ADDENDUM NO. 1. for. MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140. Marquette, Michigan.

Similar documents
Memphis Housing Authority High Rise Fire Alarm Upgrades. Questions from Contractors (Through Addendum #2) Communications Systems, Inc.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

RE: Clark East Tower Renovations DATE: November 16, 2015 Ypsilanti, Michigan

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

Brighton Area Fire Authority

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

FIRE AND SAFETY PROJECT REVIEW REPORT

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

LEA COUNTY NEW MEXICO Page 1 of 8 JUDICIAL COMPLEX RFP NO.: 03-(16-17)

Fire Alarm, Water Flow Alarm & Signaling Systems

The following information shall become and form part of the contract documents.

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

SECTION FIRE ALARM SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

DONALD H. BERG, ARCHITECT

HIGH-RISE RETROFIT ORDINANCES - NO and NO

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

1.3 REFERENCE STANDARDS

Valuation: # of Plans Submitted: # of pages: Type of Work (select one): New Addition Existing System/Modification Project Name: Scope of Work:

FIRE & LIFE SAFTEY STANDARD

SECTION WET-PIPE SPRINKLER SYSTEMS

BULLETIN. Temperature Controls (VAV) (3/11/2010)

MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

Changes to this Division since the last issuance are indicated with yellow highlighted text.

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

SECTION FIRE DETECTION AND ALARM

Full Service Central Station Fire Alarm Listing Evaluation

Additions & Alterations to Ascension Parish Library Galvez Prairieville, Louisiana Project No. 1401

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

Changes in NFPA

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Tenant Heat Pump Bulletin Temperature Controls Buildings A1, C1, and H1

IN2 Digital, Addressable Fire-alarm System

SECTION ADDRESSABLE FIRE ALARM SYSTEM

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

BULLETIN. Temperature Controls (10/2013)

Fire Permit Application

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

City of La Puente REQUEST FOR PROPOSAL ADDENDUM NO. 1

GENERAL AREAS OF INSPECTION

Division 28 - Electronic Safety and Security

Princeton Joint Unified School District Invitation for Bid Installation of District-Wide Lighting Occupancy Sensors

University Design Standard Fire Alarm Systems

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

Bold items are particular to the City of Euless

Following are the systems proposed as per NBC & Local Fire Authority:

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

BULLETIN. Temperature Controls (Chilled Water) Phase III only (3/11/2010)

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

D. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Electronic Safety and Security

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Environmental Health & Safety

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

OKLAHOMA STATE UNIVERSITY

TrueAlert Notification Appliances

SECTION INSPECTION AND TESTING OF WORK

DESIGN GUIDELINE SBA 5.11

Purpose : Project Manager. Professional. Contractor: devices/system. compatibility

SECTION FIRE DETECTION AND ALARM

HARRIS COUNTY HOUSING AUTHORITY

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

Solicitation No.: The enclosed addendum amends the bid documents for the above referenced Project.

ADDENDUM NO. 1. PREPARED BY: Justin Scott DATE PREPARED: 05/25/2018. PROJECT: Centerville-Washington Park District Park Operations Facility

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

Surviving Survivability A User s Guide to Survivable Fire Alarm Circuits Larry D. Rietz, SET 23 May 2018

SECTION FIRE DETECTION AND ALARM

TrueCom. Building Communications Systems 5115-Series , Area of Rescue Communications System. Description

WEST VIRGINIA UNIVERSITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Design & Construction Standards, Revised January

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

Photovoltaic (Solar) Array Installation Guide

Mar H: SUPPLEMENTAL FIRE DETECTION AND ALARM (16720-H)

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

Commercial Application/Plan Review Submittal Checklist

Transcription:

