HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

Similar documents
PET Drying Technology

The Digital Scroll Dryer

Heat of Compression Desiccant Air Dryers. HOC SERIES scfm ( nm 3 /h)

HYDROGARD Refrigerated Air Dryers HGD and DES Series

Refrigerated Compressed Air Dryers

Noncycling Refrigerated Air Dryers Range AD 10 to AD 4000

Heated Purge Desiccant Compressed Air Dryers. HPD SERIES 300 to 3200 scfm (510 to 5437 nm 3 /h)

Heat of Compression Desiccant Air Dryers. NRG-LES SERIES scfm ( nm 3 /h)

Heat of Compression Desiccant Air Dryers. HCD SERIES scfm ( nm 3 /h)

Refrigerated Compressed Air Dryers

Refrigerated Compressed Air Dryers

Externally Heated Desiccant Air Dryer RP Series

Refrigerated Compressed Air Dryers 5-6,000 scfm

Non-Cycling Refrigerated Air Dryers. HPRplus SERIES 100 to 3000 scfm (170 to 5097 nm 3 /h)

Non-Cycling Refrigerated Air Dryers

Refrigerated Compressed Air Dryers

Heated Purge Desiccant Compressed Air Dryers. HPD Series

Heated purge desiccant compressed air dryers. hpd Series

next generation R 1 cycling refrigerated compressed air dryers flow capacity: scfm ( Nm 3 /hr)

Refrigerated Compressed Air Dryers

Heat of Compression Desiccant Air Dryers. HCD SERIES scfm ( nm 3 /h)

Energy Saving Refrigerated Compressed Air Dryers DES Series 90 to 675 scfm (153 to 1148 nm 3 /h)

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Energy Saving Refrigerated Air Dryers. HES SERIES 800 to 3000 scfm (1357 to 5097 nm 3 /h)

Refrigerated compressed air dryers

Non-Cycling Refrigerated Air Dryers. HPRplus SERIES 100 to 3000 scfm (170 to 5097 nm 3 /h)

NGV Fueling Station Dryers. FSD-A, FSD-T, FSD-M and MRS Series Catalog

Refrigerated Air Dryers VF Series. DHT Series. Non-Cycling 10-2,000 scfm scfm

Blower Purge Desiccant Compressed Air Dryers IBP SERIES 500-4,300 SCFM

Heatless Desiccant Air Dryers. HHS SERIES, HHL SERIES AND HHE SERIES 40 to 5400 scfm (68 to 9175 nm 3 /h)

Blower Purge Desiccant Compressed Air Dryer. HBP SERIES 500-4,300 SCFM ( nm 3 /h)

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

BOGE AIR. THE AIR TO WORK. Refrigerant Dryers RA Series

Refrigerated Compressed Air Dryers

Heatless Desiccant Air Dryers. HHS SERIES, HHL SERIES AND HHE SERIES 40 to 5400 scfm (68 to 9175 nm 3 /h)

QUINCY QPNC SERIES NON-CYCLING QUINCY QRHT SERIES HIGH TEMP

Membrane Compressed Air Dryers HMD SERIES

REFRIGERATED AIR DRYERS SCFM. CRPC Energy Saving Series

NON-CYCLING REFRIGERATED AIR DRYERS. RNC Series

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Buran. Cycling Refrigerated Compressed Air Dryer With Ultrapulse Control. Intelligent Energy Management

600-10,000 scfm AES Series. AES Series Energy Saving. Refrigerated Air Dryer ,000 scfm. Front Page

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

RNC Series SCFM Global Air Treatment

LARGE CAPACITY, REFRIGERATED COMPRESSED AIR DRYERS WITH TRUE-CYCLING TM OPERATION AND REDUNDANT OPERATING SYSTEMS. MultiPlex.

