FS80-C Flow Switch. Features and Benefits. Allows user select the setting according the needs of system

Similar documents
! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions.

INSTRUCTION MANUAL MM-601REVI. Series FS4-3 General Purpose Liquid Flow Switch

! WARNING. Before using product, read and understand instructions.

INSTRUCTION MANUAL MM-615E. Series FS1 High Sensitivity Liquid Flow Switch

Powers Controls ET 134 Low Temperature Detection Thermostat

F261 Series Fluid Flow Switches

W43A Humidistat. Features and Benefits

INSTALLATION INSTRUCTIONS

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

Powers Controls Low Temperature Detection Thermostat

I ntroduction. Series F61. Liquid Flow Switches. Feature and Benefits

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

MR3CCUHV Temperature/Defrost Control

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

Series F61. Liquid Flow Switches. Feature and Benefits. T-body and Pipe-insert types available

Flow Switches. Liquid Flow Switches. Mounting Methods

Electro Controls. Flow WattsIndustries.co.uk

A19, A28 Series Thermostats for Agricultural Buildings

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-214(C) Series 61 Low Water Cut-Off OPERATION

A99B Series Temperature Sensors

TRUERH Series HE-67xx Humidity Element with Temperature Sensor

System 350 S350A Temperature, S351A Humidity, and S352A Pressure Stage Modules

TC-5231 Series, TC-5232, & TC-5241 Series

Flow Switches. Liquid Flow Switches. Mounting Methods

13-1. Temperature Regulator

T4031A,B,P; T6031A,B Refrigeration Temperature Controllers

Series A36 3- and 4 Stage Thermostats for Refrigeration, Cooling, Heating, Ventilation and Air-conditioning. Feature and Benefits

L62GB BASO Safety Shutoff Device

Series 47 and 247 Mechanical Water Feeders. Series 47-2 and Combination Mechanical Water Feeder/Low Water Cut-Off ! WARNING

Thermostats type KPU REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Engine Block Heater Service Kits (Tank Type) 30RZ/33RZ/45RZ (CSG 649 Ford Powered) Standby Generator Sets

T500 Series Non-Programmable Thermostats

Location Requirements

Aquastats. Aquatrol Indoor/Outdoor Control. Automatic Changeover Switch 16/05/08

Thermostat KPU. Data sheet

Series 1140 and 1141 Temperature Regulators

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

KOBOLD PSR/PS FLOW SWITCH

Commercial/Industrial Combustion Control Level Three Announcement

XT Series Thermostats

INTRODUCTION / TABLE OF CONTENTS

Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

Powers TM Controls ET 134 Line Voltage Room Thermostats

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

P266 Series Single-Phase Condenser Fan Speed Control

RLD-H10P Refrigerant Leak Detector

! WARNING. Before using product, read and understand instructions.

Standard Downrod for ceilings 8-10 feet high. Longer Downrod for ceilings 10 feet or higher

Pre-Fab Easy Installation For Model 0011-CF-USK Installation and Operating Instructions for Existing Homes Or Buildings with Standard Piping

Single pressure controls for Refrigeration, Air-conditioning and Heatpump applications

WAILEA OWNER S MANUAL

MODEL /4" Conduit. (By others) Terminal Strips Companion unit (without electronics) not shown. Approximate Preload

INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / , , , IMPORTANT INFORMATION

SAVE THESE INSTRUCTIONS

DISHWASHER INSTALLATION GUIDE SPECIFICATIONS, INSTALLATION, AND MORE

ARIN THERMOSTATIC SHOWER SYSTEM

EEMAX HOME ADVANTAGE

USER S MANUAL BUCKET FAN SERIES BUCKET FAN WHISPER SERIES

T R A N S F O R M I N G T E C H N O L O G I E S, L L C O U T S T A N D I N G A L T E R N A T I V E S I N S T A T I C C O N T R O L

INSTALLATION INSTRUCTIONS

Temperature, Mechanical

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

TEMPERATURE CONTROLLERS

Duct and Rough Service Carbon Monoxide Sensor

Brasch Hazardous Location Unit Heaters

1510 Side Mounted Level Switch

SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½

CORALAIS BODYSPA BATH AND SHOWER FAUCET

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Series A28 Two stage Thermostats. Feature and Benefits

y Small dimensions. Easy to install in refrigerated counters or cold rooms

T7079A,B Solid State Remote Temperature Controllers

DAD-500 (130026) DESICCANT AIR DRYING SYSTEM

Installation S19-324D1. Class I, Division 1, Groups C & D Explosion Proof. Emergency Signaling System

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

INSTALLATION USE & CARE MANUAL ALL WEATHER SL-SERIES QUARTZ TUBE ELECTRIC INFRARED RADIANT HEATER

CR7075 Two-Stage Lighting Controller

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

TK-1001, 1101, 1201, 1301, 1601

RLD-H10G Refrigerant Leak Detectors

Model 9001EXP Alarm. NOTE TO INSTALLER: Please leave this information with the Maintenance Department. LIMITED WARRANTY

