GESTRA Steam Systems BK 37 BK 28 BK 29. Installation Instructions Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

Similar documents
GESTRA Steam Systems BK 15. Installation Instructions Steam Trap BK 15, DN 40-50

MK 45-1 MK 45-2 MK 45 A-1 MK 45 A-2

GESTRA Steam Systems DK 45. English. Installation Instructions Steam Trap DK 45

BK 46. Installation Instructions Steam Trap BK 46

GESTRA Steam Systems ER 50-1, ER Installation Instructions Level electrode

GESTRA Steam Systems LRG English. Installation Instructions Conductivity Electrode

TRG 5-6x. GESTRA Steam Systems. Installation Instructions

MK 45 A. Stainless Steel Design. Installation Instructions Steam Trap MK 45 A

SMK 22 SMK SMK SMK 22-82

GESTRA Steam Systems NRGS 11-2, NRGS Installation Instructions Level Electrode Types

BK 45 BK 45-U BK 45-LT BK 46

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

TRG 5-53 TRG 5-54 TRG 5-55 TRG 5-57

NRG NRG NRG NRG

GESTRA. Program for Universal Connections. The Smart Solutions

opening trap 30 mm Space required for Space required for opening trap 30 mm MK 45-1 with flanged ends (to DIN)

ø D ø g ø k Max. service [barg] pressure [psig] H 1 96 L BK 45 with butt-weld ends End connections Screwed Socket-weld

Level Electrode NRG NRG Original Installation Instructions English

Installation & Operating Instructions

Temperature Sensor TRG Original Installation Instructions English

Level Electrode NRG Original Installation Instructions English

Conductivity Electrode LRG Original Installation Instructions English

GESTRA Steam Systems OR Installation Instructions Oil & Turbidity Detector OR 52-7

Model: 1200 Model: 1200-G Model: 1200-N Float-Controlled Condensate Trap, PN 40

Operating Manual. Model: Float-Controlled Condensate Trap, PN Safety instructions. 2 General description and usage

GESTRA Information A 1.5

Model: 1100 Float-Controlled Condensate Trap, PN 25

GESTRA Information A 1.7

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

Model: 1413 Model: 1418 Float-Controlled Condensate Trap, PN 100

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

Steam Traps and Steam Trap Testing

INSTALLATION, OPERATION

Inverted Bucket Steam Traps

Mechanical seals external, single or double, to DIN EN 12756

LP30 High Integrity Low Level Alarm Probe Installation and Maintenance Instructions

Friwa Compact. Operating instructions EN

Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

GESTRA. Steam Traps and Steam Trap Testing. For all applications

Water level controller and limiter

Installation and Maintenance Manual Forbes Marshall Tracer Line Trap FMMST63

THERMODYNAMIC STEAM TRAP

GESTRA. Product Overview. The optimum components for every application

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

INSTRUCTIONS CertoClav EL

Installation and Maintenance Manual Forbes Marshall Bucket Trap FMBT50

GESTRA. Product Overview. The optimum components for every application

Operating and installation instructions

INSTALLATION, OPERATION

Installation, Operation and Maintenance Instructions Electric Flow Heater OM009

Ball Float Steam Trap with Integral Spiratec Sensor and Flanged Connections

Product overview. the optimum components for every application

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

PLATE HEAT EXCHANGERS. Operation and Maintenance Manual

FT14 Ball Float Steam Trap (Screwed)

GESTRA Steam Systems NRS English. Installation Instructions Level Switch NRS 1-51

FLOAT AND THERMOSTATIC STEAM TRAPS FLT17 (DN 1/2 to 1 ; DN15 to DN25)

Series 1140 and 1141 Temperature Regulators

HKF 8180 Operating instructions

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

GESTRA. Steam traps and monitoring equipment. The right choice in every case

Instruction Manual. Pharma-line ESE02198-EN Original manual

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-i.

ICS Float and Thermostatic Steam Trap Installation and Operation Manual

Circulation heaters for ATEX/IECEx hazardous areas or in non-atex version

STEAM - WATER MIXERS ADCAMIX MX20

Bedienungsanleitung. Fass-, Behälter- und Containerpumpen. F dichtungslos. F ,98% Fassentleerung. F

Operating Instructions for Rotor flow Indicator. Model: DKF

! WARNING. Before using product, read and understand instructions.

