David Reynolds, Business Development Manager. Halton Group Foodservice Division

Similar documents
Demand-Controlled Ventilation for Commercial Kitchen Ventilation

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION

Demand Control Kitchen Ventilation Cameron Ritzenthaler, Air Solutions & Balancing, LLC

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION

Demand-Controlled Ventilation For Commercial Kitchens

Innovative Technologies [and Design Concepts] in Commercial Foodservice

Variable Ventilation for the Kitchen:

Demand Control Ventilation What, When and Where?

for commercial kitchen ventilation

New Era in Energy Efficiency!

FOOD SERVICE EQUIPMENT REBATES

Customer Advanced Technologies Program Technology Evaluation Report

Demand Controlled Kitchen Ventilation (DCKV) [Strategy]

90% Efficiency without Boiler Replacement TRUE GREEN SOLUTIONS NEW. Patent Pending. EcoFlex 90 + System Modulating Fan-Powered Economizer

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

DIGI-VAV APPLICATIONS

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

DemandAire. amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems. Demand Control Kitchen Ventilation System

Sustainability Best Practices for HVAC Retrofits. Cal Poly State University, San Luis Obispo. Presented to the UC/CSU/CCC Sustainability Conference

LACLEDE ENERGY EFFICIENCY PROGRAMS

Stulz CyberMOD EC Fan Retrofit Kit Switch & Save

Energy & Water Savings in Commercial Food Service

DEMAND CONTROL KITCHEN VENTILATION

Energy Efficient Fan and Dust Collection Systems

M.A.R.V.E.L. Intelligent Demand Controlled Ventilation System for Professional Galleys. Enabling Wellbeing

BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Benefits of ENERGY STAR Commercial Water Heaters in the Food Service Industry

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

Using Adaptive Defrost Control Technology to Improve Energy Savings in the Food Service Industry.

208/230V, 1-Phase. 208/230V, 460V 3-Phase. 208/230V, 460V 3-Phase

Demand-Controlled Ventilation in Multi-Story, Multi-Residential Buildings

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

DEMAND CONTROL KITCHEN VENTILATION

AHRI Certified up to. 95% efficiency P-K MACH HIGH EFFICIENCY, COMMERCIAL BOILERS

Innovative Technology Drives Real Results

HVAC System Consideration$ 05/14/2012 SAVING MONEY IN HVAC SYSTEMS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

EC Fans Growing in Popularity

Continuous Commissioning of Commercial Kitchen and Dining Facilities Case Study

Energy Management and Controls

Union County Vocational - Technical Schools Scotch Plains, New Jersey

DACC Health Sciences Building Air Handler Assessment/Study

Modular Active. Chilled. Beams

GARCIA GALUSKA DESOUSA Consulting Engineers

2018 Agricultural Programs Rebate Application Federated Rural Electric, ATTN: Jon, P.O. Box 69, Jackson, MN 56143

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

THIS IS A DESIGN GUIDE NOT A SPECIFICATION. Montgomery County Public Schools Facilities Guide DIVISION 15 MECHANICAL

Virginia Tech Standards for Building Automation System

Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts

* Peak kw is determined by the average kw load reduction occurring between 1PM and 4PM on weekdays during June, July and August.

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

Optimal control for superior lighting performance

City of Duluth Festival Center 04/25

DAIKIN Air Handling Unit Modular

Energy Recovery Ventilation

& EC Fan Retrofit Kit

RFMA 2016 March 13 15, 2016

Model 8120 and 8126 Safety & Installation Instructions

Preparing the Next Generation of Building Technicians

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

THE ULTIMATE ROOFTOP SOLUTION

End-Use Data Collection Requirements Data Trend Type

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

Would You Bolt A Swamp Cooler To Your DX Rooftop Unit? [not exactly.]

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Building Automation System (BAS) Design Criteria

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

CONTROLLED CHILLED BEAM PUMP MODULE

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

ADDENDUM 1. Southeast High School Auditorium & Gymnasium HVAC Improvements

COMcheck Software Version Mechanical Compliance Certificate

Designing Thoughtful Green Performance - On-Demand Venting and Exhaust Systems

HVAC Controls Upgrades: Requirement Details ( )

The Ed Roberts Campus Berkeley, CA

Complete Ventilation, Heat Recovery and Dehumidification Packaged System by. Maintaining Your Climate for Indoor Pools and Waterparks

Sequence of Operations (excerpt)

SMART Buildings: How sensor and information technologies are transforming the built environment

Worried aboutthe air quality in your schools?