Surna 25-Ton Chiller Operating & Maintenance Manual

Heated Bed Installation Instructions

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S2 S4 S5 SS6 SS7 S8

INSTALLATION INSTRUCTIONS AND OWNER S MANUAL

Bulletin , March Electric Hot Gas Bypass Valves

Installation and Maintenance Manual IM 1102

Table of Contents What to Expect with Your Installation. Tools Needed. Wall Control

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

CAUTION. No-Load Performance, Controls in Normal Position

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

TK-2001, TK-2012, TK-2201, TK-3001, TK-3201, TK-4001, TK-4012, TK-4212 TK

Table of Contents. What to Expect with. Mounting Options. Tools Needed. Wall Control

Cable Actuated Sensor Industrial User Scalable 4 20mA

MINIATURE THERMOSTATIC VALVE

V48 Series 3-Way Water Regulating Valves For Cooling Tower Systems

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

Transcription:

Product/Technical FS80-C Issue Date 0912 FS80-C Flow Switch Description 1) FS80-C Flow Switch responds to fluid flow in lines carrying water, ethylene glycol, or other Non-hazardous fluids 2) FS80-C Flow Switch uses a variety of paddle sizes to respond to fluid flow rates in applications with pipe sizes greater than 1-inch trade size 3) Single-Pole, Double-Throw (SPDT) flow switch that can be wired to energize one device and de-energize another device powered from the same source when liquid flow either exceeds or drop below the set flow rates Figure 1 FS80-C Flow Switch Features and Benefits Maximum fluid pressure of 1.5MPa Adjustment Flow Switch Paddle Adjustable Flow Rate Range IP55 Enclosure Permits use in a wide range of pressure flow conditions. Allows from 1 in. to 6 in. pipe application Allows user select the setting according the needs of system Allows use in indoor or outdoor applications Application FS80-C Flow Switch IP55 Enclosures Use IP55 enclosures of FS80-C flow switch for IMPORTANT:FS80-C Flow Switch is designed for use only as operating controls. Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit contrlos) that protect against, or systems (alarm. Supervisory systems) that warn of, control failure. indoor or outdoor applications in high-humidity environments. Use this model with pipes carrying fluids at temperatures in the range of -25~110 where fluid temperatures are above ambient dew point. The SPDT switch on the FS80-C has color-coded terminals. Red is common, and closed to Blue upon flow increase and to Yellow upon flow decrease. See Figure 2 and Table 1 for switch action and flow rates. Use FS80-C Flow Switch in application with fluid pressures up to 1.5MPa. A typical application for FS80-C flow switch is to shut down the refrigeration commpressor on a fluid chiller system if flow stops, reducing chances of chiller freeze-ups. The performance specifications conform to acceptable industry standard. For application to conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc., shall not be liable for damages resulting from misapplication or misuse of its products. 2009 Johnson Controls, Inc. www.johnsoncontrols.com 1

FS80-C Flow Switch comes with 4-piece paddle (1 in., 2 in,. 3 in., and 6 in. segments). Adjust the paddle to the size of the pipe in which it will be installed. If needed, use the template (see Figure 5), and trim the large paddle at the arc corresponding to pipe size and install. Example, if 3 pipe is used, Install 1,2 and 3 segments (see figure 3), if 1-1/2 pipe is used, trim the INSTALLATION AND WIRING Figure 2 Switch Action 2 paddle to the pipe size or use the 1 paddle segment. Adjusting the Flow Switch Paddle IMPORTANT:To allow the switch to detect changes in the flow condition, the paddle must not touch the pipe or any restrictions in the pipe. IMPORTANT:Do not use FS80-C on systems with Figure 3 Paddle Installation Example flow velocity greater than 3m/sec. Figure 4 Dimensions (mm) Figure 5 Teimming Template for the Extra Paddle 2 FS80-C Flow Switch Product/Technical Bulletin

