INSTALLATION INSTRUCTIONS

Similar documents
INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Unit Features & Benefits RQPM/RQRM Series

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Ruud Achiever Series Dedicated Horizontal Package Heat Pump

Ruud Commercial Achiever Series Package Gas Electric Unit

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

Ruud Commercial Achiever Series Package Gas Electric Unit featuring HumidiDry Technology

INSTALLATION INSTRUCTIONS

Packaged Rooftop Air Conditioners Precedent - Cooling, Gas/Electric, Heat Pump 3-5Ton Standard and High Efficiency 3 Phase Rooftop Units

Ruud Commercial Value Series Package Gas Electric Unit

INSTALLATION INSTRUCTIONS

Ruud Commercial Value Series Package Gas Electric Unit

Ruud Commercial Value Series Package Gas Electric Unit

Rheem Commercial Value Series Package Air Conditioner

Rheem Commercial Classic Series Package Air Conditioner

INSTALLATION INSTRUCTIONS

Rheem Commercial Classic Series Package Gas Electric Unit

PACKAGE AIR CONDITIONING UNITS

PACKAGE AIR CONDITIONERS

MAINLINE COMMERCIAL PACKAGE AIR CONDITIONER

SELF-CONTAINED AIR CONDITIONERS

PACKAGE HEAT PUMPS FEATURING INDUSTRY STANDARD R-410A REFRIGERANT

PACKAGE AIR CONDITIONING UNITS

Installation and Maintenance Manual IM

INSTALLATION INSTRUCTIONS PACKAGE HEAT PUMPS FEATURING INDUSTRY STANDARD R-410A REFRIGERANT

INSTALLATION INSTRUCTIONS

MAINLINE COMMERCIAL PACKAGE AIR CONDITIONER

Rheem Commercial Prestige Series Package Air Conditioner

Ruud Commercial Achiever Series Package Air Conditioner. Package Air Conditioner

INSTALLATION INSTRUCTIONS

Ruud Commercial Achiever Series Package Gas Electric Unit featuring HumidiDry Technology

SELF-CONTAINED COOLING PACKAGE UNITS

INSTALLATION INSTRUCTIONS

Ruud Commercial Achiever Series Package Air Conditioner. Package Air Conditioner

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Ruud Commercial Achiever Series Package Air Conditioner. Package Air Conditioner

H 2 AC Rooftop Unit featuring esync Integration Technology

SELF-CONTAINED HEAT PUMP PACKAGE UNITS

H 2 AC Rooftop Unit featuring esync Integration Technology

HEAT EXCHANGER Aluminized serpentine clamshell heat exchanger provides corrosion resistance for longer life and efficient heat transfer.

AIR COOLED SPLIT SYSTEMS LIGHT COMMERCIAL RANGE UN-PRC001-EN

TGA WARNING CAUTION ROOFTOP UNITS. Service Literature. Table of Contents

TCD-TCH. Self-contained rooftop unit. VOYAGER I and II range TCD: Downflow discharge and intake TCH: Horizontal discharge and intake

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Split System Heat Pumps

Ruud Commercial Value Series Package Gas Electric Unit

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

16 SEER TWO-STAGE AIR CONDITIONERS

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

Packaged Cooling with Electric Heat Rooftop Units

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

4YCC3048A3096A /3/ /

Packaged Rooftops. Voyager, R-410A. 12½ - 25 Tons 60 Hz. Packaged Cooling (TC*) Packaged Gas/Electric (YC*) RT-PRC028-EN.

13 SEER CONDENSING UNITS

13 GEP A L P - 1 A

Ruud Commercial Achiever Series Package Air Conditioner featuring HumidiDry Technology

Packaged Heat Pumps. Voyager 12½ to 20 Tons 60 Hz PKGP-PRC001-EN. September 2004

Commercial High-Efficiency Condensing Units

Packaged Gas/Electric Rooftop Units

Product Catalog. Packaged Rooftop Air Conditioners Foundation Cooling and Gas/Electric 3 to 5 Tons, 60Hz RT-PRC078C-EN.

