ER52 - Evaporator Controller

Similar documents
ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

ER65 - Mini Rack Controller Electronic Refrigeration Line

MR3CCUHV Temperature/Defrost Control

T125-E. Electric Fan Coil Thermostat. Product Bulletin. Operation. Appearance. Installation, Service and Maintenance

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

Thermometers and temperature controllers

MR40 Advanced Electronic Control for compressor and defrost management. Features and Benefits

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS OPERATING INSTRUCTIONS

Digital regulator for refrigeration and defrosting, 3 relays.

EC 6-295P220S001. smart guide 2 OPERATION. 2.1 How to turn the instrument ON/OFF. If you have to turn the instrument ON/OFF:

JDDT1 - Single Stage Digital Thermostat

Dixell Installing and Operating Instructions release 7.0

XWA11V. Walk-In Temp / Door /Alarm / Light Module

TM-3100 Series Room Temperature Sensor

COMMERCIAL REFRIGERATORS, STAINLESS STEEL PRODUCTS REFRIGERATORS OPERATING INSTRUCTIONS

Refrigerated air dryers

TMEF Series. SKOPE Vertical Freezer. User Manual

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module

Service Manual. LC125 Meatwell with LDU15 Controller (Feb 04 till July 09) then AT1-5 Controller (July 09 onwards)

MODEL URS-1: FACTORY RETROFIT PROGRAM

ST Wiring diagram. Product description. Standard temperature controller. Order number

ERC2 Control Instructions

Original Service Manual

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

Sf2+HF2 Sf2 Sf1 + Hf1 Sf1. 1 ON Fan1 enabled (only for XC30CX) 2 ON Fans enabled (only for XC30CX) kpa. Time

ACT2-CS Convenience Store Controller

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Installer Manual KNX Touchscreen Thermostat

Manual For Panel Air Conditioner. Table of Contents

TEC2100 Series Networked Thermostats

HT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH

MasterCase. User Manual

XC10CX and XC30CX. Digital controller for CDU management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS 2. GENERAL DESCRIPTION

FX BLAST CHILLER ISO ISO 9001

Original Service Manual

New LAE controller for Plug-in cabinets

PARAGON Commercial Refrigeration Controls

plug-in, electronic digital thermostat with defrost control User manual

Service Manual. Solid Door Upright Reach-In Units:

0LLCD003EN STANDBY NORMAL INFO MENU INFO DATA SETUP MENU PARAMETER VALUE. Not Product Air Display scale Operating Temper. (sim.

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

Electronic Controls Handbook Programming Flow Charts & Parameter Lists for

TRUE TEMPERATURE CONTROLS SEQUENCE OF OPERATION

Service Manual. Slimline Range with FD2-10 Controller ISO ISO 9001

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

Introduction. OM-THA2

Digital Controller XR70CX. Operating Manual. 5/10 Rev. B

TEC210x-2 Series Networked Thermostats

XR60C ,QVWDOOLQJDQG2SHUDWLQJ,QVWUXFWLRQV. Digital controller with defrost and fans management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS

REACH-IN SAFETEMP (-AAC)

CAREL IR33+ CONTROLLER

Technical Support Bulletin No. 23 Try ColdFace!

Capacity controller for water chiller AK-CH 650

TC-9102 Applications

Commercial Refrigerator Service Manual

FlexDrawer. Original Service Manual. FFC6-2, 3-1, 4-2 & 2-1 Models. FD2-10 Controller & LCD5S Display. English

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

DFZ. Cabin Control Description and operation

INSTRUCTIONS AK-CC 250A

Service Manual. Chiller unit MQH R 410A. Release Date Rev Review Date november

XC1008D -XC1011D- XC1015D and VGC810

IN NOURISHING SECURITY.

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

5-stage compressor racks + 2 converter outputs

Single pressure controls for Refrigeration, Air-conditioning and Heatpump applications

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

Follett Performance Plus

Top Mount Full Length Swinging Doors

Dough Retarder Prover

BSD SERIES REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

Commercial Freezer Service Manual

Instruction Manual. Open Merchandisers. Models: 1OM 2OM REFRIGERATION LTD.