MFP14 Automatic pumps. for condensate and other industrial fluids

GESTRA. GESTRA Steam Systems TRS English. Installation & Operating Instructions Temperature Switch TRS 5-50

Bulletin K. Type RSF. Size: 1/2" - 4" (13-100mm) Suitable For: Ammonia, R-22, R-134a, R-502 and Other Common Refrigerants

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Impeller Stack Kit Dismantling and Reassembly CR(I/N) 1S 1 3 5

Technical Data. Sizes 2 in. (DN50) to 16 in. (DN400) Approvals UL and ULC Listed FM Approved

1592P01. for liquids in piping DN max. DC 48 V, 1 A, 20 W

FT14 and FT14HC. SG Iron Ball Float Steam Traps (1" HC, 1¼", 1½" and 2")

Betriebsanleitung Operating Instructions

Water Safety Shut-Off Valve HON 790. Product information. serving the gas industry worldwide

Operation of heat exchangers

Installation and maintenance instructions

1592P01. for liquids in piping DN

GESTRA. GESTRA Steam Systems NRS For ONE Electrode. English. Installation Instructions Level Switch NRS 1-50

Care and Maintenance

MFP14 Automatic pumps for condensate and other industrial fluids

SERIES 46000E Bi-Directional In-Line Deflagration Flame Arrester

OPERATING & MAINTENANCE INSTRUCTIONS FOR EXHEAT RFA-OS TYPE FLAMEPROOF OVERSINK WATER HEATER

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

CRU-S Series Stainless Steel Condensate Recovery Unit

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Operating instructions

Installation, Operation and Maintenance Instructions for PlantPac Steam Plate Heat Exchanger Package

SuperKlean Washdown Products

Flow Measurement SITRANS F C

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5

Transcription:

GESTRA Steam Systems BK 37 BK 28 BK 29 Installation Instructions 818689-00 Steam Trap BK 37, BK 28, BK 29 BK 37 ASME, BK 28 ASME, BK 29 ASME

Contents Important Notes Page Usage for the intended purpose...4 Safety note...4 Danger...4 Attention...4 PED (Pressure Equipment Directive)...4 ATEX (Atmosphère Explosible)...4 Explanatory Notes Scope of supply...5 Description...5 Function...5 Technical Data Corrosion resistance...6 Sizing...6 Name plate / marking...6 Design Component parts BK 37, BK 37 ASME...7 Component parts BK 28, BK 28 ASME, BK 29, BK 29 ASME...8 Key...9 Installation BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME...10 Flanged design...10 Socket-weld design...10 Butt-weld design...11 Attention...11 Heat treatment of welds...11 Tools...11 Commissioning BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME...12 Attention...12 Operation BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME...12 Thermovit regulator...12 2

Contents continued Maintenance Page Replacing regulator...13 Tools...13 Torques required for tightening...13 Spare Parts BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME...14 Spare parts list...14 Decommissioning Danger...14 Disposal...14 3

Important Notes Usage for the intended purpose Use steam traps BK 37..., BK 28... and BK 29... only for the discharge of condensed water or for air-venting in steam lines within the admissible pressure/temperature ratings. Check the corrosion resistance and chemical suitability of this pressure equipment for the application in question. Safety note The equipment must only be installed and commissioned by qualified staff. Maintenance and service work must only be performed by adequately trained persons who have a recognised level of competence. Danger The steam trap is under pressure during operation. When loosening flanged connections, sealing plugs or the regulator, hot water and/or steam may escape. This presents the risk of severe scalding. Installation and maintenance work should only be carried out when the system is depressurized (0 bar): isolate the trap from both upstream and downstream pressure. The trap becomes hot during operation. This presents the danger of severe burns to hands and arms. Installation and maintenance work should only be carried out when the system is cold (20 C). Sharp edges on internal parts present a danger of cuts to hands. Always wear industrial gloves when replacing the regulator. Attention The name plate indicates the technical specification of the equipment. Do not commission or operate a steam trap without name plate. PED (Pressure Equipment Directive) The equipment fulfills the requirements of the Pressure Equipment Directive PED 97/23/EC. For applications with fluids of group 2. With CE marking (apart from equipment according to section 3.3). ATEX (Atmosphère Explosible) The equipment does not have its own potential source of ignition and is therefore not subject to the ATEX Directive 94/9/EC. The equipment can be used in potentially explosive areas 0, 1, 2, 20, 21, 22 (1999/92/EC). The equipment is not Ex marked. 4