PACKAGE AIR CONDITIONER

PRODUCT SPECIFICATIONS 2YCC3036A1096A /1/ /

RGE 13 A T - 1 A

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

Corp L2 Revised

INSTALLATION INSTRUCTIONS

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

Packaged Heat Pump. 20 Ton Rooftop Units with ReliaTel TM Controls NOTICE

Split System Cooling Units

INSTALLATION INSTRUCTIONS

Packaged Heat Pumps. Precedent Tons 60 Hz. Packaged Heat Pumps (WSC) PKGP-PRC003-EN. February 2007

PGB SERIES 3thru5Ton 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

R-410A LUXAIRE ACCLIMATE DYX MODELS 2-4 TON 60 Hertz

Packaged Cooling with Electric Heat Rooftop Units

Packaged Cooling 20 Ton Rooftop Units with ReliaTel Controls, 50 Hz

Product Catalog. Packaged Rooftop Air Conditioners Foundation Electric/Electric 3 to 5 Tons, 50Hz RT-PRC079B-EN. June 2017

H 2 AC Rooftop Unit featuring esync Integration Technology

48TM GAS HEATING/ELECTRIC COOLING UNITS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Packaged Heat Pumps. Precedent - R Tons 60 Hz. Packaged Heat Pumps (WSC) PKGP-PRC003-EN. November 2008

Product Data /4WCC3018A through 2/4WCC3060A Single Package Convertible Heat Pump 13 SEER 1½ - 5 Ton R-22/R-410A

Submittal. Split System Cooling 4A7A6024J-SUB-1B-EN. January A7A6024J1000B TAG:

Packaged Heat Pumps. Precedent - R-410A Tons 60 Hz. Packaged Heat Pumps (WSC) PKGP-PRC013-EN. August 2009

PAJ3. Product Specifications

RSG16**S1M. Split System Air Conditioner 16 SEER

SKYPAK II, 3 Ton Series, gives you a

Product Catalog. Packaged Rooftop Air Conditioners Foundation Electric/Electric Tons, 50 Hz RT-PRC073B-EN. May 2018

SKYPAK II, 3 Ton Series, gives you a

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

Submittal. Date: January 8, Customer P.O. Number: Customer Project Number: CARROLLTON, TX 75006

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

SPECIFICATIONS 4YCC3060A-SPEC-1A SINGLE PACKAGED GAS HEATING ELECTRIC COOLING 4YCC3060A1096/120B TAG:

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Transcription:

INSTALLATION INSTRUCTIONS FOR COMBINATION HEATING AND COOLING ROOFTOP UNITS RKKB SERIES 7.5, 8.5, 10, 12.5 & 15 TON [26.4, 29.9, 35.2 44 & 52.8 kw] RKMB SERIES 7.5, 8.5, 10 & 12.5 TON [26.4, 29.9, 35.2 & 44 kw] RKNB SERIES 7.5, 8.5 & 10 TON [26.4, 29.9 & 35.2 kw] 92-23577-35-09 SUPERSEDES 92-23577-35-08

