Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Similar documents
Purdue e-pubs. Purdue University

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Study of R161 Refrigerant for Residential Airconditioning

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Low GWP Refrigerants for Air Conditioning Applications

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental Investigation of Purification Function of Air Conditioner

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

R32 Compressor for Air conditioning and Refrigeration applications in China

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Compressor Capacity Control: A New Direction

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Evaluation of a Virtual Refrigerant Charge Sensor

Performance of CO2 Cycles with a Two-Stage Compressor

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Fifteen Years of Dehumidification Results from Heat Pump Water Heaters

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

Performance Measurement of R32 Vapor Injection Heat Pump System

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Air-Cooled Heat Exchanger Performance for R410A

Experimental Study on the Performance of Twisted Capillary Tube

High Efficiency Heat Pump for Domestic Hot Water Generation

Designated vs Non-designated Areas for Condenser Subcooling

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

A study of Transient Performance of A Cascade Heat Pump System

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Dynamic Simulation of Liquid Chillers

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Experimental Research and CFD Simulation on Microchannel Evaporator Header to Improve Heat Exchanger Efficiency

An Experimental Study of the Air-Side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Capillary Tube and Thermostatic Expansion Valve Comparative Analysis in Water Chiller Air Conditioning

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Evaluation The Effect Of Washing On The Heat Transfer Capacity And Air-Side Flow Resistance Of Air Cooled Condensers

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Review of Temperature and Humidity Control Technology for Heat Pump and Air Conditioning Systems

Performance Analysis of a Miniature-Scale Vapor Compression System for Electronics Cooling: Bread Board Setup

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Sub-Critical Operation of the CO2 Expander/ Compressor

Refrigerant Mass and Oil Migration During Start-up Transient

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Reduction Of Energy Consumption in Airconditioning Systems employing direct evaporative pre-cooling of Condenser air

Compressor Capacity Control

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

System Using Exhaust Heat from Residential GHPs

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

High Efficiency R-134a Compressor for Domestic Refrigerator

Evaluation of Mechanical Dehumidification Concepts (Part 2)

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Xiaoping Tu Chinese National Engineering Research Center of Green Refrigeration Equipment, Zhuhai City, Guangdong Province, P. R. China, txp125@126.com Xiangfei Liang Chinese National Engineering Research Center of Green Refrigeration Equipment, Zhuhai City, Guangdong Province, P. R. China, liangxf@cn.gree.com Rong Zhuang Gree Electric Appliances Inc. of Zhuhai, Refrigeration Institute, Zhuhai City, Guangdong Province, P. R. China Follow this and additional works at: http://docs.lib.purdue.edu/iracc Tu, Xiaoping; Liang, Xiangfei; and Zhuang, Rong, "Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Air-conditioner" (2014). International Refrigeration and Air Conditioning Conference. Paper 1387. http://docs.lib.purdue.edu/iracc/1387 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2185, Page 1 Experimental Study on Match of Indoor and Outdoor Heat Exchanger of Residential Airconditioner Xiaoping TU 1 *, Xiangfei Liang 1, Rong ZHUANG 2 1 Chinese National Engineering Research Center of Green Refrigeration Equipment, Zhuhai City, Guangdong Province, P. R. China Phone: +86-756-8589514, Fax: +86-756-8668982, E-mail: txp125@126.com 2 Gree Electric Appliances Inc. of Zhuhai, Refrigeration Institute, Zhuhai City, Guangdong Province, P. R. China * Corresponding Author ABSTRACT In this study, the cooling and heating performance of residential air-conditioner system varying with the match of indoor and outdoor heat exchanger were measured and analyzed by changing the indoor unit air flow rate and heat exchanger, and outdoor unit air flow rate. Increase of both indoor unit and outdoor unit were beneficial for the cooling capacity and heating capacity, however, the EER and COP showed a trend of increasing slowly even decreasing after the first rapid increase. The air-conditioner system performance improvement was increased more significantly with increase of indoor unit compared to that of outdoor unit due to constantly smaller indoor unit matched with larger outdoor unit. The heat transfer area of the indoor unit was a more dominant factor affecting system performance than that of air flow rate especially under cooling mode. The maximum increase of cooling capacity, EER, heating capacity and COP with increasing indoor unit including heat transfer area and air flow rate were 35.3%, 24%,.4% and 29.9%, respectively. About 40% increase of outdoor unit air flow rate showed only 0.6%, 4.6% and 1.2% improvement for cooling capacity, EER and heating capacity, respectively, while the COP had about 0.7% decrease. Among the systems investigated and compared in this study, the heat transfer area ratio of indoor unit and outdoor unit should not be exceed 0.37, and the average air face velocity should not exceed 1.2m/s for the indoor unit and 1.6m/s for the outdoor unit. 1. INTRODUCTION Recent years, the HVAC industry continues to develop rapidly and is becoming main part of energy consumption in China. Some Chinese national standards (GB 21455-2008, GB 21455-2013) have been instituted to control the minimum allowable values of the energy efficiency and energy efficiency grades for variable speed residential air conditioners. The newest standard calls for all new air conditioners and heat pumps manufactured for sale in China from October 1 of 2013 onwards must comply with the minimum allowable values of the energy efficiency, which have a minimum SEER (Seasonal Energy Efficiency Ratio) of 4.3 for rated cooling capacity smaller than 4500W, about 43.3% increase over the GB 21455-2008 s minimum of 3 SEER for the same cooling capacity. In order to encourage higher efficiency products manufactured, a lot of national or local saving energy allowance policies have provided rebate incentives. The residential air conditioner and heat pump systems typically consist of two parts: an indoor unit and an outdoor unit. The indoor unit includes evaporator coil and fan, and the outdoor unit includes a compressor, condenser coil, fan, capillary or EEV (Electronic Expansion Valve) and refrigerant. These two parts are specifically designed to work together as a coordinated team to provide top performance and maximum efficiency and comfort. So if we install a new high-efficiency outdoor unit, but don t include a new, equally efficient and properly matched indoor