Explanatory Notes Scope of Supply BK 37: 1 Steam trap type BK 37 1 Installation manual BK 28: 1 Steam trap type BK 28 1 Installation manual BK 29: 1 Steam trap type BK 29 1 Installation manual Description Thermostatic/thermodynamic steam trap with corrosion-resistant Thermovit Duo s.s. regulator unaffected by waterhammer. The trap features: n Integral strainer n Non-return valve action n Asbestos-free cover gasket (graphite/crni) n Installation in any position The factory setting enables the steam trap to discharge condensate with virtually no banking-up. Function During start-up of the plant the Duo stainless steel plates are flat. The service pressure acts in the opening direction, the valve is completely open. As the condensate temperature rises, the plates deflect, drawing the stage nozzle towards the closed position. As the condensate temperature sinks, the deflection of the Duo stainless steel plates decreases and the steam trap opens at the adjusted opening temperature. The thermostatic and spring characteristics of the stack of plates are balanced such that condensate is always discharged at a given undercooling temperature. The trap provides automatic air-venting at start-up and during operation. BK 37..., BK 28... and BK 29... can also be used for thermal air-venting in steam systems. 5

Technical Data Corrosion Resistance If the steam trap is used for the intended purpose, its safety is not impaired by corrosion. Sizing The trap body must not be subjected to pulsating loads. The dimensional allowances for corrosion reflect the latest state of technology. Name Plate/Marking The pressure/temperature ratings are indicated on the trap body/the name plate. For more information see GESTRA data sheets and Technical Information. According to EN 19 the name plate and the valve body indicate the type and design: Name/logo of the manufacturer Type designation Pressure class PN or Class Material number Max. temperature Max. pressure Flow direction 1 Stamp on valve body, e.g. 06 specifies the quarter and the year of production (Example: 1 st quarter 2006). Nominal pressure Size Class Nominal pressure Fig. 1 6

Design Component Parts BK 37, BK 37 ASME G I A C D H E F Fig. 2 G 7

Design continued Component Parts BK 28, BK 28 ASME, BK 29, BK 29 ASME G I A B D H E F Fig. 3 G 8

Design continued Key A Cover B Thermovit regulator BK 28, BK 28 ASME, BK 29, BK 29 ASME C Thermovit regulator BK 37, BK 37 ASME D Strainer E Gasket F Body G Hexagon nut (DIN 2510) H Expansion bolts (DIN 2510) I Name plate 9

Installation BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME Provided that the flow arrow (the arrow points towards the direction of flow) is taken into consideration, the trap can be installed in any position. In the case of a horizontal installation make sure that the cover is on top. Flanged design 1. Take care of correct position of installation. 2. Take care of flow direction. The flow arrow is on the trap body. 3. Consider space required for opening trap. When the trap is installed a minimum space of 80 mm is required for removing cover A. 4. Remove plastic plugs. They are only used as transit protection. 5. Clean seating surfaces of both flanges. 6. Install steam trap. Socket-weld design 1. Take care of correct position of installation. 2. Take care of flow direction. The flow arrow is on the trap body. 3. Consider space required for opening trap. When the trap is installed a minimum space of 80 mm is required for removing the cover A. 4. Remove plastic plugs. They are only used as transit protection. 5. Remove regulator as described under Maintenance. 6. Clean socket-weld ends. 7. Arc-weld trap (welding process 111 and 141 in accordance with ISO 4063). 10

Installation continued Butt-weld design 1. Take care of correct position of installation. 2. Take care of flow direction. The flow arrow is on the trap body. 3. Consider space required for opening trap. When the trap is installed a minimum space of 80 mm is required for removing the cover A. 4. Remove plastic plugs. They are only used as transit protection. 5. Clean butt-weld ends. 6. Arc-weld trap (welding process 111 and 141 in accordance with ISO 4063) or use gas-welding process (welding process 3 in accordance with ISO 4063). Attention Only qualified welders certified e. g. according to DIN EN 287 may weld the steam trap into pressurized lines. Do not insulate the steam trap. Heat Treatment of Welds After welding the steam trap in place a heat treatment of the welds is required (stress-relief annealing to DIN EN 100529). The heat treatment must be restricted to the immediate area of the welds. Remove the regulator as described under Maintenance before carrying out the heat treatment. Tools Spanner A. F. 24 mm, DIN 3113, form B 11