Mount the FS80-C in a section of pipe where there is a straight run of at least five pipe diameters on each side of the Flow Switch. See Figure 6 Product/Technical FS80-C Issue Date 0912 FS80-C flow switch may be mounted in a horizontal pipe line or a vertical pipe line with upward liquid flow. It is not recommended for installations where flow is downward. When mounted in a vertical pipe with upward flow, the switch will trip at a slightly higher flow than shown in table 1 Typle Flow Rates, due to the effect of gravity on the switch mechanism Wiring WARNING:Shock hazard Disconnect the power supply before the wiring Figure 6 Typical Installation The switch should be mounted so the terminals or wire leads are easily accessible for wiring Note:These flow switch must not be subjected to water hammer.if a fast-closing valve is located downstream of the flow switch, a suitable water hammer arrester must be used. See figure 7. conncetions are made to avoid possible electrical shock or damage to the equipment. Make all wiring connections using copper conductors only Use the terminal screw furnished. Substitution of other screws will void the warranty and agency approvals. Adjustments CAUTION:Improper operation hazard The switch is factory set at approximately the minimum flow rate (see table 1 Typical Flow Rate). Figure 7 Arrester Location Schematic Mount the flow switch in a standard 1 in.x 1 in.x 1 in. tee for 1 in. pipe installation. Use a reducing tee for larger sizes of pipe to keep the flow switch close to the pipe and provide adequate paddle length in th flow stream Example: Use a 2 in.x 2 in.x 2 in. tee for a 2 in. pipe. If a standard 2 in.x 2 in.x 2 in. tee is used, install a face or hex bushing in the top opening to reduce it to 1 inch. CAUTION: Equipment damage hazard. To avoid damaging the switch, do not tighten the switch to the tee by grasping the switch enclosure. Use only the wrench flats provided (see Figure 4). Screw the flow switch in position so the flat of the paddle is at a right angle to the flow. The arrow on the Do not set lower than the factory setting as this may result in the switch failing to reture to a no flow positon. CAUTION:Equipment damage hazard Sealed settings(screws marked with red paint) are not intended to be changed. Adjustment attempts may damage the control or cause loss of calibration, voiding the warranty. To adjust the setting of the flow switch: 1. Remove the FS80-C cover. 2. For higher flow rates, turn the adjusting screw clockwise. To lower the flow rates after it has been raised from the factory setting, turn the adjusting screw counterclockwise. See Figure 2. 3. Check to see that the flow switch is not set lower than side of the case must point in the direction of the flow factory setting by depressing the main lever numerous The performance specifications conform to acceptable industry standard. For application to conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc., shall not be liable for damages resulting from misapplication or misuse of its products. 2009 Johnson Controls, Inc. www.johnsoncontrols.com 3

times. If the lever fails to click upon return at any time, turn the adjusting screw clockwise until the lever clicks upon return every time. See Figure 8. Checkout Procedure The circuit between the red and blue leads (terminals) will be closed when sufficient liquid flows through the pipe to trip the flow switch. Before leaving the installation, observe at least three complete operating cycles to be sure that the Flow Switch and the system to which it is connected are functioning correctly. Figure 8 Minimum Adjustment Table 1 Typical Flow Rate- m 3 /h Required to Actuate Switch Pipe Size(in.) 1 1-1/4 a 1-1/2 a 2 2-1/2 b 3 4 c 5 c 6 c 8 c Min Adj. Flow Increase R to B Closes Flow Decrease R to Y Closes 0.95 1.32 1.70 3.11 4.09 6.24 0.57 0.84 1.14 2.16 2.84 4.32 14.8 (8.4) 11.4 (6.1) 28.4 (12.9) 22.9 (9.3) 43.2 (16.8) 35.9 (12.3) 85.2 (46.6) 72.7 (38.6) Max Adj. Flow Increase R to B Closes Flow Decrease R to Y Closes 2.0 3.02 4.36 6.59 7.84 12.0 1.93 2.84 4.09 6.13 7.3 11.4 29.1 (18.4) 27.7 (17.3) 55.6 (26.8) 53.4 (25.2) 85.2 (32.7) 81.8 (30.7) 173 (94.3) 166 (90.8) a.values for 2 in. paddle trimmed to fit pipe. b.values for 3 in. paddle trimmed to fit pipe. c.flow rates for these sizes are calculated installed 1 in., 2 in., 3 in. paddle. Bracket valves are for a switch with a 6 in. paddle, for 4 in. and 5 in. line pipe, the 6 in. paddle is trimmed to a 4 in. and 5 in. length. For 8 in. line pipe, values are for install 1 in., 2 in., 3 in. and 6 in. paddle. Table 2 Troubleshooting Symptom/Problem Solution Liquid from the tank is leaking into enclosure due to bellows failure. Switch will not activate due to debris caught within the switch mechanism Control switch action is reversed Control does not switch Control will switch on flow but won t return when there is no flow Control does not switch on flow increase Replace unit. Clear any debris within the switch mechanism. Test the operation of switch several times for proper operation Ensure connections follow wiring diagrams Check connections On vertical pipe, ensure that direction of flow is up. The arrow on switch must point in direction of flow (up). Check for cracked/broken paddle. Replace if necessary 4 FS80-C Flow Switch Product/Technical Bulletin

Technical Specification Product Maximum Fluid Pressure Fluid Temperature Ambient Temperature FS80-C 1.5MPa Minimum:-25 Maximum:110 Minimum:-20 Maximum:60 Electrical Rating 110VAC 220 VAC Horsepower(HP) 1 1 Full Load Amperes(A) 16 8 Locked Rotor Amperes(A) 96 48 Non-inductive Amperes(A) 16 16 Pilot Duty Wiring Connection Paddles Material Switch Pipe Connection Agency listings Shipping Weight, lb (kg) 125VA at 24~277VAC Screw Type Terminals 1 in., 2 in., 3 in., 6 in. Paddle are supplied with FS80-C SS301 SPDT 1 11-1/2NPT Threads CE 1.26lb(0.57kg) FS80-C Flow Switch Product/Technical Bulletin 5