2185, Page 2 unit, the results could be uncomfortable, frustrating and expensive. Therefore, the proper match of indoor and outdoor unit must become an important issue for higher efficiency units. Literature review reveals that a limited amount of work about match of indoor and outdoor unit has been done for the performance improvement evaluation of residential air conditioners. Wang et al. (2001) studied the design method of the indoor and outdoor heat exchanger heat transfer area ratio for a residential heat pump air conditioner by way of thermodynamic cycle analysis respectively in the cooling mode and heating mode, correlated the heat transfer area ratio to working condition parameters, and indicated the heat transfer area ratio designed as extreme cooling or/and heating work conditions. Shao et al. (2001) evaluated the adjusting performance of variable frequency air conditioning system by system simulation and concluded that increasing the capacity of indoor or/and outdoor heat exchanger were useful for advance system performance, while extending less and less advantage due to reach to extreme of the cooling or heating capacity and system consuming power. Zhang et al. (2005) studied the effect of the indoor and outdoor heat exchanger heat transfer area of heat pump air conditioner on system performance including cooling and heating condition base on system simulation, and found that the EER and COP showed weak sensitivity when the heat transfer area increased to a relatively bigger value and existed optimal heat transfer area for both indoor and outdoor heat exchanger. The optimal indoor and outdoor heat exchanger heat transfer area ratio was 0.315 in Zhang et al. (2005) study. The revealed studies regarding the match of indoor and outdoor unit were focused on simulation results for the possible performance improvement of residential air conditioner. However, experimental investigation on this issue could not be found in open literature. The purpose of this paper is to investigate the effects of the indoor heat transfer area and air flow rate on the performance, providing information on the parameter design of the indoor and outdoor unit. A residential heat pump air conditioner outdoor unit and three indoor units were chosen as experiment investigation object. The cooling and heating performance were experimentally carried out in steady state under various indoor heat transfer area and both of indoor and outdoor air flow rate. 2. EXPERIMENTAL SETUP AND TEST PROCEDURES 2.1 Experimental Setup The experimental apparatus as shown in Figure 1 is based on the air enthalpy-difference method proposed based on Chinese national standard GB/T 7725-2004, including indoor and outdoor environmental chambers and air enthalpydifference and air flow rate measuring apparatus. The cooling capacity and heating capacity were measured as indoor air enthalpy-difference, and the outdoor unit capacity was also measured according to the similar method. Thermocouples and pressure transducers were used to measure the thermodynamic states of refrigerant entering or/and exiting the indoor and outdoor unit. The EER was defined the ratio of cooling capacity and system input power, and the COP was the ratio of heating capacity and system input power. Figure 1: Schematic of experimental setup