Environmental Management Policy for Service Manuals and Duets.

Oxygen (O2) Single-Point Gas Detection System

Service Manual. Slimline Range With LF28 Controller ISO ISO 9001

TOQUE BLANCHE GRANDE CARTE

DFZ. In Cab Control Description and Operation

Technical description. Atec.

TLJ29 M DIGITAL ELECTRONIC CONTROLLER FOR MILK CONSERVATION REFRIGERATION UNITS

TABLE OF CONTENTS. 1. Technical specifications of the appliance 2

Ocean Breeze Model QU700 Programmable Digital Touchscreen Climate Control

dixel Installing and Operating Instructions PRELIMINAY

F 200 / F 300 TSF 200 / TSF 300 M3

ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER

EC3-X33 Stand-alone Superheat Controller Technical Data

Two-Channel Gas Controller

dixel Installing and Operating Instructions

<IMG INFO> 339,95 195, ,35 14,15-1. ENERGY 400 Four Steps Chiller Heat Pump Controller

CAREL CONTROLLER. Programming Instructions HOW TO CHANGE LEVEL 1 CONTROL SETTINGS HOW TO CHANGE LEVEL 2 CONTROL SETTINGS

technical bulletin Control Link RSC Installation Instructions

Controller for temperature control EKC 202D1

User Manual Ichill 200 L/D (Firmware version 1.7)

ST Wiring diagram. Product description. Four-stage controller. Order number

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

Transcription:

ER52 - Evaporator Controller Electronic Refrigeration Line Product Bulletin Devices are standalone digital controller for static or ventilated refrigeration units working at positive temperatures. They incorporate comprehensive controls to apply controllers with food display cases or any evaporator units. Devices can be used also as heating thermostat. Physical Features Robust front panel for durability and long term usage Direct 230V supply: no external transformer required High power relays: direct compressor command Application Features Cooling or heating thermostat Pre-set models and selectable options to extend pre-set models Comprehensive controls: compressor, fan, defrost, light, alarms, door, standby Temperature monitoring: minimum and maximum peaks Sensor selector: NTC or PTC

Dimensions (in mm) and Mounting 35 77 3.7 27.3 28.5 36 29 71 71 Wirings 1 2 3 4 5 6 7 8 7(2)A AUX 16(8)A POWER 230 VAC DI1 T2 9 10 11 T1 T1 = T2 = Return air temperature Evaporator temperature 2

Functions Device Features Description + +5 Positive Temperature It integrates all the functions to face refrigeration units at positive temperature. It can be also used as heating thermostat Pre-set models are selectable from the display. Keyboard Lock Display can be locked in order to prevent user to change parameter settings. When locked, only temperature information is available to the user. Direct Power Supply Devices are powered directly with 230 VAC. IN Multifunction Input (DI1) Digital inputs are available to manage alarm contact, door contact or remote commands such standby, defrost, night or forced ventilation. OUT Auxiliary Output (AUX) Auxiliary relays are available to manage optional outputs such light, alarm report, defrost or fan. 20 0-5 Temperature Monitoring (Min/Max) Device monitors the current temperature every 5 minutes and memorizes the minimum and maximum peaks. Peaks values are visualized on display temperature menu. Control Features Thermostat Control Cooling or Heating Fan Control Defrost Control Description See detailed description hereafter. Light Control Temperature Alarm (High-Low) 3

Thermostat Control Thermostat is off when temperature reaches the setpoint. Request turns to if temperature increases below the setpoint + hysteresis on cooling or decreases under the setpoint-hysteresis on heating. Thermostat output activation could be delayed in order to prevent from frequent on-off switching (advised when thermostat drives a compressor). Cooling Control Heating Control Temperature Temperature Setpoint+Hysteresis Setpoint Setpoint Setpoint+Hysteresis Thermostat status Time Thermostat status Time Compressor start time Thermostat status Thermostat output Re-start delay Set + +5 Setpoint Setpoint is blocked between minimum and maximum values to limit user setpoint adjustment. A second setpoint can be defined to save energy during night or reduced load periods. Periods are defined by external digital input command. Setpoint limits Maximum setpoint 2 nd Setpoint Selection (option) Normal setpoint Minimum setpoint Bias +/- 2 nd Setpoint IN 4