TABLE OF CONTENTS I. SPECIFICATIONS Components Page No. inside cover Safety Information 1 Unit Dimensions 2-4 General Data 5-42 Electrical Data 43-50 II. INSTALLATION General 51 Location Considerations 51 Exhaust & Combustion Hoods 52 Cover Panel Installation 52 Clearances 53 Rooftop 54 Ducting 54 & 55 Return Air 55 III. GAS SUPPLY & PIPING 56-58 IV. ELECTRICAL WIRING Power Supply 59 Hook-up 60 Internal Wiring 60 Thermostat 60 V. FURNACE CONTROLS 61 VI. OPERATION INFO 62-63 VII. AIRFLOW 64-68 VIII. TROUBLESHOOTING 69-71 IX. WIRING DIAGRAMS 72-77 X. CHARGE CHARTS 78-89 INTRODUCTION! WARNING THE MANUFACTURER S WARRANTY DOES NOT COVER ANY DAMAGE OR DEFECT TO THE AIR CONDITIONER CAUSED BY THE ATTACHMENT OR USE OF ANY COMPONENTS, ACCESSORIES OR DEVICES (OTHER THAN THOSE AUTHORIZED BY THE MANUFACTURER) INTO, ONTO OR IN CONJUNCTION WITH THE AIR CONDITIONER. YOU SHOULD BE AWARE THAT THE USE OF UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES MAY ADVERSELY AFFECT THE OPERATION OF THE AIR CONDITIONER AND MAY ALSO ENDANGER LIFE AND PROPERTY. THE MANUFACTURER DISCLAIMS ANY RESPONSIBILITY FOR SUCH LOSS OR INJURY RESULTING FROM THE USE OF SUCH UNAUTHORIZED COMPONENTS, ACCESSORIES OR DEVICES. This booklet contains the installation and operating instructions for your combination gas heating/electric cooling unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions. Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. Give this booklet to the owner and explain its provisions. The owner should retain this booklet for future reference. CHECKING PRODUCT RECEIVED Upon receiving the unit, inspect it for any damage from shipment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. IMPORTANT: Check the unit model number, heating size, electrical characteristics, and accessories to determine if they are correct. I. SPECIFICATIONS A. GENERAL The Combination Gas Heating/Electric Cooling Rooftop is available in 150,000, 225,000 and 252,000 BTUH heating input. Cooling capacity is 7.5, 8.5, 10, 12 & 15 nominal tons. Units are convertible from bottom supply and return to side supply and return by relocation of supply and return air cover panels. See cover installation detail. The units are weatherized for mounting outside of the building.! WARNING UNITS ARE NOT DESIGN CERTIFIED TO BE INSTALLED INSIDE THE STRUCTURE. DOING SO CAN CAUSE INADEQUATE UNIT PERFORMANCE AS WELL AS PROPERTY DAMAGE AND CARBON MONOXIDE POISONING RESULTING IN PERSONAL INJURY OR DEATH. The information on the rating plate is in compliance with the FTC and DOE rating for single phase units. The following information is for three phase units which are not covered under the DOE certification program. 1. The energy consumption of the ignition system used with this unit is 175 watts. 2. The efficiency rating of this unit is a product thermal efficiency rating determined under continuous operating conditions independent of any installed system. B. MAJOR COMPONENTS The unit includes a hermetically-sealed refrigerating system consisting of a scroll compressor, condenser coil, evaporator coil with capillary tube assembly or TXV, a circulation air blower, a condenser fan, a heat exchanger assembly, gas burner and control assembly, combustion air motor and fan, and all necessary internal electrical wiring. The cooling system of these units is factory-evacuated, charged and performance tested. Refrigerant amount and type are indicated on rating plate.

SAFETY INFORMATION! WARNING USE ONLY WITH TYPE OF GAS APPROVED FOR THIS UNIT. REFER TO THE UNIT RATING PLATE.! WARNING INSTALL THIS UNIT ONLY IN A LOCATION AND POSITION AS SPECIFIED IN THE LOCATION REQUIREMENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS. PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE UNIT SPACE AS SPECIFIED IN THE VENTING SECTION OF THESE INSTRUCTIONS.! WARNING PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR TO THE UNIT SPACE AS SPECIFIED IN THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUCTIONS.! WARNING COMBUSTION PRODUCTS MUST BE DISCHARGED OUTDOORS. CONNECT THIS UNIT TO AN APPROVED VENT SYSTEM ONLY, AS SPECIFIED IN VENT PIPE INSTALLATION SECTION OF THESE INSTRUCTIONS.! WARNING NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUCTIONS.! WARNING ALWAYS INSTALL UNIT TO OPERATE WITHIN THE UNIT'S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTERNAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO UNIT RATING PLATE.! WARNING WHEN A UNIT IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE UNIT TO AREAS OUTSIDE THE SPACE CONTAINING THE UNIT, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE UNIT CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE UNIT.! WARNING THIS UNIT MAY BE USED TO HEAT THE BUILDING OR STRUCTURE DURING CONSTRUCTION IF THE FOLLOWING INSTALLATION REQUIREMENTS ARE MET. INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING: PROPER VENT INSTALLATION; FURNACE OPERATING UNDER THERMOSTATIC CONTROL; RETURN AIR DUCT SEALED TO THE FURNACE; AIR FILTERS IN PLACE; SET FURNACE INPUT RATE AND TEMPERATURE RISE PER RATING PLATE MARKING; MEANS OF PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION; RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55 F (13 C) AND 80 F (27 C); AND INSTALLATION OF EXHAUST AND COMBUSTION AIR INLET HOODS COMPLETED; CLEAN FURNACE, DUCT WORK AND COMPONENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY FURNACE OPERATING CONDITIONS INCLUDING IGNITION INPUT RATE, TEMPERATURE RISE AND VENTING, ACCORDING TO THE INSTRUCTIONS. 1

