beam and column connections to (E) structure.

8.1 Mechanical Unit Q. When a Mechanical Unit changes, what is important? A. The following is important: SEOR is involved. Location - Roof, Wall, or on Grade. Weight of Unit to determine if the supporting structure is still adequate. Connection is still adequate or has changed as well. Calculations as required for any change.

9.1 Soffits Q. When dealing with a soffit, what is important? A. The following: SEOR is involved. Lateral Bracing for seismic load adequacy. Connection is still adequate or has changed as well. Calculations as required for any change.

9.2 Soffits Case Study #1 This one got it right! Members are Called Out Connections are Detailed ICC Report Allows Seismic Loads SEOR Stamped and Signed (No Calculations Needed)

10.1 Mounting of Non-Structural Components Q. When dealing with Non-Structural components what is important? A. The following: Weight for load adequacy. Details for attachment or mounting.

10.2 Mounting of Non-Structural Case Study #1 2x8 Blocking No Connection Details No Clear Support of the 2x8

10.3 Mounting of Non-Structural Case Study #1 DSA will require referencing ICC ESR # for Hilti Anchor Bolts specified.

Structural Safety Types of Components 1. Structural Components 2. Non-Structural Components

1.1 Structural Components Footing Elevations Footing Penetrations Dog Bone Connection Gusset Plate Yield Line at Concrete Slab or Concrete Fill Coring and Cutting through Shear Walls, CMU Concrete, Sure- Board, etc. Concrete Strength

1.2 Structural Systems 1. Dog Bone Connection 2. SCBF SCBF >2t Dog Bone

2.1 Non-Structural Components 1. Fire Sprinkler System 2. Cable Tray 3. Curtain Walls 4. Store Front 5. Canopies 6. Equipment Anchorage 7. Site Work: a. Fence b. Iron gates c. Site walls d. Stairs e. Handrail f. Drinking fountains g. Cold joints

Change Order Category Administrative ( ADMIN ) Steven Hooper, PE Ryan Guerrero

DSA Administrative Key Issues Q. What is DSA looking for in a CO Submission? A. Compliance with IR A-6: A complete description. That it is neat and orderly. That the project information is on every page.

Guidelines, Code and Other Resources DSA IR A-6

Administrative Category Top 8 Topics 1. Type of CO 2. CO Narrative 3. Organization and Formatting 4. Typical Project Information 5. Review of Sketches for Matching Scope 6. Checking Updated Stamps 7. Additional Attachments 8. Extraneous Material

1.1 Type of CO Three (3) Types of Change Orders: No Change (5-10%) Does not change the DSA approved plans or specifications. Non-DSA Content (10-15%) Changes to the plans or specifications does not affect DSA s primary review components (ACS, FLS, or SSS). DSA Content (75-85%) Changes to the plans or specifications affects DSA s primary review components (ACS, FLS, or SSS).

1.2 Type of CO No Change General Concept - CO is for Cost or Time adjustments only. Additional labor may be attributed to Rework. Examples Time Adjustment due to weather Overtime or Fire Watch Repair or Rework Off Site Work

1.3 Type of CO No-Change Requirements: 1. Clear Stand Alone Narrative for No Change Confirmation 2. Phrase NO CHANGE TO DSA APPROVED DOCUMENTS 3. Appropriate Signatures 4. No Other Documentation

1.4 Type of CO Non-DSA Content Change: General Concept CO modifies the Approved Drawings, but does not impact DSA s primary review elements (ACS, FLS, SSS). Under the 2010 Code, DSA is interested only in changes to their primary review (ACS, FLS, or SSS). Old codes still require approval for all CO s.

1.5 Type of CO DSA Content Change: General Concept CO modifies the Approved Drawings and impact DSA s primary review elements (ACS, FLS, SSS). DSA s eye are on these CO s.

2.1 CO Narrative Q. What is DSA looking for in a narrative? A. 3 W s: Where Be as specific as possible to narrow down where the change occurs. Building, Floor, Classroom, Grid Line, etc. What Fully describe what the change entails. This allows DSA to understand before they even get to review the sketches. Why By specifying the cause of the change, DSA can now understand why the modification was required.

2.2 CO Narrative Case Study #1 Q. Where was the change? Q. What modification occurred on the wall coverings? Q. Why were they changed? A.????Where is this Construction Directive #69.2??Where is this Architectural Supplemental Information #34?

2.3 CO Narrative Case Study #1 1.ASI #34 was not attached. 2.CD #69.2?Refers to a Finish Schedule to Acoustical Wall Coverings but where is it??refers to the attached ASI #45 but where is it?

2.4 CO Narrative Case Study #1 ASI #45 Revisions to acoustical wall coverings and plastic laminate schedule

2.5 CO Narrative Case Study #1 COP #186.2 provide Forbo cork board and Acoustical wall covering

2.6 CO Narrative Case Study #1 Conclusions for CO Rejection: No definitive location. Added or changed to Forbo cork board and Acoustical wall covering. No definitive reason stated.

