MCS 4000 Control Panel

Similar documents
1 measurement signal input 4-20 ma for connection to an external gas sensor 5 freely programmable alarm switching points per measuring point

Entwicklung + Fertigung + Service: Heerweg 15 D, Denkendorf Tel.: / Fax.: /

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

Fire control panel detect 3004 plus and accessories

Networked Access Control Panel. Installation Guide

Installation, Operating and Maintenance Manual

G34 AU1B (External Ultrasonic Sensor) Version 3

Fire Control Panel FS5100

FLAME AMPLIFIER MODULE 3001

TECHNICAL DATA SHEET ADDRESSABLE FIRE ALARM SYSTEMS FIRE ALARM CONTROL PANEL LF-6100 A 1/2

VAP304 PRO INSTALLATION & OPERATION MANUAL

M-Sens 2. Online-Moisture Meter for Solids. Operating Instructions. SWR engineering Messtechnik GmbH

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

M-Sens 2. Online moisture measurement for solids. Operating Instructions. SWR engineering Messtechnik GmbH PART OF THE ENVEA GROUP

User Manual. Dryer Controller M720

Danfoss gas detection units

Control/Communicator Installation Manual

REPEATER FS5200R INSTRUCTION MANUAL

561-MB256 plus. Intruder alarm control panel. Performance features

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

GMA200-MW16. Operation Manual. Gas detection controller for wall mounting

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

OPERATION MANUAL Gas Alarm Processing Unit GAZ 203 VN VN 10

Specification for On-Line UPS Battery Monitoring and Data Management System

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

Compressed air quality meas. according to ISO 8573 Residual oil content - particles - moisture

Intelligent addressable fire alarm control panel

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

Dew point. Special features: Dew point monitoring DS 400. Technical data DS 400. Technical data FA 510

Gas Controller Module GC-06

SCHMIDT LED Measured Value Display MD Instructions for Use

Danfoss gas detection unit Type GD Heavy Duty

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

Multi-Gas-Controller MGC2

Remote alarm indicator and test combination MK2430

SALES SUPPORT DOCUMENT

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

Made possible by an innovative licensing scheme, which allows individual hardware configuration, up to the maximum configuration:

FLAME AMPLIFIER MODULE 3001D

Fire Control Panel FS4000

PolyGard Controller LGC/LG2-04. Multi-Point Controller Serial Number S00 User Manual Preliminary Version. August 11, 2006

E21.X.01.6C-05 Operating Manual EB2000 MC page 1. Operating manual EB2000 MC. for up to 9 sensor modules. Version 3.0

User Manual. PolyGard Gas Controller MGC3. Two-Channel Analog Gas Controller Serial Number _E _0907. September 2007

Panel Mounted Fault Annunciator Series

GMA200-MT. Operation Manual. Gas detection controller for mounting rail assembly

Monitoring Solutions

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

Dryer Controller M720

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

BSR Addressable Fire Detection control panel. Installation operation manual

Addressable Fire Alarm Control Panel

CONTROL DEVICE SLIDETRONIC HD

UV - Monitor UVT 16. Use. Description

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

ECOLOG TN2, TN3-P, TN4, TN4-L, TP2, TP4-L,TH1, TH2

Healthy. Atmosphere. for Pigs and Poultry. for a

Instructions manual. By-alarm. By-alarm Manager software

Product overview. Alarm indicator, operator and display panels

Dew point set DS 400

Operation Manual for Drying Storage Cabinet with Drying Unit U-5002

DS 96/48 P. Digital indicator. Short manual 41/33-89 EN Rev. 00 DIM

THX-DL Data Logger USER & INSTALLATION MANUAL V

User Manual Doc.Ref : JA-KNX-UM. JA-KNX Jablotron KNX Interface ELAUSYS JA-KNX. KNX Interface for Jablotron alarm system.