Unit Dimensions FIGURE 1 BOTTOM VIEW IMPORTANT: THIS UNIT MUST BE MOUNTED LEVEL IN BOTH DIRECTIONS TO ALLOW WATER TO DRAIN FROM THE CONDENSER SECTION AND CONDENSATE PAN. BOTTOM nates Metric Conversions Illustration ST-A0734-02 FIGURE 2 CABINET DIMENSIONS AND ACCESS LOCATIONS Illustration ST-A0715-03-X1 2

FIGURE 3 SUPPLY AND RETURN DIMENSIONS FOR DOWNFLOW APPLICATIONS Illustration ST-A0738-02 FIGURE 4 SUPPLY AND RETURN DIMENSIONS FOR HORIZONTAL APPLICATIONS Illustration ST-A0736-02-X1 *RECOMMENDED DUCT DIMENSIONS ARE 26" 3

FIGURE 5 Illustration ST-A0737-01-X2 FIGURE 6 ROOFCURB INSTALLATION Illustration ST-A0801-17 4

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A090CL15E A090CL22E A090CM15E A090CM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 90000 [26.4] 90000 [26.4] 90000 [26.4] 90000 [26.4] EER/SEER 2 9.2/NA 9.2/NA 9.2/NA 9.2/NA Nominal CFM/ARI Rated CFM [L/s] 2900/3200 [1369/1510] 2900/3200 [1369/1510] 2900/3200 [1369/1510] 2900/3200 [1369/1510] ARI Net Cooling Capacity Btu [kw] 87000 [25.5] 87000 [25.5] 87000 [25.5] 87000 [25.5] Net Sensible Capacity Btu [kw] 68000 [19.9] 68000 [19.9] 68000 [19.9] 68000 [19.9] Net Latent Capacity Btu [kw] 19000 [5.6] 19000 [5.6] 19000 [5.6] 19000 [5.6] Integrated Part Load Value 3 10.5 10.5 10.5 10.5 Net System Power kw 9.4 9.4 9.4 9.4 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 25-55 [13.9-30.6] 40-70 [22.2-38.9] 25-55 [13.9-30.6] 40-70 [22.2-38.9] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 67/67 [1899/1899] 67/67 [1899/1899] 67/67 [1899/1899] 67/67 [1899/1899] Weights Net Weight lbs. [kg] 1015 [460] 1035 [469] 1023 [464] 1043 [473] Ship Weight lbs. [kg] 1078 [489] 1098 [498] 1086 [493] 1106 [502] See NOTES: Page 47 for Notes. 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. CONTINUED [ ] Designates Metric Conversions 5