Fan Control Fan is optional and can be activated on the auxiliary relays. It works in paralell to the compressor and is immediately stopped when door is opened. Fan is forced to on during defrost cycle. Defrost Control Defrost cycles are defined by setting the defrost initialization/end conditions and operations during defrost. Defrost operation cycle: unit is stopped and temperature naturally increases. Electrical: unit is stopped and electrical heater is activating. Hot gas: compressor is running and cool cycle is reversed by activating hot gas valve. Defrost Start Defrost can be initialized periodically based on time. Manual action is also available from display front panel or wired remote switch. Defrost starts at first occurrence of time or manual events. Periodical Defrost Manual Defrost or IN Interval time Defrost stop Defrost cycle ends based on a maximum duration time. Evaporator sensor could be used to stop the defrost before maximum time occurs. A dripping period can be also added to the defrost cycle in order to fill the evaporator with possible condensation. Evaporator temperature Dripping Time End temperature Duration delay Defrost Status Dripping Time Defrost Cycle Defrost Status 5

Light control It can be activated on the auxiliary output. Light command is piloted from front panel key or wired door switch. Light is switching at opening of the door. Manual switching Door switching Standby/Fan only mode Unit can be fully stopped by standby commands available on display front panel or wired remote switch. Alternatively unit can be partially stopped by maintaining only the internal ventilation (fan only mode). Name Input Output Standby mode Front panel key or digital input All outputs Fan ly mode Digital input All outputs except fan Alarm Management Table sums up all the alarms managed by the devices. Name Input Output High temperature Temperature No action on control - Alarm output activated Low temperature Temperature No action on control - Alarm output activated Interlock alarm Digital input All control outputs off - Alarm output activated Report alarm Digital input No action on control - Alarm output activated Door open Digital input Specific management (see below) - Alarm output activated Sensor Failure T1 sensor All control outputs off - Alarm output activated 6

20 0-5 Temperature alarm Alarm is detected if temperature moves outside low and high thresholds. Alarm activation could be delayed in order to consider temporary fluctuations due to specific operations such start up or defrost. Thresholds are independent from the setpoint (absolute alarm). Alarm situation is ending when temperature turns back between low and high thresholds. Temperature Absolute Alarm High Limit Low Limit Alarm status Time Door open Specific strategy is applied when door is opened: Door alarm is delayed to prevent from quick opening/closing of the door. Alarm becomes active when the delay ends. Compressor stop can be delayed. Fan is stopped. Alarm Outputs Alarms are reported on display front panel LED, internal buzzer or auxiliary output. Alarm is reset automatically. Alarm Activation Buzzer mute Display alarm LED Internal Buzzer (option) OUT Auxiliary Relays (option) 7

Display layout Alarm LED Thermostat / Compressor LED Defrost LED / Command ER52 Display Light LED / Command / Stanby Command Alarm mute Menus navigation Display Menus Home Home Temperature 3 Setpoint 5 7 Configuration >5 1 STANDBY LIGHT Parameter Setting Example >3 DEFROST Reset Escape * * Automatic ESCAPE after 30 sec. 1 ALARM MUTE Reset Menus Navigation Function Keys Min/Max Temperature reset Temperature Menu Messages and Error Codes Code Description t1 Return air temperature t2 Evaporator temperature (visible only if selected) thi Monitored temperature highest peak tlo Monitored temperature lowest peak Loc Keyboard lock parameter Setpoint Menu Code Description csp Setpoint Code Description Action F1 t1 sensor failure To check t1 wiring or replace it F2 t2 sensor failure To check t2 wiring or replace it A1 General alarm To resolve alarm cause A2 Report alarm To resolve alarm cause A3 Door open To close the door Fon Fan only mode To reset fan only mode with Digital Input off Standby To restart unit with keyboard or Digital Input d Defrost active To wait defrost completion hi Lo High temperature alarm Low temperature alarm To check plant (abnormal temperature) 8