ADDENDUM NO. 1 for MARQUETTE HOUSING COMMISSION Pine Ridge Apartments Fire Alarm Replacement Project #A1140 Marquette, Michigan December 12, 2016 TO: ALL BIDDERS OF RECORD This addendum forms a part of the contract documents and modifies the original specification and bid proposal as noted below. Acknowledge receipt of this addendum by attaching a copy to the Bid Proposal Form. Failure to do so may subject bidder to disqualification. This addendum consists of seven (7) pages plus sheet E1. A. General Items: a. The Addendum replaces all prior e-mail communication. b. The Owner has original blue-line drawings dated January 24, 1968 which include architectural, structural, plumbing, mechanical, electrical, fire protection and fire alarm which are available for the contractor s review. The drawings are also available in pdf format. c. See the attached sign-in sheet from the December 5, 2016 pre-bid meeting. d. The bid due date remains Tuesday, December 20 th at 10am. If bids are to be delivered via FedEx or UPS ensure the receipt indicates delivery by Tuesday, December 20 th at 10am in case of any delivery delays. e. The contract length will be revised to allow for six months of construction. The six months will begin after all shop drawing submittals and plan reviews have been completed.

Page 2 of 6 f. Refer to Section 00205 Wage Rates. The General Decision Number MI160135 dated 09/09/2016 which is included within the Project Manual does NOT include a rate for Electrician for Building Construction Type. All bidders to use as a minimum the rate included for Residential Construction Type, summarized below. ELEC1070-001 06/01/2014 ALGER, LUCE, MACKINAC & MARQUETTE COUNTIES Rates Fringes ELECTRICIAN $ 31.75 18.20 g. Refer to Section 00310 Form of Bid to be Used. Add the following as item 10: 10. Base Bid Breakdown Base Bid Breakdown a. Material: $ b. Labor: $ c. Base Bid Total (a+b): $ h. The contractor will be allowed to use the building s restroom facilities. The contractor will also be given access to an area within the building where they can break or eat. i. Work hours are Monday Saturday, 8am to 6pm. The contractor is not required to work Saturdays. j. No smoking is allowed within the building. Any smoking must be 25 feet from the building. Chewing tobacco is allowed but related refuse must be properly disposed of. k. Refer to the Asbestos Survey dated September 10, 2009 by Lakeshore Environmental at the following link from the Marquette Housing Commission web site: http://www.mqthc.org/wp-content/uploads/2016/12/skmbt_42316120712170.pdf l. All on-site contractors, subcontractors or suppliers are required to wear identification, examples of which include badges or clothing emblazoned with the company logo. This identification is in addition to the written verification regarding Criminal Background check and exclusion on any registered Sex Offender listed in paragraph 8.D of Section 00101 Architect s Supplemental Instructions to Bidders page 2. m. The contractor will be required to submit regular schedules to the Owner. 48 hour written tenant notification is required for all work within apartment units. The Owner will give the written notice to the tenants based upon the contractor s schedule. n. Refer to specifications 28111.1.5.A.2.b and 28111.1.7.B. NICET Level IV for is required for design. NICET Level IV is required for final programming, commissioning, testing, and training of the final system.

Page 3 of 6 B. Drawings: a. See revised sheet E1 Lower Level. i. There are two occurrences of the telephone symbol T outside of the building footprint; north of the Maintenance Garage and north of Stair 2. Disregard the two symbols. ii. The new Fire Alarm Control Panel to be located adjacent to the existing panel scheduled to be removed in the Electrical Room as shown but not noted. C. Response to Questions: Q1: Note on sheet E1 states Design shall include capacity for ½ the units on each floor to be converted to hearing impaired unit. Is this a requirement? A1: Yes, final design to have the capacity for 50% of the apartment units on each floor to be converted to hearing impaired units in the future. Q2: Specification section 2.14 requires a Listed printer. Is a network card, specifically the SafeLINC by Simplex, acceptable? A2: Yes, a network card which provides electronic documentation meeting code is acceptable. Q3: Is the elevator shaft sprinkled? A3: Contractor to verify but original drawings do not indicate suppression in the shafts. Q4a: Specification section 2.4 Manual Fire Alarm Boxes lists requirement of Indoor Protective Shield. Is this required for all pull stations? It will add depth. A4: No, Indoor Protective Shields are not required. Q4b: A4b: Specification section 2.4 states to supply manufacturer s surface back box at surface mounted stations. Is there a known quantity? Existing building is block wall construction at corridors. It can be assumed that all devices will be surface mounted except for areas where there is a drop ceiling, limited to minimal areas at the first and ground level floors. Q5: Specification says no more than 50 addressable devices per SLC. Is it ok to isolate per floor rather than per device count? This would save on field or panel mounted isolators and installation. A5: Isolation per floor is required. More than 50 is acceptable.