2185, Page 3 The outdoor unit, equipped with a constant speed hermetically-sealed reciprocating compressor, fin-and-tube heat exchanger, fan and capillary tube, was installed in the outdoor environmental chamber, and the indoor unit only contained fin-and-tube heat exchanger and fan was installed in the indoor environmental chamber. The outdoor and indoor environmental chamber can simulate all kinds of air conditions, respectively. In this study, the cooling performance was tested under the air conditions of 35 dry-bulb and 24 wet-bulb temperatures of outdoor unit and 27 dry-bulb and 19 wet-bulb temperatures, and the heating performance was tested at 7 dry-bulb and 6 wet-bulb temperatures of outdoor unit and 27 dry-bulb and 19 wet-bulb temperatures of indoor unit. The experimental object was three air conditioner system, which were three different indoor units respectively matched with one outdoor unit. As a matter of convenience, the three indoor units were successively named as A, B and C. The outdoor unit was used in 3500W split-system heat pump air conditioner using R22 as a working fluid, which was named as D. The name and heat transfer area of the four heat exchangers were shown in Table 1 and the heat transfer area was relative value of the outdoor heat exchanger. Table 1: Name and Heat transfer area of outdoor and indoor unit Unit Name Relative Heat Transfer Area Indoor A 0.23 Indoor B 0.33 Indoor C 0.37 Outdoor D 1 2.2 Test Procedures The optimal refrigerant charge of three indoor units test system was different from each other, so the first step of the experimental procedure was to determine refrigerant charge according charging or discharging the refrigerant of system, which was carried out for the specified indoor unit only in the cooling condition. The system was run at the simulated conditions described above for a 3h period under a quasi-steady operation. During the period, the dry-bulb and wet-bulb temperatures of the two rooms were carefully maintained within ±0.05. The optimal refrigerant charge for every indoor unit was determined until the maximize EER was obtained. Then the cooling and heating performance of each indoor unit system were measured under variable indoor unit air flow rate. In order to investigate the effect of increasing outdoor unit on system cooling and heating performance, the test of varying outdoor air flow rate of C indoor unit system was performed. 3. RESULTS AND DISCUSSION 3.1 Effects of indoor unit air flow rate Cooling Performance (%) 130 A-Cooling Capacity A-EER B-Cooling Capacity B-EER 120 C-Cooling Capacity C-EER 1 0 90 Heating Performance (%) 130 120 1 0 90 A-Heating Capacity B-Heating Capacity C-Heating Capacity A-COP B-COP C-COP 80 Figure 1: Cooling performance with indoor unit V fr 80 Figure 2: Heating performance with indoor unit V fr Both the increase of indoor air flow rate and heat exchanger heat transfer area can be considered as increasing the indoor unit. Figure 1, Figure 2, Figure 3, Figure 4 and Figure 5 showed the variations of cooling performance,