Passivhaus school kitchens

Energy Recovery Ventilators

USEFUL RESOURCES: Applicability. Item o of section 150. Review-Definitions Section 101

Continuous Commissioning: A Valuable Partner to Retrofit Projects

InterNACHI Home Energy Inspection for th Street

MCH Series Drives. HVAC Application Guide. ag-mch-e2

on-demand Minimizing Energy Loss through order to meet Sustainable Design Standards

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Feedback from potential users of UV in HVAC

TECHNOLOGY GUIDE. :: the dawn of a new era in commercial HVAC technology. The all-new Rheem Commercial Renaissance Line featuring:

HLR 1000E Technical Specifications

COMMERCIAL ENERGY SAVINGS GUIDE

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Focus on Energy Business Programs Summary of Services and Incentives July 2009

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

COMcheck Software Version Mechanical Compliance Certificate

Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry.

How to save money on energy at home

NATURAL GAS ENERGY ANALYSIS PROGRAM (NGEA)

25 Energy Saving Tips

Transcription:

David Reynolds, Business Development Manager Halton Group Foodservice Division www.haltoncompany.com

M.E. DESIGN VIEW OF COMMERCIAL KITCHENS BLACK HOLE Sucking Energy from Building

Why are Campus Kitchens Overlooked for Energy Efficiency? Not always the Facility Manager s responsibility? Is Kitchen area managed by Foodservice Contractor? Excess (Wasted) air is invisible Usually not monitored or managed because it is undetected loss Can reduce both Electric & Gas bills WHY? Make up Air (MUA) usually heated or cooled (Costly air replacement!!!) Kitchens: Negative pressure designs (Pulls bldg. air to kitchen) Additional MUA supplied from Office/ Open area HVAC system Kitchen energy isn t directly monitored or separated on bill Implement sub metering to define actual usage in space Less Exhaust air = Less Make Up Air (MUA) required If excess Exhaust CFM controlled, then Supply (MUA) reduced to match

Kitchen Energy Overproduction! Existing kitchen hoods used much higher design exhaust CFM/per lineal ft. standards Estimate: 20% higher CFM s (very inefficient vs. current day!!!) More efficient kitchen hood design parameters are used today Retrofit kits can reduce existing overall kitchen exhaust CFM s M.E. firms generally add a safety factor to roof fan H.P. sizing assuring good ventilation in kitchen space (no smoke) Estimate: 10 25% depending on the project/ application Be Aware: New ASHRAE 90.1 (2010) code standards will limit/ reduce the CKV Exhaust CFM s allowed in new facilities Won t affect existing kitchens, but shows importance on energy focus For New Construction/ Renovation Kitchens (over 5,000 CFM) CKV energy saving options will be required (e.g. choice of DCV)

Typical Commercial Kitchen energy consumption footprint 5 10% 10 15% 40 60% 40 60% HVAC Kitchen Equipment Lighting Cooler Freezer & other Buildings with commercial kitchens are one of the highest energy consumers of all building types HVAC (CKV) & kitchen equipment contribute up to 80% of total dining service building energy consumption

How to reduce Kitchen Energy Consumption in Campus Dining Utilize Whole Building Design approach Design efficient HVAC (CKV) system Minimize kitchen hoods exhaust airflow Use High Efficiency Kitchen exhaust hoods Use Demand Controlled Ventilation (DCV) Select efficient Kitchen equipment Energy efficient cooking equipment is available Energy Star models Both Gas and Electric models Lower BTU or KW inputs

DCV Adaptable to most Kitchens DCV (Demand Controlled Ventilation) is an automatic control system that regulates (and balances) the kitchen hood exhaust and make up airflow based on demand from cooking process Supplies the right amount of energy, at the right time, and right when and where it s needed Kitchens > 5,000 CFM: DCV usually has effective ROI Appliance status COOKING IDLE OFF Hood status Operates at Maximum design airflow (Exhaust CFM) Modulates BELOW Max. design airflow (reduced by 20 50%) Off (No hood airflow)

DCV SystemModels Exhaust Temperature + Cooking Activity Sensor Two types of DCV cooking activity sensors available 1) Infrared light beam across the hood to detect visible smoke or steam associated with the beginning of cooking process 2) Infrared array temperature sensors continuously monitor surface temperature of appliances under the hood Minimum exhaust fan speed default = 60% of design exhaust airflow Option: Single Hood VS. Multiple Hood on Common Fan/ Ductwork Temperature Only Minimum exhaust fan speed default = 80% of design exhaust airflow for systems with constant exhaust temperature set point Delayed responsiveness with temperature sensor only at duct collar and no secondary activity sensor capability If DCV has constant Exhaust Temperature Set point (Variable) Settings must be adjusted from Winter to Summer months

