INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT

Similar documents
LXG-300 Series. Models with LXG-300 Series Instruments

Installation, Operation and Maintenance Manual. RQ Series. Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw

The Danger signal indicates an immediately hazardous situation which, if not avoided, will result in death or serious injury.

INSTALLATION INSTRUCTIONS AND OWNER S MANUAL FOR

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

LC Series - Light Commercial Pump Station Installation and Operation Manual

INSTALLATION INSTRUCTIONS AND OWNER S MANUAL

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

Digital Marine Exhaust Temperature Alarm

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Thermolator TW Series

Condensing Unit Installation and Operating Instructions

EEMAX ProAdvantage Series 1

INSTRUCTION MANUAL INSTALLATION OPERATION MAINTENANCE

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Operation Manual NEMA 4X Controls

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

SE Series Modular Electric Stone-Hearth Deck Oven INSTALLATION & OPERATION MANUAL LBC BAKERY EQUIPMENT, INC st Ave NE Tulalip, WA 98271, USA

PS SERIES PARALLEL RACK SYSTEM START UP GUIDE

T-Series Air Conditioner T15 Model

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

TrueTemp II Series Water Temperature Control Units Important! Read Carefully Before Attempting to Install or Operate Equipment

Astro Express 2 - Hot Water Delivery System

YOUR PROCESS DEMANDS THE MOST DEPENDABLE TEMPERATURE CONTROL UNIT AVAILABLE.

QUICK PRIME INSTALLATION AND SERVICE MANUAL

MODEL INSTALLATION INSTRUCTIONS SEWAGE PUMP

Fluid Cooler Fan and Pump control panel

DRAFT INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information

WAIWELA SERIES-TWO WATER HEATERS

OPERATION AND MAINTENANCE MANUAL ELC-810 AUTOMATIC WATER LEVEL CONTROLLER. AquatiControl Technology

INSTALLATION AND MAINTENANCE GUIDE TRENDY 1000 T ELECTRONIC LAVATORY FAUCET

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

Model 8780 INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. Tempering Skid General Area Classification & Class I Division 2. No.

L A signature series TA T N E RE O, A L L A T S IN

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

CHILLER. Model CH3000. Operator s & Installation Manual

STAINLESS STEEL UNITS

MODEL E

OPERATING MANUAL Enertronic Control System 2

PDF Created with deskpdf PDF Writer - Trial ::

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Thermolator vacutrac. Positive/Negative Pressure Water Temperature Controller with TW-1 or TW2 Microprocessor. Installation. Operation.

EEMAX SERIES-TWO WATER HEATERS

DISPOSER CONTROL CENTER

DISPOSER CONTROL CENTER

INSTALLATION & OPERATING INSTRUCTIONS

Instruction Manual HWR MODEL RESISTO-FLO ELECTRIC BOILER

QUICK PRIME INSTALLATION AND SERVICE MANUAL

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

T-Series Air Conditioner T20 Model

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

SPECTRACOOL Air Conditioner. N21 Model INSTRUCTION MANUAL nvent Rev. G P/N

568X, 587X, 588X Series

T-SERIES Air Conditioner. T20 Model INSTRUCTION MANUAL nvent Rev. C P/N

prestige Control Application Supplement - ACVMax

Bravo. Troubleshooting Guide

DISPOSER CONTROL CENTER

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

Static Pressure Control

Hydra Negative Pressure, Closed-Loop Mold Temperature Controllers INSTRUCTION MANUAL

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

User instructions DHP-AT

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

Circulating Oil Temperature Control System

AquaSaver DISPOSER CONTROL CENTER Installation Manual. Model AS-101K

Vertical Inline Models

TROUBLESHOOTING GENERAL TROUBLESHOOTING PROBLEM PROBABLE CAUSE CORRECTIVE ACTION

DualPak Series FILE NO: DATE: Feb. 15, 1999 SUPERSEDES: DATE: Sept. 28, DualPak 6900 Series Booster System