THERMAL MASS CYCLING REFRIGERATED AIR DRYERS. GTRC Series

Membrane Technologies DMD Series Dryers ESM Series Dryers

REFRIGERATED AIR DRYERS

Refrigerated Air Dryers

HIGH INLET TEMPERATURE REFRIGERATED AIR DRYERS. GHRN Series

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

A Primer for Air Dryer Selection

SCFM REFRIGERATED COMPRESSED AIR DRYERS. CRN Series

A Treatise on Liquid Subcooling

ThermoStar Refrigeration Air Dryers

REFRIGERATED AIR DRYERS

MultiPlex INNOVATIVE COMPRESSED AIR SOLUTIONS LARGE CAPACITY TRUE-CYCLING TM REFRIGERATED COMPRESSED AIR DRYERS

Nirvana. Cycling Refrigerated Dryers

100% Outdoor Air Dehumidification Methods

RNC Series SCFM Global Air Treatment

Energy Saving Refrigerated Air Dryers SRC Cycling Dryers

SRV. Unmatched Energy Savings and Unrivaled Product Quality. DRYERS. Variable Operation Dryers SCFM

NON-CYCLING REFRIGERATED AIR DRYERS. GSRN Series

CDX Refrigerant dryers

New standard in compressed air treatment, providing Energy Savings up to 99%

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Refrigeration dryers DW 2-504

MVR Evaporators Reduce Plant Operation Costs

MCGUIRE AIR COMPRESSORS Compressed Air Dryers. CRN Series. Refrigerated. Leading Technology. MCGUIRE AIR COMPRESSORS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS

SECTION 7 AIR CONDITIONING (COOLING) UNIT 40 TYPICAL OPERATING CONDITIONS UNIT OBJECTIVES

F-H Refrigerated Dryers

AirCel. Cycling Refrigerated Compressed Air Dryers. RFC and DVF Series

Atlas Copco Oil-injected Rotary Screw Compressors GA 15-22/GA /GA VSD (11-30 kw/15-40 hp)

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION

Nirvana Cycling Refrigerated Dryers

Use this Construction/HVAC Glossary to answer the questions below.

CRN Series MCGUIRE AIR COMPRESSORS INC MCGUIRE AIR COMPRESSORS INC Refrigerated Compressed Air Dryers

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

refrigeration drying solutions

Applications of Thermodynamics: Heat Pumps and Refrigerators

CNC Series Refrigerated Air Dryer CFM

Compressed. air treatment. Refrigerated. compressed air. dryers. Totally Integrated. compressed air. treatment.

PoleStar Smart Refrigerated Air Dryers don t just cycle, cycle Smart.

MODULAR HIGH CAPACITY REFRIGERATED AIR DRYERS. GMRN & GMRC Series

Technical Note. EHPA Quality Label Model Range Definition Version

HX Series. Compressed Air Dryers 10 to 2400 scfm. Setting a new standard in Quality and Reliability DRYMAX DRYMAX DRYMAX

QUINCY QOF SERIES OIL-FREE AIR COMPRESSORS QOF 2-30 HP

OIL-INJECTED ROTARY SCREW COMPRESSORS. GA 5-11 (5,5-11 kw/7,5-15 hp)

Daikin Blueprint: Delivering Hot Water with a Chiller

The SPX World of Industrial Drying Technologies

ACHIEVING ENERGY-EFFICIENT DATA CENTER COOLING: DOES REDUCING FAN SPEED ALWAYS RESULT IN ENERGY SAVINGS?

OIL-INJECTED ROTARY SCREW COMPRESSORS. GA 5-11 (5,5-11 kw/7,5-15 hp)

Comparison Ammonia / Secondary Refrigerant System against Direct Evaporation of HCFCs /HFCs

Hybrid Refrigerated/Desiccant Compressed Air Dryers

Refrigerated compressed air dryers

GRF Series Non-Cycling Refrigeration Dryers ANDARD ELECTRONIC DRAIN STANDARD ELEC SS EXPANSION VALVE F PRESSURE DEWPOINT

Transcription:

ENERGY CONSUMPTION HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS Introduction Those in charge of specifying and purchasing equipment for industrial compressed air systems have many decisions to make. The design of a proper compressed air system does not end after determining the quantity of air required (i.e., the air compressor and receiver tank); the user must also pay particular attention to the quality of the air that his or her process needs. Today s optimal air systems demand less moisture, less particulates, less oil aerosols, and less oil vapor than ever before. For most users, a refrigerated-type compressed air dryer will satisfy their requirements for moisture removal. With so many manufacturers offering equivalent products, each with promises of delivered pressure dew point, pressure drop and consumed electrical power, how does one make an intelligent selection? Whose glossy brochure does one believe? This paper will address power consumption, and how it relates to a refrigerated dryer s ability to remove moisture. It will explain how a potential buyer can determine if the stated performance is possible with the power consumption that is published in the manufacturer s literature. Energy guidelines for the user will be determined by establishing theoretical minimums and practical expectations. To do this, we will first describe how refrigerated dryers work, and how they are rated. From there, the subject of heat loads will be discussed, determining the theoretical minimum quantities of heat that must be removed from the air stream. Next, a range of pragmatic dryer designs and their corresponding heat loads will be presented which is representative of what is available in today s marketplace. Finally, the refrigeration system capacities and the expected power consumptions will be calculated. Background How Refrigerated Air Dryers Work Water vapor from the ambient enters the compressed air system at the air compressor intake. In refrigerated dryer technology, this moisture is removed by condensing the water vapor into a liquid by cooling the air stream to the desired pressure dew point temperature in one, or more, heat exchangers. Well-designed refrigerated dryers achieve outlet pressure dew points of +38ºF(+3ºC). This means that, as long as the compressed air piping downstream of the dryer is not exposed to ambient temperatures below +38ºF(+3ºC), the user will not experience liquid water in his compressed air system. Dryers that do not perform to their publicized claims will deliver pressure dew points higher than expected by the air system designer. In some cases, this performance discrepancy, as determined by the amount of water not removed by the dryer, can be dramatic. Figure 1 presents the detrimental effects that a non-performing dryer can have on a compressed air system. As shown, the difference between a +38ºF(+3ºC) pressure dew point and a +60ºF (+16ºC) pressure dew point for a 1000 standard cubic foot per minute system can easily be over 70 gallons per week! This additional moisture is simply being passed downstream into the user s air piping. For this reason, it is imperative that the system designer receives the stated level of moisture removal specified by the manufacturer.

Innovation at Work... Since 1948, Hankison, an SPX brand has set the global standard for energy efficient compressed air treatment solutions. Our on-going product development efforts are driven by customer demand for sustainable energy savings, fault-tolerant operation and ISO quality class performance. Based in Charlotte, North Carolina, SPX Corporation (NYSE: SPW) is a global Fortune 500 multi-industry manufacturing leader. The company s highly-specialized, engineered products and technologies serve customers in three primary strategic growth markets: infrastructure, process solutions, and diagnostic systems. Gallons per week per 1000 scfm Water a Non-Performing Air Dryer Fails to Remove +60F pdp vs +38F pdp 150 125 100 75 50 25 0 25 50 75 100 125 150 175 Inlet Pressure (psig) Figure 1 The Downstream Effects of a Non-Performing Refrigerated Air Dryer Refrigerated Dryer Designs The most common design for a refrigerated dryer is shown in Figure 2. It utilizes an air-to-air heat exchanger (pre-cooler / re-heater), an air-to-refrigerant heat exchanger (evaporator), a moisture separator, and a refrigeration unit. These components are labeled as items A, B, C, and D, respectively. Many of SPX s innovative solutions are playing a role in helping to meet rising global demand, particularly in emerging markets, for electricity, and processed foods and beverages. The company s products include thermal heat transfer equipment for power plants; power transformers for utility companies; process equipment for the food & beverage industry; and diagnostic tools and equipment for the vehicle service industry. For more information, please visit www. spx.com. Figure 2 Typical Refrigerated Air Dryer 2