2185, Page 4 heating performance, cooling and heating evaporation temperature and condensation temperature, and superheat of the three indoor units matched with the outdoor unit as a function of indoor heat exchanger Vfr (average air face velocity), respectively, in which, the superheat was defined as the difference between refrigerant temperature and refrigerant saturation temperature corresponding to the pressure at the evaporator exit. It can be seen that the increase of indoor unit was extraordinarily advantageous for both the cooling capacity and heating capacity as shown in Figure 1 and Figure 2. In this study, the maximum increase of cooling capacity, EER, heating capacity and COP with indoor unit were 35.3%, 24%,.4% and 29.9%, respectively. However, the cooling capacity, EER, heating capacity and COP tended to increase rapidly only at first, which soon reduced increasing slope even decreasing. The EER of B indoor unit system trended downward when the Vfr exceeded to 1.2m/s in Figure 1, and the heating capacity of C indoor unit system was almost under that of B indoor unit system in Figure 2. In addition, the increase of indoor unit was more beneficial to improve cooling capacity especially for larger indoor heat transfer area system, and improve COP especially for smaller indoor heat transfer area system, and the heat transfer area of the indoor unit heat exchanger was a more dominant factor affecting system performance than that of air flow rate especially under cooling mode. 45 60 Saturated Temperature ( ) 40 35 30 25 20 15 Cooling Mode A-T_Evap B-T_Evap C-T_Evap A-T_Cond B-T_Cond C-T_Cond Saturated Temperature ( ) 50 40 30 20 Heating Mode A-T_Evap B-T_Evap C-T_Evap A-T_Cond B-T_Cond C-T_Cond Figure 3: T in cooling mode Superheat ( ) 14 12 8 6 4 2 0-2 A-Cooling Mode B-Cooling Mode C-Cooling Mode 0 Figure 4: T in Heating Mode A-Heating Mode B-Heating Mode C-Heating Mode Figure 5: Evaporator exit superheat The cooling capacity and heating capacity which were equal to indoor unit heat exchanger heat transfer capacity were multiplier of overall heat transfer coefficient, heat transfer area and mean heat transfer temperature difference. On the face of it, the heat transfer area was proportional to the cooling capacity or heating capacity, while the airside heat transfer coefficient directly related to the overall heat transfer coefficient can be thought as approximately proportional to the V n air.constantly, the power exponent n of V n air was less than 1, so although the increase of air flow rate can increase the overall heat transfer coefficient because of reducing the air-side heat resistance, the effect of air flow rate on the system capacity was much less than that of the heat exchanger heat transfer area.

2185, Page 5 Moreover, as the indoor unit increased, the system evaporation temperature was an increase trend in cooling mode as shown in Figure 3, and the system condensation temperature had a significant decrease in heating mode as shown in Figure 4, such that the heat transfer temperature difference of the indoor heat exchanger was decreasing in both cooling and heating mode, which restricted the continuous increasing heat transfer capacity of indoor unit. From another point of view, the variation of superheat as shown in Figure 5 can also reflect the evaporator heat transfer characteristic and system performance. It can be found that the increase of cooling capacity of A indoor unit system with air flow rate increased so slowly in Figure 1 due to very high superheat in Figure 5, and the heating capacity of C indoor unit system was a little less than that of B indoor unit at the same average air face velocity in Figure 2 also due to high superheat in Figure 5.The higher superheat meant a slight higher enthalpy difference of evaporator and a lower refrigerant mass flow rate. The two factors were opposite, so the heat exchanger heat transfer capacity was not possible to continuous increasing. That s why the cooling capacity and heating capacity showed a trend of increasing slowly after the first rapid increase with the increase of the indoor unit. In addition, the compressor ratio slowly but continuously decreased with the increase of the indoor unit because evaporation temperature increased more than condensation temperature in cooling mode, and condensation temperature decreased more than evaporation temperature in heating mode. The refrigerant mass flow rate can be derived as decreasing from the trend of superheat. Therefore, the compressor consuming power was decreasing. However, compared to the Figure 3 and Figure 4, it can be found that the variation of compressor pressure ratio was much less in cooling mode than that in heating mode, thus the decrease of compressor consuming power in cooling mode was much less, which was the reason for the increase of EER was less than that of cooling capacity, while the increase of COP was more than that of heating capacity. The system input power mainly comprised the compressor consuming power, indoor and outdoor fan consuming power. The fan consuming power was proportional to the air flow rate. The larger heat exchanger heat transfer area usually meant larger air flow rate, so no matter increase the heat transfer area or increase the air flow rate of indoor unit, the indoor fan consuming power was increasing. And the portion of the fan consuming power in system power was increasing as the increasing of indoor unit, so that the EER or COP rapidly increased at smaller indoor unit and then the slope gradually decreased with an increase of the indoor unit. In this experiment, the cooling capacity and EER were respectively from 86.9% to 9.4% and 90.1% to 6.5% of the B indoor unit system when the indoor heat exchanger heat transfer area was changed from 0.23 to 0.37 at the same 0.9m/s air face velocity, while the heating capacity and COP were respectively from 94.2% to 99.1% and 86.6% to 6.1% of the B indoor unit system at the same 0.86m/s air face velocity. The increase range of system cooling and heating performance was trending downwards at larger indoor unit, so the indoor heat transfer area and air flow should not be designed too large for the specified outdoor unit. In addition, with the specified outdoor unit in this study, the matched heat transfer area of indoor unit should not be too high or too low, and the optimal heat transfer area ratio of indoor and outdoor unit was between 0.33 and 0.37, which was better to choose the smaller value for higher indoor unit air flow rate. The indoor unit air flow rate increased about 19%, for the A indoor unit system, the cooling performance was only about 1% higher in cooling capacity and nearly no increase in EER, however, the heating performance had significant increase with about 2.8% higher in heating capacity and 6.5% higher in COP, respectively; for the C indoor unit system, the cooling performance had a significant increase with about 2.37% higher in cooling capacity and 0.9% higher in EER, and the heating performance had a slight increase with about 0.6% higher in heating capacity and 2.5% higher in COP. The results showed that the small indoor heat exchanger should design higher air flow rate, while the larger indoor unit should design lower air flow, and the optimal air face velocity should not be higher than 1.2m/s. 3.2 Effects of outdoor unit air flow rate Figure 6, Figure 7 and Figure 8 showed the variation of system cooling and heating performance, evaporation and condensation temperature, and superheat with outdoor unit air flow rate of C indoor unit matched with the outdoor unit system including cooling mode and heating mode, respectively. It showed that with the raise of outdoor unit air flow rate in Figure 6, the cooling capacity and heating capacity had a very slight increase, and the EER tended to increase rapidly at first and then almost no change, while the COP was decreasing.