6 GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A090DL15E A090DL22E A090DM15E A090DM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 90000 [26.4] 90000 [26.4] 90000 [26.4] 90000 [26.4] EER/SEER 2 9.2/NA 9.2/NA 9.2/NA 9.2/NA Nominal CFM/ARI Rated CFM [L/s] 2900/3200 [1369/1510] 2900/3200 [1369/1510] 2900/3200 [1369/1510] 2900/3200 [1369/1510] ARI Net Cooling Capacity Btu [kw] 87000 [25.5] 87000 [25.5] 87000 [25.5] 87000 [25.5] Net Sensible Capacity Btu [kw] 68000 [19.9] 68000 [19.9] 68000 [19.9] 68000 [19.9] Net Latent Capacity Btu [kw] 19000 [5.6] 19000 [5.6] 19000 [5.6] 19000 [5.6] Integrated Part Load Value 3 10.5 10.5 10.5 10.5 Net System Power kw 9.4 9.4 9.4 9.4 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 25-55 [13.9-30.6] 40-70 [22.2-38.9] 25-55 [13.9-30.6] 40-70 [22.2-38.9] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 67/67 [1899/1899] 67/67 [1899/1899] 67/67 [1899/1899] 67/67 [1899/1899] Weights CONTINUED Net Weight lbs. [kg] 1015 [460] 1035 [469] 1023 [464] 1043 [473] Ship Weight lbs. [kg] 1078 [489] 1098 [498] 1086 [493] 1106 [502] See NOTES: Page 47 for Notes 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A090YL15E A090YL22E A090YM15E A090YM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 90000 [26.4] 90000 [26.4] 90000 [26.4] 90000 [26.4] EER/SEER 2 9.2/NA 9.2/NA 9.2/NA 9.2/NA Nominal CFM/ARI Rated CFM [L/s] 2900/3200 [1369/1510] 2900/3200 [1369/1510] 2900/3200 [1369/1510] 2900/3200 [1369/1510] ARI Net Cooling Capacity Btu [kw] 87000 [25.5] 87000 [25.5] 87000 [25.5] 87000 [25.5] Net Sensible Capacity Btu [kw] 68000 [19.9] 68000 [19.9] 68000 [19.9] 68000 [19.9] Net Latent Capacity Btu [kw] 19000 [5.6] 19000 [5.6] 19000 [5.6] 19000 [5.6] Integrated Part Load Value 3 10.5 10.5 10.5 10.5 Net System Power kw 9.4 9.4 9.4 9.4 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 25-55 [13.9-30.6] 40-70 [22.2-38.9] 25-55 [13.9-30.6] 40-70 [22.2-38.9] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] 1/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 4000 [1888] 4000 [1888] 4000 [1888] 4000 [1888] No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP 1 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 67/67 [1899/1899] 67/67 [1899/1899] 67/67 [1899/1899] 67/67 [1899/1899] Weights CONTINUED Net Weight lbs. [kg] 1015 [460] 1035 [469] 1023 [464] 1043 [473] Ship Weight lbs. [kg] 1078 [489] 1098 [498] 1086 [493] 1106 [502] SeePage47forNotes NOTES: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions 7

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A102CL15E A102CL22E A102CM15E A102CM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 104000 [30.5] 104000 [30.5] 104000 [30.5] 104000 [30.5] EER/SEER 2 9.4/NA 9.4/NA 9.4/NA 9.4/NA Nominal CFM/ARI Rated CFM [L/s] 3300/3400 [1557/1604] 3300/3400 [1557/1604] 3300/3400 [1557/1604] 3300/3400 [1557/1604] ARI Net Cooling Capacity Btu [kw] 100000 [29.3] 100000 [29.3] 100000 [29.3] 100000 [29.3] Net Sensible Capacity Btu [kw] 76000 [22.3] 76000 [22.3] 76000 [22.3] 76000 [22.3] Net Latent Capacity Btu [kw] 24000 [7] 24000 [7] 24000 [7] 24000 [7] Integrated Part Load Value 3 10.5 10.5 10.5 10.5 Net System Power kw 10.6 10.6 10.6 10.6 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 25-55 [13.9-30.6] 40-70 [22.2-38.9] 25-55 [13.9-30.6] 40-70 [22.2-38.9] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 68/68 [1928/1928] 68/68 [1928/1928] 68/68 [1928/1928] 68/68 [1928/1928] Weights CONTINUED Net Weight lbs. [kg] 1054 [478] 1066 [484] 1054 [478] 1074 [487] Ship Weight lbs. [kg] 1117 [507] 1129 [512] 1117 [507] 1137 [516] See NOTES: Page 47 for Notes 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. 8 [ ] Designates Metric Conversions