The Pre-cooler The pre-cooler section of the air-to-air heat exchanger allows warm, saturated incoming air to be partially cooled by the colder air exiting the moisture separator. This pre-cooling reduces the amount of cooling required in the air-to-refrigerant heat exchanger. The size of the refrigeration unit and, consequently, the electrical energy consumption of the dryer are reduced. The Evaporator The air-to-refrigerant heat exchanger (evaporator) cools the pre-cooled air exiting the air-to-air heat exchanger to the lowest temperature in the dryer. At this point in the system, the maximum amount of water vapor has been condensed into a liquid. If proper and efficient liquid removal is achieved in the separator, this lowest air temperature should closely match the outlet pressure dew point temperature. As explained earlier, the lower the outlet pressure dew point temperature, the more moisture that is removed and discharged from the compressed air stream. However, in order to avoid condensate from freezing in the dryer, the pressure dew point temperature should not drop below +32ºF (0ºC). A second limitation to the amount of cooling done in the evaporator is that the air can only be cooled to some temperature above that of the refrigerant. The more heat exchange surface that is available, the closer the evaporator outlet temperature will be to the refrigerant temperature. This temperature difference between the air exiting the evaporator and the refrigerant entering the evaporator is defined as the evaporator approach temperature. The lower the evaporator approach temperature, the closer the exiting air temperature is to the refrigerant temperature. The Separator After the air exits the evaporator, it enters the separator where the condensed liquid water is removed from the air stream. An efficient separator is imperative in assuring the overall moisture removal performance of the dryer. Any liquid carry-over experienced here will simply be vaporized in the re-heater portion of the air-to-air heat exchanger, only to condense again in the user s air piping. This oftenunderestimated step is responsible for many elevated pressure dew points in dryers capable of achieving low evaporator approach temperatures. The Re-heater After separation, the cool, liquid-free air then enters the secondary side of the air-to-air heat exchanger. It is reheated to some temperature below the warmer incoming air. The temperature difference between the air exiting the dryer and the air entering the dryer is defined as the dryer approach temperature. The smaller the dryer approach temperature, the closer the exiting air temperature is to the inlet air temperature. We will see later how the dryer approach temperature influences the demand placed on the evaporator and the refrigeration system. Performance Standards In order to compare one dryer design and manufacturer to another, the industry has adopted rating standards for refrigerated compressed air dryers. In the United States, the Compressed Air and Gas Institute (CAGI) uses their standard, ADF-100. This document defines the dryer rating inlet condition as +100ºF (+37.8ºC) inlet temperature, saturated with water vapor, 100 psig (6.9 barg) inlet pressure and +100ºF (+37.8ºC) ambient temperature. The pressure drop across the unit must be less than 5 psi (0.34 bar). The manufacturer then assigns an inlet compressed air flow rate (expressed in standard cubic feet per minute, or scfm) and an outlet pressure dew point temperature for each individual model. In the European Community, the adopted criterion is ISO-7183. This standard sets the dryer inlet condition as +35ºC (+95ºF) inlet temperature, saturated with water vapor, 7 barg (101.5 psig) inlet pressure and +25ºC (+77ºF) ambient temperature. Again, the manufacturer must state the inlet flow rate (in normal cubic meters per hour, or nm 3 /h) and the outlet pressure dew point. When comparing equipment, it is imperative that the potential buyer first confirms that all equipment is being rated to the same standard, and produces equivalent pressure dew points at the advertised compressed air flow rates. 3

The Business of Head Loads As stated previously, the purpose of a refrigerated compressed air dryer is to remove moisture from the air stream by cooling the compressed air down to the desired pressure dew point temperature. When evaluating the energy required to accomplish this, one must first assess the amount of heat that must be removed from the air. We will now address this topic. The incoming compressed gas is comprised of two main components: compressed air (mainly, nitrogen and oxygen) and water vapor. Both of these components must be cooled simultaneously. As the mixture is cooled, the water vapor component will change phase, condensing from a vapor to a liquid. The air remains as a gas as it is cooled, and there is no phase change. The heat removed from the water vapor as it changes phase is known as the latent heat. The heat removed from the air, without a change in phase, is termed sensible heat. It is the sum of these heats that determines the total quantity of cooling required to reduce the compressed air from its incoming temperature to the stated outlet pressure dew point temperature. = Sensible + Latent Table 1 compares the latent heat, sensible heat & total heat loads for different inlet temperatures, inlet pressures & outlet pressure dew points. Inlet Inlet +38ºF +50ºF +70ºF Temperature Pressure Pressure Dew Point Pressure Dew Point Pressure Dew Point Sensible Latent Sensible Latent Sensible Latent (BTU/h per 100 scfm) (BTU/hr per 100 scfm) (BTU/hr per 100 scfm) 4536 1359 5895 3240 1122 4362 1080 483 1563 +100 ºF 75 psig 6696 2906 9602 5400 2653 8053 3240 1986 5226 +120 ºF 8856 5567 14423 7560 5284 12844 5400 4570 9970 4536 1061 5597 3240 876 4116 1080 377 1457 +100 ºF 100 psig 6696 2267 8963 5400 2069 7469 3240 1548 4788 +120 ºF 8856 4334 13190 7560 4114 11674 5400 3556 8956 4536 870 5406 3240 719 3959 1080 309 1389 +100 ºF 125 psig 6696 1858 8554 5400 1696 7096 3240 1269 4509 +120 ºF 8856 3548 12404 7560 3368 10928 5400 2910 8310 Table 1 Loads in a Refrigerated Air Dryer From this table, one can see that the sensible heat is a function of inlet temperature and outlet dew point temperature. Higher inlet temperatures will increase the sensible heat load; higher outlet dew point temperatures will lower it. The latent heat is a function of inlet temperature, inlet pressure and outlet dew point. Higher inlet temperatures, lower inlet pressures and lower outlet dew points will all work to increase the amount of latent heat. The values presented in this table substantiate the argument that, for comparability, all equipment must be rated at equivalent inlet conditions and outlet pressure dew points. For example, a dryer designed for the CAGI ADF-100 inlet criteria (+100ºF, 100 psig) and an outlet pressure dew point of 38ºF is expected to handle a total heat load of 8963 BTU/hr for every 100 scfm of inlet flow. A different dryer, rated for the same flow rate, but delivering an outlet pressure dew point of 50ºF, will only handle 7469 BTU/hr for every 100 scfm, a reduction of 17%. Theoretical Limits We have discussed how the use of an air-to-air heat exchanger reduces the amount of refrigeration (and associated energy consumption) required to dry compressed air. A more efficient air-to-air heat exchanger will result in a smaller refrigeration system. How efficient can this air-to-air heat exchanger be? Is it possible that the exchanger is so large that virtually no refrigeration is required? The answer is, of course, no. In a heat exchanger of infinite size and length, the air exiting the separator can only be reheated up to the point where it equals the temperature of the incoming air (a 0ºF dryer approach temperature). Since there is no liquid water present after the separator, 4