OPERATING MANUAL Enertronic Control System 2

GUIDE BOOK FROSTIE FROST FIGHTING CONTROLLER

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

BLAST CHILLER / SHOCK FREEZER MODEL AP3BCF30-1

TECHNICAL. Series 18. Pump Packages

5700-E Sediment Filter Installation & Start-Up Guide

HB CDA SERIES WITH TEMPERATURE SETBACK

ASTRO EXPRESS 2 HOT WATER DELIVERY SYSTEM

Portable Chillers. Water-cooled models PCW-1.5 to PCW-30 and Air-cooled models PCA1.5 to PCA-30. Installation. Operation. Maintenance.

Owner s Manual Refrigerated Compressed Air Dryer Model F-50

P6500W Air Dryer User s Guide

DRAINMAKER INSTALLATION INSTRUCTIONS PREINSTALLATION CHECKLIST

Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW

XR401. Comfort Control TCONT401AN21MA. Owner s Manual. your local dealer (distributor) For more information contact. Tyler, Texas 75711

Please record your equipment s model and serial number(s) and the date you received it in the spaces provided.

STEAMPRO. Steam Generator Troubleshooting and Service Guide

Garb-el Free Standing Models

Installation and operating instructions. E.2 Series high efficiency circulator

Rev B, 9/2/2009. Kodiak Chiller Overview

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

Control Application. Supplement - ACVMax

Aquatherm Series Temperature Controllers. Installation, Operation and Maintenance Manual

INSTALLATION INSTRUCTIONS FOR MULTI-UNIT RESIDENTIAL APPLICATIONS INSTALLATION INSTRUCTIONS ARE PER UNIT MODELS: RS-502C, RS-503C, RS-702C, RS-703C

P4200PM / P5000PM Remote Air Dryer User s Guide

Transcription:

INSTALLATION, OPERATION & MAINTENANCE MANUAL BERG TEMPERATURE CONTROL UNIT

TABLE OF CONTENTS Description Page # Introduction 3 Customer Support 3 Model Number Nomenclature 4 Control Panel 5 Display Panel Menu Navigation 6 Controller Home Page 7 Controller Display 8 Alarm Events and Controller Parameters 9 Set Up Procedure 9 Water Hook Up 10 Electrical Hook Up 11 Basic Start Up Procedures 12 Shut Down Procedures 13 Disassembly and Reassembly Procedures 14 Scott Pump 15 Troubleshooting 17 Plumbing Diagram 18 Electrical Diagrams 19 BERG SERIES TEMPERATURE CONTROL UNIT Page 2

INTRODUCTION On behalf of everyone at Berg Chilling Systems, thank you for purchasing this equipment. With over 35 years experience in developing and implementing customized Process Cooling solutions for customers around the world, we firmly believe that our equipment is second to none and that the solution provided for you in this equipment has been engineered and manufactured using only the highest quality, state of the art components, to give trouble free service with a minimum of maintenance. It is in everyone s best interest if you read this manual thoroughly and where applicable, familiarize yourself with the checklists and tips contained here, and adhere to the safety and maintenance schedules outlined. Proper care and attention to maintenance and operating procedures will ensure an extended service life and minimum downtime of your equipment. Berg will not be liable for errors contained in this manual or any damages in connection with the use of this manual. CUSTOMER SUPPORT If you have any questions in regards to this manual or if you have any problems with your unit, consult the factory at 416-755-2221. For 24 hour service inquiries, Please call (416) 755-2226 Head Office: Berg Chilling Systems Inc. 51 Nantucket Blvd., Toronto, Ontario, Canada M1P 2N5 Tel : (416) 755-2221. Fax : (416) 755-3874. Email:sales@berg-group.com Internet : www.berg-group.com BERG SERIES TEMPERATURE CONTROL UNIT Page 3