2185, Page 6 The variation of outdoor unit air flow rate mainly changed the system condensation temperature in cooling mode, the evaporation temperature in heating mode, and superheat, while the evaporation temperature in cooling mode and condensation temperature in heating mode related to the indoor heat exchanger heat transfer temperature difference showed a relatively slight variation. The variation of condensation temperature in heating mode was more significant than that of evaporation temperature in cooling mode as shown in Figure 7, so the heating capacity had a relatively significant increase compared to the cooling capacity with the rise of outdoor unit air flow rate. 115 Cooling Capacity EER 60 Performance of C (%) 1 5 0 95 Heating Capacity COP Saturated Temperature of C( ) 50 40 30 20 Cooling Mode-T_Evap Cooling Mode-T_Cond Heating Mode-T_Evap Heating Mode-T_Cond 90 1 1.5 2 2.5 Outdoor Unit V fr (m/s) Figure 6: System performance of C 14 0 1 1.5 2 2.5 Outdoor Unit V fr (m/s) Figure 7: Evaporation and Condensation T of C 12 Cooling Mode Heating Mode Superheat ( ) 8 6 4 2 0-2 1 1.5 2 2.5 Outdoor Unit V fr (m/s) Figure 8: Evaporator exit superheat The above change of system saturated temperature meant that the compressor pressure ratio in cooling mode had a relatively significant decrease compared to that in heating mode. So the decrease of compressor specific power was more evident in cooling mode than in heating mode. While the refrigerant mass had a slight decrease because of slight variation of evaporation temperature with the variation of outdoor unit air flow rate both in cooling mode and heating mode, so the compressor consuming power was decreasing with the increase of outdoor unit air flow rate and the decrease of compressor consuming power was much more in cooling mode than in heating mode. That s why the EER increased rapidly at first in Figure 6. Similarly, the system input power mainly comprised the compressor consuming power, indoor and outdoor fan consuming power. The fan consuming power was proportional to the air flow rate. With the rise of outdoor unit air flow rate, the outdoor fan consuming power increased with no doubt. In cooling mode, as the above analysis, the compressor consuming power had a decrease, so the system input power was decreasing at first but with the rapid increase of outdoor fan consuming power, the system input power will be increasing, therefore, the EER will be increase no more. In heating mode, because of a little decrease of compressor consuming power and rapid increase of outdoor fan consuming power, the system input power even increased at first, resulting the COP always decreasing. Generally, the outdoor air flow rate of a heat pump air conditioner mainly influenced the system EER or COP. In

