SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

Similar documents
SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: ARGONITE Engineered Fire Suppression System

FM-200 In-Cabinet Series

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

Data/ Specification Sheet

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

Superior by Design The Kidde ADS TM FM-200 System

Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

First Revision No. 49-NFPA 17A-2015 [ Detail ] Submitter Information Verification. Committee Statement 7/30/2015 1:35 PM

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

CORE Protection Fire System Specification

ANSUL I-101 INDUSTRIAL FIRE SUPPRESSION SYSTEM TECHNICAL MANUAL VEHICLE PAINT SPRAY BOOTH PROTECTION MANUAL

Industrial Dry Chemical Fire Suppression System

Badger Universal Control Head

STORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop

UNIFIED FACILITIES GUIDE SPECIFICATIONS

NFPA 96, 2017 REVIEW SUMMARY

Hospitals and Major Medical Centers

STR-Series Indirect-Fired Air Turnover Units

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Kitchen Fire Suppression Systems Post-Event Analysis

Types of Detection. Fusible Link Detection - Most Common

OWNER'S OPERATION AND MAINTENANCE MANUAL

Amerex Clean Agent System with FM200. Potential Applications: System Coverage Overview: Approvals and Standards:

DETECT-A-FIRE Heat Detectors

A. Section includes wet-pipe sprinkler system, system design, installation, and certification.

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

Twin-Agent Fire Fighting/Securing Systems Specifications

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Page 1 of 7. Replaces Form No. F_ Rev 16.3 (Added 16X22 and 18X20 coverage areas)

Sprinkler Identification Numbers

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

Standard Spray concealed horizontal sidewall sprinkler VK481

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

mirage standard response concealed pendent sprinkler vk492 (K5.6)

SERVICE VERSUS REMOVAL OF OBSOLETE COMMERCIAL KITCHEN PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

11.2K * Pendent Extended Coverage, Light and Ordinary Hazard General Description. Model/Sprinkler Identification Numbers (SINs) Technical Data

5.6K Horizontal Sidewall Standard and Quick Response, Extended Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

A. Section Includes: Fire extinguishers and cabinets including necessary accessories.

ANSUL TO-ANSUL. For more information... Check your local Yellow Pages for your authorized Ansul Restaurant Systems Distributor.

Series DS-1 Dry-Type Sprinklers 5.6K Pendent, Upright, and Horizontal Sidewall Quick Response, Standard Coverage General Description

A Guide for Meeting NFPA 10 Subsection

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

Model F3-80 Dry K8.0 (115 metric) Standard-Response, Standard Spray Sprinklers

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

TECHNICAL DATA. Page 1 of 5

Basic Vehicle Fire Protection Manual

VENTLESS EXHAUST HOOD OPERATORS MANUAL AND PARTS LIST REV. MAY 2016

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA. Refer to Approval Chart 1 and UL Design Criteria for culus Listing requirements that must be followed.

Design & Construction Standards, Revised January

Model F1 LO K 8.0 (115 metric) Standard Response Sprinklers

TECHNICAL DATA OBSOLETE

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

D. Reference Standards (Utilize latest editions available):

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

SECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM

MAXIMUM KNOCKDOWN ABILITY Large Dry Chemical Fire Suppression Systems

Fire Safety Compliance

Carbon Dioxide Fire Suppression Systems

CertifiedSafetyPassion. CertifiedSafetyPassion. Distributors and UL AML

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

5.6K Pendent, Upright, and Horizontal Sidewall Standard Response, Standard Coverage General Description. Model/Sprinkler Identification Numbers (SINs)

FREEDOM RESIDENTIAL CONCEALED PENDENT LEAD FREE SPRINKLER VK4570 (K4.9) TECHNICAL DATA

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

PRODUCT CATALOG FOR ALL INFORMATOIN AND REQUIREMENTS. WEB:

esfr dry pendent sprinkler Vk501 (k14.0)

FireLock High Pressure Butterfly Valve. System No. Submitted By Spec Sect Para Location Date Approved Date

mirage Quick response concealed pendent sprinkler vk465 (K4.2)

Don t Compromise on Fire Safety Choose Certified Quality Products

SPECIAL HAZARDS THE MOST ADVANCED TECHNOLOGY FOR PROTECTING

Extinguishers. Commercial Industrial High rise buildings

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

The D1000. Typical Specifications: Standard Options*: Model: D1030-I_-DF Spec & Submittal Version 2.3 D1000-I_-DF D1000-I_-DF-NFPA101

Transcription:

1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation pits and associated ductwork requiring protection. 1.2 The system shall be Kidde Dry Chemical, Model IND manufactured by Kidde Fire Systems, 400 Main Street, Ashland, MA or approved equal. The manufacturer shall be ISO 9001:2000 certified. 2. CODES/STANDARDS COMPLIANCE 2.1 The system shall conform to and be in accordance with the following: A. UL 1254, with an effective date of September 29, 1998, Underwriters Laboratories Standard for Fire Extinguishing Systems for Protection of Industrial Hazards B. FM Approvals C. NFPA 17, Standard on Dry Chemical Extinguishing Systems D. NFPA 33, Standard for Spray Application Using Flammable or Combustible Materials E. NFPA 34, Standard for Dipping and Coating Processes Using Flammable or Combustible Liquids F. Kidde Model IND Instruction Manual and all applicable addenda, as identified by Underwriters Laboratories File No. UL EX-2153 G. All applicable insurance company requirements. H. All applicable local and state codes and standards, I. Requirements of the Local Authorities Having Jurisdiction (AHJ). March 2005 1 of 5 www.kiddefiresystems.com