MODEL NUMBER NOMENCLATURE B T C 1 12 100 C Berg Temperature Control Number of Control Zones Heater Rating (kw) Pump Horsepower ¾hp - 075 1hp - 100 2hp - 200 3hp - 300 5hp - 500 7.5hp - 750 Type D C T N A - Direct Injection - Closed Circuit - Totally Closed Circuit - Negative Pressure - All (Totally Closed, Neg.Pres.) For the direct injection style, the D may be left off the model number. BERG SERIES TEMPERATURE CONTROL UNIT Page 4

Control Panel Figure 1 OK 1. Toggle Stop/Start (hold for 3 sec) 2. Accept data entry C 1. Cancel data entry/operation 2. Silence Alarm output relay (hold for 2 sec ) ^ Scroll / Increase data value v Scroll / Decrease data value BERG SERIES TEMPERATURE CONTROL UNIT Page 5

Menu Navigation Using C and scroll keys Home Page C C Menu Pages Sensors C Events Page Events are archived until repaired C Password Page C System Page To/From Sensor Page Active alarm events are displayed until any key is pressed. BERG SERIES TEMPERATURE CONTROL UNIT Page 6

Controller Home Page TEMP TEMP SETPOINT O C/ O F WATER PRESSURE PSI SUPPLY O C/ O F RETURN O C/ O F PUMP ON/OFF HI TEMP ALAR LO TEMP ALAR UNITS OF MEASURE PRI ( O C) SECO ( O F) ALARM ON/OFF Sensors Page PROCESS OK/BAD RETURN OK.BAD PRESSURE OK/BAD System Page LCD CONTRAST BACKLIGHT DEFAULT COLOR Blue (Red) ALARM COLOR Red/Blue Address 255 HOUR MINUTES DAY OF WEEK DAY MONTH YEAR BERG SERIES TEMPERATURE CONTROL UNIT Page 7

Controller Display PRESS OK FOR 2 SECONDS TO STOP OR START THE UNIT DISPLAY ICON LEGEND SYSTEM START LOW TEMP ALARM HIGH TEMP ALARM PUMP STATUS HEATER STATUS COOLING/VENT STATUS BERG SERIES TEMPERATURE CONTROL UNIT Page 8

Events System Error High Temp Low Temp Pump Fail Low Press Process Sensor Fail Supply Sensor Fail Pressure Sensor Fail Parameters (Password protected page) Return Sensor Offset Process Sensor Offset Hi Temp Alarm Shift Lo Temp Alarm Shift Heater Differential Heater Setpoint Offset Vent Time Period Percent Open Prop Band Integral Heater Control sensor selection SV Control sensor selection Pressure sensor offset Pressure sensor Upper Range Value Pressure sensor Lower Range Value Lo Pressure Trip Setpoint DAT Output PT Filter Weight SET UP PROCECURE Location The Berg Temperature Controller Unit should be located as close to the process machine as possible. A minimum footprint of 16-1/4 wide and 28 deep is required on a level surface. Rear clearance is only required to make the necessary water line hookups. Air Temperature and Humidity The Temperature Controller should be in a clean, well ventilated area with a maximum room temperature of 120 F with 95% relative humidity, non-condensing and a minimum air temperature of 32 F. BERG SERIES TEMPERATURE CONTROL UNIT Page 9

WATER HOOK-UP (SEE FIGURE 3) Pressure Requirements The Berg Temperature Control Units require a minimum of 25 PSI on the cooling water input and accommodate a maximum of 85 PSI. Note: 30 PSI to 50 PSI provides the optimum operation of the unit. To and From Process The to process and from process hookups should be connected in the back of the unit with 1¼ NPT piping. Both hookups are clearly marked on the back of the unit. Cooling Water Cooling Water Cooling Water In and Out The cooling water in and cooling water out hookups should be connected in the back of the unit with ¾ NPT piping. Both hookups are clearly marked on the back of the unit. BERG SERIES TEMPERATURE CONTROL UNIT Page 10