Section PERIMETER SECURITY SYSTEMS

Technical Manual. Level Alarm Unit CARLA & WIDS

SCR100 User Manual. Version:1.1 Date:Dec 2009

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

STANDARD TECHNICAL SPECIFICATION FOR AN ANALOGUE ADDRESSABLE FIRE DETECTION SYSTEM

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

On the job around the clock 24/7: Fire detection systems

GSM Alarm System. User s Manual. Profile. MOBILE CALL GSM Alarm System

The EN54 Part 2 & 4 Fire System

JA-63 Profi User manual

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

DCA4. Digitally controlled Audio Matrix. Current Thinking. Product Specification March Document Number DDC DCA ACS

Danfoss gas detection units

GMA200-MW4. User Manual. Gas detection controller for wall mounting

PowerRouter application guideline

Date SECTION MEASUREMENT AND CONTROL INSTRUMENTATION Project Name Page 1

Solution 880 Operators Manual. Issue 1.00

Operating Manual UV Monitor UVT 18

ZLM4 OEM Technical Manual

THE SOLUTION. MSM-Product family OPERATING MANUAL. A fault annunciator of the. BSM Basic fault annunciator for panel mounting. INFOwww.ees-online.

LaserFOCUS VLF-250 Engineering Specification

LORAIN CIP 4890/48120 DC Power System

External Dimensions: B = 600 mm D = 630 mm H = 2000 mm. Internal Dimensions: B = 451 mm D = 430 mm H = 1598 mm

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

Carbon Monoxide Transmitter

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

MC200. Users Instructions. HEATING DIVISION Hort Bridge Ilminster, Somerset TA19 9PS Tel: Fax:

ZM1 User Manual JVA TECHNOLOGIES.

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

GMA 301. Operation Manual. Worldwide Supplier of Safety Solutions. Part Number

Transcription:

Medium Control Systeme Franke & Hagenest GmbH Borngasse 1a * 04600 Altenburg Telefon : +49 3447 499 313 0 Telefax : +49 3447 499 313 6 E-Mail : info@mcs-gaswarnanlagen.de MCS Operation Manual MCS 4000 Control Panel Each operation on the gas alarm control panel requires the accurate knowledge and attention of this operation instruction manual. Liability of Operation & Defects The liability of operation of this device is transferred to the owner or operator insofar the unit is operated by any person who are not part of the service team of the manufacturer, or improper service, maintenance or repair or if an operation has been conducted which is not in accordance and compliance of the intended use and application. The manufacturer will not take any responsibility for damages occurring through non-observance of the above notice. Service / Maintenance In order to ensure proper operation of the unit / device bi-annual inspection and maintenance must be conducted by trained and authorized personnel. It is recommended to obtain a service contract with the manufacturer in order to validate full warranty oft he gas alarm control panel. Authorized Application The device is designed to: - measure and analyze analogue and digital signal inputs. - display / control of alarm notifications (warning lights, sirens, safety valves, aeration, ventilation etc..) 1

System Set-Up CPU-, Display- and Operation Module Analogue Input-, Power Supply Module Relay Outputmodule Digital Input- Analogue Output Module RS 485 RS 485 RS 485 RS 485 24 Volt 24 Volt 24 Volt RS 485 24 Volt Remote-Display Module Optional Power Pack 24 Volt e.g. MCS 2000 NSV CPU,- Display & Operation Module Microprocessor controlled unit with graphic capable display and connected push buttons. The communication with all other components is realized through the internal RS485-Bus. Analogue Input Module AEM8 Up to 16 analogue input modules AEM8 can be connected to the CPU module. The analogue input module can be integrated into an additional housing or into the main / central unit. The analogue input module provides 8 analogue inputs 4-20 ma and per input a regulated 24 Volt power supply. The inputs can be freely programmed with through the MCS programming software. The analogue input module is connected to the system BUS RS484 and addressed. The distance between the central unit and the last analogue input module must not exceed 200 meters maximum. If the distance is to be covered is larger, the system has to be added with a repeater. For the electrical connections refer to the electrical connection diagram. The address has to be set at the analogue input module via a dip-switch. Important! AEM8 Address Addressing AEM8 No. Software 01 01 0 0 0 0 02 02 1 0 0 0 03 03 0 1 0 0 04 04 1 1 0 0 05 05 0 0 1 0 06 06 1 0 1 0 07 07 0 1 1 0 08 08 1 1 1 0 09 09 0 0 0 1 10 10 1 0 0 1 11 11 0 1 0 1 12 12 1 1 0 1 13 13 0 0 1 1 14 14 1 0 1 1 15 15 0 1 1 1 16 16 1 1 1 1 The address can only be awarded one time! 2