DCV Control Systems types Energy Management Control Systems (EMS) Energy controls monitoring a specific area/ function Sub metering required for optimal energy management Building Automated System (BAS) Integrated systems approach for multiple EMS control systems in the building DCV systems can usually be integrated easily BACnet, Modbus, and LonWorks are common protocols used List of monitored Control Points (Metrics) supplied to Architect (Design Team) in design process assures BAS control wiring diagrams are complete

DCV Systems = Calculation Data HEAT Example (Energy Savings Analysis Software) Data Inputs Weather City Hours of Operation: Hrs/Day Days/Wk Wks/Year Energy Costs: Electric and Gas CKV System: Design CFM Exhaust/ Make up Air requirements Costs: Ventilation System (Kitchen Hoods & DCV system control) Energy Modeling Schedules by Market Report Calculates Annual Energy Savings Electric Energy Reduction (kwh/ per year) = $$$ Gas Energy Reduction (Therm/ per year) = $$$ Greenhouse Gas Reduction (Lbs. of CO2 ) = $$$ TOTAL PAYBACK SAVINGS (ROI) = $$$ Used as Utility Energy Rebate Submission support documents

DCV Case Study Evaluated Site Configuration Four canopy hoods attached to single exhaust fan Demand control ventilation (DCV) installed Design Exhaust Airflow = 11,290 CFM Balancing dampers installed on each hood to independently regulate exhaust proportional to actual cooking demand

DCV CONTROLS YIELD BIG SAVINGS! Energy Impacts Kitchen Hood System w/ Single Roof Fan/Duct Heating [Therms] $1.20/Therm Estimated Savings Cooling [kwh] $0.12/kWh Exhaust Fan [kwh] Supply Fan [kwh] DCV w/ Dampers (Individual Hoods) 1,307 7,425 38,075 12,692 DCV w/o Dampers (All Hoods operate as Total System) 436 2,475 15,705 5,235 Energy Difference 871 4,950 22,370 7,457 Energy Cost Savings/YEAR $1045 $594 $2684 $895

Energy Systems require Routine Preventative Maintenance After installation, HVAC/ CKV systems should be optimized by DCV manufacturer and/or BAS Controls contractor Start up: Assures installation per M.E. design specification Energy management system (EMS) monitor/control sensors require occasional system checks to assure proper operation Operation: Monitoring does not equate to Control Routine calibration is recommended to assure maximum energy savings and comfortable working/dining conditions all day Automatic DCV controls detect system weakness in HVAC Reduces overall costs because Emergency Fixes cost more than Preventative Maintenance solutions Examples: Roof fan issues, Ducts, Space Temp. spikes, etc.

Summary of Key Points MOST CAMPUS KITCHENS AREN T MONITORED COMMERCIAL KITCHENS ARE HUGE ENERGY CONSUMERS SUB METERING ALLOWS SPACE ENERGY MONITORING DEMAND CONTROLLED VENTILATION (DCV) MATCHES ENERGY USAGE = ENERGY REQUIRED ENERGY MANAGEMENT: EMS & BMS/BAS SYSTEMS ENERGY MONITORING IS NOT ENERGY MGMT. SET CONTROL POINTS FOR BMS/BAS SYSTEM (METRICS) SAVE BOTH MONEY & TIME OVER TIME ROUTINE PREVENTATIVE MAINTENANCE A MUST TURNS EMERGENCIES INTO SCHEDULED MAINTENANCE

COLLEGE & UNIVERSITY DCV SITES Dartmouth College* Francis Tuttle Culinary* Oklahoma University* Bellingham Technical College* Whitworth University* Harvard GSE* Univ. of Saint Thomas* University North Dakota* Western Kentucky Univ.* SDCCD (Miramar College)* * Real time Internet Monitoring (including alarms sent to Facilities staff) * First Year Monitoring included with new MARVEL system * Requires Annual Energy Monitoring contract (HGS) Boston College University of Colorado UCSD Stuart Commons UCLA South Campus Univ. of Hawaii West Oahu George Brown College University of Wisconsin Colorado College Oklahoma State Univ. St. Johns University Berklee College of Music McMasters University

Questions? David Reynolds Business Development Manager www.haltoncompany.com dave.reynolds@halton.com