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A102DL15E A102DL22E A102DM15E A102DM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 104000 [30.5] 104000 [30.5] 104000 [30.5] 104000 [30.5] EER/SEER 2 9.4/NA 9.4/NA 9.4/NA 9.4/NA Nominal CFM/ARI Rated CFM [L/s] 3300/3400 [1557/1604] 3300/3400 [1557/1604] 3300/3400 [1557/1604] 3300/3400 [1557/1604] ARI Net Cooling Capacity Btu [kw] 100000 [29.3] 100000 [29.3] 100000 [29.3] 100000 [29.3] Net Sensible Capacity Btu [kw] 76000 [22.3] 76000 [22.3] 76000 [22.3] 76000 [22.3] Net Latent Capacity Btu [kw] 24000 [7] 24000 [7] 24000 [7] 24000 [7] Integrated Part Load Value 3 10.5 10.5 10.5 10.5 Net System Power kw 10.6 10.6 10.6 10.6 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 25-55 [13.9-30.6] 40-70 [22.2-38.9] 25-55 [13.9-30.6] 40-70 [22.2-38.9] Steady State Efficiency (%) 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 68/68 [1928/1928] 68/68 [1928/1928] 68/68 [1928/1928] 68/68 [1928/1928] Weights CONTINUED Net Weight lbs. [kg] 1046 [474] 1066 [484] 1054 [478] 1074 [487] Ship Weight lbs. [kg] 1109 [503] 1129 [512] 1117 [507] 1137 [516] SeePage47forNotes NOTES: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions 9

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A102YL15E A102YL22E A102YM15E A102YM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 104000 [30.5] 104000 [30.5] 104000 [30.5] 104000 [30.5] EER/SEER 2 9.4/NA 9.4/NA 9.4/NA 9.4/NA Nominal CFM/ARI Rated CFM [L/s] 3300/3400 [1557/1604] 3300/3400 [1557/1604] 3300/3400 [1557/1604] 3300/3400 [1557/1604] ARI Net Cooling Capacity Btu [kw] 100000 [29.3] 100000 [29.3] 100000 [29.3] 100000 [29.3] Net Sensible Capacity Btu [kw] 76000 [22.3] 76000 [22.3] 76000 [22.3] 76000 [22.3] Net Latent Capacity Btu [kw] 24000 [7] 24000 [7] 24000 [7] 24000 [7] Integrated Part Load Value 3 10.5 10.5 10.5 10.5 Net System Power kw 10.6 10.6 10.6 10.6 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 25-55 [13.9-30.6] 40-70 [22.2-38.9] 25-55 [13.9-30.6] 40-70 [22.2-38.9] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] 11.25 [1.05] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Smooth Smooth Smooth Smooth Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 68/68 [1928/1928] 68/68 [1928/1928] 68/68 [1928/1928] 68/68 [1928/1928] Weights CONTINUED Net Weight lbs. [kg] 1046 [474] 1066 [484] 1058 [480] 1074 [487] Ship Weight lbs. [kg] 1109 [503] 1129 [512] 1117 [507] 1137 [516] See NOTES: Page 47 for Notes 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. 10 [ ] Designates Metric Conversions

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A120CL15E A120CL22E A120CM15E A120CM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 125000 [36.6] 125000 [36.6] 125000 [36.6] 125000 [36.6] EER/SEER 2 9/NA 9/NA 9/NA 9/NA Nominal CFM/ARI Rated CFM [L/s] 4000/4000 [1888/1888] 4000/4000 [1888/1888] 4000/4000 [1888/1888] 4000/4000 [1888/1888] ARI Net Cooling Capacity Btu [kw] 120000 [35.2] 120000 [35.2] 120000 [35.2] 120000 [35.2] Net Sensible Capacity Btu [kw] 90000 [26.4] 90000 [26.4] 90000 [26.4] 90000 [26.4] Net Latent Capacity Btu [kw] 30000 [8.8] 30000 [8.8] 30000 [8.8] 30000 [8.8] Integrated Part Load Value 3 9.3 9.3 9.3 9.3 Net System Power kw 13.3 13.3 13.3 13.3 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 15-45 [8.3-25] 25-55 [13.9-30.6] 15-45 [8.3-25] 25-55 [13.9-30.6] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 80/80 [2268/2268] 80/80 [2268/2268] 80/80 [2268/2268] 80/80 [2268/2268] Weights CONTINUED Net Weight lbs. [kg] 1051 [477] 1051 [477] 1059 [480] 1059 [480] Ship Weight lbs. [kg] 1114 [505] 1114 [505] 1122 [509] 1122 [509] SeePage47forNotes NOTES: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions 11