ELECTRICAL HOOK-UP Always maintain a safe ground and always disconnect incoming power before you open the unit or perform any nonstandard operating procedures, such as routine maintenance. Improper power supply could result in damage to the unit as well as serious injury to the operator! 1. Before power is initiated to the unit, make sure the specifications stated on the nameplate are met. See Figure 4 for the location of the nameplate. The electrical hookup should be identical with a maximum of ±10% variance in voltage. The electrical hookup should also run through a fused disconnect, sized in accordance with the nameplate amperage and conforming to Article 250 of the National Electrical Code. 2. Connect the power feed to the right side of the unit. Bring the four wires through the hole on the right side of the electrical enclosure. See Figure 4. 3. Connect the three hot wires to L1, L2 and L3 on the terminal block in the upper right hand corner of the electrical enclosure. See Figure 5. 4. Connect the ground wire to the copper grounding mount to the left of the terminal block. See Figure 5. Groun L1 L2 L3 Figure 5 BERG SERIES TEMPERATURE CONTROL UNIT Page 11

BASIC START UP PROCEDURES 1. After you have completed the Set Up Procedures, initiate the cooling water supply. Note: If the water supply is less than 25 PSI, the unit will not function and the low water pressure alarm will be annunciated. (Correct the water pressure if necessary and proceed with the start up.) 2. Check for leaks in your cooling water connections. 3. Initiate power from the fused disconnect. 4. Remove the top panel. Open the front door of the unit and tap the pump contactor with an insulated nonconducting device. Look down at the pump and check the rotation. The pump should be rotating in the same direction as the rotation sticker on the top or side of the pump (clockwise). If the rotation is correct, proceed with the start up. If the rotation is incorrect, stop operation and disconnect the power supply. After the power is disconnected, swap two of the three power source wires connected to the terminal block. Reinitiate power and check the pump rotation again. The pump should now be rotating correctly. Note: The unit is now ready for operation. 5. Press the OK key to start the unit. Each time the unit is started, the venting sequence will be engaged ensuring that the process water has filled the unit piping before the pump or heater turns on. The venting sequence time will vary depending on the timer settings (approximately 30 seconds). (The Cooling Valve icon will be displayed.) Quick Startup Procedure - Hook-up the lines as per the labels on the unit. - Remove the cover of the unit. - Turn the water on and check for leaks. - The make-up water pressure must be above 15 psi. - Turn the power on to the unit. - Using the C key will scroll between the home page and the menu pages. - The home page displays the temperature. - With the temperature displaying us the arrow keys to display set-point. - To change set-point to desired value push the OK key the set-point will flash. - Use the arrow keys to change the value to the require setting. - Push OK to accept the value. - To start the unit push and hold the OK key for 5 seconds an icon 1 will display. - The unit will start a auto vent for 30 seconds. Then the pump will start. - Shut the unit off by pushing the OK key for 5 seconds check the pump for proper rotation as it shuts off. - If incorrect change the incoming power leads. - If correct start unit again with the ok key and the unit will auto vent again the pump will run. If the unit requires to be warmed up to set-point the heater will come on and then shut off just before set-point. At set-point the controller will cycle the cooling solenoid on and off to control your set-point. - All control values are preset and any adjustments should not be required. BERG SERIES TEMPERATURE CONTROL UNIT Page 12