the heat added to the exiting air results only in an increase in the air temperature and no change of phase (i.e., sensible heat). It turns out that the sensible heat added to reheat the air stream from the separator temperature to the inlet temperature is equal to the sensible heat removed from the air stream as it is cooled from the inlet temperature down to the outlet pressure dew point temperature. From examining Table 1, subtracting the sensible heat load from the total heat load results in a difference equivalent to the latent heat load. Therefore, the latent heat load is the theoretical minimum heat load that must be removed by the refrigeration system in a compressed air dryer while still providing the stated level of moisture removal. Without the refrigeration capacity to remove the latent heat, the dryer can simply not perform as advertised. Table 2 presents the theoretical minimum heat load distribution for a +38ºF (+3ºC) refrigerated air dryer at different inlet temperatures and pressures. Practical Expectations While an air-to-air heat exchanger producing a dryer approach temperature of 0ºF (0ºC) sounds interesting as a discussion point (i.e., the outlet temperature equals the inlet temperature), it is not realistic from a design and manufacturing point. Even extremely large heat exchangers are not practical in a competitively designed unit. Limitations quickly become evident in the areas of packaging and the control of airside pressure drop. Most notably, the manufacturing costs of such a device makes the extremely large heat exchanger impractical. So what then, is the dryer approach temperature of a practical air-to-air heat exchanger? An examination of today s compressed air dryer designs suggests that practical air-to-air heat exchangers have dryer approach temperatures in the range of 10ºF to 20ºF (5ºC to 11ºC). For a given dryer approach temperature and outlet pressure dew point, the heat loads on the air-to-air and air-to-refrigerant heat exchanger can be calculated. As the dryer approach temperature increases, a larger percentage of the total heat load is shifted to the air-to-refrigerant heat exchanger. These results are also shown in Table 2. Inlet Inlet 0ºF 10ºF 15ºF 20ºF Temperature Pressure Dryer Approach (Theoretical Minimum) Dryer Approach Dryer Approach Dryer Approach Air Refrig Air Refrig Air Refrig Air Refrig (BTU/hr per 100 scfm) (BTU/hr per 100 scfm) (BTU/hr per 100 scfm) (BTU/hr per 100 scfm) 4536 1359 5895 3456 2439 5895 2916 2979 5895 2376 3519 5895 +100 ºF 75 psig 6696 2906 9602 5616 3986 9602 5076 4526 9602 4536 5066 9602 +120 ºF 8856 5567 14423 7776 6647 14423 7236 7187 14423 6696 7727 14423 4536 1061 5597 3456 2141 5597 2916 2681 5597 2376 3221 5597 +100 ºF 100 psig 6696 2267 8963 5616 3347 8963 5076 3887 8963 4536 4427 8963 +120 ºF 8856 4334 13190 7776 5414 13190 7236 5954 13190 6696 6494 13190 4536 870 5406 3456 1950 5406 2916 2490 5406 2376 3030 5406 +100 ºF 125 psig 6696 1858 8554 5616 2938 8554 5076 3478 8554 4536 4018 8554 +120 ºF 8856 3548 12404 7776 4628 12404 7236 5168 12404 6696 5708 12404 Table 2 Load Comparisons for a +38ºF Pressure Dew Point 5