Commissioning BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME Make sure that the flanged connections of the BK 37..., BK 28... or BK 29... are permanently bolted and tight. Attention The steam trap is under pressure at start-up and during the operation. The steam trap becomes hot during operation. This presents the risk of severe burns to hands and arms. Always wear industrial gloves when setting the regulator. Installation and maintenance work may only be carried out when the system is depressurised (zero bar). Make sure that the lines upstream and downstream of the trap are not under pressure! Operation BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME Please note that maintenance may be required for certain operating modes (see Maintenance). Thermovit regulator The factory setting of the Thermovit regulator enables the regulator to be steam-tight when closed and to open just before the pressure-dependent boiling temperature is reached. 12

Maintenance GESTRA steam traps type BK 37... BK 28... and BK 29... do not require any special maintenance. However, if used in new installations which have not been rinsed it may be necessary to check and clean the trap. Replacing Regulator 1. Remove cover A from body F, Fig. 2, Fig. 3 2. Remove regulator B or C using a spanner. 3. Unscrew regulator B or C and take off strainer D. 4. Clean body, regulator, cover and strainer. 5. Clean gasket seating surfaces and insert new gasket E. 6. Clean sealing surfaces of regulator B or C and body F. 7. Replace strainer D. 8. Screw in regulator B or C and tighten with a torque of 100 Nm. 9. Apply heat-resistant lubricant to threads of the expansion bolts H (use for instance MOLYKOTE HSC+ ) 10. Replace cover A. Insert expansion bolts H and tighten hexagon nuts G at room temperature in diagonally opposite pairs with a torque of 225 Nm. Tools Spanner A.F. 24 mm, DIN 3113, form B Torque spanner 20-100 Nm, ISO 6789 Torque spanner 80-400 Nm, ISO 6789 Torques required for tightening Item Designation Torque [Nm] B / C Thermovit regulator 100 G Hexagon nut 60 All torques are based at 20 C room temperature. MOLYKOTE is a registered trademark of Dow Corning GmbH, Wiesbaden 13

Spare Parts BK 37, BK 37 ASME, BK 28, BK 28 ASME, BK 29, BK 29 ASME B/C D E Fig. 4 Spare parts list Item Designation Stock code B C Regulator for BK 28..., BK 29..., complete including cover gasket E Regulator for BK 37..., complete including cover gasket E 370281 377722 E Gasket (graphite/crni) 372095 D Strainer 096701 Decommissioning Danger Risk of severe burns and scalds to the whole body! Before loosening flanged connections or sealing plugs, make sure that all connected lines are depressurized (zero bar) and cooled down to room temperature (20 C). Disposal Dismantle the trap and separate the waste materials, using the specifications in the table Materials on page 9 as a reference. For the disposal of the trap observe the pertinent legal regulations concerning waste disposal. 14

For your notes 15

GESTRA Agencies all over the world: www.gestra.de España GESTRA ESPAÑOLA S.A. Luis Cabrera, 86-88 E-28002 Madrid Tel. 00 34 91 / 5 15 20 32 Fax 00 34 91 / 4 13 67 47; 5 15 20 36 E-mail: aromero@flowserve.com Polska GESTRA Polonia Spolka z.o.o. Ul. Schuberta 104 PL - 80-172 Gdansk Tel. 00 48 58 / 3 06 10-02 od 10 Fax 00 48 58 / 3 06 33 00 E-mail: gestra@gestra.pl Great Britain Flowserve Flow Control (UK) Ltd. Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 57 E-mail: gestraukinfo@flowserve.com Portugal Flowserve Portuguesa, Lda. Av. Dr. Antunes Guimarães, 1159 Porto 4100-082 Tel. 0 03 51 22 / 6 19 87 70 Fax 0 03 51 22 / 6 10 75 75 E-mail: jtavares@flowserve.com Italia Flowserve S.p.A. Flow Control Division Via Prealpi, 30 l-20032 Cormano (MI) Tel. 00 39 02 / 66 32 51 Fax 00 39 02 / 66 32 55 60 E-mail: infoitaly@flowserve.com USA Flowserve GESTRA U.S. 2341 Ampere Drive Louisville, KY 40299 Tel.: 00 15 02 / 502 267 2205 Fax: 00 15 02 / 502 266 5397 E-mail: dgoodwin@flowserve.com GESTRA AG P. O. Box 10 54 60, D-28054 Bremen Münchener Str. 77, D-28215 Bremen Telephone +49 (0) 421 35 03-0 Fax +49 (0) 421 35 03-393 E-Mail gestra.ag@flowserve.com Internet www.gestra.de 818689-00/806cm 2006 GESTRA AG Bremen Printed in Germany 16