SHUT DOWN PROCEDURES Shut Down to Change Water Line Hook-Up Allow the process temperature to cool to at least 120 F. Press the stop button to stop operation of the unit. Close the cooling process water input. Press the start button or open the relief valve on the back of the unit to relieve pressure. Drain the water from the unit using both 1/4 plugs on the lower back of the unit. See Figure 8. Once the unit is cooled to at least 120 and the water is drained, the water hook-ups can be removed. Shut Down for Mold Purge (Option) To prepare for mold purge, just press the stop button to stop operation of the unit and close the cooling process water input. Connect the compressed air (80 to 100 PSI recommended) and hit the mold purge button. The mold purge will continue until timer 2 is timed out. Shut Down for Relocation When relocating the unit within the same general area, press the stop button. The water feeds may or may not need to be disconnected depending on the new location. Shut Down for Storage or Shipment Shut down the unit as you would for changing the water line hook-up. Then loosen the compression fitting at the pump volute. See Figure 9. Take extra care to make sure all trapped water is drained from the bottom of the mixing/heater tubes and the pump volute. This trapped water will freeze at 32 or below. The expansion of this freezing water can/will damage the equipment. Note: The Temperature Controller Unit can withstand temperatures as low as -40 F when shipping and storing the completely drained unit. 1/4 Plug 1/4 Plug Figure 8 Bottom of Mixing Tube 1/4 Plug (2 Places) Pump Volute Compression Fitting Figure 9 Side View of Pump BERG SERIES TEMPERATURE CONTROL UNIT Page 13

DISASSEMBLY AND REASSEMBLY PROCEDURES Cooling Solenoid 1. Disconnect the water connections and drain the unit completely. 2. Remove the red cap. 3. Push the solenoid down. 4. With a flathead screwdriver, remove the nameplate/retainer by prying under and pushing the nameplate/retainer. 5. For reassembly, make sure to put the wide end of the core spring into the core first. The closed end protrudes from the top of the core. Red Nameplate/Retain Solenoid with 1/2 NPT Spring See Step 4 Grounding Wire Green or Green with Yellow Solenoid Base Sub- 0.9375-26 UNS-2A Core Spring Core Assembly Body Valve Body 1/4 NPT Brass BERG SERIES TEMPERATURE CONTROL UNIT Page 14

SCOTT PUMP (12R) Motor J56 (4) Flinger (40) Iron Adapter (71) 5/8 EPDM Seal (89) Impeller (2) Iron Heater Tank (HT) 2 required D Washer (30) Nut (24) Case Gasket O-Ring, (73) Iron Case (1) Tank EPDM O-Ring (73A) 2 Required BERG SERIES TEMPERATURE CONTROL UNIT Page 15

SCOTT PUMP (50R) Motor JM 140/180 Flinger Shaft BUNA O-Ring Bronze Shaft Sleeve (14) Iron Adapter (71) 1-1/2 EPDM Seal (89) Seal Retainer (89A) Case Gasket (73) Impeller (2) Key (32) Impeller Retainer (26) Iron Heater Tank (HT) 2 Required Bronze Wear Ring (25) Iron Case EPDM O-Ring (73A) 2 Required BERG SERIES TEMPERATURE CONTROL UNIT Page 16

Troubleshooting When an error occurs, the display1 will alternate back and forth from the error code and current display readout. This section will describe the error codes and any actions you need to take to correct the problem. Problem Possible Cause Solution Nothing happens, Display Power feed is not connected Re-wire power feed does not light up correctly Power disconnect is off Turn on power disconnect Power fuses or breakers are Check fuse/breaker status open Control transformer fuses Check fuse continuity are blown Pump does not engage Improperly set time delay Reset the ITD to 30 seconds after vent sequence ITD Defective time delay ITD Replace the ITD Pump overload tripped Reset overload if tripped Pump starter defective Replace the pump starter Pump motor defective Replace the pump motor The power is on but the Insufficient cooling water Water pressure must be 25 to 80 PSI unit does not start or vent pressure Defective water pressure Replace the water pressure switch switch Unit will not heat to set Cooling solenoid is leaking Clean seat or replace point Heater or heater contactor Check the amperage (each leg should be equal). Replace as required. failure Optional high temp safety tripped Preset 260 F cutout. Replace if required. BERG SERIES TEMPERATURE CONTROL UNIT Page 17