Relay Output Module RAM10 Up to 16 relay output modules RAM10 can be connected to the CPU module. The relay output module can be integrated into an additional housing or into the main / central unit. The relay output module consist of 10 relays with potential free changeover contacts, which are free programmable with the MCS programming software, based on different alarms and zones. The relay module is connected to the system BUS RS484 and addressed. The distance between the central unit and the last analogue input module must not exceed 200 meters maximum. If the distance is to be covered is larger, the system has to be added with a repeater. For the electrical connections refer to the electrical connection diagram. The address has to be set at the relay output module via a dip-switch (see table AEM8). Important! The address can only be awarded one time! Digital Input and Analogue Output Module DEM8 / AAM8 Up to 16 digital input and analogue modules DEM8/AAM8 can be connected to the CPU module. The digital input and analogue module DEM8/AAM8 can be integrated into an additional housing or into the main / central unit. The digital input and analogue module DEM8/AAM8 provides 8 digital inputs potential free and 8 analogue outputs 4-20mA. The outputs and inputs can be freely programmed with the MCS programming software. The digital input and analogue module DEM8/AAM8 is connected to the system BUS RS484 and addressed. The distance between the central unit and the last analogue input module must not exceed 200 meters maximum. If the distance is to be covered is larger, the system has to be added with a repeater. For the electrical connections refer to the electrical connection diagram. The address has to be set at the relay output module via a dip-switch (see table AEM8) Important! The address can only be awarded one time! 3

Alarm Notification The unit provides 4 alarm switch point levels. Once a measuring signal is reaching its average value of its switch point level, the respective alarm will be triggered. The respective alarm-led (L1) illuminates and the connected and programmed relay will activate with a timedelay of 5 seconds. Once the alarm is quit the connected and programmed relay will de-activate with a timedelay of 5 seconds. The setting of the measuring parameters and the switch point levels for the different measuring points as well as the addressing of the output relays for the alarm notification are programmed. The adjusted parameters are documented in the inspection and test report records. Single alarm notifications may still be present, even after the abolition and lapse of the initiating cause. This is the case if for the alarm level a timed over-running has been programmed, e.g. for sufficient area ventilation or if minimal fan running times have to be followed, or if the alarm level has been programmed as `self-storing`. Those can be only reset through the operation of the key button: Alarm-Reset T8 A reset of a stored gas detector alarm is only possible after the cause for the gas alarm has been eliminated. Otherwise the alarm will be automatically deleted after completing a signal hysteresis (min. 3 digits), once the cause for the alarm notification has been removed. Connected acoustic alarm transmitters can be reset as well in case of an alarm, through operation of the key Horn-Reset T7 Unit Failure Indication System An unit failure will be indicated under following conditions: - Mains power failure (*) - During coldstart 1 min after power re-establishment - Failure of cutout fuse - Unit defect - Supply voltage dip of the gas detectors (< 18 V) (*) - Disruption or short circuit of the gas detector feed cable, (*) - Measuring signal deviates from max. measuring range (<2.5mA bzw. >25mA) (*) The surveillance of the gas detectors for their failure includes this situation as well - Disruption of software - Loss of parameter adjustments (*) The respectively programmed disruption relay will be activated in case of any failures. The standby state LED switches off and a device error notification LED will flash continuously. With (*) marked device failures can be programmed, that they automatically trigger alarm level 1 4 and subsequently start ventilation systems, warning lights, sirens, horns, safety valves etc. The other device failures can only through looping of the alarm relay take action via the failure notification relay. 4