2185, Page 7 this study, the air flow rate increased about 42%, the cooling performance showed about 0.6% higher in cooling capacity and 4.6% higher in EER, and the heating performance showed about 1.2% higher in heating capacity and 0.7% lower in COP, respectively. It was shown that excessive or insufficient air flow rate can cause the degradation of the system performance. The proposed designed outdoor unit average air velocity should not be higher than 1.6m/s especially under heating condition. 4. CONCLUSIONS The effects of indoor unit heat transfer area and air flow rate and outdoor unit air flow rate on the system performance of residential air-conditioner were experimentally investigated under rated cooling and heating conditions. Conclusions were shown as follows: The system cooling and heating performances had an evident increase with indoor unit, but the increase range was trending downwards. The maximum increase of cooling capacity, EER, heating capacity and COP with increasing indoor unit including heat transfer area and air flow rate were 35.3%, 24%,.4% and 29.9%, respectively. The average air velocity should be higher for smaller heat transfer area of indoor unit, and that not be higher than 1.2m/s especially under cooling condition. The heat transfer area ratio of indoor unit matched with the specified outdoor unit should not be too high or too low. In this study, the heat transfer area ratio of indoor unit and outdoor unit was between 0.33 and 0.37, which should choose the smaller value for higher indoor unit air flow rate. With a rise of indoor unit heat transfer area or/and air flow rate, the increase of cooling capacity was more obvious than EER, while the increase of COP was more obvious than heating capacity. The improvement with indoor unit air flow rate was more significant for smaller heat transfer area indoor unit system especially in the heating mode. For the studied smallest heat transfer area indoor unit, the indoor unit air flow rate increased about 19%, the cooling performance was only about 1% higher for cooling capacity and nearly no increase for EER, however, the heating performance had a significant increase with about 2.8% higher for heating capacity and 6.5% higher for COP, respectively. The outdoor unit air flow rate mainly influenced the system EER or COP compared to the capacity, and excessive or insufficient air flow rate can cause the degradation of the system performance. In this study, the air flow rate increased about 42%, the cooling performance showed about 0.6% higher for cooling capacity and 4.6% higher for EER, and the heating performance showed about 1.2% higher for heating capacity and 0.7% lower for COP, respectively. The average air velocity should not be higher than 1.6m/s especially under heating condition. The indoor unit heat transfer area and air flow rate should not be too small or too large for specified outdoor unit, and the outdoor unit was the same designed principle for specified indoor unit. Existing a proper match range for the indoor unit and outdoor unit made the system overall performance best. NOMENCLATURE COP coefficient of performance ( ) Cond condensation ( ) EER energy efficiency ratio ( ) Evap evaporation ( ) Vfr air face velocity (m/s) REFERENCES GB 21455-2008, 2008, Minimum Allowable Values of the Energy Efficiency and Energy Efficiency Grades for Variable Speed Room Air Conditioners. GB 21455-2013, 2013, Minimum Allowable Values of the Energy Efficiency and Energy Efficiency Grades for Variable Speed Room Air Conditioners. GB/T 7725-2004, 2004, Room air conditioners. Shao, S.Q., Shi, W.X., Li, X.T., Yan, Q.S., 2001, Study on the Adjusting Performance of Variable Frequency Air Conditioning System, Refrigeration and Air-Conditioning, vol. 1, no. 4: p. 17-20.

2185, Page 8 Wang, R.X., Li, H.Q., Shao, Z.Y., 2001, Investigation on Match for two Heat Exchangers of Heat Pump Type Air Conditioner, Science and Technology of Household Electric Appliance, no. : p. 64-67. Zhang, X.G., Hu, Y.X., 2005, Matching of Heat Exchangers of Heat Pump Based on Simulation, Refrigeration and Air-Conditioning, vol. 5, no. 6: p. 98-1