Page 4 of 6 Q6: Page 10 from 2.7 Notification Appliances states: A. General Requirements for Notification Appliances: Individually addressed, connected to a signaling line circuit, equipped for mounting as indicated and with screw terminals for system connections. Does Individually Addressed require truly addressable notification? A6: Yes, the design intent is for addressable notification, detection and monitoring. Voluntary alternate may be provided outside of base bid. Q7: Section 2.3 Fire Alarm Control Unit part K states: K. Voice/Alarm Signaling Service: Central emergency communication system with redundant microphones, preamplifiers, amplifiers, and tone generators provided in a separate cabinet located in the fire command center. A7: The main Fire Alarm Control Panel is intended to be in the basement, adjacent to (replacing) the existing fire alarm panel, see revised sheet E1. A spare of each on site is acceptable if it meets minimum code requirements. If the Fire Command Center does not increase in size, it is acceptable to have the main Fire Alarm Control Panel in the Fire Command Center. Q8: Please confirm the date of the first complete annual inspection required with the bid. Please advise whether paper or electronic reports of the results are required. A8: Provide a complete inspection including testing of all addressable devices per NFPA 72 one year after the date of substantial completion. Provide Owner electronic i.e. pdf results of the testing. Q9: Please detail the FCC, Fire Command Center. A9: The command center is required for high rise buildings and is required to have monitoring and overrides for the following: Elevator, fire pump, transfer switches, generator, smoke evacuation, (if installed), to allow for managed control of the building from the single location. This includes the voice communication along with all of the building s associated documentation to allow the fire department full knowledge of possible threats during a fire or active event at the site. Q10: The bid form has the alternate wireless system as a deductive alternate. Is that correct? A10: Yes, the wireless system is a deductive alternate. Refer to section 012300 Alternates. Base bid is a wired telephone system which includes all of the stairwell and elevator lobby hardwired phones. The alternate provides a wireless system in lieu of the wired system and to include the communication system booster to allow for appropriate signal strength for the fire department in the building. Q11: What is Smoke EVAC sequence of operation? A11: Contractor to verify existing system and provide monitoring of status, manual override, and automatic operation per NFPA72. Coordinated documentation to be provided with delegated design submittal.

Page 5 of 6 Q12: What is Voice EVAC sequence of operation? A12: Contractor shall provide sequence of operation matrix per NFPA 72. Shall include individual messages per floor with evacuation of the floor above and below dependent upon coordination with fire marshal requirements. Coordinated documentation to be provided with delegated design submittal. Q13: Are there stairwell pressurization fans? A13: Contractor to verify but Owner states there are no stairwell pressurization fans. Q14: Are there existing duct detectors and dampers in the chase? A14: Field verify and confirm, per plans. Plan on worst case scenario. Q15: What is the voltage and current draw on the existing dampers if they do existing? A15: Contractor to field verify. Q16: Is the evacuation going to be general evacuation of the whole building or is the system partial evacuation with defend in place? A16: Design intent is for partial evacuation. Q17: If partial evacuation is being used is the EOR requiring Circuit Integrity cable between floors and the panel? A17: Yes Q18: Are protective guard required at each manual station as noted in 283111-2.4A.3? A18: No. Q19: Spec section 283111-2.5.2 call for 4 wire smoke detectors. Addressable detectors are not 4 wire detectors. Please clarify. A19: All devices shall be addressable. Provide base plate style units per specifications. Q20: Are all detectors to have integral heat detectors as indicated in spec section 28311-2.5.7.b? A20: Unable to verify specification section. Smoke detectors shall have sensitivity adjustment but not smoke and heat detection. Q21: Spec section 2831a1-2.5.C.3 requires weather proof duct detectors. Is this a requirement for the detectors inside of the building? A21: This requirement is for duct detectors requiring weatherproof enclosures. Standard enclosure is acceptable for installation inside in a dry location. Q22: Spec section 2831a1-2.7.A call for addressable notification appliances. This requirement will drive up the cost of the project significantly. A22: All devices shall be addressable. Contractor may provide voluntary alternate for review.