Mains Power Failure Alarm Suppression The unit is fitted with a programmable time delay which will be activated after each failure of power supply (coldstart) and suppresses any alarms until the sensors are operational ready. During this period the service LED will flash. If the time delay is activated the unit will be operational after 1 minute, once the power supply is reestablished and if there are no other failures present. Data Interface USB and TCP/IP The interface USB Type B is used for the connection of a computer or terminal for the programming of the alarm control panel and the output of test-, measuring- and alarm reports. The length of the connecting cable to the computer or terminal shall not be longer than 5 meter (direct connection). As a connecting cable a commercially available USB-connecting cable can be used. TCP/IP-Interface This interface is optional. Integrating this interface allows the user via the software to address any IPaddress, alternatively via DHCP. This interface can be used for the parameterization, alternatively to the USB port. Otherwise is this interface used during normal-modus to transfer data regarding current status and occurrences for a visualization. Start-Up of Operation The system start-up must be only conducted by factory authorized and trained personnel. Programming of the Control Panel The programming of the alarm control panel must be only conducted by MCS service technicians or factory authorized and trained personnel. For the programming the software TMCS4000 is required. The software is not part of the unit order and delivery. Operating Control Pad Key Button Set Menu Set Menu Set Menu Set Menu Function In menu forward In menu backward Selection of detailed information regarding the present menu item Display of parameters Menu ESC Reset Alarm Reset Horn E1 Offnet menu Leave menu subitem, return to normal operation mode Quitting of alarm relay during self-preservation Quitting of acoustic signal (relay horn) Not assigned 5

LED-Display LED Color Status Description Miscellaneous Power green continious Mains power supplied flashing Mains power loss Ready green continious Unit without disturbance flashing Process disturbance Software bug / processor defect Error yellow flashing Unit in disturbance Failure of the central unit, gas detector Service yellow continious service cycle During programming of the unit flashing maintenance / service required New calibration required A1 red continious Alarm 1 triggered A2 red continious Alarm 2 triggered A3 red continious Alarm 3 triggered A4 red continious Alarm 3 triggered Menu yellow continious Menu selected Acoustic red continious Acoustic triggered E 1 green Optional / not assigned LCD-Display Normal Operation MCS Gaswarnanlage 10.08.2014 09:55:00 Display of date and time. There are no reports of disturbance or alarm notifications. 6

Warranty The manufacturer provides a warranty of 4 years with the signing of a service contract conducted by the manufacturer s service team or an authorized and appointed service partner. In case of no service contract, the provided warranty expires after 12 months of date of installation and no longer than 18 months after date of purchase. Shutdown During a shutdown the programmed data is not lost. The data saved in the memory for past notification is not lost as well. If the unit is more than 4 weeks out of operation, it is required that after system re-activation, the gas detectors are tested with test gas and if necessary re-calibrated. Service / Maintenance Gas warning systems must be serviced and maintained bi-annually or annually when indicated. The service interval is mentioned on the service sticker. A service and maintenance contract with the service team of the manufacturer is highly recommended. As a notification for the required service following information is displayed on the display: 12.01.2002 09:55:00 Service required Additionally the service-led will flash. This notificatioin will only be de-activated after successful service. 7

Technical Specifications Subject to change Case Wall housing or blind frame for switch cabinet installation Case material Polystyrene Measurements H x L x W 260 x 250 x 90 mm, incl. cable glands Protection class IP 58 Temperature range Relative humidity 15-90% -20 C. +50 C Signal thresholds Alarm 1 self-extinguishing / saving free programmable Alarm 2 self-extinguishing / saving free programmable Alarm 3 self-extinguishing / saving free programmable Alarm 4 self-extinguishing / saving free programmable Switching outputs 10 potentialfreie Wechsler 250 V/2,5A frei programmierbar Erweiterbar mit Relaismodulen bis 120 Relaisausgänge über RS 485Bus Operating elements 1 button horn-reset 1 button alarm-reset 1 button digital input 7 buttons system control External connection 2 digitale Eingänge frei programmierbar Indicators LED - Display red Alarm 1... 4 horn aktive yellow Error Service Menu green Power Ready LCD - graphic- display illuminated Data interface USB RJ45 Connected loads 230 V/50Hz/60W or 24V /DC/60W Sensor connection Sensors basic structure with 8 sensor connection inputs Expandable with sensor input modules up to 120 measuring points via RS 485Bus Series terminal 3-pole 24V/DC, measuring signal 4-20 ma, GND all sensors with 4-20 ma output Options sensor input modules 8 inputs per module Relay output modules 10 Relays per module digital-/analogue module 8 digital inputs/8 analogue outputs per module emergency power supply module 24 Volt GSM telephone dialing unit forwarding of alarm- and default reports Key switch blocking of alarm in case of service LAN TCP/IP visualization, remote service 8