2.2 The fire suppression system must have the following listings and approvals: The manufacturer shall meet ISO 9001 requirements for the design, production and distribution of the IND Dry Chemical fire suppression systems. 3. SYSTEM DESCRIPTION 3.1 All Industrial Dry Chemical fire suppression equipment and accessories must be manufactured and/or supplied by: Kidde Fire Systems 400 Main Street Ashland, MA 01721 U.S.A. Phone: (508) 881-2000 URL: http://www.kiddefiresystems.com 3.2 The manufacturer shall warrant all IND fire suppression system products for six years from the date of purchase. 3.3 The system shall be supplied and installed by a factory-authorized, Kidde Fire Systems distributor. The organization and Installer shall be trained by the manufacturer to calculate and design, install, test and maintain the IND Dry Chemical Fire suppression system and shall be able to produce a certificate stating such on request. 3.4 The systems design shall be of a pre-engineered, modular type 3.5 The system shall consist of Kidde Dry Chemical storage Cylinder(s), Kidde actuation hardware and Kidde agent distribution nozzles attached to a pipe network. 3.6 Agents 4. COMPONENTS The system shall use Kidde BC (sodium bicarbonate) dry chemical agent. 4.1 IND Cylinder and Valve Assembly A. The Kidde dry chemical agents shall be contained in one or more stored pressure DOT rated steel cylinder and valve assemblies. Cylinders requiring an external source to pressurize the agent shall not be acceptable. The cylinder and valve assemblies shall have the following features: 1. The Kidde Model IND cylinder(s) shall be of type and size as required by the Kidde Instruction Manuals. March 2005 2 of 5 www.kiddefiresystems.com

2. The cylinder(s) shall have a tin-nickel alloy plated brass valve, with pressure gauge. Agent cylinders without pressure gauges shall not be acceptable. The valve shall contain a check stem which is operated by the action of the actuating assembly. Agent cylinders utilizing a burst disc as a means of sealing the discharge outlet will not be acceptable. 3. The cylinder and valve assemblies shall be pressurized to 360 PSIG (24.8 bar) with nitrogen. The cylinder and valve assemblies shall be capable of being stored and operated at the following temperature ranges: -40 F to 120 F (-40 C to 49 C) for industrial applications 0 F to 120 F (-17 C to 49 C) for paint booth applications 4. The cylinder shall have a shield to protect the gauge. The shield shall be a separate assembly from that of the gauge, and shall be separately mounted. B. Sufficient cylinder and valve assemblies shall be provided to protect the entire hazard area. Listed bracketing shall be provided to mount the cylinder securely to the intended mounting surface. 4.2 Control Equipment A. The system control equipment shall be capable of all functions associated with automatically and manually discharging the dry chemical agent from all cylinder and valve assemblies, including automatic shutdown of the heat source or fuel and electrical power to all protected areas upon system discharge. B. The system control equipment shall include a control head, and actuator(s) for each system cylinder valve. The control head can attach with two bolts to an actuator or can be wall mounted, whichever is applicable. All mechanical components of the control heads shall be enclosed. No exposed levers, except for the local manual actuation handle, will be permitted. C. The control head shall be actuated automatically, by mechanical means. The control head shall be equipped with micro-switch contacts for audible alarm and/or equipment shutdown. For multiple cylinder systems additional actuators shall be provided for each additional cylinder. All cylinders protecting one hazard area must be connected for simultaneous discharge by all methods of system actuation. March 2005 3 of 5 www.kiddefiresystems.com

D. For automatic mechanical actuation, the system control head shall be activated by Kidde Fire Systems KG series link fire detectors. A mechanical thermo-bulb link system shall require no outside source of power for operation. Thermo-bulb links shall be located in accordance with Kidde's Model IND Instruction Manual part number 220423 or 83-100036-001, and applicable NFPA and UL standards. Thermo-bulb links shall be chosen with a rating suitable to their expected normal exposure temperature. 4.3 Distribution Nozzles Nozzles shall be located to protect the exhaust duct(s), plenum(s), and all work areas requiring protection. Nozzle choice, coverage and location shall be per the applicable Kidde UL listed instruction manual. 4.4 Distribution Piping A. The distribution system shall be NPT Schedule 40 black steel, stainless steel, or galvanized pipe. B. All fittings for Schedule 40 pipe shall be standard weight black malleable iron, galvanized, ductile iron, steel or stainless steel. Fittings may be chrome plated. 5. SYSTEM INSTALLATION AND COMMISSIONING 5.1 IND Fire Suppression System Equipment The installer shall install the system in accordance with the manufacturer s installation, operation and maintenance manual. 5.2 Training Requirements The installer shall be certified and trained by the manufacturer on installation, design and maintenance of the Kidde IND fire suppression system. March 2005 4 of 5 www.kiddefiresystems.com

5.3 Routine Maintenance Routine maintenance shall be performed as recommended by the manufacturer s Design, Installation, Operation and Maintenance manual, NFPA 17, NFPA 33, NFPA 34, and other appropriate standards. March 2005 5 of 5 www.kiddefiresystems.com