Page 6 of 6 Q23: Where is the location of the new fire alarm control panel? There is a key note on E1 but I cannot find it on the actual drawing. A23: New main panel to be located adjacent to existing panel in basement. Q24: Spec section 283111-2.3.C.c call for 1 SLC circuit per floor. Is this intent? A24: (1) Minimum per floor, per specifications. Q25: Spec section 283111-2.3.C.d limits the number of addressable devices to 50 most system have 250 or more addresses available on a SLC circuit. Is this truly intent or are isolation module an acceptable alternative? A25: See response A5. Isolation per floor is minimum requirement. More than 50 per floor is acceptable. Q26: If a printer is required I do not see a location for the printer indicated on the drawings. A26: Printer location would be in Fire Command Center. See response to Question 2 for alternative to printer. Q27: Spec section 283111-2.3-M.2 call for the system to be designed assuming all candela ratings are a minimum of 110cd. Is that the intent on this project? This adds extra expense. A27: Yes, this is the intent. Q28: The drawing indicated that symbol [10] is a combination smoke detector and A/V. These will be separate devices. Are the devices in the bedroom the only location for the 177cd strobes? A28: Separate is acceptable. See plans for locations. Q29: Does this project have a Seismic requirement as stated in spec section 28311-3.1.B.1 A29: All areas are seismic. The system shall be installed per the seismic rating of the area. END OF ADDENDUM

PRE-BID SIGN-IN: Project Name: Marquette Housing Commission Fire Alarm Replacement Date: December 5, 2016 Time: 1:00 p.m. Attendee s Name Company Name Phone No. E-mail Address Kathleen Waters M. C. Smith Associates 616.451.3346 kwaters@mcsagroup.com Sharon Maki Marquette Housing Commission 906.226.7559 x11 smaki@mqthc.org Scott Nielson SimplexGrinnell 920.883.9309 snielson@simplexgrinnell.com Dallas Barrow Master Electric 906.786.4600 dallas@masterelectricinc.net Denny Fleming First Contracting, Inc. 989.834.1500 bill@firstcontracting.net Jason Niemi J & N Electric 906.485.1704 jasonniemi@ymail.com Jack Leadbetter Leadbetter Electric 906.425.4413 jleadbetter.leco@gmail.com Tom Parent VanErt Electric 715.573.0068 tparent@vanert.com Mike Parent VanErt Electric 906.282.0550 mparent@vanert.com Page - 1 -