GENERAL DATA - RKKB MODELS 12 NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A120DL15E A120DL22E A120DM15E A120DM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 125000 [36.6] 125000 [36.6] 125000 [36.6] 125000 [36.6] EER/SEER 2 9/NA 9/NA 9/NA 9/NA Nominal CFM/ARI Rated CFM [L/s] 4000/4000 [1888/1888] 4000/4000 [1888/1888] 4000/4000 [1888/1888] 4000/4000 [1888/1888] ARI Net Cooling Capacity Btu [kw] 120000 [35.2] 120000 [35.2] 120000 [35.2] 120000 [35.2] Net Sensible Capacity Btu [kw] 90000 [26.4] 90000 [26.4] 90000 [26.4] 90000 [26.4] Net Latent Capacity Btu [kw] 30000 [8.8] 30000 [8.8] 30000 [8.8] 30000 [8.8] Integrated Part Load Value 3 9.3 9.3 9.3 9.3 Net System Power kw 13.3 13.3 13.3 13.3 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 15-45 [8.3-25] 25-55 [13.9-30.6] 15-45 [8.3-25] 25-55 [13.9-30.6] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 80/80 [2268/2268] 80/80 [2268/2268] 80/80 [2268/2268] 80/80 [2268/2268] Weights CONTINUED Net Weight lbs. [kg] 1051 [477] 1051 [477] 1059 [480] 1059 [480] Ship Weight lbs. [kg] 1114 [505] 1114 [505] 1122 [509] 1122 [509] SNOTES: P 4 7 f N t 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions

GENERAL DATA - RKKB MODELS NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A120YL15E A120YL22E A120YM15E A120YM22E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 125000 [36.6] 125000 [36.6] 125000 [36.6] 125000 [36.6] EER/SEER 2 9/NA 9/NA 9/NA 9/NA Nominal CFM/ARI Rated CFM [L/s] 4000/4000 [1888/1888] 4000/4000 [1888/1888] 4000/4000 [1888/1888] 4000/4000 [1888/1888] ARI Net Cooling Capacity Btu [kw] 120000 [35.2] 120000 [35.2] 120000 [35.2] 120000 [35.2] Net Sensible Capacity Btu [kw] 90000 [26.4] 90000 [26.4] 90000 [26.4] 90000 [26.4] Net Latent Capacity Btu [kw] 30000 [8.8] 30000 [8.8] 30000 [8.8] 30000 [8.8] Integrated Part Load Value 3 9.3 9.3 9.3 9.3 Net System Power kw 13.3 13.3 13.3 13.3 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 112500/225000 [33/65.9] 75000/150000 [22/44] 112500/225000 [33/65.9] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] 60750/121500 [17.8/35.6] 91125/182250 [26.7/53.4] Temperature Rise Range F [ C] 15-45 [8.3-25] 25-55 [13.9-30.6] 15-45 [8.3-25] 25-55 [13.9-30.6] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 2 2 3 3 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 56 56 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 80/80 [2268/2268] 80/80 [2268/2268] 80/80 [2268/2268] 80/80 [2268/2268] Weights CONTINUED Net Weight lbs. [kg] 1051 [477] 1051 [477] 1059 [480] 1059 [480] Ship Weight lbs. [kg] 1114 [505] 1114 [505] 1122 [509] 1122 [509] SeePage47forNotes NOTES: 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions 13