2.7 CO Narrative Case Study #2 Before Amended Scope Statements After

2.8 CO Narrative Case Study #3 Before Amended Scope Statements After

2.9 CO Narrative Case Study #4 Before Amended Scope Statements After

3.1 Organization & Formatting DSA Transmittal Form District Change Order Cover District Approvals Signature Sheet New Sketches Revised Sketches As-Approved Sketches Applicable Calculations Example of Change Order Form

4.1 Typical Project Information Change Order Number DSA Application & File Number School Name & Project Number AOR Reserved Stamp Space DSA Reserved Approval Space Sketch Number Date

5.1 Review of Sketches for Matching Scope Sketches must match Scope Description!

6.1 Checking Updated Stamps Verify that AOR/EOR/SEOR has Signed the Stamp Verify Expiration Date on Stamp Verify AOR/EOR/SEOR Name to Match the Name on the Stamp

7.1 Additional Attachments Provide For Reference Only Sketches Pertaining to Changes in Scope Provide the Full and Complete Approved FCD Manufacturer Product Data sheets Supporting Calculations Reference Photo of Field Conditions

8.1 Extraneous Materials Remove Contractor s cost estimates, proposal, RFC s, progress sketches, etc. Remove sketches not related to scope. Remove correspondence paperwork between Contractor and OAR. Remove any duplicate copies.

For Reference Reference Documents Steven Hooper, PE

DSA Sticker Samples

Owen Group Administrative Checklist

Owen Group Typical Comments Access 1. Access Compliance a. General Items that apply to ALL Access Compliance changes at any location. i. Clearances ii. Slopes iii. Coefficient of friction on a surface iv. Signage v. Mounting heights vi. Projections into the POT vii. Hardware viii. Handrails ix. Door Jamb Clearances b. Path of Travel (POT) i. All changes in the POT shall be clearly shown and verified by the AOR. c. Parking Stalls i. For Changes in the number of stalls in a parking lot, ensure that there are an adequate number of Accessible stalls (including Van Accessible). The POT, appropriate signage, and slopes shall be clearly shown at the Accessible Stalls.

Owen Group Typical Comments FLS 1. Fire & Life Safety a. Changes to the Approved Site Plan that affect Fire Access shall be clearly shown and re-signed by the Fire Department. b. The As Approved Construction Type will be required for any NEW Construction. c. New Fencing and/or Gates (Including Temporary) shall be clearly shown for impact on both Fire Access and Exiting from the Site. 2. Fire Alarm a. Specify the number of devices Added, Deleted, and/or Modified. b. For adding uncommon devices (i.e. Linear Heat Detector, Exterior Heat Detector, etc), proof of SF M approval of use of the device on the site may be required (Symbols List is acceptable). i. If not approved for the project, then provide the Revised and As Approved Symbols List and Current Cut Sheets for the device. c. Provide the revised Plan Views and Riser Diagrams for the Changes. d. Adding and modifying devices (or major deletions) will require revisions to the voltage drops and battery calculations. e. Deletions and modifications in particular will require adequate narrative for justification.

Owen Group Typical Comments Structural Safety 1. Structural Safety a. Changes to Structural Components (Foundation, Shear Walls, Bearing Walls, Retaining Walls, Beams, Columns, Openings, etc.) i. Requires specific and adequate description and justification. ii. iii. All members, dimensions, and connections shall be specified. Structural Calculations shall be provided 1. ln some cases, but not all, Structural Calculations can be avoided by providing the Seal and Signature of SEOR on the Revisions. b. Changes to Non-Structural Components (Guard Rails, Soffits, Access Hatches, etc.) i. All Members, dimensions, and connections shall be specified. ii. iii. iv. Specify the location relative to supporting structural components Specify how the item will be connected to the Structure. Structural Calculations shall be provided (Specifically, but not limited to, Lateral Forces). 1. In some cases, but not all, Structural Calculations can be avoided by providing the Seal and Signature of SEOR on the Revisions.

DSA Access Resources RESOURCES of the DIVISION OF THE STATE ARCHITECT For the Division of the State Architect, there is more than one way to get to the agency s on-line publications. However, some of the agency s information is only in one location and is not easily found. Therefore, for all of those involved in work related to the DSA it is recommended they periodically explore the agency s website, with its many links, in order to maintain familiarity with its information, which may be updated. In order to assist with the exploration of the DSA s publications, see the following information: DSA Home http://www.dgs.ca.gov/dsa/home.aspx DSA Publications http://www.dgs.ca.gov/dsa/resources/pubs.aspx

LAUSD QA/QC s Most Frequent Recurring Comments 1. Two packages for DSA to be identical @ Reg before COPU (a1) 2. Missing A/E stamp with signature or signature with printed name and call out license number (see DSATracker) (c7) 3. "As approved" not included with "revised" drawings (d2) 4. "Revised" not clouded (d2) 5. "New detail" not referenced on "revised" plans (d2) 6. Clouds on "approved" drawing or details (d4) 7. Change order number not on DSA transmittal letter (b8) 8. Before and after specifications not included; only those pages effected need to be revised, each page must be stamped and signed (d2) 9. Conflicting application numbers or CO # on DSA form VS change order form (b8) 10. Drawing submitted with no titles as required by LLB-83 (d2) 11. Local district # missing on DSA-143 (b)

LAUSD Checklist

DSA IR A-6

Summary Think like a Plan Checker Provide a Solid Narrative Complete and Detailed Submissions GOAL: Deliver High Quality Submissions to Optimize DSA Turnaround and be set for Certification