Energy Consumption Once the heat demand on the evaporator has been established, the size of the refrigeration unit can be determined, and the power consumption of the entire dryer can be calculated. To do this, one must first recognize that there are three (3) main components in a refrigerated dryer that consume electrical power: The refrigeration compressor, The refrigerant condenser cooling fan motors (assuming air-cooled units), And the electrical control system. For this analysis, we will assume that the units are air-cooled, and the electrical power consumed by the control system (indicator lights, electronic control boards, electronic condensate drain valves, etcetera) is negligible. We will now assess the power consumption of the refrigeration compressor and the cooling air fan motors. Refrigeration Compressor The refrigeration industry has experienced a dramatic change over the past fifteen years. New environmental laws have resulted in a large selection of new CFC-free refrigerants. Traditional reciprocating compression technologies (piston-type machines) are being replaced with more efficient rotary technologies (scroll and screw compressors). This vast product mix has complicated the issue of energy efficiency in refrigeration units. The simplest way to assess the amount of electrical power required to produce a desired amount of refrigeration is to use the Energy Efficiency Rating (EER) of the compressor. This value is simply the quotient of the amount of refrigeration produced (expressed in BTUs per hour, or Watts), divided by the amount of energy consumed by the refrigeration compressor (expressed in Watts). These figures, for a given compressor, will vary as the compressor suction and discharge conditions change. Therefore, it is important that compressors are competitively analyzed at equivalent inlet and outlet conditions. When used in a refrigerated dryer, it is proper to use the suction and discharge values that occur as the dryer is operating at its rated condition (either CAGI ADF-100 or ISO-7183). For most dryers running at the CAGI ADF-100 rating point, these approximate values are +35ºF (+1.7ºC) saturated suction temperature and a +130ºF (+54ºC) saturated discharge temperature. For ISO-7183 conditions, the saturated suction temperature is also +35ºF (+1.7ºC), but the saturated discharge temperature drops to +105ºF (+41ºC) due to the lower ambient temperature. Typical refrigeration compressors at the CAGI operating points will generate EERs in the range of 8.0 to 10.0 BTU/hr-Watt (2.3 to 2.9 Watts/Watt). Table 3 shows the expected compressor power consumption for both the theoretical (infinite air-to-air) and the practical cases (dryer approach temperature of 15ºF) discussed earlier in Table 2. This table assumes a dryer inlet condition of +100ºF, saturated with water vapor, 100 psig and a +38ºF outlet pressure dew point. An average refrigeration compressor EER value of 9.0 BTU/hr-Watt (2.6 Watts/Watt) is used. The user should be cautioned that, in most cases, dryer designers would not utilize compressors with the exact refrigeration capacity necessary for the evaporator heat load. Compressors are only available in incremental sizes, and the dryer designer will likely be forced to use a compressor with more capacity than actually required. In these cases, the air-to-air heat exchanger may be reduced in size so as to optimize the design and reduce manufacturing costs and pressure drop. Cooling Air Fan Motors Evaluating the power consumed by the cooling fan motors is more difficult than assessing the refrigeration compressor. These motors are smaller, less efficient electrical components. Variations affecting air-cooled condenser designs include the fan blade pitch, the condenser face area, static pressure drop and the desired cooling air velocities. These design variables can result in fan motors of drastically different 6