GENERAL DATA - RKKB MODELS 14 NOM. SIZES 7.5-12.5 TONS [26.4-44.0 kw] ASHRAE 90.1-1989 COMPLIANT MODELS Model RKKB- Series A150CL15E A150CL25E A150CM15E A150CM25E Cooling Performance 1 Gross Cooling Capacity Btu [kw] 152000 [44.5] 152000 [44.5] 152000 [44.5] 152000 [44.5] EER/SEER 2 9/NA 9/NA 9/NA 9/NA Nominal CFM/ARI Rated CFM [L/s] 4800/4800 [2265/2265] 4800/4800 [2265/2265] 4800/4800 [2265/2265] 4800/4800 [2265/2265] ARI Net Cooling Capacity Btu [kw] 144000 [42.2] 144000 [42.2] 144000 [42.2] 144000 [42.2] Net Sensible Capacity Btu [kw] 108000 [31.6] 108000 [31.6] 108000 [31.6] 108000 [31.6] Net Latent Capacity Btu [kw] 36000 [10.5] 36000 [10.5] 36000 [10.5] 36000 [10.5] Integrated Part Load Value 3 9.3 9.3 9.3 9.3 Net System Power kw 16 16 16 16 Heating Performance (Package Gas/Electric) 4 Heating Input Btu [kw] (1st Stage / 2nd Stage) 75000/150000 [22/44] 126000/252000 [36.9/73.8] 75000/150000 [22/44] 126000/252000 [36.9/73.8] Heating Output Btu [kw] (1st Stage / 2nd Stage) 60750/121500 [17.8/35.6] 102000/204000 [29.9/59.8] 60750/121500 [17.8/35.6] 102000/204000 [29.9/59.8] Temperature Rise Range F [ C] 15-45 [8.3-25] 25-55 [13.9-30.6] 15-45 [8.3-25] 15-45 [8.3-25] Steady State Efficiency (%) 81 81 81 81 No. Burners 6 9 6 9 No. Stages 2 2 2 2 Gas Connection Pipe Size in. [mm] 0.5 [12.7] 0.75 [19.05] 0.5 [12.7] 0.75 [19.05] Compressor No./Type 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll 2/Copeland Scroll Outdoor Sound Rating (db) 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 27 [2.51] 27 [2.51] 27 [2.51] 27 [2.51] Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] 0.375 [9.5] Face Area sq. ft. [sq. m] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] 13.5 [1.25] Rows / FPI [FPcm] 3 / 18 [7] 3 / 18 [7] 3 / 18 [7] 3 / 18 [7] Refrigerant Control Capillary Tubes Capillary Tubes Capillary Tubes Capillary Tubes Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] 1/1 [25.4] Outdoor Fan Type Propeller Propeller Propeller Propeller No. Used/Diameter in. [mm] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] 2/24 [609.6] Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1 CFM [L/s] 8000 [3775] 8000 [3775] 8000 [3775] 8000 [3775] No. Motors/HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP 2 at 1/3 HP Motor RPM 1075 1075 1075 1075 Indoor Fan Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal No. Used/Diameter in. [mm] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] 1/15x15 [381x381] Drive Type/No. Speeds Belt/Variable Belt/Variable Belt/Variable Belt/Variable No. Motors 1 1 1 1 Motor HP 3 3 5 5 Motor RPM 1725 1725 1725 1725 Motor Frame Size 56 56 184 184 Filter Type Disposable Disposable Disposable Disposable Furnished Yes Yes Yes Yes (No.) Size Recommended in. [mm] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] (6)2x18x18 [51x457x457] Refrigerant Charge Oz. (Sys. 1/Sys. 2) [g] 179/179 [5075/5075] 179/179 [5075/5075] 179/179 [5075/5075] 179/179 [5075/5075] Weights CONTINUED Net Weight lbs. [kg] 1125 [510] 1125 [510] 1059 [480] 1151 [522] Ship Weight lbs. [kg] 1162 [527] 1162 [527] 1122 [509] 1188 [539] See NOTES: Page 47 for Notes 1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner Equipment certification program, which is based on ARI Standard 210/240 or 360. 2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. 3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at ARI rated cfm. 4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level. 5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. [ ] Designates Metric Conversions