Configuration Menu Code Default Range Description Setup Mod ref ref / hea Application selector: cooling (ref), heating (hea) St ntc ntc, A99 Sensor types un 1 c 0 1, 1 c, 1 F Scale selector: C (decimal), C (degree), F WARNING: Setup parameters have to be defined before setting the configuration parameters. Any new setup could recover default settings. Thermostat Control LL -40-40 / hl Setpoint Low Limit hl 70 LL / 70 C Setpoint High Limit csp 2 (40*) LL to hl Setpoint hy 2 0.5 / 10 C Hysteresis cc 3 0 / 10 min Compressor Min time Sc 2 0 / 10 min Compressor stop delay at door opened Temperature Alarm Setting ALA -40-40 / 70 C Absolute alarm low limit AhA 70-40 / 70 C Absolute alarm high limit At 30 0 / 120 min Alarm delay at normal operation AbE no no, YES Alarm buzzer enable Defrost Setting ds tim (no*) no, tim Defrost selector: not used, periodical di 06 1 / 168 hours Defrost periodical interval df off off, ELE, hga Defrost operation: off cycle, electrical, hot gas dt 7-40 / 70 C End defrost temperature dd 40 1 / 99 Defrost maximum duration dc 0 0 / 99 Defrost dripping time dp Lt Lt, SP, df Display value on defrost: last temperature, setpoint, Defrost flag dr 20 0 / 99 Display delay after defrost Code Default Range Description Multi function Input Setting Digital input 1 selector: if1 00 00 / 07 00 = Not used 01 = Interlock alarm 02 = Alarm report 03 = Door 04 = 2 nd setpoint 05 = Standby 06 = Fan only mode 07 = Defrost start id1 5 Digital input 1 delay 0 / 99 min (alarms, door) bio 0-12 / 12 C 2 nd setpoint (bias) LGS MAn no, MAn, dor Light switch command: not used, manual, door opened SbE YES no, YES Standby key enable Probe Setting SF1 3 Compressor 0 / 10 min time at sensor failure SF2 3 Compressor 0 / 10 min time at sensor failure So1 0-12 / 12 C Sensor T1 offset SE2 no no, YES Sensor T2 enable So2 0-12 / 12 C Sensor T2 offset Display Setting Pu 3 0 / 100 Display refreshing time Auxiliary Output Setting AA1 LGt Auxiliary output 1 and 2 selectors no, AL0, no: Not used LGt = Light AL1, LGt, ALO = Alarm at command def, Fan opening def = Defrost output AL1 = Alarm at Fan output closing FAn = * Default values of Mod = hea (heating) 9

Ordering Codes All ordering codes are relative to individual product package. All items are also available with bulk pack (i.e. quantity of 10 controllers). Please refer to JC customer service. Controllers ER52-PM230-501C Accessories & Spare parts ER-NTC-0C Controller, 1 NTC sensor included NTC Sensor, 2 m, universal replacement Technical Specification Product Codes Power Requirements Protection Class ER52-PM230-501C 230 VAC/VDC ±10%, 50/60 hz, 3 W IP55 (front) - IP20 (back) Ambient Operating Conditions -10 C to 50 C 15 to 80% RH (non-condensing) Range -40 to 70 C Accuracy +/- 1K Sensor NTC, A99 Johnson Controls, Inc., declares that these products are in compliance with the essential Conformity requirements and other relevant provisions of the EMC Directive 2004/108/EC, Low Voltage Directive 2006/95/EC. Building Efficiency Headquarters: Milwaukee, Wisconsin, USA Branch icies: Principal Cities World-wide Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. Copyright 2013 Johnson Controls, Inc. All rights reserved. Any unauthorized use or copying is strictly prohibited. www.johnsoncontrols.com