ELECTRICAL KEYNOTES: 1. FIRE PUMP CONTROLLER, FTA1000-AA40H-AM-BY-P-R, TO REMAIN. INTEGRATE INTO ALARM SYSTEM. ELECTRICAL GENERAL SCOPE OF WORK NOTES: PROVIDE NEW SURFACE MOUNTED RACEWAY THROUGHOUT ALL PUBLIC SPACES. CONCEAL IN CONDUIT ABOVE LOCATIONS WITH A DROP CEILING. NEW SURFACE MOUNTED RACEWAY SHALL BE WHITE. RACEWAY SHALL HAVE CLIPS TO RETAIN CONDUCTORS, 3' ON CENTER, AND SHALL BE MOUNTED PER UL LISTING. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. REUSE OF CONDUIT IN NON-PUBLIC SPACES IS ACCEPTABLE. CONDUIT IN BACK OF HOUSE EXPOSED LOCATIONS SHALL BE PAINTED TO MATCH. REUSE OF EXISTING FLOOR TO FLOOR PENETRATIONS/ WIREWAYS IS ACCEPTABLE. CONTRACTOR TO REMOVE ALL EXISTING FIRE ALARM CONDUCTORS, COMPONENTS, RACEWAY, AND CONDUITS THAT ARE NOT NOTED AS ACCEPTABLE TO REMAIN. EXISTING SYSTEM TO REMAIN ACTIVE DURING INSTALLATION OF NEW SYSTEM. CONTRACTOR TO PROVIDE ALL FIRE WATCH REQUIREMENTS IN BASE SCOPE OF WORK. CONTRACTOR TO PATCH, REPAIR, AND PAINT ALL AREAS WHERE EXISTING CONDUIT AND WIREWAY IS TO BE REMOVED. PAINT TO MATCH EXISTING CEILING/ WALL. PATCH TO BE CLEAN OF BURRS, SMOOTH, AND MINIMALLY VISIBLE. CONTRACTOR TO FIRE CAULK ALL WALL AND FLOOR PENETRATIONS ASSOCIATED WITH DEMOLITION OF EXISTING AND INSTALLATION OF NEW FIRE ALARM SYSTEM. FINISH SMOOTH AND PAINT TO MATCH WALL/CEILING IN ALL EXPOSED LOCATIONS. CONTRACTOR TO REPLACE ANY DAMAGED CEILING TILE OR GRID DAMAGED DUE TO WORK BEING PERFORMED. CONTRACTOR TO PROVIDE NEW TUBES AND HOUSINGS FOR DUCT DETECTION AND REMOVE EXISTING. PATCH AND REPAIR EXISTING DUCT. FIELD VERIFY AND PROVIDE ALL REQUIRED FLOW SWITCH, TAMPER SWITCH, FIRE DAMPER, AND SMOKE DAMPER MONITORING BASED ON EXISTING DEVICES. PROVIDE NEW DETECTION FOR ALL SMOKE DAMPERS. TO BE PROVIDED IN BASE SCOPE OF WORK. SCOPE TO INCLUDE UPGRADES TO EXISTING ELEVATORS TO MEET CURRENT CODE REQUIREMENTS FOR ELEVATOR LOBBY SMOKE DETECTION AND ELEVATOR SMOKE/ HEAT DETECTION. -ELECTRICAL CONTRACTOR SHALL INCLUDE ELEVATOR CONTRACTOR FEE IN THEIR SCOPE OF WORK. -CONTACT - OTIS ELEVATOR - STEVE KAPE - 920-371-0100 SCOPE TO INCLUDE NEW COMMUNICATION SYSTEM INSIDE OF ELEVATOR CAR. ALL WALL MOUNTED DEVICES SHALL BE RED WITH WHITE LETTERING. CEILING DEVICES SHALL BE WHITE WITH RED LETTERING. UNITS 101, 207, 310, 508, AND 810 SHALL BE PROVIDED FOR PROVISIONS FOR HEARING IMPAIRED. DESIGN SHALL INCLUDE CAPACITY FOR 1/2 THE UNITS ON EACH FLOOR TO BE CONVERTED TO HEARING IMPAIRED UNIT. ALTERNATE: SEE SPECIFICATIONS FOR ALTERNATE WIRELESS SYSTEM. 2. EXISTING FIRE ALARM CONTROL PANEL TO BE DEMOLISHED. 3. NEW MAIN FIRE ALARM CONTROL PANEL. 4. EXISTING EMERGENCY TRANSFER SWITCH AND PANELS, TO REMAIN. P:\2016\2016297 Pine Ridge Marquette MI - Fire Alarm\Working Drawings\2016297 E1.dwg, 12/9/2016 2:35:02 PM, mdelora, Classic Engineering