sizes and energy requirements. Fortunately, the power consumed by the cooling air fan motors is much less that the refrigeration compressor. A study of current manufacturers data provides the necessary information to develop an industry average. A good approximation of the fan power required for air-cooled refrigeration units is expressed by the equation: P = (1.5 x 10-5) Q + 0.3, Where, P = fan power, in kw Q = refrigeration capacity, in BTU/hr The results are shown in Table 3. Inlet Flow Rate 0ºF 15ºF Dryer Approach (Theoretical Minimum) Dryer Approach (Expected Practical) Compressor Estimated Fan Power Compressor Estimated Fan Power Refrigerant Power @ Power Consumption Refrigerant Power @ Power Consumption Load EER=9.0 Load EER=9.0 (scfm) (BTU/hr) (kw) (kw) (kw) (BTU/hr) (kw) (kw) (kw) 500 11,335 1.26 0.47 1.73 19,435 2.16 0.59 2.75 750 17,003 1.89 0.56 2.44 29,153 3.24 0.74 3.98 1000 22,670 2.52 0.64 3.16 38,870 4.32 0.88 5.20 1250 28,338 3.15 0.73 3.87 48,588 5.40 1.03 6.43 1500 34,005 3.78 0.81 4.59 58,305 6.48 1.17 7.65 2000 45,340 5.04 0.98 6.02 77,740 8.64 1.47 10.10 2500 56,675 6.30 1.15 7.45 97,175 10.80 1.76 12.55 3000 68,010 7.56 1.32 8.88 116,610 12.96 2.05 15.01 Table 3 Power Consumption in a Refrigerated Air Dryer Power The total power consumed by the refrigerated dryer is simply the sum of the compressor power and the cooling fan power: Power = PowerCompressor + PowerFan The results are given in Table 3. Results Table 3 displays the total theoretical minimum power consumption for air-cooled refrigerated compressed air dryers at different compressed air flow rates. Also shown are the expected practical values. This information can be used when evaluating air-cooled equipment. (When evaluating water-cooled designs, the user should subtract the power consumed by the fan motors.) For example, in a 1000 scfm refrigerated dryer, power consumption less than 3.16 kw is simply not possible; whereas a value closer to the expected number of 5.20 kw is acceptable. In anther example, Manufacturer A advertises a 2000 scfm refrigerated air dryer to deliver a +38ºF (+3ºC) outlet pressure dew point at the CAGI ADF-100 rating conditions. This manufacturer also claims the unit will consume 7.0 kw of electrical power. Referring to Table 3, this value is only slightly above the theoretical minimum power consumption of 6.02 kw. It is highly unlikely that all of the performance claims of this particular dryer manufacturer are going to be met. Either the unit will consume more power than listed, while providing the promised level of moisture removal, or, the unit will not remove the stated amount of moisture. In the worst scenario, neither the power consumption nor the moisture removal performance will be met. 7

Conclusion Evaluating different brands of refrigerated compressed air dryers can become a difficult and confusing task. The extensive array of performance criteria (flow rate, inlet temperature, inlet pressure, outlet pressure dew point, pressure drop, etcetera) permits manufacturers to publish data at conditions that benefits them favorably. An educated potential buyer can wade through these issues by first confirming that all equipment under consideration is rated at the same industry standard, the same inlet flow rate and the same outlet pressure dew point. When evaluating energy consumption, the information presented above provides guidelines for determining the quantity of electrical power that must be consumed if the unit is to perform to the advertised specifications. Any unit with advertised energy consumption below the theoretical minimum values in Table 3 is suspect for actual energy consumption and / or outlet pressure dew point performance. In these cases. buyers beware- if it appears too good to be true, it most likely is! Advertised energy consumption values should be centered on the practical expected values listed above. By confirming that a reasonable amount of energy is being consumed, the user has additional assurance that the expected quality of the compressed air system will be realized. Written by Timothy J. Fox, P.E. Hankison International, an SPX Brand Canonsburg, Pennsylvania For more information please contact Jay Francis, Vice President of Global Strategic Accounts and Marketing SPX Flow Technology at jay.francis@spx.com SPX FLOW TECHNOLOGY 1000 Philadelphia Street Canonsburg, PA 15317-1700 USA P: (724) 745-1555 F: (724) 745-6040 E: hankison.sales@spx.com SPX reserves the right to incorporate our latest design and material changes without notice or obligation. Design features, materials of construction and dimensional data, as described in this bulletin, are provided for your information only and should not be relied upon unless confirmed in writing. Please contact your local sales representative for product availability in your region. For more information visit www.spx.com. The green > is a trademark of SPX Corporation, Inc. 8 ISSUED 10/2012 Energy Consumption COPYRIGHT 2012 SPX Corporation